rEQUIERMENT REVIEW

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

1 FIRE & LIFE SAFETY SYSTEM’S REVIEW FOR DRAGON & PHOENIX EXHIBITION AT NORTH GALLERY OF TG GF

REQUIREMENT COMMENTS RECOMMENDATION ACTION STATUS


 Occupant load has been reduced due to the new Occupant load to be decided by
Occupant load Hypsos Completed
installation from base design calculating the net area.
Mean of Egress

 3 No’s of exits are installed from the beginning and it is Exit light to be installed from both
Exits & Exit as per base built design and there is no change in it and side view Hypsos
Open
Signs all are operational. 1 No exit light showing wrong side team
 Total 12 Nos of Exit lights proposed in fit out design from inside the room
Emergency
 There is no change from the base built design NIL NA NA
Lights
Exit Widths  There is no change from the base built design NIL NA NA
 Vesda system is installed in the museum space and
Spot type in floor voids in the GF as per the base built
design and there are no changes for the new exhibition.
Additional fire detection is provided for the large closed Provide provision to access the
Fire detection and display case and Technical space. FV MSD in case of an emergency Hypsos /
Open
Notification or for any false alarm. Education
 Total 19 Nos of Floor void smoke detectors are installed
and fully covering the new exhibition in which 6 floor
void smoke detector is covered with art and there is no
provision to access.
 Sprinkler system is not installed inside the new
Sprinkler exhibition space area. Sprinkler protection is installed at NIL NA NA
backside of exit circulation
 Fire hose reels are installed at back side of exit
Fire Fighting

Fire hose reel circulation and main entrance corridor as per the base NIL NA NA
built and there is no change in it
 Access for fire hose reel is clear and it has full coverage
Fire Hose reel from front side and back side. Additional access
NIL NA NA
Access provision is provided in the new fit out to have 30-meter
reach for all hose reel.
Fire  Total 8 no’s of fire extinguishers are installed inside the
NIL NA NA
Extinguishers new art exhibition
 The installation of the luxury exhibition have an impact All floor void access panel shall
Smoke management in the smoke control strategy for the Temporary Gallery have clearance for smoke Hypsos Open
because of the closed showcase and server rooms, management
 Main Structure of the Temporary Gallery GF museum is
Structure fire unchanged and it is a base built design. Inside the
resistance, Fire rated certificates are Provided
museum space area of GF temporary structures are NA NA
Furnishing and wall – BH to Confirm
finish installed as part of new art exhibition and all materials
are fire rated.
 The art materials are made with cotton, fabric and
Fire load woods rarely they all are combustible NIL NA NA
 All fit out installation is fire rated
 Doors installation is as per the base built design and
Fire Doors NIL NA NA
there are no changes in the doors.
All the Fire Curtains installed are as per the base built design
and there are no changes in the fire curtain design for the new
Compartmentation

exhibition.

1- 8 No’s of Horizontal Fire Curtain installed are not Ensure the all fire curtains are
Fire Curtains operational and all the fire curtain panels are in OFF operational and will complied with FLS HFM Open
condition. system requirements
2- 2 Vertical Fire Curtain installed at the backside of the
exit sliding door is not working and wedged.
3- 1 Vertical Fire Curtain at Exhibition side towards the
opening to the café is operational.
Fire Shutters  No Fire Shutter in the TG GF NIL NA NA
Civil defense Access  There is no change to the base design NIL NA NA