Professional Documents
Culture Documents
Rtu Fibre - 23ok24
Rtu Fibre - 23ok24
Rtu Fibre - 23ok24
RS232C
optical
1
transmitter
x71
x8
optical
SPB I/O bus transmitter
RS485
1 optical
receiver
x72
RS232C optical
1 receiver
x9
Characteristics
Hence it follows the following applications:
– Substitution of the RTU560 electrical SPB I/O bus between
Application the subracks of a station
– Coupling of digital protection relays with fiber optic inter-
The fiber optic coupler 23OK24 is intended for use in the faces according to IEC60870-5-103
RTU560. The module is used to transmit data via 2 independent – With point to point connection
optical links (receive and transmit). – In a multi-drop link connection
– In a bus link
Optical fiber cables are not sensitive to inductive and capacitive
interferences, as well for potential differences between the 2 data – Optical booster to extend a fiber optic link
communication equipments. Fiber optic cables will be used to – Connection to any other unit with optical interface
bridge over distances in critical environments, or if a potential
isolation is required. The maximum distance can be up to 2600 The module 23OK24 occupies one slot in a RTU560 rack. It cou-
m via fiber optic cable type 200 μm. ples itself via the backplane direct with the RTU560 SPB I/O bus.
The module can be used for signal conversion to fiber optic The module is available for 820 nm glass fiber optic cable with
signals of the received and transmitted data for the following bajonet lock socket type BFOC/2.5 according to IEC 874-10.
electrical interface standards:
– RTU560 SPB I/O bus The fiber optic cable connection is done by the four lock sockets
– RS-485 bus on the front plate.
– RS-232 C
The maximum distance between two 23OK24 depends on
The fiber optic coupler 23OK24 can be connected to the – the fiber optic cable type
RTU500 series coupler 560FOC40, to the RTU520 I/O adapter – the number of fiber slices
520ADD03 R0002 and to the RTU511 I/O adapter 23AD64
R0002. The maximum transfer rate is only limited by the transmission rate
of the electrical interface. Interface standard and output optical
power can be selected and configured by jumper.
* : Recommended cable types Dimensions 160 mm x 100 mm, 3HE euro card
format
4R (20 mm) front panel
Available fiber optic cable length
Housing type Printed circuit board
Fiber optic cable length with consideration of a 3 dBm reserve, in dependence
of the output power and typical fiber optic cable attenuations: Mounting for mounting in RTU560 racks
Fiber optic System pow- Plug attenua- Cable attenu- Fiber optic Weight 0,2 kg
cable type er (dBm) tion (dB) ation (dB/km) cable length
(m)
Safety
50/125 μm 1,3 0,3 3,0 447
Transmitter Class 1 LED
*62,5/125 μm 5,1 3,5 1469
Ordering information
SPB I/O bus and RS485 Bus
23OK24 R5001 1KGT011800R5001
Signals TA / TB; RxA / RxB
68128 Mannheim, Germany poses and shall in no respect be binding. The Brochure does not claim to be ex-
haustive. Technical data in the Information are only approximate figures. We re-
www.abb.com/substationautomation serve the right at any time to make technical changes or modify the contents of
this document without prior notice. The user shall be solely responsible for the
use of any application example or information described within this document.
The described examples and solutions are examples only and do not represent
any comprehensive or complete solution. The user shall determine at its sole
discretion, or as the case may be, customize, program or add value to the ABB
products including software by creating solutions for the end customer and to
assess whether and to what extent the products are suitable and need to be ad-
justed or customized.
ABB AG reserves all rights in particular copyrights and other intellectual property
rights. Any reproduction, disclosure to third parties or utilization of its contents -
in whole or in part - is not permitted without the prior written consent of ABB AG.