Professional Documents
Culture Documents
BD Guide
BD Guide
Climate Controller
Technical Manual
This declaration of conformity is issued under the sole responsibility of the manufacturer.
Standards: EN 63000:2018
EN 61000-6-2:2019
EN 61000-6-4:2019
EN 62368-1:2019
We declare as manufacturer that the products meet the requirements of the listed directives and
standards.
Tommy Bak
CTO
307Pro • 310Pro
In case of an operating error or inappropriate use, ventilation systems can result in production
losses or cause loss of lives among livestock.
We recommend that ventilation systems should be mounted, operated and serviced only by
trained staff and that a separate emergency opening unit and an alarm system be installed as well
as maintained and tested at regular intervals, according to terms and conditions of sale and deliv-
ery.
Installation, servicing and troubleshooting of all electrical equipment must be carried out by quali-
fied personnel in compliance with the applicable national and international standard EN 60204-1
and any other EU standards that are applicable in Europe.
The installation of a power supply isolator is needed for each motor and power supply to facilitate
voltage-free work on the electrical equipment. The power supply isolator is not included.
Note
• All rights belong to Big Dutchman. No part of this manual may be reproduced in any manner whatsoever
without the expressed written permission of Big Dutchman in each case.
• All reasonable efforts have been made to ensure the accuracy of the information contained in this manual.
Should any mistakes or imprecise information occur in spite of this, Big Dutchman would appreciate being
notified thereof.
• Irrespective of the above, Big Dutchman shall not accept any liability with regard to loss or damage caused
or alleged to be caused by reliance on any information contained herein.
• Copyright by Big Dutchman.
Technical Manual 3
307Pro • 310Pro
1 Product description........................................................................................................................................ 8
2 Procedure........................................................................................................................................................ 9
4 Calibration..................................................................................................................................................... 43
4.1 The menu calibration............................................................................................................... 43
4.2 Calibration of air inlet and air outlet ...................................................................................... 45
Technical Manual
307Pro • 310Pro
5 Testing........................................................................................................................................................... 50
5.1 Testing basis components...................................................................................................... 50
5.1.1 Testing temperature and air humidity sensors........................................................................... 50
5.1.2 Testing Alarm............................................................................................................................. 50
5.1.3 Testing emergency opening....................................................................................................... 50
5.2 Testing optional components: Manual control ..................................................................... 50
5.2.1 Testing climate functions ........................................................................................................... 51
5.2.1.1 Testing Air Intake and Air Outlet ................................................................................................ 51
5.2.1.2 Testing of Dynamic MultiStep .................................................................................................... 51
5.2.1.3 Stepless fans ............................................................................................................................. 52
5.2.1.4 Emergency change-over switch AUT/MAN................................................................................ 52
5.2.1.5 MultiStep .................................................................................................................................... 53
5.2.1.6 Testing relay functions ............................................................................................................... 53
5.2.1.7 Testing heat recovery unit.......................................................................................................... 54
5.2.1.8 Testing natural ventilation .......................................................................................................... 54
5.2.1.9 Emergency inlet ......................................................................................................................... 54
5.2.2 Testing production functions ...................................................................................................... 55
5.2.2.1 Testing light................................................................................................................................ 55
5.2.2.2 Testing water meter ................................................................................................................... 55
5.2.2.3 Testing relay for 24-hour clock................................................................................................... 56
5.2.3 Testing management funtions.................................................................................................... 56
5.2.3.1 Testing of current sensor ........................................................................................................... 56
5.2.3.2 Testing auxiliary sensor ............................................................................................................. 56
5.3 Testing network connection ................................................................................................... 56
6 Service........................................................................................................................................................... 57
6.1 The Service Menu .................................................................................................................... 57
6.2 Settings..................................................................................................................................... 57
6.2.1 The menu Settings..................................................................................................................... 57
6.2.1.1 Climate....................................................................................................................................... 59
6.2.1.1.1 Setting natural ventilation........................................................................................................... 59
6.2.1.1.2 Setting of Exhaustion (MultiStep)............................................................................................... 60
6.2.1.1.3 Fan settings ............................................................................................................................... 61
6.2.1.1.4 Stepless to Step......................................................................................................................... 62
6.2.1.1.5 Setting outside temperature limit ............................................................................................... 62
6.2.1.1.6 Setting of Heating ...................................................................................................................... 63
6.2.1.1.7 Setting of day and night adjustment........................................................................................... 63
6.2.2 Network settings ........................................................................................................................ 63
6.2.3 UTC time.................................................................................................................................... 65
6.3 Display ...................................................................................................................................... 65
6.4 Backup ...................................................................................................................................... 66
6.4.1 Backup of historical data............................................................................................................ 66
6.4.1.1 IMX based CPU module (2 LAN ports) ...................................................................................... 66
6.4.2 SD card and USB stick .............................................................................................................. 66
6.5 Software update ....................................................................................................................... 68
6.5.1 Preparing for a software update................................................................................................. 69
6.5.2 Carrying out the software update............................................................................................... 69
6.5.3 Check after software update ...................................................................................................... 71
Technical Manual
307Pro • 310Pro
7 General .......................................................................................................................................................... 97
7.1 About......................................................................................................................................... 97
8 Troubleshooting guide................................................................................................................................. 98
8.1 Troubleshooting shared equipment....................................................................................... 98
8.2 Temperature sensor control table.......................................................................................... 99
8.2.1 Table for DOL 114 temperature sensor control ......................................................................... 99
8.2.2 Table for DOL 12 temperature sensor control ......................................................................... 100
Technical Manual
307Pro • 310Pro
Technical Manual
307Pro • 310Pro
1 Product description
307Pro is a one- or two-house climate controller for pig houses, which can regulate and monitor the climate in
the house.
10" and 7" controller display
The displays shown in this manual are from a 10” controller display. When using a controller with a 7” display,
you must press the arrow in the left side of the screen to see the content of the Settings menu.
To select a menu found under Settings, you must first press ,, then , and then to be able to open the
menu you want.
8 Technical Manual
307Pro • 310Pro
2 Procedure
This technical manual deals with the installation of the controller and and is aimed primarily at the technicians
and electricians who will be mounting, installing and testing the controller.
According to current national and in Europe also EU regulations, the installation must be carried out by expert
personnel.
Note that electrical equipment may not be opened without removing the supply voltage, and only competent per-
sonnel may carry out servicing operations and troubleshooting.
In the manual the menus are depicted as tables with primary menus and
sub-menus. The outline is used to give an overview of the setting options
as well as to see where in the menus a given setting can be found.
If a setting is only available in some variants or in specific setups, it is in-
dicated in the table.
It is also possible to search for a function in the search field in the upper
left corner of the page Settings .
The individual functions and settings are described in the following sec-
tions which are presented in the same order as the menus.
The following checklist indicates the main points of the work flow regarding set up of the house controller.
Mounting
1. House controller.
2. Emergency opening, if applicable.
Installation
1. Connect cables according to the circuit diagrams for the emergency opening of the system.
2. Set voltage in the controller.
3. Connect mains voltage to the controller.
4. Select components in the house controller's menu Technical | Installation | Installation wizard by
reviewing all points in the Installation Installation wizard.
5. Connect the individual components by means of the controller's menu Technical | Installation |
Show connections and the circuit diagrams.
6. Customize the controller page views to show precisely those functions and values used in the individual
house.
7. Adjust the system.
8. Test the system.
Start-up
1. Setting and calibration.
Technical Manual 9
307Pro • 310Pro
3 Installation guide
10 Technical Manual
307Pro • 310Pro
Technical Manual 11
307Pro • 310Pro
The same I/O allocation in several controllers – i.e. when the in-
dividual components are connected to the same terminal num-
bers – is ensured by saving the set-up on a USB stick and en-
tering the set-up into several controllers.
Press the arrow buttons in the top right corner to move one step
forwards or backwards in the installation.
Press the X in the upper left corner to terminate the installation
before all steps are completed.
Press Cancel to finish without saving.
Press Confirm to save changes.
Also see section Procedure [} 9] for an overview of the com-
plete procedure for setting up the house controller.
12 Technical Manual
307Pro • 310Pro
If the connection between the controllers is lost, an alarm appears on both the ‘Master’ and the ‘Client’
controller.
Technical Manual 13
307Pro • 310Pro
14 Technical Manual
307Pro • 310Pro
1 zone setup
Air inlet
Side inlet Number of side inlets
Side inlet None
Relay with feedback
Relay without feedback
0-10V with feedback
0-10V without feedback
Relay with feedback and with M.O.sw.
Relay without feedback and with M.O.sw
Combi diffuse inlet Settings for Combi diffuse Combi diffuse None
inlet
Inside temperature
Outside temperature
Inside and outside tem-
perature
Technical Manual 15
307Pro • 310Pro
16 Technical Manual
307Pro • 310Pro
Air outlets
Side outlet Load stepless fan settings Last loaded
Load stepless fan settings
Stepless Air outlets None
Relay with feedback
Relay without feedback
0-10V with feedback
0-10V without feedback
Relay with feedback and
with M.O.sw.
Relay without feedback
and with M.O.sw
Fan speed controller None
Internal
0-10 V
0-10 V + stop relay
Dynamic Air stepless Number of outlets
Number of sensors
Fan speed controller Power supply 200 V
210 V
220 V
230 V
240 V
250 V
Stop fan 5.0 V
Full speed 5.0 V
MultiStep system Number of side MultiStep
MultiStep system Standard
Dynamic MultiStep
Flap control MultiStep
Fans active at failure MultiStep
Natural outlet Natural outlet No
Relay with feedback
Relay without feedback
0-10V with feedback
0-10V without feedback
Relay with feedback and with M.O.sw.
Relay without feedback and with M.O.sw
Tunnel outlet Stepless fan Air outlets None
Relay with feedback
Relay without feedback
0-10V with feedback
0-10V without feedback
Technical Manual 17
307Pro • 310Pro
2 zone setup
Air inlet
Front inlet/ Rear Inlet Inlet None
Relay with feedback
Relay without feedback
0-10V with feedback
0-10V without feedback
Relay with feedback and with M.O.sw.
Relay without feedback and with M.O.sw
Tunnel inlet Tunnel inlet None
Relay with feedback
Relay without feedback
0-10V with feedback
18 Technical Manual
307Pro • 310Pro
Technical Manual 19
307Pro • 310Pro
20 Technical Manual
307Pro • 310Pro
Technical Manual 21
307Pro • 310Pro
Outlet fan No
Internal
0-10V
0-10V with stop relay
Inlet temperature sensor Yes/No
Inlet temperature sensor DOL 12
type
DOL 15/114
Anti ice temperature sen- Yes/No
sor
Anti ice temperature sen- DOL 12
sor type
DOL 15/114
Anti ice heater Yes/No
Cleaning system Yes/No
EMERGENCY OPENING
378 T Yes/No
Emergency inlet Yes/No
Emergency inlet Front/ Yes/No
Rear
HOUSE HEATERS
Heat controlled by own ON/OFF
sensor
Number of heaters One zone: Own sensor: 0- 2
Common: 0- 6
Two zone: Own sensor: (0-2 Front /
0-2 Rear)
Common: (0-4 Front / 0-4
Rear)
House heaters Type None
Relay
0-10V
Heater slave relay 1-2 Yes/No
FLOOR HEATING
Floor heating mode None
0-10V - No sensor
Relay - No sensor
0-10V - With sensor
Relay - With sensor
Floor heating temperature DOL 12/DOL 114
sensor
STAND-ALONE HEATER
Number of stand-alone 0-4 (2 Front / 2 Rear)
heaters
Heater 1-4 type None/ Relay/ 0-10V
COOLING
Side cooling
22 Technical Manual
307Pro • 310Pro
HOUSE TYPE
House type settings Loaded house type
Load house type settings
3.9 Climate
3.9.1 One- and two-zone control
Two-zone control is only available in CT variants and the LPV variant with eight MultiStep.
Technical Manual 23
307Pro • 310Pro
The livestock house can be controlled as two separate zones: front and rear. Thus, the following functions must
be set up separately for each zone: Temperature and humidity sensor, air inlet, air outlet, emergency opening,
heating, stir fan, stand alone heating and side cooling.
The functionality is also useful in houses where used litter is stored in the inactive zone in the house. It is possi-
ble to use the air outlets in the inactive zone.
Roof inlet Air inlet in the roof which regulates via a flap, a fan and a recirculation fan.
Side inlet E.g. wall inlets regulated by a winch motor.
Tunnel inlet Tunnel openings regulated by a winch motor.
The function Manual tunnel input enables the connection of a change-over switch so
the change to/from side mode to tunnel ventilation can be carried out manually.
A combination of the three types of air inlets - Roof, Side and Tunnel - allows the possibility to accommodate an
increasing need for ventilation by automatic adjustment of the fan mode.
Combi diffuse inlet Air intake via ceiling inlets as a supplement to air intake via diffuse ceiling plates.
Combi diffuse is a low pressure system, where the amount of air is regulated exclusively with the aid of low
pressure in the livestock house.
During cold periods, air is taken in through the ceiling, where fresh air is added through tiny holes or pores. This
ensures low air velocity and minimizes the risk of draughts in the animals' living quarters.
During hot periods, an additional air inlet can be opened (typically ceiling inlets). This ensures increased air ve-
locity and thus a cooling effect in the animals' living quarters.
When setting up the Combi diffuse air inlet, select which climate
conditions (inside and outside temperature) must be fulfilled be-
fore the inlet opens.
24 Technical Manual
307Pro • 310Pro
Air inlet %
Max. air inlet position
Air outlet
Air inlet
Min. air inlet position
Figure 1: Cycle time. Cycle time: the flap in the air inlet is regulated according to cycle time
Air outlet
Air inlet
Min. air inlet position
Figure 2: Stop flaps. Stop flap: the flap in the air inlet remains in the current position regardless of the ventilation level.
Air outlet
Air inlet
Min. air inlet position
Figure 3: Open only. Open only: the flap in the air inlet remains in the current position, but is able to open further if the need
for ventilation increases.
Technical Manual 25
307Pro • 310Pro
Exhaustion %
Air outlet
Air inlet
Heat time
Figure 4: Stopping fans in air outlet. The fans in the air outlets will stop completely for a short period, e.g. 10 minutes. This
will also help to prevent the formation of ice in the air inlets.
Zone 3
Zone 2
Zone 1
Zone 6
Zone 5
Zone 4
Select the menu Technical | Installation | Manual installation | Climate | Air inlet | Zone setup
26 Technical Manual
307Pro • 310Pro
Select the menu Technical | Installation | Manual installation | Climate| Ventilation | Air outlet|
Select a type of outlet | Fan speed control
Power supply Enter the typical mains supply voltage to obtain correct control of the fan.
Select the menu Technical | Installation | Manual installation | Climate | Ventilation | Air outlet|
Select a type of outlet | Fan speed control
Stop fan Voltage at 0 % fan capacity.
Full speed Voltage at 100 % fan capacity.
Note that the factory setting for both menu items is 5.0 V. The house controller will send an alarm if the settings
are not adjusted.
Technical Manual 27
307Pro • 310Pro
Dynamic MultiStep makes it possible to reduce power consumption for the fans in the MultiStep system. This is
achieved by the fans' ability to run at two speeds (Low and High) and by letting them run as long as possible at
low speed.
When a low level of ventilation is needed ventilation is carried out as an ordinary MultiStep system, but the fan
output is limited so that it can only provide a percentage of the fan's maximum capacity.
All exhaust units that are set up to run only in the low area in the Dynamic MultiStep system must be able to run
at reduced capacity.
When a high degree of ventilation is required, the fan output varies steplessly from low to full speed and the
flaps are fully open.
28 Technical Manual
307Pro • 310Pro
Ventilation sequence
From low to high regulation
Method of Operation
Flap in stepless unit: The stepless ventilation sequence is
achieved by opening and closing the flap.
Technical Manual 29
307Pro • 310Pro
Low
High
Stepless unit Variable ON/OFF Variable ON/OFF
Flap: stepless Flap: ON/OFF Flap: ON/OFF
Fan: Stepless Fan: stepless Fan: stepless
Low High
Figure 7: Dynamic MultiStep All fans are variable
30 Technical Manual
307Pro • 310Pro
Technical Manual 31
307Pro • 310Pro
Stepless unit Variable ON/OFF Variable ON/OFF Variable ON/OFF Variable ON/OFF
Flap: stepless Flap: ON/OFF Flap: ON/OFF Flap: ON/OFF Flap: ON/OFF Fan: ON/OFF
Fan: Stepless Fan: stepless Fan: stepless Fan: ON/OFF Fan: ON/OFF
Low High
32 Technical Manual
307Pro • 310Pro
Measuring the varying stepless output provides an accurate expression of the output of the ventilation system
according to which regulation can be carried out by varying fan revolutions/flap position.
Technically, one sensor is sufficient for 6 chimneys, but Big Dutchman usually recommends that a Dynamic Air
sensor be installed in every other stepless exhaust unit in order to ensure optimum regulation conditions. The
house controller regulates stepless air outlet without sensors based on a calculated output.
Chimney type Choice of in which type of air outlet the Dynamic Air sensor is placed, so that cli-
mate controller can adjust the air measurement according to the dimensions of
the air outlet.
Minimum fan speed When applying Dynamic Control and frequency-controlled stepless speed control
(0-10 V), a minimum fan speed can be entered, so it does not run too slowly.
Although Dynamic Control has been selected, it is important that the curve values
of the fan in the stepless outlet are also set, due to the fact that climate controller
will regulate according to these values in case of an error situation.
Technical Manual 33
307Pro • 310Pro
To ensure that the chimney can provide the necessary air output, the climate controller will increase the flap
opening by 2% pr. minute (in relation to the stepless curve), if the fan has been running at maximum speed for
more than 1 minute.
In the same way the climate controller will reduce the flap opening by 2% pr. minute (in relation to the stepless
curve) when the fan speed is 10% below the maximum speed for 1 minute. This helps to ensure that the flap po-
sition is stable and does not alternate between opening and closing.
Tunnel block by outside Select if the house controller must block the change to tunnel as long as the outside
temperature temperature is below the settings in the batch curve for outside temperature.
Maximum air speed Read-out of the maximum achievable air speed. It is calculated based on maximum
air output and the cross-sectional area of the house.
3.9.4.6 Shared air outlet - use of the same fan for side and tunnel control
With this function one fan can be use for both side and tunnel ventilation.
When the fan is physically placed in the livestock house to contribute at both side and tunnel ventilation, the
controller can use it for both. Thus the purpose of this function is to reduce the costs of acquisition and installa-
tion of the ventilation system, both when it comes to number of fans and the need for I/O modules in the climate
controller. It is possible to share fans both for stepless, MultiStep and Dynamic MultiStep.
For Dynamic MultiStep we recommend that you share all variable ON/OFF fans.
Press and and select the menu Technical | Installation | Manual installation | Climate | Air outlet
First install the air outlet as usual by installing side and tunnel
outlets.
Then select how many stepless and MultiStep should be
shared.
Conditions for sharing:
• An air outlet can only be shared once.
• Side and tunnel must be setup in exactly the same way (re-
lay/0-10V, speed control, motor/air controlled).
Note that the climate controller will automatically remove the
sharing, if it is not possible.
Set up the individual shared air outlets:
Terminal: Select if the shared air outlet should use the connec-
tion from the tunnel or side outlet.
Tunnel outlet: Select which stepless/MultiStep should be used
as tunnel outlet.
Side outlet: Select which stepless/MultiStep the side outlet
should be shared with.
34 Technical Manual
307Pro • 310Pro
Limitation:
Use only shared air outlets installed with additional ventilation from tunnel fans and Dynamic Multi-
Step together with Stepless to Step Automatic. See also the sections Settings [} 57] and Stepless to
Step [} 62].
Technical Manual 35
307Pro • 310Pro
Natural outlet setup Regulatory interlinking of air inlet and air outlet
Start/Stop conditions Selecting start and stop conditions for Natural ventilation.
by:
Relative values: Start/stop is relative to the setting and therefore follow the related
batch curve, see also the User manual for the climate controller.
Absolute values: Fixed values that are not changed during the batch course. Only
changed by means of operation.
At Natural ventilation, the opening of the air inlets is adjusted based on the input from the inside temperature
sensors - and possibly a weather station. The livestock house can be divided into areas. Each area can be con-
nected to one or several temperature sensors.
Setup of temperature sensors
You can set up several temperature sensors in the livestock
house to register the temperature in each zone.
If several sensors are being used for the same inlet, the same
inlet, the controller calculates an average temperature accord-
ing to which the controller carries out the regulation.
36 Technical Manual
307Pro • 310Pro
Air outlet 1
Air outlet 2
Minimum ventilation Setting up whether Minimum ventilation shall be shown either as a percentage of
the nominal ventilation rate or as m3/h per animal (real air).
3.9.8 Heating
Room heating can be regulated as common or individual heating, depending on the number of temperature sen-
sors (not for Heat controlled by own sensor).
Common regulation: A sensor combination with a common setpoint for all room heaters
Heat control Choose whether heat sources 1 and 2 should start in parallel or sequentially.
(only house heaters)
Heat distribution Distribution of capacity between heat sources 1 and 2 (for separate heat control only)
Sequential heating is typically used when there are two different heat sources in the
house.
For example:
• heating pipes and air heaters
• heating pipes and blow heater as extra capacity
Technical Manual 37
307Pro • 310Pro
It is important to distribute correctly between the two types of heat sources, in order to
obtain a steady heat control. The heating system’s dimensions and output determine the
actual distribution.
Temperature sensor se- Location of temperature sensors for ventilation and heat control.
lection
You can set up several temperature sensors in the livestock house to register the
temperature in each area.
Tunnel cooling sensor Setup of the tunnel cooling sensors to be used for tunnel cooling.
setup
Tunnel cooling sensors: A temperature sensor dedicated to tunnel cooling.
With this control the sensor must also be set up for alarms for tunnel cooling and for
controlling the cooling respectively.
Tunnel temperature: An average from the temperature sensors showing tunnel tem-
perature.
Temperature sensor: A temperature sensor placed appropriately in relation to tun-
nel cooling.
38 Technical Manual
307Pro • 310Pro
Note that in an emergency situation the house controller cannot regulate according to temperature and
humidity. If you select Yes (Active at failure), side cooling runs no matter whether the temperature is too
low and humidity is too high in the house.
Note also that a combination of a high inside temperature and high air humidity can be life-threatening to
the animals.
Cooling type Selection between types of tunnel cooling (High pressure spray/Pad).
Cooling mode Only with high pressure spray and multiple cooling relays.
The tunnel cooling relays can be controlled in sequence or in parallel.
Tunnel cooling relay 1 The percentage share between cooling relays that are controlled sequentially.
ratio
E.g. with two relays: 50 %/50 %
The controller automatically calculates the percentage share for relay 1.
For sequential tunnel cooling, cooling can be set up for MultiStep-like regulation in
order to avoid major temperature differences in the house.
Technical Manual 39
307Pro • 310Pro
0-10 V
Control method: temperature.
The stir fan is regulated with a minimum and a maximum speed based on a positive temperature offset at the
temperature sensor.
See elaborate descriptions of the control methods in the climate controller’s User Manual.
3.10 Production
3.10.1 Light control
The main light can be fitted with a light dimmer.
The light control consists of two different types of light: main light and inspection light.
Light dimmers with relays are used in houses, where the light source used cannot be switched off by means of
the dimmer alone.
Light control
Main light Setting the main light with or without dimmer, with or without relay.
Number of light sensors Setting the number of light sensors.
Light control settings
Light sensor settings Selecting light sensor type.
Main light This is used to name a light source according to function, so that it can be recog-
nized in the menus and alarms.
Light intensity unit Lux or percentage.
Light sensor controlled
Use boost This is used for light fixtures that cannot be switched on unless they start at maxi-
mum power for a short period of time.
Max. light intensity Setting how wide a scale you should be able to adjust the light within. This en-
ables you to adapt the light control to the type of light source used in the house.
The scale can be set from 1-1000 lux and the factory setting is 100 lux.
Inspection light Setting up if inspection light is available or not.
Inspection light settings Duration: Setting an active period and light sources for the inspection light.
Active: Activation or deactivation of inspection light.
Light intensity: When a light source has been installed with a light dimmer, a re-
quired light intensity (lux) for the inspection light can also be set.
Light dimmer boost time Setting the duration of the boost when the light is turned on.
40 Technical Manual
307Pro • 310Pro
When light has been installed with a light dimmer, it can turn on using a so-called
boost. It means that it turns on with the maximum intensity and that it then adjusts
according to the setting.
Light active at failure Setting if the light should switch on at power failure.
When installing light you must decide how the function is to re-
act in an emergency situation.
Yes: In case of control failure, the light is on.
No: In case of control failure, the light is off.
3.10.2 Water
Number of water meters Setting the number of water meters.
Liters pr. pulse Setting the number of liters that runs through the water meter for every pulse.
Water meter settings By selecting a relay for a water meter, it is possible to shut off the water in the
event of excessive water consumption.
The relay cannot be activated in the event of power failure. In this case the water
will be switched on.
Technical Manual 41
307Pro • 310Pro
Name Naming of 24-hour clock according to function, so that it can be recognized in the
menus.
Timer Select if the 24-hour clock is to regulate according to Stop time or ON time.
Stop time: Set the time for start and stop.
ON time: Set a time for start and how long the function will run.
3.11 Management
3.11.1 Set up equipment monitoring
Select number of current sensors.
Then select the function to be monitored by each sensor. One
function, for example, MultiStep 3 can be associated with multi-
ple current sensors.
The function can be named for recognition in alarm log and
overview.
3.11.2 Auxiliary
Number of auxiliary sen- Select a number of auxiliary sensors.
sors
Auxiliary sensor setup Select the required type of auxiliary sensor.
Name the auxiliary sensor according to function to make it recognizable in alarms
and other info.
42 Technical Manual
307Pro • 310Pro
4 Calibration
4.1 The menu calibration
Climate
Calibrate inlets Side inlet Autocalibration time of day
Run time
Runs before autocalibration
Minimum voltage
Maximum voltage
Side inlet
Calibration
Combi diffuse inlet Autocalibration time of day
Run time
Runs before autocalibration
Minimum voltage
Maximum voltage
Combi diffuse inlet
Calibration
Roof inlet Autocalibration time of day
Run time
Runs before autocalibration
Minimum voltage
Maximum voltage
Roof inlet position
Calibration
Tunnel inlet Autocalibration time of day
Tunnel inlet time
Tunnel runs before calibration
Minimum voltage
Maximum voltage
Calibrate tunnel inlet
Natural inlets Autocalibration time of day
Run time
Runs before autocalibration
Minimum voltage
Maximum voltage
Inlets
Calibration
Calibrate air outlet flap Run time
Runs before autocalibration
Technical Manual 43
307Pro • 310Pro
44 Technical Manual
307Pro • 310Pro
Production
Calibrate light Manual calibration Yes/No
Main light Output - Illuminance ON/OFF - Illuminance
Calibrate light sensors Enter value from calibration in-
strument
Light sensor value too low to
calibrate
Light sensor 1 correction factor
Light sensor 1
Technical Manual 45
307Pro • 310Pro
Winch motors with feedback must be calibrated by a technician, while winch motors without feedback are cali-
brated automatically once the technician has set up a time for Air inlet time.
During the automatic calibration, the air inlets/air outlets open and close completely for a short time and then re-
turns to the position which the controller calculates.
The change-over switch on the winch motor must be se to AUT.
Run time Setting of the time it takes to run from fully open to fully closed.
Runs before recalibra- Setting of the number of times the inlet flap has to run before it calibrates automati-
tion cally.
Minimum voltage When the air inlets or air outlets are 0-10 V controlled, the output voltage can be ad-
justed via Min. voltage and Max. voltage.
Maximum voltage
Calibration of other air inlets and air outlets are carried out in the same way.
46 Technical Manual
307Pro • 310Pro
Wind speed minimum speed Enter a Minimum value and a Maximum value to indicate the area
within which the weather station can measure.
Wind speed maximum speed
The sensor's offset should only be changed when there are no animals in the house and it has been thoroughly
ventilated.
The offset adjustment should always be carried out in relation to atmospheric air and not in relation to other
types of CO2 sensors.
Technical Manual 47
307Pro • 310Pro
1. Replace the air in the house in Empty house mode by running with 100% exhaust and 100% open inlets for
at least 20 minutes. The reading of the CO2 level should now be 450 ppm +/- 50 ppm or the same value as
the atmospheric air +/- 50 ppm.
2. Check if the reading deviates more than +/- 50 ppm from 450 ppm (or from the same value as the atmo-
spheric air value).
3. If the reading deviates more than the +/-50 ppm the sensor must be offset-adjusted to atmospheric air as
follows: Adjust Calibration offset until the read CO2 value shows 450 ppm.
The other values must not be changed.
Checking the sensor reading is recommended each time the house is in Empty house mode.
Note: Offset adjustment should only be carried out by staff trained by Big Dutchman.
48 Technical Manual
307Pro • 310Pro
Relay-controlled light
Enter the measured lux value for ON.
Light dimmer
Enter a lux value which corresponds to the measured light level
at the given voltage.
Technical Manual 49
307Pro • 310Pro
5 Testing
After installation of the system a thorough test must be carried out, to ensure that the system works as intended.
The component currently set for manual control are listed in the
menu Technical | Manual/Auto | Manual mode.
The manual control can also be deactivated here.
50 Technical Manual
307Pro • 310Pro
After testing the components, you must set the function back to automatic control, so that the house
controller continues to operate as before.
I/O will remain in the setting that it was on at the moment the component was set to manual. This means that
operation continues when it is returned to automatic control.
Repeat the test for the installed air inlets and outlets.
Technical Manual 51
307Pro • 310Pro
The testing of fans for Dynamic MultiStep is done in the same way as described for Stepless fans. See section
Stepless fans [} 52].
52 Technical Manual
307Pro • 310Pro
5.2.1.5 MultiStep
This test is to show that flaps and fans in the chimneys work in relation to each other.
The installed MultiStep units should be tested in the same way for each step, by checking the exhaust units indi-
vidually.
Deactivate MultiStep 1.
Check that the swivel shutter in the chimney closes again.
When the shutter is less than approx. 15% open, the fan must
stop.
Heating
• Check that the unit which you activate in the house controller is the unit intended for the house.
Relay heating
Technical Manual 53
307Pro • 310Pro
54 Technical Manual
307Pro • 310Pro
Test the light dimmer by increasing and dimming the light inten-
sity.
Set the Light dimmer requirement to maximum.
Set to medium and check that the light is dimmed in the house.
Set the Light dimmer requirement to 0 and check that the light
is off in the house.
Technical Manual 55
307Pro • 310Pro
56 Technical Manual
307Pro • 310Pro
6 Service
Settings Climate
Production
Network settings
UTC time
Display [} 65] Display
Backup [} 66] CPU module
SD card
USB stick
General Save logs
Install software [} 68]
Control parameters Control parameters
Negative pressure Pressure curves
Adjust pressure curve
Stepless Adjustment of Stepless
System Reset [} 96]
Diagnostics
6.2 Settings
Technical Manual 57
307Pro • 310Pro
Sequential
Stepless tunnel distribu- Parallel
tion
Sequential
Power up delay 00:03 mm:ss
Rotate ON/OFF
Maximum output
Stepless to Step Auto- ON/OFF
matic
Stepless to Step
Outside temperature limit Inlet limit 100%
Outside temperature
curve
Gradual limit 5℃
Heat recovery unit Cleaning pre runtime
Cleaning Minimum ON
time
Heating House heater Pre runtime
Adjust heaters 0-10V Heater 1 min. voltage
Heater 1 max. voltage
Heat control Parallel
Sequential
Heating 1 ratio 50%
Stand-alone heaters Pre runtime
Adjust heaters 0-10V Minimum voltage
58 Technical Manual
307Pro • 310Pro
Only climate
Only production
IP configuration MAC address
IP configuration mode
IP address
Net mask
Gateway IP address
Configuration of IP ad- IP configuration mode Static IP
dress
DHCP
IP address
Net mask
Gateway IP address
UTC-time
6.2.1.1 Climate
6.2.1.1.1 Setting natural ventilation
This section is relevant only to houses with a weather station.
Location Indicate where the air inlets are placed physically in the house.
This is used when the inlets are regulated in relation to the wind direction.
Side: Right or left side of the house.
Location: Front, middle or back of the house (in relation to the placement of
the house controller).
Limitation factor The controller limits the opening of the air inlets using the set factor.
The discontinuance of limita- When the outside temperature exceeds the Temperature setpoint by the
tion if outside temperature ex- specified number of degrees, the controller reduced the limitation of the air in-
ceeds the temperature set- let opening.
point
Left
Right
Rear
Middle
Front
Technical Manual 59
307Pro • 310Pro
Figure 13: The limitation of the opening of the air inlets based on wind direction
On the windward side of the house the opening of the air inlets is limited based on wind direction. The more of-
ten the wind is directly on the house and the stronger it is, the small will the opening of the air inlet be.
Wind direction (*) Wind speed (m/s) Air inlet 1 opening Air inlet 2 opening Air inlet 3 opening
(%) (%) (%)
60-90 <6 100 100 100
7 72 72 72
9 44 44 44
10 30 30 30
60 Technical Manual
307Pro • 310Pro
In order to obtain correct adjustment of the house climate with MultiStep, you must adjust the climate controller
using the ventilation system data:
• Nominal air output of the system in m3/h (air requirement of the animals).
• Exhaustion capacity of the stepless exhaustion unit(s)
• Exhaustion capacity of the various steps, MultiStep
In addition, it is possible to use two stepless units for Tunnel ventilation in the same way as for MultiStep so that
the Tunnel ventilation is also regulated steplessly.
When two stepless fans are used, they can be set up to work in
parallel or sequentially.
This also applies to stepless fans in tunnel.
Rotate This function makes the controller switch between activating MultiStep with the
same output.
This will ensure that the operating time is distributed evenly between the fans. This
will prevent some fans from wearing out while others rust.
Rotate timer Setting for the time, after which the house controller switches to the next MultiStep
with the same output.
Maximum output The ventilation system's maximum output, as a percentage. This value is calculated
based on the data entered.
Technical Manual 61
307Pro • 310Pro
When the function Stepless to Step Automatic is active, the controller automatically switches from Stepless to
step adjustment when tunnel MultiStep is activated.
Stepless to Step shows the ventilation percentage when the change is made.
Stepless MultiStep 1 MultiStep 2 MultiStep 3 Tunnel MultiStep 1 Tunnel MultiStep 2 Tunnel MultiStep 3
10,000 m3/h 10,000 m3/h 20,000 m3/h 40,000 m3/h 58,300 m3/h 58,300 m3/h 116,600 m3/h
The unit output at different ventilation requirements
Stepless mode
Adjustment in steps
Ventilation Tunnel MultiStep 1 is also used for side
requirement ventilation
Figure 15: Transition from Stepless to Step adjustment.
Outside temperature Ventilation limitation via outside temperature can be adjusted to the age of the ani-
limit mals over two curve points.
62 Technical Manual
307Pro • 310Pro
Below this outside temperature, the flaps will not open more than Inlet limit.
°C
Day Limit
0 21 °C
35 18 °C
Day
Figure 16: Curve for outside temperature limit
The Outside temperature limit can be regulated via a curve over two day numbers so that ventilation can be lim-
ited when there are small animals in the house. The limit is factory set to 18 °C for both day numbers.
Return period When the function is ended, the temperature adjustment will be stopped after this pe-
riod.
Technical Manual 63
307Pro • 310Pro
A controller may be the ‘Master’ of, for example, an outside temperature sensor, but at the same time be the
‘Client’ of a outside humidity sensor connected to another controller.
Figure 17: Example of network setup in two houses each with 3 controllers.
Usually, 3 controllers in each of the 2 houses would mean that you would have to install 6 outside temperature
sensors. However, if all of the 6 controllers are connected in the same network, they may share information from
one single outside temperature sensor.
The management program BigFarmNet Manager has access to the house controllers through the network of the
farm.
MAC address MAC address of the controller. It is, for example, used in connection with error tracing
in the network.
Note that if the connection between the ‘Master’ and the ‘Client’ controllers is interrupted, the
‘Client’ controller loses information from the shared equipment.
64 Technical Manual
307Pro • 310Pro
House 2
House 1
6.3 Display
Select the menu Technical | Service | Display
Backlight Adjust the brightness of the display to best suit the current location of the controller.
Backlight (Dimmed) Set the brightness of the display when the controller is not being used.
Backlight timeout Setting the time from when the controller was operated and until the backlight
dimmes.
Technical Manual 65
307Pro • 310Pro
6.4 Backup
Select the menu Technical | Service | Backup
This CPU module will automatically save This CPU module will automatically save all
all historical data to the SD card, regard- historical data to the internal memory and
less of how menu settings have been only use the SD card as backup media.
made.
66 Technical Manual
307Pro • 310Pro
When the settings and pages are saved on the SD card, the
house name, date and time is added automatically.
When loading you can select between loading settings, loading
pages or loading settings and pages.
Note that the CAN protocol and IP setup is also saved when using the backup function.
Technical Manual 67
307Pro • 310Pro
Please note that there should only be one USB stick in the CPU module at a time when it is used
for storage of data and logs.
Save Save settings and pages from the controller on the SD card or USB stick.
Load Load settings and pages from the SD card or USB stick onto the controller.
Backup Create a backup copy of the controller data. Among other things data comprises
settings, pages, historical data, house name, IP address, calibration values, etc.
Restore Restore data on the controller from the backup. Among other things data comprises
settings, pages, historical data, house name, IP address, calibration values, etc.
Daily backup Activate backup of the controller data every night at 01:30.
Format SD card Erases all data from the SD card or USB stick.
Format USB stick
SD card status See the status of the SD card or USB stick.
USB stick status
Big Dutchman recommends that you always save the setup on a USB stick before updating a program.
In 2-house controllers the backup can be used to transfer all settings from one house to the second
house. Set up the first house and make a backup. The restore the data in the second house.
68 Technical Manual
307Pro • 310Pro
If there are animals in the house, climate and production functions which need to be run manually
during the update must be activated now.
Technical Manual 69
307Pro • 310Pro
3. Insert the USB stick containing the software update in the USB port (C) on the CPU module.
Do not remove the USB stick until the installation is fully completed. In other words, when the graphical user in-
terface is accessible and usable.
The software update is now complete.
If necessary, check the software version number via the menu General | About | Software.
70 Technical Manual
307Pro • 310Pro
Technical Manual 71
307Pro • 310Pro
72 Technical Manual
307Pro • 310Pro
Technical Manual 73
307Pro • 310Pro
Figure 19: The P-band control will be less stable as the systems will start and stop to maintain the required setting.
Figure 20: PID control is a stable control as the climate controller continuously adapts the control to the required setting.
74 Technical Manual
307Pro • 310Pro
Figure 21: Adaptive control will automatically adapt to the changed conditions. The stability of the control depends on the
settings of adaption time.
Soft
Medium
Fast
Fast
Medium
Soft
Figure 22: The regulation takes place within a band. The narrower the band, the faster the regulation can adjust the devia-
tion between setting and measuring point. From the factory the adaption time is set to Medium but it can be changed to Fast
and Soft.
Technical Manual 75
307Pro • 310Pro
Figure 23: Check via the management program BigFarmNet Manager how stable the climate controller is able to keep the
control at the required level. It may be necessary to change the adaption time to make the control react faster or softer.
6.6.3 Ventilation
Side ventilation
P-band adjustment
P-band Working range of the ventilation.
Sample time Time between each calculation of ventilation requirement.
Short time: Fast regulation.
Long time: Calm/slow regulation.
PID regulation
Gain@100 Gain at 0-100 % flap opening. Percentage flap per degree deviation from Tempera-
ture setpoint.
Gain@1
High gain: Large reaction.
Low gain: Small reaction.
Accept band Maximum acceptable error before the controller calculates a new ventilation re-
quirement.
76 Technical Manual
307Pro • 310Pro
Gradual limitation by
Flaps
Limits flap for air inlet. Gradual transition from max. flap limitation to 100 %.
Ventilation
Limits flap for air inlet and outlet. Gradual transition from max. flap limitation to 100
%.
Switch function
Limits flap for air inlet. Immediate transition from max. flap limitation to 100 %.
Hysteresis Changes smaller than this hysteresis are not made but summed up until they ex-
ceed the hysteresis.
See section Adaptive control [} 75] for a general description of adaptive control.
Minimum ON time
At ventilation requirement: The fan is ON for minimum this time.
Technical Manual 77
307Pro • 310Pro
Accept band The air intake is only regulated if the current position deviates more from the de-
sired position than the accept band allows.
Maximum inlet position Maximum inlet position for the air inlet when controlled according to cycle time.
Hysteresis The de-ice function stops when the outside temperature exceeds the temperature
set for de-icing + the temperature hysteresis.
Heat time The interval within one hour during which the fan in the air outlet stops. The function
can be overridden by setting heat time to 0.
Cycle time
Side ventilation Cycle time. The total running time for steps, which modulate (ON + OFF-time) or at
Cycle time.
Minimum ON/OFF time. When a step is activated, it will be ON/OFF for at least this
time. ON/OFF at Cycle time.
Air inlet delay
Open: Opening delay of air inlet at Cycle time.
Close: Closing delay of air intake at Cycle time.
Tunnel ventilation Cycle time. Total running time for cycle ventilation in tunnel mode.
Minimum ON time. The fans will run for at least this time.
Please note that the cycle time function in side mode is only available when a setting is made for the Minimum
air inlet. Also, see section Setting of minimum air inlet [} 91].
78 Technical Manual
307Pro • 310Pro
Exhaustion %
Air inlet %
Sec.
Figure 24: When the ventilation requirement exceeds the capability of the cycle time function, the house controller will again
regulate the ventilation in relation to the inside temperature and air humidity.
6.6.3.6 Comfort
Comfort ventilation
Day At batch production. Setting the comfort temperature as a curve over two day num-
bers.
6.6.4 Heating
6.6.4.1 Room heating and stand-alone heater
Heating is supplied while ventilating. This makes the temperature adjustment as stable as possible and at the
same time it is ensured that ventilation or heating is supplied as soon as it is needed.
However, please note that the ventilation is limited as long as heating is supplied. The more heat is supplied,
the less ventilation is used.
• At 1% heat, ventilation can run up to 10% above the minimum ventilation.
• At 100% heat, the ventilation can only run at minimum ventilation.
Control mode Setting of control mode: PID - user settings or Adaptive - self learning.
Select Adaptive - self learning for the heating to continuously adapt to the changing
conditions in the house.
When using the adaptive control mode an adaption time can be set (in the menu
Climate | Temperature| Heating). This will affect how quickly the controller
will react to changed conditions in the house.
See section Adaptive control [} 75] for a general description of adaptive control.
Relay control
Technical Manual 79
307Pro • 310Pro
Minimum ON time At heating requirement: The heating relay is ON for minimum this time.
Minimum OFF time When the heating relay is released, it is OFF for minimum this time.
At PID regulation
P-band Working range for 0-10 V heating.
Relay
Cycle time ON + OFF-time of the heating relay.
Pre runtime Time from the heating relay is picked up until heating is physically supplied.
At PID regulation
P-band Working area for 0-10 V floor heating.
6.6.5 Cooling
6.6.5.1 Side cooling
When side cooling and humidification are set up on the same relay, the cycle time and ON time are shared.
Minimum ON time At cooling requirement: The side cooling relay is ON for minimum this time.
80 Technical Manual
307Pro • 310Pro
Minimum ON time At cooling requirement: The cooling relay is ON for minimum this time.
Pre runtime Time from the cooling relay is picked up until cooling is physically added (flush
time).
Rinse pads before tunnel The time elapsed from when the pads are rinsed with water until the ventilation
switches to tunnel.
Dry out after rapid tem- A safety function that stops tunnel cooling at low inside temperature (2 oC below set
perature drop tunnel temperature). This is to ensure that the animals are not cooled too much.
The function stops the tunnel cooling and adjusts the ventilation to the air speed re-
quired to make the tunnel cooling start. This ventilation level is maintained for 10
minutes (factory setting) to dry out the pads.
Tunnel cooling can start again from 0% after 10 minutes, if the conditions for tunnel
cooling are fulfilled (air speed, temperature and humidity).
Technical Manual 81
307Pro • 310Pro
Bleed off time (Pad rins- The period in which drainage must run.
ing)
Control mode Setting the control mode to PID - user settings or Adaptive - self learning.
See section Control modes [} 74].
P-band The proportional band according to which cooling is controlled at PID control.
Rinse pads prior to tun- The time elapsed from when the pads are rinsed with water until the ventilation
nel switches to tunnel.
6.6.6 Humidity
6.6.6.1 Humidity control
Maximum temperature At Temperature reduction.
reduction
Setting the maximum reduction from temperature setpoint when humidity ventilation
is used.
High outside tempera- The function requires use of an outside humidity sensor.
ture and humidity
In areas with high outside temperature and humidity, the standard humidity control
does not have a large effect as it just brings in more hot and humid air into the
house. It may therefore be an advantage to stop it and possibly let the inside tem-
perature rise.
Selecting the required humidity control based on climate conditions and the ani-
mals’ needs (Use humidity control. Block humidity control. Increase temperature
+ block humidity control).
Use humidity control: Standard humidity control according to one of the following
principles: Humidity ventilation, Temperature reduction or Humidity heat. The re-
quired principle is selected in the menu Climate | Humidity | Humidity con-
trol mode.
Block humidity control: The house controller blocks the humidity control when it is
hot and humid outside.
Increase temperature + block humidity control: The house controller blocks the
humidity control when it is hot and humid outside and the temperature setpoint is in-
creased to reduce the humidity. You should only select this setting when the ani-
mals are able to withstand a rise in temperature.
See also the section Humidity in the User Manual.
82 Technical Manual
307Pro • 310Pro
The adaption time is set in the menu Climate | Humidity | Settings | Adap-
tive reaction for ventilation.
This feature is only available when a humidity sensor is installed.
See section Adaptive control [} 75] for a general description of adaptive control.
Outside temp. 0 °C/32 Factor for humidity control. Ventilation is changed by the set factor (1.5) for each 1
°F factor % relative humidity at an outside temperature of 0 °C.
Technical Manual 83
307Pro • 310Pro
6.6.6.2 Humidification
Cycle time ON + OFF-time of the humidification relay.
Minimum ON time At humidification requirement: The relay is ON for minimum this time.
P-band The proportional band according to which humidification is controlled.
Integration time Reaction time for humidification.
Short time: Fast reaction.
Long time: Slow reaction.
Sync. start with ventila- The humidification starts at the same time as the fans.
tion fans start
This ensures there is sufficient moving air in the house to distribute the humidifica-
tion.
Stop with ventilation The humidification starts at the and stop same time as the fans.
fans stop
To ensure that there is sufficient carrier air for the humidification, you can set the
humidification to only run in sync with the fans in the exhaust units.
84 Technical Manual
307Pro • 310Pro
Note that if there is not any ventilation requirement, the humidification cannot start
when this type of control is selected.
Start sync. delay The time the fans should run before the humidification starts.
Humidification
Delta demand Change of the air inlet flap position in percentage if the pressure is outside the accept
band.
Sample rate The sample rate is a setting of how often a new calculation is to be made.
Adjustment to outside In areas with very low outside temperatures, the pressure regulation in livestock
temperature houses with ceiling inlet can be adapted to decreasing temperatures by using a pres-
sure curve. A higher pressure level can prevent warm housing air from flowing up into
the air inlet and forming ice.
Technical Manual 85
307Pro • 310Pro
Minimum ventilation
Outside temperature
86 Technical Manual
307Pro • 310Pro
Technical Manual 87
307Pro • 310Pro
Adjust the pressure by making a curve course for the required pressure.
Negative pressure (Pa)
Outlet % Side
0 0
1 5
8 10
16 15
20 27
28 33
33 37
40 42
50 50
60 60
70 70
80 80
90 90
100 100
The controller has different ventilation modes depending on the variant, for example, side, tunnel and roof. It is
possible to set up a ventilation course that switches between these ventilation modes to optimize the ventilation
for changing climatic conditions (e.g. air humidity, inside and outside temperatures). In areas with large fluctua-
tions in the outside temperature, the ventilation sequence can be optimized, from minimum to maximum ventila-
tion, by using one of the three ventilation modes: side, tunnel and roof.
Note that the controller does not regulate according to pressure as long as the pressure adjustment is taking
place. This is shown by a yellow marking on the page, as long as the controller is set up for pressure adjust-
ment. When no adjustment has been made for 30 minutes, the controller returns to automatic adjustment.
88 Technical Manual
307Pro • 310Pro
Technical Manual 89
307Pro • 310Pro
6.7.4 Using two curves for air inlets (side and tunnel)
The climate controller can adjust both side and tunnel inlets according to two different pressure curves.
This is an advantage in, for example, long tunnel houses. By opening the front tunnel inlets first and then open-
ing the next tunnel inlets with a delay, it is easier to reach sufficient air speed and air exchange in the entire live-
stock house.
Tunnel - inlet 2
Tunnel - inlet 1
Figure 29: Example of a house with two separate tunnel inlets that are regulated according to their respective curves.
Two separate curves must be set to allow the air inlets to be ad-
justed independently.
Each inlet must be set up with the curve it is adjusted according
to.
90 Technical Manual
307Pro • 310Pro
Technical Manual 91
307Pro • 310Pro
If a tunnel outlet has also been used for side ventilation, it will, however, still be active when changing to tunnel.
Side inlet
Tunnel outlet
Set the roof pressure curve and tunnel pressure curve in the same way (exhaustion: Tunnel pressure curve: air
speed m/sec.).
92 Technical Manual
307Pro • 310Pro
Flap position
Fan voltage
Output %
With Dynamic MultiStep, two set-ups must be carried out for the stepless units for low regulation and high regu-
lation respectively. Also see section Dynamic MultiStep [} 27]
Pressure curves must therefore be set up for both heat recovery mode and for side mode.
Changing from heat recovery mode to side mode takes place from the last point on the heat recovery unit's
pressure curve (point 10).
For optimal use of the heat recovery unit, the system should be set up to allow the controller to stay in heat re-
covery mode in as large a part of the ventilation sequence as possible.
When adjusting the negative pressure, there are two modes of configuration.
Technical Manual 93
307Pro • 310Pro
Use the side inlet's side curve (Yes). Use the side inlet's side curve (No).
Heat recovery unit is using the side curve Side integrated into the heat recovery curve
The heat recovery unit has no effect on the house The heat recovery unit has major effect on the house
negative pressure. negative pressure.
When the ventilation requirements exceed the heat re- The negative pressure can be controlled throughout
covery unit's capacity, the negative pressure cannot the heat recovery mode.
be controlled in heat recovery mode.
Easy adjustment - as in side. Setting the additional side curve for heat recovery
mode.
Setup
1. Adjust the negative pressure curve for the side mode as for
an LPV house.
2. In the heat recovery unit's negative pressure curve, no side
inlet is shown. The side inlet opening is regulated by the
negative pressure curve.
3. Adjust the negative pressure curve for heat recovery.
With this set-up, the side inlet and outlet are used when the ventilation requirement exceeds the heat recovery
unit's capacity.
94 Technical Manual
307Pro • 310Pro
Adjust the negative pressure curve for the heat recovery unit to
ensure correct negative pressure at all points of the curve. This
curve is used when the heat recovery unit is active.
First set the columns for Heat recovery unit and Side as de-
sired.
Next, adjust the points for Output in order to get the desired
negative pressure.
It is recommended that the points in Side correspond to the first
10 points of the side curve.
There is no regulation in heat recovery unit mode under the following conditions:
• The heat recovery unit has deactivated due to the outside temperature (high/low).
• The heat recovery unit is in cleaning mode.
• The user has turned off the heat recovery unit.
• The ventilation requirement is greater than the heat recovery unit can provide (the last point on the heat re-
covery unit's curve).
Select the menu Technical | Service | Negative pressure | Pressure curves and Heat recovery unit
curve
Activate Show inlet and outlet in curve to make the heat recov-
ery unit use its own curve to adjust the air inlets.
Technical Manual 95
307Pro • 310Pro
Inlet Outlet
0 0
10 25
20 50
40 100
60 100
100 100
Table 7: Natural inlet/outlet curve
6.9 System
6.9.1 Resetting data
Please note that the controller will restart after it has been reset.
Reset settings and pages The controller deletes all settings and restores the factory settings.
Reset BigFarmNet data The controller deletes all data that has been saved in connection with the manage-
ment program. The house must be set up again in the program's configurator.
Factory reset The controller deletes all settings and restores the factory settings. It also deletes all
data that has been saved in connection with the management program (the house
must be set up again in the program’s configurator).
96 Technical Manual
307Pro • 310Pro
7 General
7.1 About
SOFTWARE
Software version
System ID
System name
Build time
CPU MODULE
License request code
MAC address
SDK version
Boot loader version
MAIN MODULE
Type
Software version
Serial no.
Calibrated
ADDITIONAL MODULES
Modules 1-13 Type
Software version
Serial no.
Technical Manual 97
307Pro • 310Pro
8 Troubleshooting guide
• Is there 230 V current on terminals A1+ A2 (if not, check installation fuses and fault current relay)?
• Is the change-over switch of the fan speed controller MAN/AUT set on AUT?
• Is the controller set to automatic control?
• Are the temperature sensors OK?
• Is the motor relay/switch of the fan OK?
• Is the source of heating and its supply OK?
• Is the winch motor and its change-over switches OK?
• Is the electrical connection of the winch motors correct? See the circuit diagrams; please pay extra attention
to the supply voltage via the relays.
• Is the potentiometer of the winch motor adjusted?
• Is the controller installed correctly?
3.
1. Inside <IP_Addr> enter the IP address of the controller you want to check.
98 Technical Manual
307Pro • 310Pro
Technical Manual 99
307Pro • 310Pro
9 Technical data
Electrical
Rated voltage V AC 115*, 200* and 230/240 (*not speed controller)
Operating voltage V AC 103.5-264
Frequency Hz 50/60
Effect W 75
Max. current consumption A 0.7
Main module
Configurable main module. Number 0-10 V:
-11 inputs and 2 outputs – or
- 9 inputs and 4 outputs – or
- 7 inputs and 6 outputs
Inputs 7 x 0-10 V DC input impedance 2.1 mOhm.
Outputs/power supply 2 x 15 V DC power supply +/- 10 % max. 40 mA in total.
2 x motor supply 24 V DC +/- 20 %, 0.4 A 0.4 A (in total for the entire
controller).
2 x supply for winch motor potentiometer 10 V DC max. 40 mA in total.
2 x 0-10 V DC Output impedance 100 Ohm.
Relays 12 x NO/NC potential free.
Max. voltage/current at resistive load 250 V AC / 5 A AC.
Max. voltage/current at inductive load 250 V AC / 2A AC CosPhi 0.8.
1 x alarm relay NC, max. 24 V 2 A, min. 12 V 10 mA (resistive load).
I/O module type 3
IO type 3, 10RL 8AI 8AO With jumpers for configuration of inputs.
Inputs 8 x 0-10 V DC input impedance 2.1 mOhm.
Pulsing Inputs Minimum pulse length: 75 ms.
(e.g. water meter, energy Minimum pulse interval: 75 ms.
meter) Maximum frequency/pulse per sec.: 6 Hz.
Outputs/power supply 8 x 0-10 V DC output impedance 10 Ohm.
1 x motor supply 24V DC +/- 20% 0.4 A.
Relays 10 x NO/NC potential free max.
Max. voltage/current at resistive load 250 V AC / 5 A AC.
Max. voltage/current at inductive load 250 V AC / 2A AC CosPhi 0.8.
Network
Network interface 2 x 10/100 BASE+TX RJ 45
USB 2 x USB 2.0 A type
Accessories
Speed control (output) Motor load max. 6.8 A 230-240 V AC/min. 150 W.
Environment
Operating temperature °C (°F) -10 to +45 (+14 to 113)
Storage temperature °C (°F) -25 to +60 (-13 to +140)
Ambient humidity, operation % RH 0-80
Protection class IP 54 (splash-proof).
It is assumed that the base is level, i.e. ≤ 1.5 mm difference of height
and that the screws of the front panel are tightened with min. 1.5 Nm.
Mechanical
Cable knock-out holes
20 x M25 For metrical cable
glands
Shipment
Dimensions (H x W x D) mm 381 x 400 x 170
Dimensions crated H x W x mm 425 x 555 x 195
D
Weight g 5800
Shipping weight g 6900
10 Functionality
System software L1 T-L1 T-S1 CT+N CT-S1 CE N+T S1 XL
L1
Ventilation mode
LPV X X X X X
Tunnel X X X X X
Combi-Tunnel (tunnel + side) X X
Central exhaust X
Natural X X
Natural feature can be purchased sepa- X
rately
Positive pressure feature can be pur- X X X X X X X X X
chased separately
Ventilation and temperature
2 zone X X
Dynamic Air X X X X X
MultiStep X X X X X X X X X
Dynamic MultiStep (side and tunnel) X X X X X X
Side MultiStep 5 16 4 16 4 8 8 1 8
Tunnel MultiStep 8/16 16
Adaptive ventilation X X X X X X X
PID control (or P-band) X X X X X X X X X
Minimum ventilation in % X X X X X X X X
Number of stepless groups controlled 2 2 2 2 2 2 2 2 2
separately
Number of flaps in each stepless group 2 2 1 2 2 1 1 2 2
Parking of ON/OFF-MultiStep X X X X X
Cycle time minimum ventilation X X X X X
Active pressure control - inlets X X X X X
Comfort control X X X
Heat wave comfort control (batch pro- X X X X X X
duction)
Day and night adjustment X X X X X X
De-ice function for inlets X X X X
Shared air outlets (between side and X X
tunnel)
Central exhaust control (duct pressure X
control)
Dynamic pressure control for central ex- X
haust duct
Extra ventilation (**CT-variant in side- X X X X X
mode)
CO2 minimum ventilation control X X X X
NH3 ventilation X X X X
Outside temperature sensor X X X X X X X X
Stir fan control 4 4 4 4 4 4
Big Dutchman International GmbH • Calveslage • Auf der lage 2 • 49377 Vechta; Germany
Tel. +49(0)4447/801-0 • Fax +49(0)4447/801-237 • big@bigdutchman.com