Professional Documents
Culture Documents
Written Instruction For LP Assignment
Written Instruction For LP Assignment
Written Instruction For LP Assignment
Non-Destructive Evaluation A
1. Scope……………………………………………………………………………………………………………………………..3
3. Personnel Qualifications…………………………………………………………………………………………………3
4. Equipment…………………………………………………………………………………………………………………..3-4
5. Performance Checks……………………………………………………………………………………………………4-5
6. Safety………………………………………………………………………………………………………………………….5-6
8. Testing Instructions……………………………………………………………………………………………………..6-7
9. Reporting…………………………………………………………………………………………………………………….7-8
10.
2
Document: LPT-1482
Procedure for Liquid Revision: 01
Penetrant Testing September 29, 2023
1. Scope:
1.1 This procedure shall be followed for the examination of a steel shaft coupling, 4 inches long,
bore diameter of 1”, outer diameter of 1.75” and a keyway size of 1/4". Type II visible
penetrant, Removal Method C and Developer Form E Nonaqueous Type II will be used for
this procedure.
3. Personnel Qualifications:
3.1 Individuals conducting inspections as per this procedure must possess qualifications and
certifications in alignment with the most recent edition of ASNT SNT-TC-1A and the
company’s personnel qualification protocol.
3.2 Inspections as per this procedure will be conducted exclusively by personnel certified at
Level II or higher in the applicable method.
4. Equipment:
3
4.1.8 Removal Method C: Solvent removable
4.1.9 Developer Form E: Nonaqueous Type II
4.1.10 Solvent cleaner
5. Performance Checks:
4
5.5 Tests for Developer (Nonaqueous Type II):
5.5.1 Verify the expiration date on the developer aerosol can. Do not use developers that have
exceeded their shelf life.
5.5.2 Aerosol cans require agitation before spraying.
5.5.3 A check spray should be performed before spraying the test surface to prevent
spattering of the developer.
6. Safety:
6.1.1 Wear appropriate PPE, including safety boots, safety glasses, gloves, and any additional
gear specified by the safety guidelines of your organization.
6.2.1 Choose a designated, well-ventilated area free from open flames, smoking, and potential
ignition sources.
6.2.2 Ensure the work area is clean and free from flammable materials.
6.2.3 Have suitable fire extinguishers on hand, especially those designated for Class B fires
(flammable liquid fires).
5
6.4.1 Exhaust fans should be installed for the use of dry developers. Inhalation of excessive
amounts can be a health hazard.
8. Testing Instructions:
6
8.5 Developer Application:
8.5.1 Apply a Non-Aqueous wet developer evenly, light, thin coats across the entire surface of
the test specimen. The developer should remain on the surface for a minimum of 10
minutes and a maximum of 30 minutes after it has completely dried.
8.5.2 Inspection shall be performed.
8.6 All discontinuities found shall be evaluated in accordance with the applicable code or
specification as dictated by the client.
8.6.1 Indications shall be determined as either relevant or non-relevant.
8.6.1.1 Relevant indications shall be defined as an indication, which is caused by an actual
discontinuity in the test specimen, with a dimension greater than 1/16”, unless
otherwise specified by the applicable code.
8.6.1.2 Non-relevant indications shall be defined as indications, which may or may not be
caused by an actual discontinuity, which is equal to or smaller than 1/16”, unless
otherwise specified by the applicable code. Non-relevant indications may also be
defined as false indications caused by part geometry or some other abnormality.
8.6.2 Once relevance is determined, indications shall then be defined in terms of type, either
linear or round.
8.6.2.1 Linear indication is defined as an indication having one dimension at least three times
greater than another.
8.6.2.2 Round indication is defined as an indication having a dimension less than three times
greater than another.
8.7 Unless otherwise specified, non-relevant indications shall be checked for relevance by
redressing the area in question and re-inspecting using the same method and technique.
8.8 The client is ultimately responsible for dictating the applicable reject criteria.
8.9 Upon completion of the inspection the test specimen shall be cleaned, and penetrant
materials removed.
9. Reporting:
9.1 All rejected findings shall be reported to the client or client representative immediately.
9.2 Testing and Inspection personnel will produce a report at the end of the job with the
following minimum requirements:
9.2.1 Name of inspector (printed and signed)
9.2.2 Inspector’s certification level and method
9.2.3 Date of inspection
9.2.4 Description of test specimen
7
9.2.5 Liquid penetrant method used
9.2.6 Results of inspection (acceptable or rejected) including types and location
9.2.7 Inspection procedure number including revision level
9.2.8 Acceptance criteria including revision level
9.2.9 Test equipment serial number and calibration due date (as applicable)
9.2.10 Inspection variable (light intensity, temperatures)
9.2.11 Inspection report number
9.2.12 Traceability of test specimens (part number, revision level, serial number)
9.2.13 Penetrant manufacturer, type, and batch number
9.2.14 Developer manufacturer, form, and batch number
9.2.15 Cleaner/Remover manufacturer and type
9.2.16 Test specimen thickness
9.2.17 Client representative name and date (if applicable)
9.2.18 Customer name
9.2.19 Customer project name (if applicable)
9.2.20 Customer PO or job number (if applicable)
9.2.21 Drawing number and revision (if applicable)