3 - RM Electrical Troubleshooting
3 - RM Electrical Troubleshooting
Modulating Class
Electrical
Troubleshooting
for RM Style Units
1
New RM24-42C Style
Electrical Boxes
3
New RM Style Electrical Box
Has 3 lug 10 lug terminal
terminal strip strip for wiring the
for line voltage input side to the
and pump output triggers
PC board part #
Time Delay A-550
part # 4135502
Crydom Relay
part # 4134200
Run and Start
Capacitors
Start Relay
Five triggers come standard for up to five air handlers, and they are
powered up by the same 230 volts that energize the solenoid valve on
the air handlers.
5
Explanation Of Electrical
Components For Condensing Unit
6
Starting Components for all
RM Style
•Start relay senses
the back EMF
generated by
the start windings
•Contacts opens in
seconds as the
•Run cap is motor starts
permanently
connected in
series with the
start winding
•Start cap operates only for a
few seconds during start up.
•Taken out of start winding
circuit by the start relay.
7
Crydom, Solid State Relay
Compressor Relay
Line 1 Load
Output
Terminals 1 & 2
break Line 1 to
the Compressor
and Pump Circuit
Terminals 4 and 3
are the Input side or
the Control voltage Input Line 2
8
Pilot Duty Time Delay
Time Delay is wired in series between the pressure switches and the input
of the crydom relay. This is used to protect the compressor from short cycling.
9
Line Voltage, Pilot Duty, Low
and High Pressure Switches
Pressure switches do not wire into the SMX controls,
they are wired in series with the Time Delay
10
Wiring Diagram for RM
Models
11
Troubleshooting Guide For
The Electrical Components
While trouble shooting a modulating unit, it’s very important to keep in mind
1. On a 230 volt single phase system, we only break line 1 to any component. With
the breaker on to the condensing unit or the air handlers, there will always be
line 2 present. So even on a trigger there is a potential of 115 volts to ground.
2. The high & low pressures are rated for line voltage pilot duty. There is a potential
of 230 volts across the terminals or 115 volts to ground.
3. While working in a RM electrical box, you will need to turn the breaker off to the
condensing and all of the air handlers to insure no voltage to be present.
12
Compressor won’t start from
any Switch Assembly
Always Check for Proper Incoming Voltage
13
Bypassing Everything but the
Starting Components to Power
up the Compressor
Jump Line 1 to P1 Terminal
14
If Compressor doesn’t Start,
Check Starting Components or
Compressor Windings
15
Visually Inspect Run Capacitors
Top is Swollen
19
Check Compressor
Windings
C
R S
R C S
20
Ohm Out The Compressor
Windings
21
If you Don’t have Proper Control
Voltage From PC Board
Check for 230 V from
evaporators to the input
side of the Triggers
22
Checking Operation of the
Crydom Solid State Relay
Make sure the
load is hooked
up and check for
230V output
from terminal # 2
or the purple
wire to line 2
23
Check Operation of the
Time Delay
Check 230 Volts Or Simply Jump out the TD
Between L2 and Terminal 1 Between Terminals 1 and 3
Then Check
Between
L2 and Term 2
24
Checking the Operation of
Pressure Switches / Volt Meter
If no Voltage is Present at Switch If Voltage is Present at Switch
26
Thank You for your
Continued Support
Dometic Environmental