Coordinación de Protecciones

Tramo S2-S1-PG520/U1
Fase / Tierra-Neutro

050324
Amps X 10 PG520 (Nom. kV=23, Plot Ref. kV=23)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
541 MVAsc
CFE 1

R CFE Av - P
500 OC1 500
CFE Av
Foxcoon
751 OCR o

300 CT Ratio 600:5 R CFE Av 300

Cfe Av - VPG Acom 23kV


U3 - U.S. Very Inverse
CB CFE Av
Pickup = 1.168 (0.02 - 3.2 Sec - 5A)
Time Dial = 2.75
3x = 1.6 s, 5x = 0.709 s, 8x = 0.434 s
3-1/C 500
Inst = 20 (0.1 - 20 Sec - 5A)
Time Delay = 0.03 s VPG Acom.
100 100
R S2-J-04 - P
OC1 OCR o

VPG Acomet
Siemens
CB R1-R2
50 7SR12 50

R2 - S2 23kV.
CT Ratio 600:5
ANSI - Extremely Inverse
30 Pickup = 0.14 (0.05 - 2.5 xCT Sec) 3-1/C 500 30
Time Dial = 0.52
3x = 1.9 s, 5x = 0.674 s, 8x = 0.296 s R o

Inst = 2.1 (0.05 - 50 xCT Sec) R S2-J-01

CB S2-J-01
R S1-J01 - P S2

10 OC1 10
Siemens CB S2-J-04.
7SR12 R
CT Ratio 600:5
o

R S2-J-04
ANSI - Extremely Inverse
5 R S2-J-01 - P 5

S2 - S1 23KV
CB S2-J-04
Pickup = 0.13 (0.05 - 2.5 xCT Sec)

Seconds
Seconds

OC1
Time Dial = 0.48
Siemens 3x = 1.75 s, 5x = 0.622 s, 8x = 0.273 s 3-1/C 500
3 7SR12 3
Inst = 1.77 (0.05 - 50 xCT Sec)
CT Ratio 600:5
ANSI - Extremely Inverse R o

R S1-J01
Pickup = 0.15 (0.05 - 2.5 xCT Sec)
CB S1-J-01
Time Dial = 0.55
3x = 2.01 s, 5x = 0.713 s, 8x = 0.313 s S1
Inst = 2.2 (0.05 - 50 xCT Sec)

S1 - PG520 23KV
1 CB S1-J-02 1

R S1-J02
.5 .5
Siemens 3-1/C 3/0
7SR11
.3 CT Ratio 200:5 .3
CB PG-J01
ANSI - Extremely Inverse
Pickup = 0.34 (0.05 - 2.5 xCT Sec) o

R
Time Dial = 0.45
R PG-J01
3x = 1.64 s, 5x = 0.584 s, 8x = 0.256 s
PG520
Inst = 4.4 (0.05 - 50 xCT Sec)

.1 .1

VPG Acomet - P
Entec
.05 ETR102-04_2 .05
Siemens
7SR12 CT Ratio 1000:1
CT Ratio 300:5 Extremally Inverse ANSI
.03 Pickup = 0.125 (0.02 - 3.2 Sec - 1A) .03
ANSI - Extremely Inverse
Pickup = 0.21 (0.05 - 2.5 xCT Sec) Time Dial = 2.2
Time Dial = 0.4 3x = 1.7 s, 5x = 0.618 s, 8x = 0.282 s
3x = 1.46 s, 5x = 0.519 s, 8x = 0.228 s Inst = 2 (0.05 - 15 Sec - 1A)
Inst = 2.41 (0.05 - 50 xCT Sec)

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 10 PG520 (Nom. kV=23, Plot Ref. kV=23) ETAP Star 20.6.0C

Project: FOXCONN Date: 03-03-2024


Location: Vesta Park Guadalajara Nave 7 Fault: Phase
Amps X 10 PG520 (Nom. kV=23, Plot Ref. kV=23)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
541 MVAsc
R CFE Av - N CFE 1
OC1
Foxcoon
500 751 CFE Av
500
CT Ratio 600:5
C2 - IEC Cls B Very Inverse OCR o

300 Pickup = 0.42 (0.1 - 3.2 Sec - 1A) R CFE Av 300

Cfe Av - VPG Acom 23kV


Time Dial = 1 CB CFE Av
3x = 6.75 s, 5x = 3.38 s, 8x = 1.93 s
Inst = 16.7 (0.1 - 20 Sec - 5A)
Time Delay = 0.03 s 3-1/C 500

VPG Acom.
100 100
R S2-J-01 - N
OCR
OC1 o

VPG Acomet
Siemens
CB R1-R2
50 7SR12 50

R2 - S2 23kV.
CT Ratio 600:5
ANSI - Extremely Inverse
30 Pickup = 0.05 (0.05 - 2.5 xCT Sec) 3-1/C 500 30
Time Dial = 0.9
3x = 3.28 s, 5x = 1.17 s, 8x = 0.512 s R o

Inst = 1.76 (0.05 - 50 xCT Sec) R S2-J-01


R S2-J-04 - N
OC1 CB S2-J-01
S2
Siemens
10 7SR12 10
CB S2-J-04.
CT Ratio 600:5
ANSI - Extremely Inverse R o

Pickup = 0.05 (0.05 - 2.5 xCT Sec) R S2-J-04

5 Time Dial = 0.84 5

S2 - S1 23KV
CB S2-J-04

Seconds
Seconds

3x = 3.06 s, 5x = 1.09 s, 8x = 0.478 s


Inst = 1.68 (0.05 - 50 xCT Sec)
3-1/C 500
3 3
R S1-J02 - N
OC1 R o

R S1-J01
Siemens CB S1-J-01
7SR11
CT Ratio 200:5 S1

S1 - PG520 23KV
ANSI - Extremely Inverse
1 CB S1-J-02 1
Pickup = 0.14 (0.05 - 2.5 xCT Sec)
Time Dial = 0.45
3x = 1.64 s, 5x = 0.584 s, 8x = 0.256 s o

R
Inst = 3.29 (0.05 - 50 xCT Sec) R S1-J02
.5 .5
R S1-J01 - N 3-1/C 3/0

OC1
.3 CB PG-J01 .3
Siemens
7SR12 o

CT Ratio 600:5 R

ANSI - Extremely Inverse R PG-J01

Pickup = 0.05 (0.05 - 2.5 xCT Sec) PG520


Time Dial = 0.6
.1 3x = 2.19 s, 5x = 0.778 s, 8x = 0.342 s .1
Inst = 1.39 (0.05 - 50 xCT Sec)

VPG Acomet - G
R PG-J01 - N Entec
.05 .05
OC1 ETR102-04_2
Siemens CT Ratio 1000:1
7SR12 Extremally Inverse ANSI
.03 Pickup = 0.033 (0.02 - 3.2 Sec - 1A) .03
CT Ratio 300:5
ANSI - Extremely Inverse Time Dial = 5.4
Pickup = 0.08 (0.05 - 2.5 xCT Sec) 3x = 4.18 s, 5x = 1.52 s, 8x = 0.693 s
Time Dial = 0.35 Inst = 1.4 (0.05 - 15 Sec - 1A)
3x = 1.28 s, 5x = 0.454 s, 8x = 0.199 s
Inst = 1.65 (0.05 - 50 xCT Sec)
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 10 PG520 (Nom. kV=23, Plot Ref. kV=23) ETAP Star 20.6.0C

Project: FOXCONN Date: 03-03-2024


Location: Vesta Park Guadalajara Nave 7 Fault: Ground
Amps X 100 TGF_PG-01 (Nom. kV=0.48, Plot Ref. kV=0.48)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500

TR-PG-01
300 2000 kVA (Secondary) 6.94 %Z 300
Wye Solid Grd-Wye Solid Grd
Curve Shift = 1

100 CB TGF_PG-01 100


Square-D MICROLOGIC 6.0
Sensor = 4000
LT Pickup = 0.6 (2400 Amps)
50 LT Band = 0.5 50
ST Pickup = 2.5 (6000 Amps)
ST Band = 0.1 (I^x)t = OUT
30 Inst. Pickup = 3 (12000 Amps) 30
R PG-J01 - P
OC1
Siemens
7SR12
CT Ratio 300:5
ANSI - Extremely Inverse
10 Pickup = 0.21 (0.05 - 2.5 xCT Sec) 10
Time Dial = 0.4
3x = 1.46 s, 5x = 0.519 s, 8x = 0.228 s
Inst = 2.41 (0.05 - 50 xCT Sec)
5 5

Seconds
Seconds

3 Fuse1 PG-J-02 3

CB PG-J01
Siba
o
HV- Fuse Links
R Very Fast 24 kV
R PG-J01
125A

1 PG520
1

Fuse1 PG-J-02

.5 .5
PG520 - TGF_PG-01 23KV

TR-PG-01
Inrush
.3 .3
Multiplier = 8 xFLA
3-1/C 1/0 (19245.01 Amps @ 0.48 kV)
Duration = 6 Cycles

.1 TR-PG-01
2000 kVA
.1
PG520 - TGF_PG-0 .48kV

.05 .05
21-1/C 500
CB TGF_PG-01

.03 .03
TGF_PG-01

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 TGF_PG-01 (Nom. kV=0.48, Plot Ref. kV=0.48) ETAP Star 20.6.0C

Project: FOXCONN Date: 03-03-2024


Contract: SN:
Engineer: Rev: Base
Filename: C:\Users\oswaldor\Desktop\Everything\1. Papa\1. Simulaciones\040324\CB PG52 Fault: Phase
Amps X 100 TGF_PG-01 (Nom. kV=0.48, Plot Ref. kV=0.48)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500

300 300

CB TGF_PG-01
Square-D MICROLOGIC 6.0
Sensor = 4000
100 Ground Pickup = A (500 Amps) 100
Ground Band = 0 (I^x)t = OUT

50 50

30 R PG-J01 - N 30
OC1
Siemens
7SR12
CT Ratio 300:5
ANSI - Extremely Inverse
10 Pickup = 0.08 (0.05 - 2.5 xCT Sec) 10
Time Dial = 0.35
3x = 1.28 s, 5x = 0.454 s, 8x = 0.199 s
Inst = 1.65 (0.05 - 50 xCT Sec)
5 5

Seconds
Seconds

3 Fuse1 PG-J-02 3

CB PG-J01
Siba
o
HV- Fuse Links
R Very Fast 24 kV
R PG-J01
125A

1 PG520
1

Fuse1 PG-J-02

.5 .5
PG520 - TGF_PG-01 23KV

.3 .3
3-1/C 1/0

.1 TR-PG-01
2000 kVA
.1
PG520 - TGF_PG-0 .48kV

.05 .05
21-1/C 500
CB TGF_PG-01

.03 .03
TGF_PG-01

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 TGF_PG-01 (Nom. kV=0.48, Plot Ref. kV=0.48) ETAP Star 20.6.0C

Project: FOXCONN Date: 03-03-2024


Contract: SN:
Engineer: Rev: Base
Filename: C:\Users\oswaldor\Desktop\Everything\1. Papa\1. Simulaciones\040324\CB PG52 Fault: Ground
Amps X 10 CFE Av (Nom. kV=23, Plot Ref. kV=23)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
CFE 1
R CFE Av - P 541 MVAsc
OC1
Foxcoon
500 751 CFE Av 500
CT Ratio 600:5
U3 - U.S. Very Inverse
Pickup = 1.168 (0.02 - 3.2 Sec - 5A) OCR
300 Time Dial = 2.75 R CFE Av
o
300
3x = 1.6 s, 5x = 0.709 s, 8x = 0.434 s

Cfe Av - VPG Acom 23kV


Inst = 20 (0.1 - 20 Sec - 5A) CB CFE Av
Time Delay = 0.03 s

VPG Acomet - P
3-1/C 500
Entec
ETR102-04_2
100 CT Ratio 1000:1 VPG Acom.
100
Extremally Inverse ANSI
Pickup = 0.125 (0.02 - 3.2 Sec - 1A)
OCR
Time Dial = 2.2 o

VPG Acomet
3x = 1.7 s, 5x = 0.618 s, 8x = 0.282 s CB R1-R2
50 Inst = 2 (0.05 - 15 Sec - 1A) 50

R2 - S2 23kV.
R S2-J-01 - P
30 OC1 3-1/C 500 30
Siemens R
7SR12 o

R S2-J-01
CT Ratio 600:5
CB S2-J-01
ANSI - Extremely Inverse S2
Pickup = 0.15 (0.05 - 2.5 xCT Sec)
Time Dial = 0.55 CB S2-J-04.
3x = 2.01 s, 5x = 0.713 s, 8x = 0.313 s
10 Inst = 2.2 (0.05 - 50 xCT Sec) R
10
o

R S2-J-04

CB S2-J-04

S2 - S1 23KV
R S2-J-04 - P
OC1
5 5
Siemens
Seconds

Seconds
3-1/C 500
7SR12
CT Ratio 600:5
3 ANSI - Extremely Inverse R
o 3
Pickup = 0.14 (0.05 - 2.5 xCT Sec) R S1-J01
CB S1-J-01
Time Dial = 0.52
3x = 1.9 s, 5x = 0.674 s, 8x = 0.296 s S1
Inst = 2.1 (0.05 - 50 xCT Sec)
R S1-J01 - P
OC1 CB S1-J-03

Siemens
1 7SR12
o

R
1
CT Ratio 600:5 R S1-J-03

S1 - U-01 23 kV
ANSI - Extremely Inverse
Pickup = 0.13 (0.05 - 2.5 xCT Sec)
Time Dial = 0.48
.5 3x = 1.75 s, 5x = 0.622 s, 8x = 0.273 s .5
Inst = 1.77 (0.05 - 50 xCT Sec) 3-1/C 500

.3 R S1-J-03 - P .3
OC1 CB U-01-J-01

Siemens o

7SR11 R

CT Ratio 300:5 R U-01-J-01


ANSI - Extremely Inverse
U-01
Pickup = 0.24 (0.05 - 2.5 xCT Sec)
Time Dial = 0.4
.1 3x = 1.46 s, 5x = 0.519 s, 8x = 0.228 s .1
Inst = 2.8 (0.05 - 50 xCT Sec)

.05 R U-01-J-01 - P
.05
OC1
Schneider Electric
.03 VIP400 .03
CT Ratio 600:1
IEEE extremely inverse
Pickup = 0.11 (0.05 - 2 xCT Pri)
Time Dial = 1.4
3x = 1.02 s, 5x = 0.363 s, 8x = 0.159 s
Inst = 1.1 (0.1 - 20 xCT Pri)
Time Delay = 0.05 s
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 10 CFE Av (Nom. kV=23, Plot Ref. kV=23) ETAP Star 20.6.0C

Project: FOXCONN Date: 03-03-2024


Location: Vesta Park Guadalajara Nave 7 Fault: Phase
Amps X 10 CFE Av (Nom. kV=23, Plot Ref. kV=23)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
CFE 1
541 MVAsc

VPG Acomet - G
500 CFE Av 500
Entec
ETR102-04_2
CT Ratio 1000:1
OCR
300 Extremally Inverse ANSI o
300
R CFE Av
Pickup = 0.033 (0.02 - 3.2 Sec - 1A)

Cfe Av - VPG Acom 23kV


Time Dial = 5.4
CB CFE Av
3x = 4.18 s, 5x = 1.52 s, 8x = 0.693 s
Inst = 1.4 (0.05 - 15 Sec - 1A)

R CFE Av - N 3-1/C 500


OC1
100 Foxcoon 100
VPG Acom.
751
CT Ratio 600:5
C2 - IEC Cls B Very Inverse OCR
o

Pickup = 0.42 (0.1 - 3.2 Sec - 1A) VPG Acomet


Time Dial = 1 CB R1-R2
50 50
3x = 6.75 s, 5x = 3.38 s, 8x = 1.93 s

R2 - S2 23kV.
Inst = 16.7 (0.1 - 20 Sec - 5A)
Time Delay = 0.03 s
30 3-1/C 500 30
R S2-J-01 - N
OC1 R
o

Siemens R S2-J-01
7SR12 CB S2-J-01
S2
CT Ratio 600:5
ANSI - Extremely Inverse
CB S2-J-04.
Pickup = 0.05 (0.05 - 2.5 xCT Sec)
10 Time Dial = 0.9
R
10
3x = 3.28 s, 5x = 1.17 s, 8x = 0.512 s o

R S2-J-04
Inst = 1.76 (0.05 - 50 xCT Sec)
CB S2-J-04

S2 - S1 23KV
5 R S2-J-04 - N 5
Seconds

Seconds
3-1/C 500
OC1
Siemens
3 7SR12 R
o 3
CT Ratio 600:5 R S1-J01
CB S1-J-01
ANSI - Extremely Inverse
R S1-J01 - N
Pickup = 0.05 (0.05 - 2.5 xCT Sec) S1
OC1
Time Dial = 0.84
Siemens 3x = 3.06 s, 5x = 1.09 s, 8x = 0.478 s
7SR12 Inst = 1.68 (0.05 - 50 xCT Sec) CB S1-J-03
CT Ratio 600:5
ANSI - Extremely Inverse
1 Pickup = 0.05 (0.05 - 2.5 xCT Sec)
o

R
1
Time Dial = 0.6 R S1-J-03

S1 - U-01 23 kV
3x = 2.19 s, 5x = 0.778 s, 8x = 0.342 s
Inst = 1.39 (0.05 - 50 xCT Sec)

.5 .5
3-1/C 500

.3 R S1-J-03 - N CB U-01-J-01
.3
OC1
Siemens o

R
7SR11
R U-01-J-01
CT Ratio 300:5
ANSI - Extremely Inverse U-01
Pickup = 0.095 (0.05 - 2.5 xCT Sec)
Time Dial = 0.425
.1 3x = 1.55 s, 5x = 0.551 s, 8x = 0.242 s .1
Inst = 2.05 (0.05 - 50 xCT Sec)

R U-01-J-01 - N
.05 OC1
.05
Schneider Electric
VIP400
.03 CT Ratio 600:1 .03
IEEE extremely inverse
Pickup = 0.045 (0.025 - 1 xCT Pri)
Time Dial = 0.6
3x = 0.438 s, 5x = 0.156 s, 8x = 0.0683 s
Inst = 0.9 (0.1 - 10 xCT Pri)
Time Delay = 0.06 s

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 10 CFE Av (Nom. kV=23, Plot Ref. kV=23) ETAP Star 20.6.0C

Project: FOXCONN Date: 03-03-2024


Location: Vesta Park Guadalajara Nave 7 Fault: Ground
Amps X 100 TGF-U-01-01 (Nom. kV=0.48, Plot Ref. kV=0.48)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500
CB U-01-J-01
Fuse U-1-J-02
300 o 300
Driescher R

H 220 R U-01-J-01
Standard 24 kV
U-01
40

U-01 - TGF-U-01 23 kV
Fuse U-1-J-02
100 100

3-1/C 1/0

50 50

30 TR-U-01-01 2000 kVA 30

U-01 - TGF-U-01 .48kV


21-1/C 500
10 10

CB TGF-U-01-01
5 5
Seconds

Seconds
TGF-U-01-01
3 3

R U-01-J-01 - P
OC1
Schneider Electric
VIP400
1 CT Ratio 600:1 1
IEEE extremely inverse
Pickup = 0.11 (0.05 - 2 xCT Pri)
Time Dial = 1.4
.5 3x = 1.02 s, 5x = 0.363 s, 8x = 0.159 s .5
Inst = 1.1 (0.1 - 20 xCT Pri)
CB TGF-U-01-01
Time Delay = 0.05 s
.3 Square-D MICROLOGIC 6.0 .3
Sensor = 4000
LT Pickup = 0.6 (2400 Amps) TR-U-01-01
LT Band = 0.5 Inrush
ST Pickup = 2.5 (6000 Amps)
ST Band = 0.1 (I^x)t = OUT
Inst. Pickup = 3 (12000 Amps)
.1 .1

.05 .05

.03 .03

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 TGF-U-01-01 (Nom. kV=0.48, Plot Ref. kV=0.48) ETAP Star 20.6.0C

Project: FOXCONN Date: 03-03-2024


Location: Vesta Park Guadalajara Nave 7 Fault: Phase
Amps X 100 TGF-U-01-01 (Nom. kV=0.48, Plot Ref. kV=0.48)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500
CB U-01-J-01
Fuse U-1-J-02
300 o 300
Driescher R

H 220 R U-01-J-01
Standard 24 kV
U-01
40

U-01 - TGF-U-01 23 kV
Fuse U-1-J-02
100 100

3-1/C 1/0

50 50

30 TR-U-01-01 2000 kVA 30

U-01 - TGF-U-01 .48kV


21-1/C 500
10 10

CB TGF-U-01-01
5 5
Seconds

Seconds
TGF-U-01-01
3 3

R U-01-J-01 - N
OC1
Schneider Electric
VIP400
1 CT Ratio 600:1 1
IEEE extremely inverse
Pickup = 0.045 (0.025 - 1 xCT Pri)
Time Dial = 0.6
.5 3x = 0.438 s, 5x = 0.156 s, 8x = 0.0683 s .5
Inst = 0.9 (0.1 - 10 xCT Pri)
Time Delay = 0.06 s
CB TGF-U-01-01
.3 .3
Square-D MICROLOGIC 6.0
Sensor = 4000
Ground Pickup = A (500 Amps)
Ground Band = 0 (I^x)t = OUT

.1 .1

.05 .05

.03 .03

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 TGF-U-01-01 (Nom. kV=0.48, Plot Ref. kV=0.48) ETAP Star 20.6.0C

Project: FOXCONN Date: 03-03-2024


Location: Vesta Park Guadalajara Nave 7 Fault: Ground
Project: FOXCONN ETAP Page: 1
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

OCR: R CFE Av
MFR: Foxcoon Tag #: CT Base kV If (kA)
Model: 751 Phase: 600:5

GND: 600:5

OC Level: OC1
Range Setting
Phase TOC U3 - U.S. Very Inverse
Pickup (Tap) 0.02 - 3.2 Sec - 5A 1.168
Time Dial 2.750
Phase INST Pickup 0.1 - 20 Sec - 5A 20.000
Time Delay 0 - 10 Sec 0.030
Neutral TOC C2 - IEC Cls B Very Inverse
Pickup (Tap) 0.1 - 3.2 Sec - 1A 0.420
Time Dial 1.000
Neutral INST Pickup 0.1 - 20 Sec - 5A 16.700
Time Delay 0 - 10 Sec 0.030

OCR: R PG-J01
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 300:5 23.000 13.58 3 ph, Sym. (Calc.)
15.06 LG, Sym. (Calc.)
GND: 300:5 23.000 15.06 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.210
Time Dial 0.400
Phase INST Pickup 0.05 - 50 xCT Sec 2.410
Time Delay 0 - 14400 Sec 0.000
Neutral TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.080
Time Dial 0.350
Neutral INST Pickup 0.05 - 50 xCT Sec 1.650
Time Delay 0 - 14400 Sec 0.000
Project: FOXCONN ETAP Page: 2
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

OCR: R S1-J01
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 600:5

GND: 600:5

OC Level: OC1
Range Setting
Phase TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.130
Time Dial 0.480
Phase INST Pickup 0.05 - 50 xCT Sec 1.770
Time Delay 0 - 14400 Sec 0.000
Neutral TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.050
Time Dial 0.600
Neutral INST Pickup 0.05 - 50 xCT Sec 1.390
Time Delay 0 - 14400 Sec 0.000

OCR: R S1-J02
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR11 Phase: 200:5 23.000 13.58 3 ph, Sym. (Calc.)
15.06 LG, Sym. (Calc.)
GND: 200:5 23.000 15.06 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.340
Time Dial 0.450
Phase INST Pickup 0.05 - 50 xCT Sec 4.400
Time Delay 0 - 14400 Sec 0.000
Neutral TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.140
Time Dial 0.450
Neutral INST Pickup 0.05 - 50 xCT Sec 3.290
Time Delay 0 - 14400 Sec 0.000
Project: FOXCONN ETAP Page: 3
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

OCR: R S2-J-01
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 600:5

GND: 600:5

OC Level: OC1
Range Setting
Phase TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.150
Time Dial 0.550
Phase INST Pickup 0.05 - 50 xCT Sec 2.200
Time Delay 0 - 14400 Sec 0.000
Neutral TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.050
Time Dial 0.900
Neutral INST Pickup 0.05 - 50 xCT Sec 1.760
Time Delay 0 - 14400 Sec 0.000

OCR: R S2-J-04
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 600:5

GND: 600:5

OC Level: OC1
Range Setting
Phase TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.140
Time Dial 0.520
Phase INST Pickup 0.05 - 50 xCT Sec 2.100
Time Delay 0 - 14400 Sec 0.000
Neutral TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.050
Time Dial 0.840
Neutral INST Pickup 0.05 - 50 xCT Sec 1.680
Time Delay 0 - 14400 Sec 0.000
Project: FOXCONN ETAP Page: 4
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

OCR: VPG Acomet


MFR: Entec Tag #: CT Base kV If (kA)
Model: ETR102-04_2 Phase: 1000:1

GND: 1000:1

OC Level: OC1
Range Setting
Phase TOC Extremally Inverse ANSI
Pickup (Tap) 0.02 - 3.2 Sec - 1A 0.125
Time Dial 2.200
Phase INST Pickup 0.05 - 15 Sec - 1A 2.000
Time Delay 0 - 10 Sec 0.000
Ground TOC Extremally Inverse ANSI
Pickup (Tap) 0.02 - 3.2 Sec - 1A 0.033
Time Dial 5.400
Ground INST Pickup 0.05 - 15 Sec - 1A 1.400
Time Delay 0 - 10 Sec 0.000
Project: FOXCONN ETAP Page: 5
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

OLR: R PG-J01
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 300:5 23.000 13.58 3 ph, Sym. (Calc.)
15.06 LG, Sym. (Calc.)
GND: 300:5 23.000 15.06 LG, Sym. (Calc.)
Range Setting
Thermal Thermal Overload
Trip 0.1 - 3 xCT Sec 0.100
Multiplier 1.000
K Factor 0.010

OLR: R S1-J01
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 600:5

GND: 600:5
Range Setting
Thermal Thermal Overload
Trip 0.1 - 3 xCT Sec 0.100
Multiplier 1.000
K Factor 0.010

OLR: R S1-J02
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR11 Phase: 200:5 23.000 13.58 3 ph, Sym. (Calc.)
15.06 LG, Sym. (Calc.)
GND: 200:5 23.000 15.06 LG, Sym. (Calc.)

OLR: R S2-J-01
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 600:5

GND: 600:5
Range Setting
Thermal Thermal Overload
Trip 0.1 - 3 xCT Sec 0.100
Multiplier 1.000
K Factor 0.010
Project: FOXCONN ETAP Page: 6
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

OLR: R S2-J-04
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 600:5

GND: 600:5
Range Setting
Thermal Thermal Overload
Trip 0.1 - 3 xCT Sec 0.100
Multiplier 1.000
K Factor 0.010
Project: FOXCONN ETAP Page: 1
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

OCR: R PG-J01
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 300:5 23.000 13.58 3 ph, Sym. (Calc.)
15.06 LG, Sym. (Calc.)
GND: 300:5 23.000 15.06 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.210
Time Dial 0.400
Phase INST Pickup 0.05 - 50 xCT Sec 2.410
Time Delay 0 - 14400 Sec 0.000
Neutral TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.080
Time Dial 0.350
Neutral INST Pickup 0.05 - 50 xCT Sec 1.650
Time Delay 0 - 14400 Sec 0.000

OLR: R PG-J01
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 300:5 23.000 13.58 3 ph, Sym. (Calc.)
15.06 LG, Sym. (Calc.)
GND: 300:5 23.000 15.06 LG, Sym. (Calc.)
Range Setting
Thermal Thermal Overload
Trip 0.1 - 3 xCT Sec 0.100
Multiplier 1.000
K Factor 0.010

Fuse: Fuse1 PG-J-02


MFR: Siba* Tag #: 3-Phase kA: 0.00 Sym. (Calc.)
Model: HV- Fuse Links kV: 24.000 LG kA: 0.00 Sym. (Calc.)
Speed: Very Fast Breaking kA: 40.000 Base kV: 0.000 (Calc.)
Size: 125A Cont. Amp: 125.000
* Retrieved library data is modified by user.

CB: CB TGF_PG-01
MFR: Square-D Tag #: 3-Phase kA: 0.00 Sym. (Calc.)
Model: NW40H1 Rating: 143 kA, 0.69 kV LG kA: 0.00 Sym. (Calc.)
Size: 4000 Rated Amp: 4000.000 Base kV: 0.000 (Calc.)
Project: FOXCONN ETAP Page: 2
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

CB: CB TGF_PG-01
MFR: Square-D Tag #: 3-Phase kA: 0.00 Sym. (Calc.)
Model: NW40H1 Rating: 143 kA, 0.69 kV LG kA: 0.00 Sym. (Calc.)
Size: 4000 Rated Amp: 4000.000 Base kV: 0.000 (Calc.)
LV Solid State Trip Device
MFR: Square-D
Model: MICROLOGIC 6.0
Sensor: 4000
Phase Setting Ground Setting
Long-Time LT Pickup 0.6 LT Band 0.5 Ground Pickup A
Ground Band 0 I^xt=OUT
Short-Time ST Pickup 2.5
ST Band 0.1 I^xt=OUT
INST Inst. Pickup 3
Project: FOXCONN ETAP Page: 1
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

OCR: R CFE Av
MFR: Foxcoon Tag #: CT Base kV If (kA)
Model: 751 Phase: 600:5

GND: 600:5

OC Level: OC1
Range Setting
Phase TOC U3 - U.S. Very Inverse
Pickup (Tap) 0.02 - 3.2 Sec - 5A 1.168
Time Dial 2.750
Phase INST Pickup 0.1 - 20 Sec - 5A 20.000
Time Delay 0 - 10 Sec 0.030
Neutral TOC C2 - IEC Cls B Very Inverse
Pickup (Tap) 0.1 - 3.2 Sec - 1A 0.420
Time Dial 1.000
Neutral INST Pickup 0.1 - 20 Sec - 5A 16.700
Time Delay 0 - 10 Sec 0.030

OCR: R S1-J01
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 600:5

GND: 600:5

OC Level: OC1
Range Setting
Phase TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.130
Time Dial 0.480
Phase INST Pickup 0.05 - 50 xCT Sec 1.770
Time Delay 0 - 14400 Sec 0.000
Neutral TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.050
Time Dial 0.600
Neutral INST Pickup 0.05 - 50 xCT Sec 1.390
Time Delay 0 - 14400 Sec 0.000
Project: FOXCONN ETAP Page: 2
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

OCR: R S1-J-03
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR11 Phase: 300:5

GND: 300:5

OC Level: OC1
Range Setting
Phase TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.240
Time Dial 0.400
Phase INST Pickup 0.05 - 50 xCT Sec 2.800
Time Delay 0 - 14400 Sec 0.000
Ground INST Pickup 0.005 - 5 xCT Sec 5.000
Time Delay 0 - 14400 Sec 0.010
Neutral TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.095
Time Dial 0.425
Neutral INST Pickup 0.05 - 50 xCT Sec 2.050
Time Delay 0 - 14400 Sec 0.000

OCR: R S2-J-01
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 600:5

GND: 600:5

OC Level: OC1
Range Setting
Phase TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.150
Time Dial 0.550
Phase INST Pickup 0.05 - 50 xCT Sec 2.200
Time Delay 0 - 14400 Sec 0.000
Neutral TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.050
Time Dial 0.900
Neutral INST Pickup 0.05 - 50 xCT Sec 1.760
Time Delay 0 - 14400 Sec 0.000
Project: FOXCONN ETAP Page: 3
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

OCR: R S2-J-04
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 600:5

GND: 600:5

OC Level: OC1
Range Setting
Phase TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.140
Time Dial 0.520
Phase INST Pickup 0.05 - 50 xCT Sec 2.100
Time Delay 0 - 14400 Sec 0.000
Neutral TOC ANSI - Extremely Inverse
Pickup (Tap) 0.05 - 2.5 xCT Sec 0.050
Time Dial 0.840
Neutral INST Pickup 0.05 - 50 xCT Sec 1.680
Time Delay 0 - 14400 Sec 0.000

OCR: R U-01-J-01
MFR: Schneider Electric Tag #: CT Base kV If (kA)
Model: VIP400 CT Input: 600:1

OC Level: OC1
Range Setting
Phase TOC IEEE extremely inverse
Pickup (Tap) 0.05 - 2 xCT Pri 0.110
Time Dial 1.400
Phase INST Pickup 0.1 - 20 xCT Pri 1.100
Time Delay 0.05 - 9.99 Sec 0.050
Neutral TOC IEEE extremely inverse
Pickup (Tap) 0.025 - 1 xCT Pri 0.045
Time Dial 0.600
Neutral INST Pickup 0.1 - 10 xCT Pri 0.900
Time Delay 0.05 - 9.99 Sec 0.060
Project: FOXCONN ETAP Page: 4
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

OCR: VPG Acomet


MFR: Entec Tag #: CT Base kV If (kA)
Model: ETR102-04_2 Phase: 1000:1

GND: 1000:1

OC Level: OC1
Range Setting
Phase TOC Extremally Inverse ANSI
Pickup (Tap) 0.02 - 3.2 Sec - 1A 0.125
Time Dial 2.200
Phase INST Pickup 0.05 - 15 Sec - 1A 2.000
Time Delay 0 - 10 Sec 0.000
Ground TOC Extremally Inverse ANSI
Pickup (Tap) 0.02 - 3.2 Sec - 1A 0.033
Time Dial 5.400
Ground INST Pickup 0.05 - 15 Sec - 1A 1.400
Time Delay 0 - 10 Sec 0.000
Project: FOXCONN ETAP Page: 5
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

OLR: R S1-J01
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 600:5

GND: 600:5
Range Setting
Thermal Thermal Overload
Trip 0.1 - 3 xCT Sec 0.100
Multiplier 1.000
K Factor 0.010

OLR: R S1-J-03
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR11 Phase: 300:5

GND: 300:5
Range Setting
Thermal Thermal Overload
Trip 0.1 - 3 xCT Sec 0.100
Multiplier 1.000
K Factor 0.010

OLR: R S2-J-01
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 600:5

GND: 600:5
Range Setting
Thermal Thermal Overload
Trip 0.1 - 3 xCT Sec 0.100
Multiplier 1.000
K Factor 0.010

OLR: R S2-J-04
MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SR12 Phase: 600:5

GND: 600:5
Range Setting
Thermal Thermal Overload
Trip 0.1 - 3 xCT Sec 0.100
Multiplier 1.000
K Factor 0.010
Project: FOXCONN ETAP Page: 6
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

OLR: R U-01-J-01
MFR: Schneider Electric Tag #: CT Base kV If (kA)
Model: VIP400 CT Input: 600:1

Range Setting
Thermal ANSI 49RMS
Trip 0.05 - 1 xCT Pri 0.050
Multiplier 1.000
Project: FOXCONN ETAP Page: 1
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: Revision: Base
Engineer:
Filename: IE-15 Protective Device Settings

OCR: R U-01-J-01
MFR: Schneider Electric Tag #: CT Base kV If (kA)
Model: VIP400 CT Input: 600:1

OC Level: OC1
Range Setting
Phase TOC IEEE extremely inverse
Pickup (Tap) 0.05 - 2 xCT Pri 0.110
Time Dial 1.400
Phase INST Pickup 0.1 - 20 xCT Pri 1.100
Time Delay 0.05 - 9.99 Sec 0.050
Neutral TOC IEEE extremely inverse
Pickup (Tap) 0.025 - 1 xCT Pri 0.045
Time Dial 0.600
Neutral INST Pickup 0.1 - 10 xCT Pri 0.900
Time Delay 0.05 - 9.99 Sec 0.060

OLR: R U-01-J-01
MFR: Schneider Electric Tag #: CT Base kV If (kA)
Model: VIP400 CT Input: 600:1

Range Setting
Thermal ANSI 49RMS
Trip 0.05 - 1 xCT Pri 0.050
Multiplier 1.000

Fuse: Fuse U-1-J-02


MFR: Driescher* Tag #: 3-Phase kA: 0.00 Sym. (Calc.)
Model: H 220 kV: 24.000 LG kA: 0.00 Sym. (Calc.)
Speed: Standard Breaking kA: 33.300 Base kV: 0.000 (Calc.)
Size: 40 Cont. Amp: 65.000
* Retrieved library data is modified by user.

CB: CB TGF-U-01-01
MFR: Square-D Tag #: 3-Phase kA: 0.00 Sym. (Calc.)
Model: NW40H1 Rating: 143 kA, 0.69 kV LG kA: 0.00 Sym. (Calc.)
Size: 4000 Rated Amp: 4000.000 Base kV: 0.000 (Calc.)
Project: FOXCONN ETAP Page: 1
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Electrical Transient Analyzer Program

Short-Circuit Analysis

ANSI Standard
3-Phase, LG, LL, & LLG Fault Currents
1/2 Cycle Network

Swing V-Control Load Total


Number of Buses: 1 0 17 18

Line/Cable/
XFMR2 XFMR3 Reactor Busway Impedance Tie PD Total
Number of Branches: 3 0 0 14 0 0 17

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load Total
Number of Machines: 0 1 0 1 0 2

System Frequency: 60.00

Unit System: English

Project Filename: IE-15

Output Filename: C:\Users\oswaldor\Desktop\Everything\1. Papa\1. Simulaciones\030324\CB PG520 & U1


(030324)\Untitled.SA2S
Project: FOXCONN ETAP Page: 2
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Adjustments

Apply Individual
Tolerance Adjustments /Global Percent
Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable / Busway Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C
Transmission Line Resistance: Yes Individual

Cable / Busway Resistance: Yes Individual


Project: FOXCONN ETAP Page: 3
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Bus118 Load 23.000 23.000 1 100.00 0.00


Bus119 Load 0.480 0.480 1 100.00 0.00
Bus120 Load 0.220 0.220 1 100.00 30.00
Bus121 Load 0.480 0.480 1 100.00 0.00
Bus124 Load 0.480 0.480 1 100.00 0.00
Bus129 Load 0.480 0.480 1 100.00 0.00
Bus130 Load 23.000 23.000 1 100.00 0.00
Bus131 Load 0.480 0.480 1 100.00 0.00
CFE Av SWNG 23.000 23.000 1 100.00 0.00
LP (19-20) Load 0.220 0.220 1 100.00 30.00
PG520 Load 23.000 23.000 1 100.00 0.00
S1 Load 23.000 23.000 1 100.00 0.00
S2 Load 23.000 23.000 1 100.00 0.00
TDF-PG-UPS-06 Load 0.480 0.480 1 100.00 0.00
TGF-U-01-01 Load 0.480 0.480 1 100.00 0.00
TGF_PG-01 Load 0.480 0.480 1 100.00 0.00
U-01 Load 23.000 23.000 1 100.00 0.00
VPG Acom. Load 23.000 23.000 1 100.00 0.00

18 Buses Total

All voltages reported by ETAP are in % of bus Nominal kV.


Base kV values of buses are calculated and used internally by ETAP.
Project: FOXCONN ETAP Page: 4
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Line/Cable/Busway Input Data

ohms or siemens per 1000 ft per Conductor (Cable) or per Phase (Line/Busway)

Line/Cable/Busway Length
ID Library Size Adj. (ft) % Tol. #/Phase T ( C) R1 X1 Y1 R0 X0 Y0
Cable45 0.6MCUN1 350 65.6 0.0 4 75 0.0378055 0.0273301 0.0001038 0.0385026 0.47487 0.0001038
Cfe Av - VPG Acom 23kV 0.6MCUN1 500 2296.6 0.0 1 75 0.0288678 0.0297345 0.0001216 0.047044 0.6891418 0.0001216
PG-Chiller 01 .480 0.6MALN1 500 479.0 0.0 3 75 0.0444474 0.0297345 0.0001216 0.0492657 0.5976052 0.0001216
PG520 - TGF_PG-0 .48kV 0.6MCUN1 500 16.4 0.0 7 75 0.0274198 0.0265014 0.0001216 0.0275952 0.3691834 0.0001216
PG520 - TGF_PG-01 23KV 25MCUS1 1/0 85.3 0.0 1 75 0.1217936 0.0508418 0.0000215 0.1226556 0.4891329 0.0000215
R2 - S2 23kV. 0.6MCUN1 500 16.4 0.0 1 75 0.0288678 0.0297345 0.0001216 0.0290432 0.3691834 0.0001216
S1 - PG520 23KV 25MCUS1 3/0 49.2 0.0 1 75 0.0775715 0.0474679 0.0000252 0.0780712 0.4422593 0.0000252
S1 - U-01 23 kV 0.6MCUN1 500 16.4 0.0 1 75 0.0288678 0.0297345 0.0001216 0.0290432 0.3691834 0.0001216
S2 - S1 23KV 0.6MCUN1 500 16.4 0.0 1 75 0.0288678 0.0297345 0.0001216 0.0290432 0.3691834 0.0001216
TDF-PG - LP (19-20) .220 0.6MCUN1 350 16.4 0.0 4 75 0.0378055 0.0273301 0.0001038 0.0379809 0.3797408 0.0001038
TDF-PG - LP (19-20) .480 0.6MCUN1 350 36.1 0.0 2 75 0.0378055 0.0273301 0.0001038 0.0381904 0.4339212 0.0001038

TGF_PG-01 TDF-PG-UPS 0.6MCUN1 350 16.4 0.0 4 75 0.0378055 0.0273301 0.0001038 0.0379809 0.3797408 0.0001038
06
U-01 - TGF-U-01 23 kV 25MCUS1 1/0 49.2 0.0 1 75 0.1217936 0.0508418 0.0000215 0.1222933 0.4515387 0.0000215
U-01 - TGF-U-01 .48kV 0.6MCUN1 500 39.4 0.0 7 75 0.0274198 0.0265014 0.0001216 0.0278395 0.429333 0.0001216

Line / Cable / Busway resistances are listed at the specified temperatures.


Project: FOXCONN ETAP Page: 5
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted Phase Shift

ID MVA Prim. kV Sec. kV %Z X/R + 5% - 5% % Tol. Prim. Sec. %Z Type Angle

TR-13. 0.500 0.480 0.220 4.00 4.70 0 0 0 0 0 4.00 Dyn -30.00


TR-PG-01 2.000 23.000 0.480 6.94 7.10 0 0 0 0 0 6.94 YNyn 0.00
TR-U-01-01 2.000 23.000 0.480 6.94 7.10 0 0 0 0 0 6.94 YNyn 0.00

2-Winding Transformer Grounding Input Data

Grounding
Transformer Rating Conn. Primary Secondary
ID MVA Prim. kV Sec. kV Type Type kV Amp ohm Type kV Amp ohm
TR-13. 0.500 0.480 0.220 D/Y Solid
TR-PG-01 2.000 23.000 0.480 Y/Y Solid Solid

TR-U-01-01 2.000 23.000 0.480 Y/Y Solid Solid


Project: FOXCONN ETAP Page: 6
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb


ID Type From Bus To Bus R X Z Y
TR-13. 2W XFMR Bus121 Bus120 166.49 782.48 800.00
TR-PG-01 2W XFMR Bus118 Bus119 48.41 343.61 347.00
TR-U-01-01 2W XFMR Bus130 Bus129 48.41 343.61 347.00
Cable45 Cable TGF_PG-01 Bus124 26.92 19.46 33.21 0.0000063
Cfe Av - VPG Acom 23kV Cable VPG Acom. CFE Av 1.25 1.29 1.80 0.1477109
PG-Chiller 01 .480 Cable TGF-U-01-01 Bus131 308.02 206.06 370.59 0.0000403
PG520 - TGF_PG-0 .48kV Cable Bus119 TGF_PG-01 2.79 2.70 3.88 0.0000032
PG520 - TGF_PG-01 23KV Cable PG520 Bus118 0.20 0.08 0.21 0.0009722
R2 - S2 23kV. Cable S2 VPG Acom. 0.01 0.01 0.01 0.0010551
S1 - PG520 23KV Cable S1 PG520 0.07 0.04 0.08 0.0006572
S1 - U-01 23 kV Cable S1 U-01 0.01 0.01 0.01 0.0010551
S2 - S1 23KV Cable S1 S2 0.01 0.01 0.01 0.0010551
TDF-PG - LP (19-20) .220 Cable Bus120 LP (19-20) 32.03 23.16 39.53 0.0000003
TDF-PG - LP (19-20) .480 Cable TDF-PG-UPS-06 Bus121 29.61 21.40 36.54 0.0000017
TGF_PG-01 TDF-PG-UPS 06 Cable Bus124 TDF-PG-UPS-06 6.73 4.86 8.30 0.0000016
U-01 - TGF-U-01 23 kV Cable U-01 Bus130 0.11 0.05 0.12 0.0005609
U-01 - TGF-U-01 .48kV Cable Bus129 TGF-U-01-01 6.69 6.47 9.31 0.0000077
Project: FOXCONN ETAP Page: 7
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Power Grid Input Data

% Positive Seq. Impedance % Zero Seq. Impedance


Power Grid Connected Bus Rating 100 MVA Base Grounding 100 MVA Base
ID ID MVASC kV X/R R X Type X/R R0 X0
CFE 1 CFE Av 541.000 23.000 6.20 2.94330 18.24845 Wye - Solid 6.46 1.993535 12.87823

Total Power Grids (= 1 ) 541.000 MVA


Project: FOXCONN ETAP Page: 8
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Induction Machine Input Data

Induction Machine Rating (Base) Positive Seq. Imp. Grounding Zero Seq. Imp.

ID Type Qty kVA kV RPM X"/R %R % X" % X' Conn. Type Amp X/R % R0 % X0
PG-Chiller 01 Motor 1 524.42 0.480 1800 18.39 1.088 20.00 50.00 Wye Open 18.39 1.09 20.00

Total Connected Induction Machines ( = 1 ): 524.4 kVA


Project: FOXCONN ETAP Page: 9
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

SHORT- CIRCUIT REPORT

Fault at bus: CFE Av

Prefault voltage = 23.000 kV = 100.00 % of nominal bus kV ( 23.000 kV)


= 100.00 % of base kV ( 23.000 kV)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

CFE Av Total 0.00 13.637 0.00 95.23 94.90 15.108 15.108 2.93E+000 1.82E+001 1.99E+000 1.29E+001

VPG Acom. CFE Av 0.04 0.057 0.03 95.23 94.92 0.042 0.000 5.72E+002 4.37E+003
CFE 1 CFE Av 100.00 13.580 100.00 100.00 100.00 15.066 15.108 2.94E+000 1.82E+001 1.99E+000 1.29E+001

# Indicates fault current contribution is from three-winding transformers


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta-Y transformer
Project: FOXCONN ETAP Page: 10
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Fault at bus: PG520

Prefault voltage = 23.000 kV = 100.00 % of nominal bus kV ( 23.000 kV)


= 100.00 % of base kV ( 23.000 kV)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

PG520 Total 0.00 12.567 0.00 120.14 113.46 9.026 9.026 4.26E+000 1.95E+001 4.13E+000 4.34E+001

Bus118 PG520 0.00 0.000 0.00 120.14 113.46 0.000 0.000


S1 PG520 0.42 12.567 0.65 119.81 113.21 9.026 9.026 4.26E+000 1.95E+001 4.13E+000 4.34E+001

# Indicates fault current contribution is from three-winding transformers


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta-Y transformer
Project: FOXCONN ETAP Page: 11
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Fault at bus: S1

Prefault voltage = 23.000 kV = 100.00 % of nominal bus kV ( 23.000 kV)


= 100.00 % of base kV ( 23.000 kV)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

S1 Total 0.00 12.604 0.00 119.91 113.35 9.083 9.083 4.19E+000 1.95E+001 4.05E+000 4.30E+001

PG520 S1 0.00 0.000 0.00 119.91 113.35 0.000 0.000


U-01 S1 0.00 0.057 0.00 119.91 113.35 0.027 0.000 5.71E+002 4.37E+003
S2 S1 0.06 12.547 0.16 119.82 113.28 9.056 9.083 4.21E+000 1.96E+001 4.05E+000 4.30E+001

# Indicates fault current contribution is from three-winding transformers


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta-Y transformer
Project: FOXCONN ETAP Page: 12
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Fault at bus: TDF-PG-UPS-06

Prefault voltage = 0.480 kV = 100.00 % of nominal bus kV ( 0.480 kV)


= 100.00 % of base kV ( 0.480 kV)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

TDF-PG-UPS-06 Total 0.00 30.047 0.00 118.97 112.37 22.087 22.087 8.93E+001 3.90E+002 8.97E+001 8.31E+002

Bus121 TDF-PG-UPS-06 0.00 0.000 0.00 118.97 112.37 0.000 0.000


Bus124 TDF-PG-UPS-06 2.07 30.047 4.89 116.08 110.29 22.087 22.087 8.93E+001 3.90E+002 8.97E+001 8.31E+002

# Indicates fault current contribution is from three-winding transformers


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta-Y transformer
Project: FOXCONN ETAP Page: 13
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Fault at bus: TGF-U-01-01

Prefault voltage = 0.480 kV = 100.00 % of nominal bus kV ( 0.480 kV)


= 100.00 % of base kV ( 0.480 kV)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

TGF-U-01-01 Total 0.00 35.090 0.00 108.14 105.97 30.556 30.556 5.35E+001 3.39E+002 5.94E+001 4.92E+002

Bus131 TGF-U-01-01 9.14 2.968 5.31 107.52 108.62 1.723 0.000 5.15E+002 4.02E+003
Bus129 TGF-U-01-01 2.49 32.123 10.01 102.58 102.21 28.834 30.556 5.94E+001 3.70E+002 5.94E+001 4.92E+002

# Indicates fault current contribution is from three-winding transformers


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta-Y transformer
Project: FOXCONN ETAP Page: 14
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Fault at bus: TGF_PG-01

Prefault voltage = 0.480 kV = 100.00 % of nominal bus kV ( 0.480 kV)


= 100.00 % of base kV ( 0.480 kV)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

TGF_PG-01 Total 0.00 32.499 0.00 103.23 101.99 30.864 30.864 5.57E+001 3.66E+002 5.55E+001 4.25E+002

Bus124 TGF_PG-01 0.00 0.000 0.00 103.23 101.99 0.000 0.000


Bus119 TGF_PG-01 1.05 32.499 3.74 101.33 100.79 30.864 30.864 5.57E+001 3.66E+002 5.55E+001 4.25E+002

# Indicates fault current contribution is from three-winding transformers


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta-Y transformer
Project: FOXCONN ETAP Page: 15
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Fault at bus: U-01

Prefault voltage = 23.000 kV = 100.00 % of nominal bus kV ( 23.000 kV)


= 100.00 % of base kV ( 23.000 kV)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

U-01 Total 0.00 12.597 0.00 119.98 113.39 9.069 9.069 4.20E+000 1.95E+001 4.06E+000 4.31E+001

S1 U-01 0.06 12.540 0.16 119.88 113.32 9.041 9.069 4.22E+000 1.96E+001 4.06E+000 4.31E+001
Bus130 U-01 0.00 0.057 0.00 119.98 113.40 0.027 0.000 5.71E+002 4.37E+003

# Indicates fault current contribution is from three-winding transformers


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta-Y transformer
Project: FOXCONN ETAP Page: 16
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Short-Circuit Summary Report

1/2 Cycle - 3-Phase, LG, LL, & LLG Fault Currents

Prefault Voltage = 100 % of the Bus Nominal Voltage

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground


ID kV Real Imag. Mag. Real Imag. Mag. Real Imag. Mag. Real Imag. Mag.
CFE Av 23.000 2.170 -13.463 13.637 2.380 -14.919 15.108 11.660 1.879 11.810 10.343 10.243 14.557
PG520 23.000 2.680 -12.278 12.567 1.368 -8.922 9.026 10.633 2.321 10.883 10.222 5.812 11.759
S1 23.000 2.650 -12.322 12.604 1.362 -8.981 9.083 10.671 2.295 10.915 10.261 5.816 11.794
TDF-PG-UPS-06 0.480 6.703 -29.290 30.047 3.628 -21.787 22.087 25.366 5.805 26.021 24.234 14.448 28.214
TGF-U-01-01 0.480 5.477 -34.660 35.090 4.305 -30.252 30.556 30.016 4.743 30.389 28.269 18.158 33.598
TGF_PG-01 0.480 4.887 -32.129 32.499 4.405 -30.548 30.864 27.825 4.232 28.145 25.830 18.788 31.940
U-01 23.000 2.653 -12.314 12.597 1.360 -8.966 9.069 10.664 2.298 10.909 10.255 5.810 11.787

All fault currents are symmetrical (1/2 Cycle network) values in rms kA.
* LLG fault current is the larger of the two faulted line currents.
Project: FOXCONN ETAP Page: 17
Location: Vesta Park Guadalajara Nave 7 20.6.0C Date: 03-04-2024
Contract: SN:
Engineer: Study Case: SC Revision: Base
Filename: IE-15 Config.: Normal

Sequence Impedance Summary Report

Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)
ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance
CFE Av 23.000 0.15493 0.96133 0.97374 0.15493 0.96133 0.97374 0.10546 0.68126 0.68937 0.00000 0.00000 0.00000
PG520 23.000 0.22538 1.03237 1.05668 0.22538 1.03237 1.05668 0.21829 2.29781 2.30816 0.00000 0.00000 0.00000
S1 23.000 0.22156 1.03003 1.05359 0.22156 1.03003 1.05359 0.21445 2.27605 2.28613 0.00000 0.00000 0.00000
TDF-PG-UPS-06 0.480 0.00206 0.00899 0.00922 0.00206 0.00899 0.00922 0.00207 0.01915 0.01926 0.00000 0.00000 0.00000
TGF-U-01-01 0.480 0.00123 0.00780 0.00790 0.00123 0.00780 0.00790 0.00137 0.01134 0.01142 0.00000 0.00000 0.00000
TGF_PG-01 0.480 0.00128 0.00843 0.00853 0.00128 0.00843 0.00853 0.00128 0.00980 0.00988 0.00000 0.00000 0.00000
U-01 23.000 0.22203 1.03051 1.05416 0.22203 1.03051 1.05416 0.21493 2.28210 2.29220 0.00000 0.00000 0.00000
One-Line Diagram - OLV1 (Load Flow Analysis)
541 MVAsc
CFE 1

1590 kVA
CFE Av 39.9 A

1590 kVA 100 %


39.9 A

23 kV

Cfe Av - VPG Acom 23kV


VPG Acom.
%
1639 kVA 99.97
41.2 A

23 kV

R2 - S2 23kV.
S2
%
1640 kVA 99.97
41.2 A

23 kV

S2 - S1 23KV
%
S1 99.97
149.2 kVA 1502 kVA
23 kV 3.7 A 37.7 A

S1 - PG520 23KV

S1 - U-01 23 kV
%
PG520 99.97
149.2 kVA
23 kV
3.7 A

U-01
%
99.97

PG520 - TGF_PG-02 23KV


541.8 kVA 545.6 kVA

PG520 - TGF_PG-03 23KV


23 kV
PG520 - TGF_PG-04 23KV
PG520 - TGF_PG-01 23KV

13.6 A 13.7 A

U-01 - TGF-U-02 23 kV
U-01 - TGF-U-01 23 kV

U-01 - TGF-U-05 23 kV
U-01 - TGF-U-03 23 kV
TR-PG-02
2000 kVA
TR-PG-01. TR-PG-03
2000 kVA 2000 kVA

TR-PG-04
2000 kVA

PG520 - TGF_PG-02 .48kV


PG520 - TGF_PG-0 .48kV

PG520 - TGF_PG-03 .48kV


PG520 - TGF_PG-04 .48kV

2000 kVA
TR-U-01-01 2000 kVA TR-U-01-02 TR-U-01-03 TR-U-01-04
2000 kVA 2000 kVA

U-01 - TGF-U-02 0.480 kV


U-01 - TGF-U-01 .48kV

U-01 - TGF-U-05 0.480 kV


TGF_PG-02
149.1 kVA
% TGF_PG-03
TGF_PG-01 179.5 A 99.89 TGF_PG-04 0.48 kV
0.48 kV 149.1 kVA 0.48 kV
179.5 A 0.48 kV

Cable32
Cable44

Cable31

Cable38
Cable3

Cable36

Cable37
Battery8
Cable7

Cable35

Battery10.
Cable46

Battery11.
Cable22

Cable34
Cable45

Battery12
Cable21

Battery05
Battery07

Cable39
Battery06
Cable47

Battery09
dcBus10
dcBus14 535.3 kVA % 539 kVA %
dcBus6 dcBus11 98.71 TGF-U-01-02 656.9 A 98.7
dcBus1 TGF-U-01-01 652.3 A TGF-U-04
dcBus15 dcBus7
dcBus3 UPS 08 539 kVA
UPS 10 0.48 kV 535.3 kVA 0.48 kV

U-01 - TGF-U-03 .48kV


UPS 11 656.9 A 0.48 kV
UPS 12 652.3 A
UPS 05
UPS 06 UPS 07
UPS 09

PG-Chiller 01 .480

PG-Chiller 02 .480

PG-Chiller 03 .480

PG-Chiller 04 .480

PG-Chiller 05 0.480

PG-Chiller 04 .2
TGF_PG-02 TDF-PG-UPS 08

PG-Chiller 05 0.2
TGF_PG-04 TDF-PG-UPS 05

TGF_PG-02 TDF-PG-UPS 12
524.4 kVA
TGF_PG-03 TDF-PG-UPS 07
TGF_PG-01 TDF-PG-UPS 06

524.4 kVA
TGF_PG-04 TDF-PG-UPS 09

652.3 A
656.9 A

PG-Chiller 01
PG-Chiller 02 PG-Chiller 03 PG-Chiller 04 PG-Chiller 05
415.8 kW
415.8 kW 415.8 kW 415.8 kW
415.8 kW

453.8 kVA %
TGF-U-03 547.9 A 99.63
TDF-PG-UPS-12
149 kVA 104.9 kVA 9.85 kVA 104.9 kVA 9.85 kVA 104.9 kVA 9.85 kVA 104.9 kVA 9.85 kVA 2.97 kVA
% 0.48 kV
TDF-PG-UPS-06 TDF-PG-UPS-07 126.7 A 11.9 A 126.7 A 11.9 A 126.7 A 11.9 A 126.6 A 11.9 A 3.6 A
179.5 A 99.84 TDF-PG-UPS-09
0.48 kV
149 kVA 0.48 kV Open
0.48 kV
0.48 kV

UMA 08 HUM PG .480


UMA 07 HUM PG .480
179.5 A

UMA 05 HUM PG .480

UMA 06 HUM PG .480


UMA 04 HUM PG .480
UMA 03 HUM PG .480
UMA 01 HUM PG .480

UMA 02 HUM PG .480

UMA 08 HUM PG .2
TDF-PG - LP(13-16) .480
TDF-PG - CRT-UPS 09 .480

TDF-PG - LP(9-12) .480

TDF-PG - DIS-ASSY .48


TDF-PG - LP(57-60) .48
TDF-PG -LP (21-24) .480

TDF-PG - LP(33-36) .480


TDF-PG - LP (19-20) .480

TDF-PG - LP(37-40) .48

UMA 05 RES PG .480

UMA 06 RES PG .480

UMA 07 RES PG .480

UMA 08 RES PG .480


UMA 01 RES PG .480

UMA 02 RES PG .480

UMA 03 RES PG .480

UMA 04 RES PG .480


% % % %
UMA 01 HUM PG 99.48 UMA 02 HUM PG 99.47 UMA 03 HUM PG 99.45 UMA 04 HUM PG 99.47 UMA 05 HUM PG UMA 06 HUM PG
UMA 07 HUM PG UMA 08 HUM PG

0.48 kV 0.48 kV 0.48 kV


0.48 kV 9.84 kVA 0.48 kV 9.84 kVA 0.48 kV9.84 kVA 0.48 kV 9.84 kVA 0.48 kV
11.9 A 11.9 A
11.9 A 11.9 A
500 kVA
TR-5

2000 kVA
TR-PG-01-
TGF_PG-02 TDF-PG-UPS 10

Load UMA 05 HUM PG Load UMA 06 HUM PG Load UMA 07 HUM PG Load UMA 08 HUM PG
Load UMA 01 HUM PG Load UMA 02 HUM PG Load UMA 03 HUM PG Load UMA 04 HUM PG
7.8 kW 7.8 kW
7.8 kW 7.8 kW 7.8 kW 7.8 kW
TDF-PG- LP(09-12) .220

7.8 kW 7.8 kW
TR-Cuart. UPS-09.

TR-Cuart. UPS-09

2.98 kVA
300 kVA

%
CC Carga PG-01 7.8 A 99.61
500 kVA
300 kVA

500 kVA

TR-24
TR-23
500 kVA

500 kVA

0.22 kV 2.98 kVA


500 kVA
500 kVA

TR14

TR-18
TR-17
TR-13.

7.8 A
% % % % UMA 05 RES PG UMA 06 RES PG UMA 07 RES PG UMA 08 RES PG
UMA 01 RES PG 99.47 UMA 02 RES PG 99.45 UMA 03 RES PG 99.43 UMA 04 RES PG 99.41
0.48 kV 0.48 kV
0.48 kV 104.8 kVA 0.48 kV 104.7 kVA 0.48 kV 104.7 kVA 0.48 kV 104.7 kVA 0.48 kV 0.48 kV
TDF-PG - DIS-ASSY .220
TDF-PG - LP(57-60) .220

126.7 A 126.7 A 126.7 A 126.6 A


TDF-PG_Cua UPS 09 .220
TDF-PG -LP (21-24) .220

Load CC Carga PG-01


TDF-PG - LP(33-36) .220

3 kVA

Load UMA 06 RES PG Load UMA 08 RES PG


LP (09-12) Load UMA 02 RES PG Load UMA 03 RES PG Load UMA 04 RES PG Load UMA 05 RES PG Load UMA 07 RES PG
Load UMA 01 RES PG
105.9 kVA 105.9 kVA 105.9 kVA 105.9 kVA 105.9 kVA
0.22 kV 105.9 kVA 105.9 kVA 105.9 kVA
TDF-PG - LP (19-20) .220

TDF-PG - LP(13-16).220

TDF-PG - LP(33-36) .3

LP (33-36)
LP(57-60)
0.22 kV 0.22 kV
LP (21-24) Load LP (09-12)
0.22 kV
300 kVA

Load LP (33-36)
Load LP (21-24)
TGF_PG-03 TDF-PG-UPS 11

0.38 kV 300 kVA


DIS-ASSY
Cuart. UPS-09 Load LP(57-60)
300 kVA
LP (37-40) 0.22 kV
300 kVA
0.22 kV

148.5 kVA TDF-PG-UPS-05


% TDF-PG-UPS-10
391.6 A
99.49 Load Cuart. UPS-09 0.48 kV
Load LP (37-40) Load DIS-ASSY
0.22 kV 148.5 kVA 0.48 kV TDF-PG-UPS-11
TDF-01 - Cuart. .480

LP (19-20) 300 kVA 300 kVA 300 kVA TDF-PG-UPS-08


TDF-01 - LP (05-06) .480

UNIFILAR PG520 & U-01


391.6 A
LP (13-16) 0.48 kV
TDF-PG - LP (01-04) .480
TDF-PG - LP (25-28) .480

0.48 kV
0.22 kV
TDF-PG -LP (29-32) .480

TDF-PG - LP (49-52) .480


TDF-PG - LP (41-44) .480

TDF-PG - LP (53-56) .480


TDF-PG - LP (45-48) .480

Load LP (19-20)

150 kVA
Load LP (13-16)
300 kVA
TR-Cuart. UPS-05
500 kVA
TR-10
500 kVA
TR-09

300 kVA
500 kVA
TR-15.

500 kVA

500 kVA
TR-21
TR-16.

500 kVA
TR-19

500 kVA
500 kVA

TR-22
TR-20
TDF-PG - LP (05-06) .220
TDF-PG -LP (29-32) .220

TDF-PG - LP (53-56) .220


TDF-PG - LP (45-48) .220
TDF-PG - LP (01-04) .220

LP (05-08)
TDF-PG - LP (25-28) .220

TDF-PG_Cua UPS 05 .220

TDF-PG - LP (49-52) .220


TDF-PG - LP (41-44) .220

0.22 kV

LP (45-48) LP (53-56)

LP (29-32) Load LP (05-08) 0.22 kV


0.22 kV
300 kVA
0.22 kV

Load LP (53-56)
Load LP (29-32)
LP (01-04) 300 kVA
Load LP (45-48)
300 kVA 0.22 kV
300 kVA

LP (49-52)2 LP (49-52)
Load LP (01-04)
0.22 kV
0.22 kV
300 kVA
LP (41-44)
Cuart. UPS-05
0.22 kV
0.22 kV
Load LP (49-52)
Load LP (25-28)
300 kVA
300 kVA

Load LP (41-44)
300 kVA

page 1 18:30:36 mar. 05, 2024 Project File: IE-15

You might also like