PowlVac® Circuit Breaker Series 4 Ratings
Cubicle
Voltage Short Circuit Power
Product Width BIL Continuous Current Rating
Class Rating Frequency
Form Factor
(kV) (in) (kA) (kV) (kV) 1200A 2000A 3000A 5000A2
36 60 19 • •
5kV PowlVac-ND® 26
50 60 19 • •
36 60 19 • • •
5kV PowlVac® 36 50 60 19 • • •
63 60 19 • • •
25 95 36 • • •
36 95 36 • • •
36 50 95 36 • • •
15kV PowlVac®
63 95 36 • • •
63G1 95 36 • • •
48 63G1 95 36 •
27kV 36 25 125 60 • •
PowlVac-ND®
29.8kV 36 25 125 60 • •
25 125 60 • •
27kV PowlVac® 40
40 125 60 • •
25 150 80 • •
PowlVac® 40
38kV 40 150 80 • •
PowlVac® 54 40 150 80 •
1
63G indicates a generator rated circuit breaker tested in accordance with C37.013
2
The 5000 amp circuit breaker is applied in stationary metal-enclosed applications. An isolation switch is required.