GENERAL NOTES
1.1.1 PROJECT NOTES:
*CEC2022I

1 1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE CALIFORNIA ELECTRIC
NEW PV SYSTEM: 6.970 kWp SHEET LIST TABLE
SHEET NUMBER SHEET TITLE
CODE (CEC) ARTICLE 690, ALL MANUFACTURERS’S LISTING AND INSTALLATION
INSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY
HAVING JURISDICTION’S (AHJ) APPLICABLE CODES.
1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEM
NEW BESS SYSTEM: 13.5 KWH G-1
G-2
PV-1
COVER PAGE
NOTES
SITE PLAN
INSPECTED PRIOR TO PARALLEL OPERATION
1.1.4 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVE INVERTERS, AND
SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE IN
PHOTOVOLTAIC SYSTEMS AS REQUIRED BY CEC 690.4: PV MODULES: UL1703,
SANFILLIPPO-HOUSTON RESIDENCE PV-2
PV-3
PV-4
ELECTRICAL PLAN
SOLAR ATTACHMENT PLAN
LINE DIAGRAM
IEC61730, AND IEC61215, AND NFPA 70 CLASS C FIRE INVERTERS: UL 1741 CERTIFIED,
IEEE 1547, 929, 519 COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY
2 1.1.5 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP
63 SEA PINE REACH, PV-5
PV-6
DESIGN TABLES
PLACARDS
COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATED
ACCORDING TO CEC 690.7.
SEA RANCH, CA 95497 PV-7
PV-8
ASSEMBLY DETAILS
RESOURCE DOCUMENT
1.1.6 ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AND SOURCE
CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL
BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D). SHALL BE
ASSESSOR'S #: 156280026000 PV-9
PV-10
RESOURCE DOCUMENT
RESOURCE DOCUMENT
INSTALLED ACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING [CEC PV-11 RESOURCE DOCUMENT
110.3]. PV-12 RESOURCE DOCUMENT
1.1.7 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. IF PV-13 RESOURCE DOCUMENT
EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE
WILL BE INSTALLED AS REQUIRED BY THE CEC AND AHJ. PV-14 RESOURCE DOCUMENT

1.2.1 SCOPE OF WORK:


3 1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND SPECIFICATIONS OF
THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BE
RESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN,
SPECIFY, AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THE
PHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT.
PROJECT INFORMATION
1.3.1 WORK INCLUDES: OWNER
1.3.2 PV ROOF ATTACHMENTS - IRONRIDGE FLASHFOOT2 NAME: SANFILLIPPO-HOUSTON RESIDENCE
1.3.3
1.3.4
PV RACKING SYSTEM INSTALLATION - IRONRIDGE XR-100
PV MODULE AND INVERTER INSTALLATION - AERIAL PHOTO PHONE:

1.3.5
REC SOLAR REC410AA PURE / TESLA 1707000-XX-Y 11.5 KW
PV EQUIPMENT GROUNDING
01 NOT TO SCALE
E-MAIL:

PROJECT MANAGER
1.3.6 PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX NAME: ERIC DUFF
1.3.7 PV LOAD CENTERS (IF INCLUDED) PHONE: 707-412-3181
4 1.3.8 PV METERING/MONITORING (IF INCLUDED)
1.3.9 PV DISCONNECTS CONTRACTOR
1.3.10 PV FINAL COMMISSIONING NAME: MD ELECTRIC AND SOLAR INC.
1.3.11 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV PHONE: 707-412-3181
1.3.12 SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE
AUTHORITIES HAVING JURISDICTION
BUILDING: SONOMA COUNTY
ZONING: SONOMA COUNTY
UTILITY: PG&E

H
DESIGN SPECIFICATIONS

AC
RE
SCOPE OF WORK OCCUPANCY: R-3

NE
SYSTEM SIZE: STC: 17 X 410W = 6.970KW CONSTRUCTION: SINGLE-FAMILY

PI
PTC: 17 X 390.32W = 6.635KW ZONING: RESIDENTIAL

A
SE
(17) REC SOLAR REC410AA PURE RISK CATEGORY: II
5 (1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW) ROOF SNOW LOAD: 0 PSF
(1) TESLA BACKUP SWITCH (1624171-XX-Y) WIND EXPOSURE: D
WIND SPEED: 91 MPH
PLOT MAP
ATTACHMENT TYPE: IRONRIDGE FLASHFOOT2
02 NOT TO SCALE
APPLICABLE CODES & STANDARDS
BUILDING:
ELECTRICAL:
CBC 2022, CRC 2022
CEC 2022
MSP UPGRADE: NO FIRE: CFC 2022
CONTRACTOR COVER PAGE
MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
G-1
A B C D E F G H
A B C D E F G H
2.1.1 SITE NOTES:
*CEC2022I
MARKED GREEN IF #4 AWG OR LARGER [CEC 250.119] 2.7.7 ACCORDING TO CEC 200.7, UNGROUNDED SYSTEMS DC CONDUCTORS COLORED OR MARKED
2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 2.4.9 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH CEC 690.47 AND CEC 250.50 THROUGH AS FOLLOWS:
2.1.3 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY 250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE DC POSITIVE- RED, OR OTHER COLOR EXCLUDING WHITE, GRAY AND GREEN
1 INTERACTIVE SYSTEM WITH STORAGE BATTERIES. SYSTEM PROVIDED ACCORDING TO CEC 250, CEC 690.47 AND AHJ. DC NEGATIVE- BLACK, OR OTHER COLOR EXCLUDING WHITE, GRAY AND GREEN
2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING 2.4.10 DC PV ARRAYS SHALL BE PROVIDED WITH DC GROUND-FAULT PROTECTION MEETING THE 2.7.8 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS:
ROOF VENTS. REQUIREMENTS OF 690.41(B)(1) THROUGH (3) TO REDUCE FIRE HAZARDS PHASE A OR L1- BLACK
2.1.5 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE
EQUIPMENT WILL BE PROVIDED AS PER SECTION CEC 110.26. PHASE C OR L3- BLUE, YELLOW, ORANGE*, OR OTHER CONVENTION
2.1.6 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH 2.5.1 INTERCONNECTION NOTES: NEUTRAL- WHITE OR GRAY
THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF 2.5.2 LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [CEC 705.12]
COVERING SERVES TO PROTECT THE BUILDING OR STRUCTURE. 2.5.3 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT AND THE * IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED
RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL NOT EXCEED 120 ORANGE [CEC 110.15].
2 2.2.1 EQUIPMENT LOCATIONS PERCENT OF THE AMPACITY OF THE BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE
2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY CEC 110.26. LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [CEC 705.12(B)(3)(2)].
2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING 2.5.4 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTAL RATING OF ALL
TEMPERATURE AS SPECIFIED BY CEC 690.31 (A),(C) AND CEC TABLE 310.15 (B)(1). OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THE
*CEC2022I

2.2.4 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO CEC COMBINED OVERCURRENT DEVICE MAY BE EXCLUDED ACCORDING TO CEC 705.12 (B)(3)(3). 2.8.1 ENERGY STORAGE SYSTEMS (ESS) NOTES:
690.34. 2.5.5 FEEDER TAP INTERCONNECTION (LOAD SIDE) ACCORDING TO CEC 705.12 (B)(1) AND (2) 2.8.2 CEC 706.5 ENERGY STORAGE SYSTEMS SHALL BE LISTED.
2.2.5 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN 2.5.6 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO CEC 705.11 WITH SERVICE ENTRANCE 2.8.3 CEC 706.6 MULTIPLE ESS'S SHALL BE PERMITTED TO BE INSTALLED IN OR ON BUILDING OR
SIGHT OF THE AC SERVICING DISCONNECT. CONDUCTORS IN ACCORDANCE WITH CEC 230.42 STRUCTURE.
2.2.6 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO 2.5.7 BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT FROM 2.8.4 CEC 706.9 THE MAXIMUM VOLTAGE OF AN ESS SHALL BE RATED ESS INPUT AND OUTPUT
CEC APPLICABLE CODES. ADDITIONAL FASTENING [CEC 705.12 (E)]. VOLTAGES INDICATED ON ESS NAMEPLATE.
2.2.7 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN 2.8.5 CEC 706.15(A) A DISCONNECTING MEANS SHALL BE PROVIDED FOR ALL UNGROUNDED
APPROPRIATE. 2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES: CONDUCTORS DERIVED FROM AN ESS AND SHALL BE PERMITTED TO BE INTEGRAL TO LISTED
2.6.2 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE ESS EQUIPMENT. DISCONNECT SHALL BE READILY ACCESSIBLE AND WITHIN SIGHT OF THE ESS
3 2.3.1 STRUCTURAL NOTES: CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINE OR AS CLOSE AS POSSIBLE IF IMPRACTICAL TO INSTALL WITHIN SIGHT. DISCONNECTING MEANS
2.3.2 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT SIDE” (TYPICALLY THE UPPER TERMINALS). SHALL BE LOCKABLE.
INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES, 2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A 2.8.6 CIRCUIT SIZING AND CURRENT SHALL BE CALCULATED PER CEC 706.30(A)(1) THROUGH (A)(5).
AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE VISIBLE-BREAK SWITCH. 2.8.7 OVERCURRENT PROTECTION SHALL BE BE RATED IN ACCORDANCE OF NEC 240 AND WITH
ARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS. 2.6.4 BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED. THEREFORE BOTH MUST REQUIREMENTS OF CEC 706.31 (B) THROUGH (F).
2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IF OPEN WHERE A DISCONNECT IS REQUIRED, ACCORDING TO CEC 690.13. 2.8.8 SEE NOTES FOR LOAD SIDE SOURCE CONNECTION OF ESS WITH POWER CONTROL SYSTEM
ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS. 2.6.5 ISOLATING DEVICES OR EQUIPMENT DISCONNECTING MEANS SHALL BE INSTALLED IN CIRCUITS (PCS).
2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/ APPROVED CONNECTED TO EQUIPMENT AT A LOCATION WITHIN THE EQUIPMENT, OR WITHIN SIGHT AND 2.8.9 INSTALLATION SHALL BE IN COMPLIANCE TO PRESENTLY APPLICABLE FIRE CODE REGARDING
CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR. WITHIN 10 FT. OF THE EQUIPMENT. AN EQUIPMENT DISCONNECTING MEANS SHALL BE LIMITATIONS ON QUANTITY, SIZE OR MINIMUM SPACING REQUIREMENTS APPROPRIATE TO
2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE PERMITTED TO BE REMOTE FROM THE EQUIPMENT WHERE THE EQUIPMENT DISCONNECTING STRUCTURE CATEGORY, TO MANUFACTURER'S INSTRUCTIONS AND TO PRODUCT LISTING.
SPECIFIED BY THE RACKING MANUFACTURER. MEANS CAN BE REMOTELY OPERATED FROM WITHIN 10 FT. OF THE EQUIPMENT, ACCORDING
2.3.6 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST TO CEC 690.15 (A).
THE ROOF FRAMING MEMBERS. 2.6.6 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN
4 FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY RESPONDERS IN ACCORDANCE WITH
2.4.1 GROUNDING NOTES: 690.12(A) THROUGH (D)
2.4.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING 2.6.7 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO CEC 690.8, 690.9, AND 240.
DEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE. 2.6.8 BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED, THEREFORE BOTH
2.4.3 PV SYSTEMS REQUIRE AN EQUIPMENT GROUNDING CONDUCTOR. ALL METAL ELECTRICAL REQUIRE OVER-CURRENT PROTECTION, ACCORDING TO CEC 240.21. (SEE EXCEPTION IN CEC
EQUIPMENT AND STRUCTURAL COMPONENTS BONDED TO GROUND, IN ACCORDANCE WITH 690.9)
250.134 OR 250.136(A). ONLY THE DC CONDUCTORS ARE UNGROUNDED. 2.6.9 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TO
2.4.4 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO CEC 690.43 AND MINIMUM CEC TABLE CEC 690.11 AND UL1699B.
250.122.
2.4.5 METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURE CONSIDERED 2.7.1 WIRING & CONDUIT NOTES:
GROUNDED IN ACCORD WITH 250.134 AND 250.136(A). 2.7.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND
2.4.6 EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT
5 MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED, TO LIMIT UP-SIZING.
MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES 2.7.3 ALL CONDUCTORS SIZED ACCORDING TO CEC 690.8, CEC 690.7.
PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS. 2.7.4 EXPOSED PV SOURCE CIRCUITS AND OUTPUT CIRCUITS SHALL USE WIRE LISTED AND
2.4.7 THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL IDENTIFIED AS PHOTOVOLTAIC (PV) WIRE [690.31 (C)]. PV MODULES WIRE LEADS SHALL
OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE. BE LISTED FOR USE ON PV ARRAYS, ACCORDING TO CEC 690.31 (A).
2.4.8 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR 2.7.5 PV WIRE BLACK WIRE MAY BE FIELD-MARKED WHITE [CEC 200.6 (A)(5)].
2.7.6 MODULE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY.

CONTRACTOR NOTES
MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
G-2
A B C D E F G H
A B C D E F G H

GENERAL NOTES
1 1. FIELD VERIFY ALL MEASUREMENTS
EXTERIOR PV EQUIPMENT
2. ITEMS BELOW MAY NOT BE ON THIS PAGE
TESLA POWERWALL 3
3. THE SOLAR PANELS ARE LESS THAN 4 FEET
CAL-FIRE ROOF ACCESS POINT RSD BUTTON PROPERTY LINE
PER CRC 2022 SEC. R324.6 TYP METER/MAIN WITH TESLA BACKUP SWITCH

AREA OF WORK
100'-9"

2
DRIVEWAY
CAL-FIRE ROOF ACCESS POINT
PER CRC 2022 SEC. R324.6 TYP

INTERIOR PV EQUIPMENT
SUB PANEL

45'-5"

3 ENTRANCE

42'-8"
47'-11" PROPERTY LINE

CONSTRUCTION NOTES
1. SOLAR PHOTOVOLTAIC SYSTEM TO BE INSTALLED ON RESIDENTIAL
4 STRUCTURE.
2. THIS PROJECT HAS BEEN DESIGNED IN COMPLIANCE WITH THE
CBC SECTION 1609 TO WITHSTAND A BASIC WIND SPEED OF 91 MPH
(3 SECOND GUST), WIND EXPOSURE D.
3. THE ROOF MEMBERS ARE 2X10 IN. RAFTER AT 24 O.C. CONNECTION
TO STRUCTURE SHALL NOT BE WITHIN 6 IN. OF NAILING PLATES.
4. THE SOLAR PHOTOVOLTAIC INSTALLATION SHALL NOT OBSTRUCT
ANY PLUMBING, MECHANICAL OR BUILDING ROOF VENTS.
ACH
5. ALL CONDUCTORS AND CONDUITS MOUNTED ON ROOF SHALL BE
E RE
MINIMUM 3 3/4 IN. ABOVE ROOF SURFACE (INCLUDING CABLES P IN
UNDERNEATH MODULES AND RACKING).
SEA
6. ROOF ACCESS POINTS SHALL BE PROVIDED PER THE FOLLOWING
(CRC 2022 SEC. R324.6, CBC 3111.3.4):
5 - LOCATED IN AREAS NOT REQUIRING PLACEMENT OF GROUND
LADDERS OVER OPENINGS SUCH AS DOORS OR WINDOWS.
- LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION IN N
LOCATIONS WHERE ACCESS POINT DOES NOT CONFLICT WITH
SITE PLAN
OVERHEAD OBSTRUCTIONS SUCH AS: TREE LIMBS, WIRES, OR
SIGNS. 01 1/32" = 1'-0" 0 16' 32'
W E

CONTRACTOR SITE PLAN


MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
PV-1
A B C D E F G H
A B C D E F G H

EXTERIOR PV EQUIPMENT
GENERAL NOTES
(N)(1) TESLA POWERWALL 3
1 1. FIELD VERIFY ALL MEASUREMENTS
(N)(1) RSD BUTTON
2. ITEMS BELOW MAY NOT BE ON THIS PAGE
18 IN. FIRE ACCESS PATH (E)(1) METER/MAIN WITN (N)(1) TESLA BACKUP SWITCH
3. THE SOLAR PANELS ARE LESS THAN 4 FEET
A MODULE STRINGING

B MODULE STRINGING

CAL-FIRE ROOF ACCESS POINT


PER CRC 2022 SEC. R324.6 TYP FIRE CLEARANCE

2 INTERIOR PV EQUIPMENT
(E)(1) SUB PANEL SQUARE FOOTAGE OF ROOF: 3179 SQ. FT.
SQUARE FOOTAGE OF ARRAY: 338.58 SQ. FT.
PERCENTAGE OF ROOF COVERED BY THE ARRAYS: 10.65%

CAL-FIRE ROOF ACCESS POINT


PER CRC 2022 SEC. R324.6 TYP
3

36 IN. FIRE ACCESS PATH

(N) (1) JUNCTION BOX

A A

A A A A A
ARRAY 1 - 6.970 KW
[x17] (N) MODULES
TILT: 18 DEGREES
A A В В В 40''
ROOF PITCH: 4:12
AZIMUTH: 210 DEGREES
5 MODULE:
6 IN. FIRE ACCESS PATH
В В В В В
N REC SOLAR
ELECTRICAL PLAN E
71.7'' REC410AA PURE
01 3/32" = 1'-0" 0 5'-4" 10'-8" W
S
410 WATTS

CONTRACTOR ELECTRICAL PLAN


MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
PV-2
A B C D E F G H
A B C D E F G H

GENERAL NOTES
1 1. FIELD VERIFY ALL MEASUREMENTS
2. ITEMS BELOW MAY NOT BE ON THIS PAGE
3. THE SOLAR PANELS ARE LESS THAN 4 FEET
ROOF RAFTERS

2"X10" RAFTER @24" O.C.

ROOF ATT. TYP.


@72" MAX.

ROOF MATERIAL IS COMP. SHINGLE

FLUSH MOUNT SOLAR MODULES


ATTACHED TO ROOF SURFACE (SEE 40''
SHEET PV-7 FOR MOUNTING DETAILS) 16'-9"
5 MODULE:
N REC SOLAR
SOLAR ATTACHMENT PLAN E

01 3/32" = 1'-0" 0 5'-4" 10'-8" W


S
71.7'' REC410AA PURE
410 WATTS

CONTRACTOR SOLAR ATTACHMENT PLAN


MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
PV-3
A B C D E F G H
A B C D E F G H
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
MAX.
CURRENT-CARRYING TEMP. CORR. CONDUIT FILL CONT. DERATED TERM. TEMP. AMP. @
ID TYPICAL CONDUCTOR CONDUIT OCPD EGC CURRENT BASE AMP. LENGTH VOLTAGE DROP
1 CONDUCTORS IN CONDUIT FACTOR FACTOR CURRENT AMP. RATING TERMINAL
(125%)
1 2 10 AWG PV WIRE, COPPER FREE AIR 2 N/A 6 AWG BARE, COPPER 1.08 (16.4 °C) 1 13.03A 16.28A 55A 59.4A 75°C 50A 45FT 0.37%
2 1 10 AWG THHN, COPPER 0.75'' DIA EMT 4 N/A 10 AWG THWN-2, COPPER 1.08 (16.4 °C) 0.8 13.03A 16.28A 40A 34.56A 75°C 35A 70FT 0.57%
3 1 6 AWG THHN, COPPER 0.75'' DIA EMT 2 60A 8 AWG THWN-2, COPPER 1.08 (16.4 °C) 1 48A 60A 75A 81A 75°C 65A 10FT 0.18%

A MODULE STRINGING

2 TO UTILITY
B MODULE STRINGING GRID (UG)

L2
(N) TESLA BACKUP SWITCH N
L1
(N) 4-CONDUCTOR COMMUNICATION CABLE
16/4 TC-ER (Е)
0.5" EMT CONDUIT UTILITY GROUND
PG&E UTILITY METER#: METER NOTE: PRODUCERS STORAGE DEVICE(S) WILL NOT CAUSE THE
ROD
____________________ HOST LOAD TO EXCEED ITS NORMAL PEAK DEMAND. NORMAL
PEAK DEMAND IS DEFINED AS THE HIGHEST AMOUNT OF POWER
(E) GROUNDING REQUIRED FROM THE DISTRIBUTION SYSTEM BY PRODUCERS
N G COMPLETE FACILITIES WITHOUT THE INFLUENCE OR USE OF THE
3 ELECTRODE
(E) MAIN ENERGY STORAGE DEVICE(S).
200A
NOTE: SOLAR INVERTER INSTALLED IS A SMART INVERTERS PER
TO (E) CALIFORNIA RULE 21
LOADS
(N) (6) TESLA RAPID SHUTDOWN DEVICE MCI-1 (Е) METER/MAIN WITH
(N) TESLA WITH (N) TESLA BACKUP SWITCH
(N) (17) REC SOLAR POWERWALL 3 100А 1624171-XX-Y
REC410AA PURE (N) JUNCTION BOX
1707000-XX-Y 11.5 KW (240V) 240/120 V 1Ø, 3W
410 WATTS MAIN BUSS: 200A
- BATTERY
DC
1 2
+ DC
G
4
A 9

B 8
N G
RSD OUT

COMMS
RSD IN

(N) RSD G L1L2 N


СВ1
PV SYSTEM EQUIPPED WITH RAPID 3 N (N) TO (E)
SHUTDOWN DISCONNECT PER CEC 690.12 60A/2P LOADS
SYSTEM COMPLIANT WITH CEC 690.13 14 AWG THHN, 12V RSD
L2
L1

5 (Е) SUB PANEL


240/120 V 1Ø, 3W
MAIN BUSS: 100A

CONTRACTOR LINE DIAGRAM


MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
PV-4
A B C D E F G H
A B C D E F G H

PV SYSTEM SUMMARY MODULES


INVERTER #1 REF. QTY. MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING
MPPT #1 MPPT #2 PM1-17 17 REC SOLAR REC410AA PURE 410W 390.32W 10.42A 9.72A 49.4V 42.2V -0.119V/°C (-0.24%/°C) 25A
MODULES PER MPPT 9 8
ARRAY VMP 379.8V 337.6V
ARRAY IMP 9.72A 9.72A INVERTERS
ARRAY VOC 444.6V 395.2V AC OCPD RATED MAX OUTPUT MAX INPUT MAX INPUT CEC WEIGHTED
REF. QTY. MAKE AND MODEL GROUND
3 ARRAY MAX VOC 472V 419.6V VOLTAGE RATING POWER CURRENT CURRENT VOLTAGE EFFICIENCY
I1 1 TESLA POWERWALL 3 (1707000-xx-y) 11.5 KW 240V FLOATING 60A 11500W 48A 6X13A 600V 97.0%
ARRAY ISC 10.42A 10.42A
ARRAY STC POWER 6,970W
ARRAY PTC POWER 6,635W
MAX AC CURRENT 48A
BATTERY ENERGY STORAGE SYSTEM
MAX. CONTINUOUS MAX. CONTINUOUS MAX. CONTINUOUS
MAX AC POWER 11,500W REF. QTY. MAKE AND MODEL NOMINAL BATTERY ENERGY
CURRENT CHARGE POWER DISCHARGE POWER
DERATED (CEC) AC POWER 6,436W BS1 1 TESLA POWERWALL 3 (1707000-XX-Y) 13.5KWH 48A 5 KW 11.5 KW

RAPID SHUTDOWN DEVICE


REF. QTY. MAKE AND MODEL NOMINAL CURRENT MAX.CURRENT MAX DC VOLTAGE
4
RS1-6 6 TESLA RAPID SHUTDOWN DEVICE MCI-1 12А 19A 600VDC

ASHRAE EXTREME LOW -0.6°C (30.9°F), SOURCE: POINT ARENA (38.95°; -123.73°) OCPDS
ASHRAE 2% HIGH 16.4°C (61.5°F), SOURCE: POINT ARENA (38.95°; -123.73°) REF. QTY. RATED CURRENT MAX VOLTAGE
CB1 1 60A 240VAC

CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS


5

CONTRACTOR DESIGN TABLES


MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
PV-5
A B C D E F G H
A B C D E F G H

1 LABELING NOTES
!CAUTION!
1.1 LABELING REQUIREMENTS BASED ON THE 2022 CALIFORNIA ELECTRICAL CODE,
CALIFORNIA FIRE CODE, OSHA STANDARD 1910.145, ANSI Z535 POWER TO THIS BUILDING IS ALSO SUPPLIED
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING
JURISDICTION. FROM ROOF MOUNTED SOLAR ARRAYS WITH
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
INVOLVED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
SAFETY DISCONNECTS AS SHOWN:
1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED
BACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVE
YELLOW BACKGROUND. [ANSI Z535] ESS
1.6 ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHER
2 RESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN PER CEC 110.21(B)

BACK
WARNING INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTED
ELECTRICAL SHOCK HAZARD
PHOTOVOLTAIC POWER SOURCE PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED MAIN DISTRIBUTION
NE SIDE OF THE ATTACHED GARAGE UTILITY DISCONNECT
TERMINALS ON THE LINE AND DIRECTORY
LOAD SIDES MAY BE ENERGIZED LABEL 4
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE
IN THE OPEN POSITION AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING
METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE
LABEL 1 MEANS IF NOT IN THE SAME LOCATION (5 3/4" X 1 1/8").
SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,
AT EACH DISCONNECTING MEANS FOR [CEC 690.56(B)] FRONT
OR FLOORS (5 3/4" X 1 1/8").
PHOTOVOLTAIC EQUIPMENT (2" X 4"). [CEC 690.31(D)(2)] WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A
[CEC 690.13]. DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PV
SYSTEM DISCONNECTING MEANS. N
WARNING PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED IN
3 BATHROOMS
POWER SOURCE [CEC 690.4(D),(E)]
W E PV ARRAY
OUTPUT CONNECTION
DO NOT RELOCATE THIS RAPID SHUTDOWN PHOTOVOLTAIC SOLAR AC DISCONNECT S

OVERCURRENT DEVICE SWITCH FOR AC DISCONNECT PHOTOVOLTAIC SYSTEM


LABEL 2 SOLAR PV SYSTEM LABEL 9 POWER SOURCE
AT POINT OF INTERCONNECTION AT EACH AC DISCONNECTING MEANS RATED AC
OVERCURRENT DEVICE (2" X 4"). 48 AMPS
LABEL 5 (4" X 1"). OUTPUT CURRENT
[CEC 705.12(B)(3)(2)]. [CEC 690.13(B)]. NOMINAL OPERATING
AT RAPID SHUTDOWN DISCONNECT SWITCH (5 1/4" X 2"). 240 VOLTS
[CEC 690.56(C)(3)]. AC VOLTAGE
SOLAR PV SYSTEM PHOTOVOLTAIC SOLAR LABEL 11
DC DISCONNECT AT POINT OF INTERCONNECTION, MARKED
EQUIPPED WITH CAUTION AT DISCONNECTING MEANS (4" X 2").
LABEL 10 [CEC 690.54]
4 RAPID SHUTDOWN MULTIPLE SOURCES OF POWER AT EACH DC DISCONNECTING MEANS
(4" X 1").
LABEL 6 [CEC 690.13(B)].
AT UTILITY METER (5 3/4" X 1 1/8")
SOLAR ELECTRIC
[CEC 690.56(B)] BATTERY STORAGE
PV PANELS DIRECT CURRENT
PHOTOVOLTAIC POWER SOURCE SYSTEM RATING
MAX BATTERY CURRENT: 48 A
MAX AC VOLTAGE: 240 V
MAXIMUM VOLTAGE 472 VDC MAX DC VOLTAGE: 400 VDC
MAX CIRCUIT CURRENT 10.42 AMPS ENERGY: 13.5 KWH
TURN RAPID SHUTDOWN SWITCH TO WARNING
THE "OFF" POSITION TO SHUT DOWN DUAL POWER SUPPLY
WARNING LABEL 12 LABEL 13
PV SYSTEM AND REDUCE SHOCK
SOURCES: UTILITY GRID SOLAR ELECTRIC AT EACH DC DISCONNECTING
HAZARD IN ARRAY AND PV SOLAR CIRCUIT BREAKER MEANS (3" X 4").
ELECTRIC SYSTEM IS BACKFED [CEC 690.53].
LABEL 3 LABEL 8
5 AT RAPID SHUTDOWN SYSTEM LABEL 7
AT POINT OF INTERCONNECTION AT POINT OF
(3 3/4" X 5 1/4"). [CEC 690.56(C)(1)(A)]. INTERCONNECTION
(2 3/4" X 1 5/8").
[CEC 705.12(B)(3)] (2" X 1").
[CEC 705.12(B)(3)]

CONTRACTOR PLACARDS
MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
PV-6
A B C D E F G H
A B C D E F G H

GENERAL NOTES
1 1. FIELD VERIFY ALL MEASUREMENTS
D-4
2. ITEMS BELOW MAY NOT BE ON THIS PAGE
PV-7 3. THE SOLAR PANELS ARE LESS THAN 4 FEET

27

4 5 8

23 24 25

2 20
2
D-5
3 1 PV-7

11 15 18 22
13 14 12

3 RACKING DETAIL (TRANSVERSE) RACKING DETAIL (LONGITUDINAL) SHEET KEYNOTES


D1 NOT TO SCALE D2 NOT TO SCALE 1.
2.
ROOF MATERIAL: COMP. SHINGLE
ROOF STRUCTURE: SINGLE SPAN RAFTER
3. ATTACHMENT TYPE: IRONRIDGE FLASHFOOT2
4. MODULE MANUFACTURER: REC SOLAR
5. MODULE MODEL: REC410AA PURE
10 9
6. MODULE LENGTH: 71.7''
7. MODULE WIDTH: 40''
8. MODULE WEIGHT: 45 LBS.
ROOF SLOPE

10 9. SEE SHEET PV-3 FOR DIMENSION(S)


10. MIN. FIRE OFFSET: 18" FROM RIDGE, AT LEAST 2 PATHWAY
TO A STREET OR DRIVEWAY MINIMUM 3' WIDE, 6" FROM
4 EAVES
11. RAFTER SPACING: 24 IN. O.C.
6 21
12. RAFTER SIZE: 2X10 IN. NOMINAL
13. LAG BOLT DIAMETER: 5/16 IN.
14. LAG BOLT EMBEDMENT: 2 1/2 IN.
15. TOTAL # OF ATTACHMENTS: 30.
16. TOTAL AREA: 338.58 SQ. FT.
17. TOTAL WEIGHT: 842.07 LBS.
18. WEIGHT PER ATTACHMENT: 28.07 LBS.
19. DISTRIBUTED LOAD: 2.49 PSF
7 20. MAX. HORIZONTAL STANDOFF: 72 IN.
21. MAX. VERTICAL STANDOFF: IN ACCORDANCE WITH
MODULE MANUFACTURER'S INSTRUCTIONS.
5 RACKING DETAIL (TOP) DETAIL (TRANSVERSE) DETAIL (LONGITUDINAL) 22. STANDOFF STAGGERING: YES
D3 NOT TO SCALE D4 NOT TO SCALE D5 NOT TO SCALE
23.
24.
RAIL MANUFACTURER (OR EQUIV.): IRONRIDGE
RAIL MODEL (OR EQUIVALENT): XR-100
25. RAIL WEIGHT: 0.68 PLF
26. MAX. RAFTER SPAN: N/A.
27. MODULE CLEARANCE: 3 IN. MIN., 7 IN. MAX.

CONTRACTOR ASSEMBLY DETAILS


MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
PV-7
A B C D E F G H
A B C D E F G H

CONTRACTOR RESOURCE DOCUMENT


MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
PV-8
A B C D E F G H
A B C D E F G H

CONTRACTOR RESOURCE DOCUMENT


MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
PV-9
A B C D E F G H
A B C D E F G H

CONTRACTOR RESOURCE DOCUMENT


MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
PV-10
A B C D E F G H
A B C D E F G H

CONTRACTOR RESOURCE DOCUMENT


MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
PV-11
A B C D E F G H
A B C D E F G H

CONTRACTOR RESOURCE DOCUMENT


MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
PV-12
A B C D E F G H
A B C D E F G H

CONTRACTOR RESOURCE DOCUMENT


MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
PV-13
A B C D E F G H
A B C D E F G H

CONTRACTOR RESOURCE DOCUMENT


MD ELECTRIC AND SOLAR INC. SANFILLIPPO-HOUSTON RESIDENCE SYSTEM AC SIZE @ STC: 11.500 kW SYSTEM DC SIZE @ STC: 6.970 kW (N) BESS CAPACITY: 13.5 KWH PAGE:
6 38191 OLD STAGE RD, RESIDENTIAL GRID INTERACTIVE SOLAR AND ENERGY STORAGE INSTALLATION
(17) REC SOLAR REC410AA PURE
GUALALA, CA 95445 63 SEA PINE REACH, SEA RANCH, CA 95497
PHONE: 707-412-3181
CONTRACTOR LICENSE: 815891
ASSESSOR'S #: 156280026000
PHONE:
(1) TESLA POWERWALL 3 (1707000-XX-Y 11.5 KW)

DRAWN: V.D.
CHECKED: D.A.
(1) TESLA BACKUP SWITCH (1624171-XX-Y)

REV: PERMIT SET


DATE:
3.24.2024
PV-14