Annexure - A

Load Calculation
1.0 Wind Load
The wind loads have been calculated based on the parameters established for the standard site conditions. For wind loads design code IS-875
(Part – 3) has been followed.
Basic Design Wind Speed (Vb) 39.00 m/s IS 875 part 3, Fig. 1
Risk Coeff. (k1) 1.00 IS 875 part 3, Section 6.3.1, table 1
Terrain & height factor (k2) 1.00 IS 875 part 3, Section 6.3.2.2, table 2
Topography factor (k3) 1.00 IS 875 part 3, IS 875 part 3, Section 6.3.1
Cyclonic Region (k4) 1.00 IS 875 part 3, IS 875 part 3, Section 6.3.4
Design Wind Speed (Vz) Vb x k1 x k2 x k3 x k4
(Vz) 39.00 m/s
Design Wind Pressure (Pd)
(Pz) 0.6 Vz2
912.60 N/m2
(Pz) 0.913 KN/m2
Wind directionality factor(kd ) 0.90 IS 875 part 3 (2015), Section7.2.1

Area averaging Factor ( ka) 0.90 IS 875 part 3 2015, Section 7.2.2, Table 4

(Pd) = ka x kd x PZ
(Pd) = 739.21 N/m2
(Pd) = 0.739 KN/m2
20% reduction = 0.591 KN/m2 IS 875 Part 3 - 2015 Clause 6.3

Internal pressure coeff. (Cpi) ± 0.2


(Building with medium opening with 5 (Page No. 38 IS 875 part 3)
Length of building (L) 10.21 m
Width of building (W) 6.35 m
height of building (eave height) (H) 4.6 m
H/W 0.72
L/W 1.61

Wind load Calculation for Roof


Roof angle a 17
Table 5 (Page 16 of IS 875 Part 3)
Wind angle (q) 0 in staad X direction EF GH
Cpe -0.7 -0.5
Cpe-Cpi -0.9 -0.7 E G
Cpe+Cpi -0.5 -0.3

Wind pressure E F G H F H
Cpe-Cpi -0.53 kN/m2 -0.53 kN/m2 -0.41 kN/m2 -0.41 kN/m2
Cpe+Cpi -0.30 kN/m2 -0.30 kN/m2 -0.18 kN/m2 -0.18 kN/m2

Wind angle (q) 90 in staad X direction EG FH


Cpe -0.8 -0.6
Cpe-Cpi -1 -0.8
Cpe+Cpi -0.6 -0.4

Wind pressure E F G H
Cpe-Cpi -0.59 kN/m2 -0.59 kN/m2 -0.47 kN/m2 -0.47 kN/m2
Cpe+Cpi -0.35 kN/m 2
-0.35 kN/m2
-0.24 kN/m 2
-0.24 kN/m2