Download as pdf or txt
Download as pdf or txt
You are on page 1of 154

DOCUMENT / DRAWING

COMMENTS RESOLUTION SHEET (CRS)

Review
Project Name: NGHP – Green Hydrogen Element (GHE) AP Project No.: PM210011
Code:

3rd Party/Vendor Transmittal


NUI-TRANSMIT-000046 Actual Date Received: 28-May-2023 Code 2
Ref.:

3rd Party/Vendor Name: NUI - Nesma United Industries Unit Code: 900 - Common Buildings

Document / Drawing Title: Document / Drawing Ref. No.: Rev. No.

MATERIAL TECHNICAL SUBMITTAL PANEL BOARDS (NESMA UNITED INDUSTRY) PM210011-NUI900-ESE-00001 01

COMMENTS RESPONSE

REVIEWER'S COMPANY NAME DOCUMENT ORIGINATOR'S COMPANY NAME STATUS


Reviewers' Reviewers'
Page /
Item No. Names Comments
Sht. No.
/Initials Incorporated? Document
AIR PRODUCTS Comments NESMA Response Reviewer
Originator

R0 : NESMA to provide separate documents for Pre-qualification and Vendor


PQ Submittal approved under Submittal Ref. : PM210011-NUI900-
01 BHINDEG Page 1 documents. Yes Closed
OSE-00058 dated 13 May 2023.
R1 : Mention the document no in which Pre-qualification details are submitted.
R0 : CHSS to check and Endorse the Vendor document information first with respect
AP specs and Detail Engineering Deliverables and then re-submit the document for AP
noted , no deviations will be considered unless the ones officially
02 BHINDEG Page 1 review. Yes Closed
approved by AP
R1 : NUI/CHSS to check and response. Incase any deviation on the AP requirement
then same shall be provided to AP.
R0 : DB shall be in compliance with the site environmental condition (PM210011- 000-
03 BHINDEG Page 1 GD1-00001). Comply Yes Closed
R1 : This document is already attached in RFP package of building.
R0 : Show available Hardwired contact for incomer & outgoing MCCB Please Refer attached drawings with clouded part with ref. C04 on
04 BHINDEG Page 1 Trip/common alarm. Page 5,6&7 (drawing No. NPB-DWG-2210009-01 & NPB-DWG- Yes Closed
R1 : Comment is not incorporated in document 2210009-02).
R0 : Check the requirement for internal Wiring low smoke halogen free as per Saudi
05 Shahn Page 1 building code. Comply Yes Closed
R1 : Is it considered? kindly respond.

Reply to Comments - R1 (2) PM210011-NUI900-ESE-00001_02 1 of 154 Page 1 of 3


DOCUMENT / DRAWING
COMMENTS RESOLUTION SHEET (CRS)

Review
Project Name: NGHP – Green Hydrogen Element (GHE) AP Project No.: PM210011
Code:

3rd Party/Vendor Transmittal


NUI-TRANSMIT-000046 Actual Date Received: 28-May-2023 Code 2
Ref.:

3rd Party/Vendor Name: NUI - Nesma United Industries Unit Code: 900 - Common Buildings

Document / Drawing Title: Document / Drawing Ref. No.: Rev. No.

MATERIAL TECHNICAL SUBMITTAL PANEL BOARDS (NESMA UNITED INDUSTRY) PM210011-NUI900-ESE-00001 01

COMMENTS RESPONSE

REVIEWER'S COMPANY NAME DOCUMENT ORIGINATOR'S COMPANY NAME STATUS


Reviewers' Reviewers'
Page /
Item No. Names Comments
Sht. No.
/Initials Incorporated? Document
AIR PRODUCTS Comments NESMA Response Reviewer
Originator
R0 : Mention/show following details:
- Clearance requirement
- Mark distance for power and control termination from ground
- Weight of panel
- Nameplate details
Comply, Please find here attached revised drawing ref. C06 on
- Earth tab
06 Shahn Page 1 Page 4 (drawing No. NPB-DWG-2210009-01 & NPB-DWG-2210009- Yes Closed
- Lifting eyes
02).
- Gland plate details
- panel mounting arrangement
- Panel thickness, MOC
- Safety warning signs.
R1 : Add lifting eyes, panel mounting arrangement, Panel thickness and MOC
General comments:-
1. Provide the comment response excel file along with document for tracking the
Comply, Please find here attached revised drawings with clouded
07 Page 1 response. Yes Closed
part.
2. Revision marking shall be provided where ever change is done from previous
revision.

Reply to Comments - R1 (2) PM210011-NUI900-ESE-00001_02 2 of 154 Page 2 of 3


DOCUMENT / DRAWING
COMMENTS RESOLUTION SHEET (CRS)

Review
Project Name: NGHP – Green Hydrogen Element (GHE) AP Project No.: PM210011
Code:

3rd Party/Vendor Transmittal


NUI-TRANSMIT-000046 Actual Date Received: 28-May-2023 Code 2
Ref.:

3rd Party/Vendor Name: NUI - Nesma United Industries Unit Code: 900 - Common Buildings

Document / Drawing Title: Document / Drawing Ref. No.: Rev. No.

MATERIAL TECHNICAL SUBMITTAL PANEL BOARDS (NESMA UNITED INDUSTRY) PM210011-NUI900-ESE-00001 01

COMMENTS RESPONSE

REVIEWER'S COMPANY NAME DOCUMENT ORIGINATOR'S COMPANY NAME STATUS


Reviewers' Reviewers'
Page /
Item No. Names Comments
Sht. No.
/Initials Incorporated? Document
AIR PRODUCTS Comments NESMA Response Reviewer
Originator

08 Page 7 Project Client name to be : NEOM GREEN HYDROGEN COMPANY Comply, Please find here attached revised drawings. Yes Closed

Separate excel file shall be submitted which shall include AP clause no., clause
statement, deviations/clarification, remarks, etc. Deviation & Clarification file shall
09 Page 17 Noted. Yes Closed
clearly identify Deviations or clarification with proper technical justification. (Type for
all point where not complying)

Comply, Please find here attached revised drawings (NPB-DWG-


10 Page 34 Add project number, Weight in name plate Yes Closed
2210009-01, Page 04).

5R 3C+N x300/150 as per Doc. no. PM210011-900-ES1-00002 Comply, Please find here attached revised drawings (NPB-DWG-
11 Page 35 Yes Closed
Vendor to suitably consider the termination arrangement inside panel. 2210009-01, Page 05).

2R 3C+NX240/120 as per Doc. no. PM210011-900-ES1-00002 Comply, Please find here attached revised drawings (NPB-DWG-
12 Page 43 Yes Closed
Vendor to suitably consider the termination arrangement inside panel. 2210009-02, Page 05).

Reply to Comments - R1 (2) PM210011-NUI900-ESE-00001_02 3 of 154 Page 3 of 3


Release Purpose: IFR

DOCUMENT COVERSHEET

Document Information
Project No: PM210011 Project Name: NEOM GREEN HYDROGEN ELEMENTS
Project Doc No: PM210011-NUI900-ESE-00001 Rev: 02

Client Doc No: N/A Rev:


Contractor Doc N/A Issue Date: 22-Aug-
Rev:
No. 2023

Document Title NUI-MATERIAL TECHNICAL SUBMITTAL PANEL BOARDS (NESMA UNITED INDUSTRIES)

VDR Code(s)
Tag No(s):(1):
Note 1 – For multiple Tag No: refer to page 2

Review Status
Sign.
Status Code: CODE-4
Date:
Status Code Legend
Code 1 Reviewed by Air Products – REJECTED Resubmit for Review
Code 2 Reviewed by Air Products – COMMENTS AS NOTED Resubmit for Review
Code 4 Reviewed by Air Products – NO COMMENTS, No Further Submittal Required Unless Drawing/Document is Revised
Code 5 ACCEPTED FOR INFORMATION ONLY
Vendor is not relieved of responsibility for accuracy of dimensions, performance, design, design of details or any code requirements. Further, review by
Air Products does not relieve Vendor of responsibility or liability, or from furnishing material in conformance with the contract, purchase order, or
other agreement. Air Products’ review shall not be construed as an Approval by Air Products of such documents or an opinion by Air Products that such
documents are true and accurate

Purchase Order Information


Air Products Specifier:
PO Number: N/A
PO Date: N/A
Contractor Name: Nesma United Industries
Contractor Org Code: NUI
Vendor SAP ID: 10031185

PM210011-NUI900-ESE-00001_02 4 of 154
NEOM GREEN HYDROGEN ELEMENT

Contractor : Nesma United Industries Co. Ltd. Project Code: PM210011

Document No. : PM210011-NUI900-ESE-00001 Rev. 02 Date Submitted: 22-Aug-23

NUI-MATERIAL TECHNICAL SUBMITTAL PANEL


BOARDS (NESMA UNITED INDUSTRIES)
for

NEOM GREEN HYDROGEN ELEMENTS


at
NEOM INDUSTRIAL CITY, KSA
AIR PRODUCTS PROJECT NO.: PM21001

REVISION HISTORY

Rev Pages Date Description

Issued by: Checked by: Approved by:


02-Feb- Issued for Bency Mohan Wael Amari Air Products
00 138
2023 Review QA/QA Manager Project Manager Representative

13-May- Issued for Bency Mohan Wael Amari Air Products


01 138
2023 Review QA/QA Manager Project Manager Representative

22-Aug- Issued for Bency Mohan Wael Amari Air Products


02 154
2023 Review QA/QA Manager Project Manager Representative

=======================

PM210011-NUI900-ESE-00001_02 5 of 154
PM210011-NUI900-ESE-00001_02 6 of 154
PM210011-NUI900-ESE-00001_02 7 of 154
PM210011-NUI900-ESE-00001_02 8 of 154
PM210011-NUI900-ESE-00001_02 9 of 154
PM210011-NUI900-ESE-00001_02 10 of 154
PM210011-NUI900-ESE-00001_02 11 of 154
PANEL BOARD FACTORY

TECHNICAL SUBMITTAL (PANEL BOARDS)

PROJECT : NEOM GREEN HYDROGEN PROJECT - U900

CONSULTANT : SAUDI CONSOLIDATED ENGINEERING COMPANY

CLIENT : NEOM

SUBMITTED BY
Nesma United Industries Co. Ltd. (Previously - Nesma Trading Co. Ltd.)
Aug-23

Rev-2

PM210011-NUI900-ESE-00001_02 12 of 154
Project Name NEOM GREEN HYDROGEN PROJECT - U900

System PANEL BOARDS

Client NEOM

Subject TECHNICAL SUBMITTAL

INDEX
Section Description
1 Compliance Statement
2 Drawings
3 Product Catalogues
4 Sample Test Certificates

************

PM210011-NUI900-ESE-00001_02 13 of 154
1

Compliance Statement

PM210011-NUI900-ESE-00001_02 14 of 154
PM210011-NUI900-ESE-00001_02 15 of 154
PM210011-NUI900-ESE-00001_02 16 of 154
PM210011-NUI900-ESE-00001_02 17 of 154
PM210011-NUI900-ESE-00001_02 18 of 154
PM210011-NUI900-ESE-00001_02 19 of 154
PM210011-NUI900-ESE-00001_02 20 of 154
PM210011-NUI900-ESE-00001_02 21 of 154
PM210011-NUI900-ESE-00001_02 22 of 154
PM210011-NUI900-ESE-00001_02 23 of 154
PM210011-NUI900-ESE-00001_02 24 of 154
PM210011-NUI900-ESE-00001_02 25 of 154
PM210011-NUI900-ESE-00001_02 26 of 154
PM210011-NUI900-ESE-00001_02 27 of 154
PM210011-NUI900-ESE-00001_02 28 of 154
PM210011-NUI900-ESE-00001_02 29 of 154
PM210011-NUI900-ESE-00001_02 30 of 154
PM210011-NUI900-ESE-00001_02 31 of 154
PM210011-NUI900-ESE-00001_02 32 of 154
PM210011-NUI900-ESE-00001_02 33 of 154
2

Drawings

PM210011-NUI900-ESE-00001_02 34 of 154
1 2 3 4 5 6 7 8

A A

B B

C C

D D

E E

PANEL BOARD FACTORY


F F

PROJECT: PANEL TAG

NEOM GREEN HYDROGEN MDB-900-B917-E


G PROJECT - U900 (CELL ASSEMBLY BUILDING) G

QTY: 01No.

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-01


PR PR 08-02-23
H TITLE: MDB-900-B917-E (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 35 1of
OF 9
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

POWER SUPPLY APPARATUS DEGREE OF PROTECTION CIRCUIT MARKING


A A
SOURCE : SWGR-900-P412E (900-B906) MOUNTING : INCOMINGOUTGOING PROTECTION : LABELS :
FIXED IP 31 IP 42 IP 54 IP 65 ENGRAVED GRAVOPLY
400/230V, 3PH, 4W, 60Hz
DRAW-OUT ALUMINUM PVC
NO PARALLEL OPERATION PLUG-IN FORM : 1 3B TYPE : 2 4 6 MECHANICAL SCREWED (EXT.)
PARALLEL OPERATION OF OPERATION : RIVETED SELF STICK
2 4B 3 5 7
BEHIND DOOR GLUED (INT.)
ALL SOURCES PARALLEL ENCLOSURES
THROUGH PLATE COLOR : BLACK LETTERS IN WHITE BACKGROUND
B B
NEUTRAL SYSTEM : INTERLOCK Schneider Electric LANGUAGE : ENGLISH
PADLOCKING
Color : RAL 7035 PACKING
DIRECT TO EARTH (TT) EARTHED(TN) SHUTTER
THROUGH DOOR Floor Mounted Type LAND TRANSPORT
ISOLATED (IT) TNS
TERMINAL COVER PRESENTATION :
_______________
DIRECT CURRENT : TO EARTH ISOLATED CONNECTIONS FIXED FRONT TRANSPARENT DOOR
INCOMINGOUTGOING FUNCTIONAL DOOR WITH KEY _______________
C C
DIRECT
BUS BARS PLAIN DOOR PARTICULAR NOTES
TO TERMINAL PADS

MATERIAL : ALUM.
TO LINKS SELECTOR SWITCH/PUSH BUTTONS/LAMPS
COPPER APPARATUS DEFINED
ACCESS :
SYSTEM : PARTIC DIMENSIONS
REAR (CABLING) PUSH BUTTONS :
CONSTANT SECTION H V EXTENSION OF
FRONT (CABLING)
DECREASING H V ON OFF L.TEST RESET
LEFT SIDE/RIGHT SIDE SIMILAR TO
TIN PLATED H V SPECIFICATION
D ENTRY : D
WITH COLOUR CODED PVC SLEEVE LAMPS :
TOP (BY CABLES) DEVIATION
NEUTRAL : PE : BOTTOM (BY CABLES) RED GREEN YELLOW BLUE LOOSE MATERIAL
NOT DISTRIBUTED HORIZONTAL ACCESSORIES :
SCREWS _______________
SAME SECTION AS PHASES VERTICAL SELECTOR SWITCH :
HALF SECTION HALF SECTION GLAND PLATES
HOA ON/OFF AM. SS VM. SS DRAWINGS :
CABLE GLAND
SUPPLY OF AUXILIARIES SHROUDING :
E For Approval AS BUILT E
CABLE ENDS OTHERS :
VOLTAGE : ORIGIN :
FOR PRODUCTION
AUXILIARY WIRING ________________________
-ALL CIRCUITS 230 VAC / 24V DC CONTROL TRANFR.
-CONTROL 230 VAC / 24V DC FROM POWER SUPPLY SEC.VOLTAGE : 2.50 2.50 SQ.MM QUANTITY : 1 No.
-SIGNALLING 230 V AC,60HZ. FROM BUSBAR CURRENT : 2.50 2.50 SQ.MM INDICATING INSTRUMENT (METERS) REMARKS
POWER CKT.: RYB&N Y/G (GROUNDING)
INSTRUMENTS :
F CLIMATIC CONDITION CT: RYB&N F
SIZE 96 X 96 SIZE 72 X 72
ALARM: GRAY
TYPE OF CLIMATE : NORMAL
OTHERS :
TYPE OF ATMOSPHERE : ORDINARY TO SUIT DESERT
MARKING OF CIRCUITS
CONDITIONS
POWER : STAND R,Y,B,N
POLLUTION RISKS :
AUXILIARY : LOCAL END METER RELAY :
-MOUNTING INDOOR OUTDOOR
BOTH ENDS
G -AMBIENT TEMP. 50°C G
COMPOSED
-RELATIVE HUMIDITY 50% AT 50°C

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-01


PR PR 08-02-23
H TITLE: MDB-900-B917-E (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 36 2of
OF 9
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A
LEGENDS & SYMBOL A

S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION

X1
AIR CIRCUIT BREAKER
1 ACB 10 INDICATING LAMP
SURGE PROTECTION DEVICE
(ACB) 19 28
X2

B B
T2 T4 T6
A1
MOULDED CASE CIRCUIT BREAKER
2 (MCCB) 11 CONTACTOR / RELAY COIL 20 CONTROL FUSE 29
A2
T1 T3 T5

MANUAL

AUTO
OFF
HAND/OFF/AUTO
3 MCB 12 CURRENT TRANSFORMER 21
3 3
30
C SELECTOR SWITCH C
4 4

21 A
QM-OF

L3
L2

L1
MCCB AUXILIARY CONTACTS AMMETER

0
4 13 4 10
22 SPACE HEATER 31
24 22
1 3 5 11
WITH SELECTOR SWITCH

D D
C12 V

L3-L1
L2-L3
L1-L2

L1-N
L2-N
L3-N
VOLTMETER
5

0
MCCB SHUNT TRIP CONTACTS
MX 14 4 10

WITH SELECTOR SWITCH


23 THERMOSTAT 32
1 3 5 11
C11

L1 L2 L3

6 CONTACTOR 15 V POWER FACTOR METER


24 EARTH 33
E T1 T2 T3
E

A1 S1 S2 S1 S2 S1 S2
DIGITAL MULTIFUNCTION TERMINALS
7 T1 24H TIMER 16 L1 L2 L3
25 34
MFM METER
A2 V1 V2 V3 VN 0V - +

F F
CBCT

L 1

8 PANEL MOUNTED PHOTOCELL 17 26 35


S2 S1

EARTH LEAKAGE RELAY WITH


5 8
1

2
CBCT
N 2 6 9 7

1 8

XX
9 XX AUXILIARY CONTACTS 18 27 36
480V

230V

CONTROL TRANSFORMER
7 9
G 2 G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-01


PR PR 08-02-23
H TITLE: MDB-900-B917-E (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 37 3of
OF 9
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

MDB-9 00-B917-E PL-1 DS-1 PL-1 DS-1

100mm
(CELL AS SEM BLY BUILDING)
(400/230V,3PH.,4W,60Hz.)

C06
A A
POWER ON POWER ON POWER ON

R Y B
T1 T2
Q1 Q2
AMMET ER V OL T M E T ER

A 00
00 V 00
00

Q1 Q2
300 300

00 00

Electric
Schneider
T3 T4

Elect ric

Elect ric
Sc hneider

Sc hneider
Q3 Q4
Q3 Q4
T5

Electric
Schneider
Elect ric

Elect ric
Sc hneider

Sc hneider
Q5
Q5 Q6

Electric
Schneider
Elect ric
Sc hneider
Q7 Q8

B Q7 Q8 B
T9 Q9 Q10 T10

Q9 Q10

Q11 Q12
DANG ER ‫ﺧﻄﺮ‬

Q11 Q12
2000

Q13 Q14

Q13 Q14

C C
CT CT CT

TH

FU1
FU2
FU3
FU4
FU4
E1 E2 E3 E4 E5

QM

N QM
E6 E7

D D

300mm
(DRAWING POCKET INSIDE DOOR )

E
Earth Stud
ACH

E E

1200 1200 1200 600


200

FRONT VIEW INTERNAL VIEW


INTERNAL VIEW SIDE VIEW
(WITH FRONT COVER)
NOTES:
1. BUSBAR : TIN PLATED COPPER 1075
DANGER ‫ﺧﻄﺮ‬
2. ENCLOSURE:
F - FRAME WORK COMPONENTS : 2mm HAZAR D OF ELECTRICAL SHOCK OR BURN
TURN O FF POWER TO THIS EQUIPMENT
F
- DOOR, BACK & SIDE COVER : 1.5mm BEFORE WORKING INSIDE
‫ﺧﻄـــــﺮ اﻟﺼـــــﺪﻣﺔ اﻟﮑﮫﺮﺑﺎﺋﯿـــــﺔ أو اﻻﺣـــــﺘﺮاق‬
- PLINTH : 3mm 12
.5 ‫إﻳﻘـــﺎف اﻟﻄﺎﻗـــﺔ ﻟﮫـــﺬه اﻟﻤﻌــــﺪات‬
‫ﻗﺒــــﻞ ااﻟﻌﻤــــﻞ ﺑﺎﻟــــﺪاﺧﻞ‬
3. PANEL WEIGHT : 592Kg (APPX.)
4. PANEL MOUNTING : FLOOR MOUNTED TYPE DANGER LABEL
(WHITE LETTERS IN RED BACKGROUND)

475
GLAND PLATE (CUSTOMIZED)
C06

PANEL BOARD FACTORY: MDB-900-B917-E


PROJECT : NEOM GREEN HYDROGEN PROJECT - U900
G PROJECT NO. : PM210011 (CELL ASSEMBLY BUILDING) G
PANEL REF. : MDB-900-B917-E (CELL ASSEMBLY BUILDING)
CURRENT RATING : 400A
SYSTEM VOLTAGE : 400/230V,3PH., 4W, 60Hz 400/230V,3PH.,4W,60Hz.
DEGREE OF PROTECTION : IP 54
PANEL WEIGHT
YEAR OF MANUFACTURE
:
:
592Kg
2023 TOP VIEW BOTTOM VIEW PANEL TAG
MANUFACTURER REF. : NPB-2210009

NAME PLATE DETAILS


(BLACK LETTERS IN WHITE BACKGROUND)

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-01


PR PR 08-02-23
H TITLE: MDB-900-B917-E (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 38 4of
OF 9
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

1X30X10mm Main Bus bar - 400A


R
Y
A B
A
N

1x30x10mm Busbar 1x30x10mm Busbar 1x20x5mm Busbar 1x15x5mm Busbar 1x15x5mm Busbar

L3
1ASS
AMMETER
L2
SELECTOR SWITCH
L1
0
B B

S2
1CT1
S1
400/5A 9
A
4
S2
1CT2
S1 2
400/5A 5
S2
1CT3
S1
400/5A 1
C C

C04

C04

C04

C04
PE

L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3

1 11 11 11 11

QM-SDE QM-SDE QM-SDE QM-SDE

14 12 14 12 14 12 14 12
3
V
1FU1-1FU3 4

10 3 4 5 6 7 8 9 10
X1 X1 X1 6 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3
TRIP STATUS TRIP STATUS TRIP STATUS TRIP STATUS
D X2 X2 X2 D
RED YELLOW BLUE
11 Q1 Q2 Q3 Q4
1HP1 1HP2 1HP3
L3-L1 160AT/160AF TP 160AT/160AF TP 100AT/100AF TP 100AT/100AF TP
L2-L3
MCCB (TMD) MCCB (TMD) MCCB (TMD) MCCB (TMD)
QM 1VSS L1-L2

25kA 25kA 25kA 25kA


VOLTMETER 0
N L1 L2 L3 L1-N
SELECTOR SWITCH
400AT/400AF 4P L2-N
L3-N
MCCB (MIC. 2.3)
36kA 11

QM-SDE

14 12
E E

N L1 L2 L3
1 2 E1 E2 E3 E4
TRIP STATUS
C04

T1 T2 T3 T4
F F

N L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3

Incoming Supply PACU-01A (DUTY) PACU-01B (STANDBY) PACU-02 ACCU-01A (DUTY)

G
400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W G
Fed From : SWGR-900-412E (900-B906) Cable Size : 1-3Cx120 mm2 Cable Size : 1-3Cx120 mm2 Cable Size : 1-3Cx70 mm2 Cable Size : 1-3Cx70 mm2
Cable Size : 5R-3C+Nx300mm2 + 150mm2

E - 1bx30x5mm

ISSUE REVISION DATE PROJECT: DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009
NEOM GREEN HYDROGEN PROJECT - U900
01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-01
PR PR 08-02-23
H TITLE: MDB-900-B917-E (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 39 5of
OF 9
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

1X30X10mm Main Bus bar - 400A


R
Y
A B
A
N

1x15x5mm Busbar 1x15x5mm Busbar 1x20x5mm Busbar 1x20x5mm Busbar 1x20x5mm Busbar 1x20x5mm Busbar

B B

C C
C04

C04

C04

C04

C04
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

11 11 11 11 11

QM-SDE QM-SDE QM-SDE QM-SDE QM-SDE

14 12 14 12 14 12 14 12 14 12

11 12 13 14 15 16 17 18 19 20
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3
TRIP STATUS TRIP STATUS TRIP STATUS TRIP STATUS TRIP STATUS
D D
Q5 Q6 Q7 Q8 Q9 Q10
100AT/100AF TP 160AT/160AF 4P 100AT/100AF 4P 125AT/160AF 4P 125AT/160AF 4P
MCCB (TMD) MCCB (TMD) MCCB (TMD) MCCB (TMD) MCCB (TMD)
25kA 25kA 25kA 25kA 25kA

E5 E9 E10
E E

T5 T9 T10

F F

L1 L2 L3 L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

ACCU-01B (STANDBY) SPACE (100A) SPARE SPARE HUMIDIFIER FOR AHU-01A (DUTY) HUMIDIFIER FOR AHU-01B (STANDBY)

G
400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W G
Cable Size : 1-3Cx70 mm2 Cable Size : N/A Cable Size : N/A Cable Size : 1-4Cx50 mm2 Cable Size : 1-4Cx50 mm2

E - 1bx30x5mm

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-01


PR PR 08-02-23
H TITLE: MDB-900-B917-E (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 40 6of
OF 9
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

1X30X10mm Main Bus bar - 400A


R
Y
A B
A
N

1FU4(4A)

1x15x5mm Busbar 1x15x5mm Busbar 1x15x5mm Busbar 1x15x5mm Busbar

B B
Flexible Wire - 25mm2,65A 1
11
TH1 DS-1
THERMOSTAT 12
2

X1

PL-1
C ACH1
C
C04

C04

C04

C04
X2

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 QSPD
11 11 11 11
63A 3P Fuse
QM-SDE QM-SDE QM-SDE QM-SDE

14 12 14 12 14 12 14 12

21 22 23 24 25 26 27 28
N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3
TRIP STATUS TRIP STATUS TRIP STATUS TRIP STATUS
D D
Q11 Q12 Q13 Q14
80AT/100AF 4P 63AT/100AF 4P 63AT/100AF 4P 40AT/100AF 4P
MCCB (TMD) MCCB (TMD) MCCB (TMD) MCCB (TMD)
25kA 25kA 25kA 25kA
SPD1

E E

F F

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

SPARE DB-B917-E2 SPARE DB-B917-E1

G
400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W G
Cable Size : N/A Cable Size : 4CX50mm2 + 1CX35mm2 (G) Cable Size : N/A Cable Size : 4CX25mm2 + 1CX16mm2 (G)

E - 1bx30x5mm

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-01


PR PR 08-02-23
H TITLE: MDB-900-B917-E (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 41 7of
OF 9
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

1FU5
L

T1

C CBCT 8 C
E1
7 9
S2 S1

E1

(FROM MAIN BUSBAR)


AFTER INCOMER
5 8
1

230V AC
D 2 D
21
6 9 7 Q1-OF2

24 22

E E

C2
MX
C1
N

F TYPICAL CONTROL CIRCUIT FOR ELR WITH CBCT(Q1-Q7) F

G G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-01


PR PR 08-02-23
H TITLE: MDB-900-B917-E (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 42 8of
OF 9
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

BILL OF QUANTITY
A ITEM TAG CAT. REF. No. DESCRIPTION RATING QTY MANUFACTURER A

1 QM LV432677 / C40F42D400 + 29450 MCCB 4P 400AT/400AF 36kA with Micrologic 2.3 Trip Unit 400A 1 Schneider Electric
2 Q1,Q2 LV430310 / C16B3TM160C + 29450 Circuit breaker, ComPact NSX160B, 25kA/415VAC, TMD trip unit 160A, 3 poles 3d 160A 2 Schneider Electric
3 Q3,Q4,Q5 LV429550 / C10B3TM100C + 29450 Circuit breaker, ComPact NSX100B, 25kA/415VAC, TMD trip unit 100A, 3 poles 3d 100A 3 Schneider Electric
4 Q7 LV430320 / C16B6TM160C + 29450 Circuit breaker, ComPact NSX160B, 25kA/415VAC, TMD trip unit 160A, 4 poles 3d 160A 1 Schneider Electric
B 5 Q8 LV429560 / C10B6TM100C + 29450 Circuit breaker, ComPact NSX100B, 25kA/415VAC, TMD trip unit 100A, 4 poles 3d 100A 1 Schneider Electric B

6 Q9,Q10 LV430321 / C16B6TM125C + 29450 Circuit breaker, ComPact NSX160B, 25kA/415VAC, TMD trip unit 125A, 4 poles 3d 125A 2 Schneider Electric
7 Q11 LV429561 / C10B6TM080C + 29450 Circuit breaker, ComPact NSX100B, 25kA/415VAC, TMD trip unit 80A, 4 poles 3d 80A 1 Schneider Electric
8 Q12,Q13 LV429562 / C10B6TM063C + 29450 Circuit breaker, ComPact NSX100B, 25kA/415VAC, TMD trip unit 63A, 4 poles 3d 63A 2 Schneider Electric
9 Q14 LV429564 / C10B6TM040C + 29450 Circuit breaker, ComPact NSX100B, 25kA/415VAC, TMD trip unit 40A, 4 poles 3d 40A 1 Schneider Electric
C 10 1HP1-1HP3 XB7EV04MP/05MP/06MP Pilot Light - Integral LED - 230V AC (Red/Yellow/Blue) 230V AC 3 Schneider Electric C

11 1FU1-1FU5 A9N15636 SP Control Fuse Carrier 230V AC 5 Schneider Electric


12 TH1 NSYCCOTHC ClimaSys CC - simple thermostat 250V - range of temperature 0…60°C - NC - 230V AC 1 Schneider Electric
13 ACH1 NSYCR55WU2 ClimaSys PTC heating resistance 55W, 110-250V 230V AC 1 Schneider Electric
14 E1-E7 56173 Residual current protection relay, VigiPacT RH99M, 30mA-30A, 220/240VAC 50/60Hz 30mA-30A 7 Schneider Electric
D 15 T1-T7 50439 Closed toroid A type, VigiPacT, Vigilohm, IA80, inner diameter 80mm, rated current 160A - 7 Schneider Electric D

16 Encl NSYSF2012602DP Spacial SF enclosure with mounting plate - assembled - 2000x1200x600 mm IP55 1 Schneider Electric
17 1CT1-1CT3 - Current Transformer 400/5A 4 Elmex
18 A - Analog Ammeter 0-400A, 96mmx96mm 0-400A 1 Elmex
19 V - Analog Voltmeter 0-500V, 96mmx96mm 0-500V 1 Elmex
E 20 ASS - Ammeter Selector Switch - 1 Selec E

21 VSS - Voltmeter Selector Switch - 1 Selec


22 DS1 - Door Limit Switch - 1 Andeli
23 PL1 - Panel Mounted LIght - LED 220V AC, 60Hz - 1 Reputed
24 QSPD TD00-D + 63NHG000B 63A 500 Volts gG/gL NH Fuse With 3-pole NH Bases - 1 Eaton
F 25 SPD1 HLA50-255/4+0 S Panel Mounted Surge Arrester - 50KA - 1 Hakel F

26
27
28
29
G 30 G

31
32

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-01


PR PR 08-02-23
H TITLE: MDB-900-B917-E (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 43 9of
OF 9
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

C C

D D

E E

PANEL BOARD FACTORY


F F

PROJECT: PANEL TAG

NEOM GREEN HYDROGEN MDB-900-B917-N


G PROJECT - U900 (CELL ASSEMBLY BUILDING) G

QTY: 01No.

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-02


PR PR 08-02-23
H TITLE: MDB-900-B917-N (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 44 1of
OF 8
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

POWER SUPPLY APPARATUS DEGREE OF PROTECTION CIRCUIT MARKING


A A
SOURCE : SWGR-900-P412A (900-B906) MOUNTING : INCOMINGOUTGOING PROTECTION : LABELS :
FIXED IP 31 IP 42 IP 54 IP 65 ENGRAVED GRAVOPLY
400/230V, 3PH, 4W, 60Hz
DRAW-OUT ALUMINUM PVC
NO PARALLEL OPERATION PLUG-IN FORM : 1 3B TYPE : 2 4 6 MECHANICAL SCREWED (EXT.)
PARALLEL OPERATION OF OPERATION : RIVETED SELF STICK
2 4B 3 5 7
BEHIND DOOR GLUED (INT.)
ALL SOURCES PARALLEL ENCLOSURES
THROUGH PLATE COLOR : BLACK LETTERS IN WHITE BACKGROUND
B B
NEUTRAL SYSTEM : INTERLOCK Schneider Electric LANGUAGE : ENGLISH
PADLOCKING
Color : RAL 7035 PACKING
DIRECT TO EARTH (TT) EARTHED(TN) SHUTTER
THROUGH DOOR Floor Mounted Type LAND TRANSPORT
ISOLATED (IT) TNS
TERMINAL COVER PRESENTATION :
_______________
DIRECT CURRENT : TO EARTH ISOLATED CONNECTIONS FIXED FRONT TRANSPARENT DOOR
INCOMINGOUTGOING FUNCTIONAL DOOR WITH KEY _______________
C C
DIRECT
BUS BARS PLAIN DOOR PARTICULAR NOTES
TO TERMINAL PADS

MATERIAL : ALUM.
TO LINKS SELECTOR SWITCH/PUSH BUTTONS/LAMPS
COPPER APPARATUS DEFINED
ACCESS :
SYSTEM : PARTIC DIMENSIONS
REAR (CABLING) PUSH BUTTONS :
CONSTANT SECTION H V EXTENSION OF
FRONT (CABLING)
DECREASING H V ON OFF L.TEST RESET
LEFT SIDE/RIGHT SIDE SIMILAR TO
TIN PLATED H V SPECIFICATION
D ENTRY : D
WITH COLOUR CODED PVC SLEEVE LAMPS :
TOP (BY CABLES) DEVIATION
NEUTRAL : PE : BOTTOM (BY CABLES) RED GREEN YELLOW BLUE LOOSE MATERIAL
NOT DISTRIBUTED HORIZONTAL ACCESSORIES :
SCREWS _______________
SAME SECTION AS PHASES VERTICAL SELECTOR SWITCH :
HALF SECTION HALF SECTION GLAND PLATES
HOA ON/OFF AM. SS VM. SS DRAWINGS :
CABLE GLAND
SUPPLY OF AUXILIARIES SHROUDING :
E For Approval AS BUILT E
CABLE ENDS OTHERS :
VOLTAGE : ORIGIN :
FOR PRODUCTION
AUXILIARY WIRING ________________________
-ALL CIRCUITS 230 VAC / 24V DC CONTROL TRANFR.
-CONTROL 230 VAC / 24V DC FROM POWER SUPPLY SEC.VOLTAGE : 2.50 2.50 SQ.MM QUANTITY : 1 No.
-SIGNALLING 230 V AC,60HZ. FROM BUSBAR CURRENT : 2.50 2.50 SQ.MM INDICATING INSTRUMENT (METERS) REMARKS
POWER CKT.: RYB&N Y/G (GROUNDING)
INSTRUMENTS :
F CLIMATIC CONDITION CT: RYB&N F
SIZE 96 X 96 SIZE 72 X 72
ALARM: GRAY
TYPE OF CLIMATE : NORMAL
OTHERS :
TYPE OF ATMOSPHERE : ORDINARY TO SUIT DESERT
MARKING OF CIRCUITS
CONDITIONS
POWER : STAND R,Y,B,N
POLLUTION RISKS :
AUXILIARY : LOCAL END METER RELAY :
-MOUNTING INDOOR OUTDOOR
BOTH ENDS
G -AMBIENT TEMP. 50°C G
COMPOSED
-RELATIVE HUMIDITY 50% AT 50°C

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-02


PR PR 08-02-23
H TITLE: MDB-900-B917-N (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 45 2of
OF 8
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A
LEGENDS & SYMBOL A

S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION

X1
AIR CIRCUIT BREAKER
1 ACB 10 INDICATING LAMP
SURGE PROTECTION DEVICE
(ACB) 19 28
X2

B B
T2 T4 T6
A1
MOULDED CASE CIRCUIT BREAKER
2 (MCCB) 11 CONTACTOR / RELAY COIL 20 CONTROL FUSE 29
A2
T1 T3 T5

MANUAL

AUTO
OFF
HAND/OFF/AUTO
3 MCB 12 CURRENT TRANSFORMER 21
3 3
30
C SELECTOR SWITCH C
4 4

21 A
QM-OF

L3
L2

L1
MCCB AUXILIARY CONTACTS AMMETER

0
4 13 4 10
22 SPACE HEATER 31
24 22
1 3 5 11
WITH SELECTOR SWITCH

D D
C12 V

L3-L1
L2-L3
L1-L2

L1-N
L2-N
L3-N
VOLTMETER
5

0
MCCB SHUNT TRIP CONTACTS
MX 14 4 10

WITH SELECTOR SWITCH


23 THERMOSTAT 32
1 3 5 11
C11

L1 L2 L3

6 CONTACTOR 15 V POWER FACTOR METER


24 EARTH 33
E T1 T2 T3
E

A1 S1 S2 S1 S2 S1 S2
DIGITAL MULTIFUNCTION TERMINALS
7 T1 24H TIMER 16 L1 L2 L3
25 34
MFM METER
A2 V1 V2 V3 VN 0V - +

F F
CBCT

L 1

8 PANEL MOUNTED PHOTOCELL 17 26 35


S2 S1

EARTH LEAKAGE RELAY WITH


5 8
1

2
CBCT
N 2 6 9 7

1 8

XX
9 XX AUXILIARY CONTACTS 18 27 36
480V

230V

CONTROL TRANSFORMER
7 9
G 2 G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-02


PR PR 08-02-23
H TITLE: MDB-900-B917-N (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 46 3of
OF 8
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PL-1 DS-1 PL-1 DS-1


MDB-9 00-B917-N

100mm
(CELL AS SEM BLY BUILDING)
(400/230V,3PH.,4W,60Hz.)

A A

C06
POWER ON POWER ON POWER ON

R Y B Q1 Q2 Q1 Q2

AMMET ER V OL T M E T ER

A 00
00 V 00
00

300 300

00 00

Q3 Q4 Q3 Q4

Q5 Q6 Q5 Q6

B T7 T8 B
Q7 Q8 Q7 Q8

T9

Elect ric

Elect ric

Electric
Schneider
Sc hneider

Sc hneider
Q9 Q9
Q10 Q10

Elect ric

Electric
Schneider
Sc hneider
1800

DANG ER ‫ﺧﻄﺮ‬

CT CT CT

TH

FU1

FU3
FU2

FU4
FU4
C C

QM E7 E8 E9

N QM

250mm
D D
(DRAWING POCKET INSIDE DOOR )

Earth Stud
E ACH

1200 1200 1200 400


200

E E
FRONT VIEW INTERNAL VIEW INTERNAL VIEW SIDE VIEW
(WITH FRONT COVER)
NOTES:
1. BUSBAR : TIN PLATED COPPER 1075
2. ENCLOSURE:
- FRAME WORK COMPONENTS : 2mm
- DOOR, BACK & SIDE COVER : 1.5mm DANGER ‫ﺧﻄﺮ‬

12.
F - PLINTH : 3mm HAZAR D OF ELECTRICAL SHOCK OR BURN
F

275
GLAND PLATE (CUSTOMIZED)

5
TURN O FF POWER TO THIS EQUIPMENT
BEFORE WORKING INSIDE
3. PANEL WEIGHT : 435Kg (APPX.)
‫ﺧﻄـــــﺮ اﻟﺼـــــﺪﻣﺔ اﻟﮑﮫﺮﺑﺎﺋﯿـــــﺔ أو اﻻﺣـــــﺘﺮاق‬
4. PANEL MOUNTING : FLOOR MOUNTED TYPE ‫إﻳﻘـــﺎف اﻟﻄﺎﻗـــﺔ ﻟﮫـــﺬه اﻟﻤﻌــــﺪات‬
‫ﻗﺒــــﻞ ااﻟﻌﻤــــﻞ ﺑﺎﻟــــﺪاﺧﻞ‬

DANGER LABEL
C06

(WHITE LETTERS IN RED BACKGROUND)

TOP VIEW BOTTOM VIEW


PANEL BOARD FACTORY:
PROJECT : NEOM GREEN HYDROGEN PROJECT - U900 MDB-900-B917-N
PROJECT NO. : PM210011

G PANEL REF. : MDB-900-B917-N (CELL ASSEMBLY BUILDING) (CELL ASSEMBLY BUILDING) G


CURRENT RATING : 400A
SYSTEM VOLTAGE : 400/230V,3PH., 4W, 60Hz
DEGREE OF PROTECTION : IP 54 400/230V,3PH.,4W,60Hz.
PANEL WEIGHT : 435Kg
YEAR OF MANUFACTURE : 2023
MANUFACTURER REF. : NPB-2210009 PANEL TAG
NAME PLATE DETAILS (BLACK LETTERS IN WHITE BACKGROUND)

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-02


PR PR 08-02-23
H TITLE: MDB-900-B917-N (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 47 4of
OF 8
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

1X30X10mm Main Bus bar - 400A


R
Y
A B
A
N

1x30x10mm Busbar

L3
1ASS
AMMETER
L2 1x20x5mm Busbar 1x20x5mm Busbar 1x15x5mm Busbar 1x15x5mm Busbar
SELECTOR SWITCH
L1
0
B B

S2
1CT1
S1
400/5A 9
A
4
S2
1CT2
S1 2
400/5A 5
S2
1CT3
S1
400/5A 1
C C

C04

C04

C04

C04
PE

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

1 11 11 11 11

QM-SDE QM-SDE QM-SDE QM-SDE

14 12 14 12 14 12 14 12
3
V
1FU1-1FU3 4

10 3 4 5 6 7 8 9 10
X1 X1 X1 6 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3
TRIP STATUS TRIP STATUS TRIP STATUS TRIP STATUS
D X2 X2 X2 D
RED YELLOW BLUE
11 Q1 Q2 Q3 Q4
1HP1 1HP2 1HP3
L3-L1 160AT/160AF 4P 160AT/160AF 4P 63AT/100AF 4P 80AT/100AF 4P
L2-L3
MCCB (TMD) MCCB (TMD) MCCB (TMD) MCCB (TMD)
C04

QM 1VSS L1-L2

25kA 25kA 25kA 25kA


VOLTMETER 0
N L1 L2 L3 L1-N
SELECTOR SWITCH
400AT/400AF 4P L2-N
L3-N
MCCB (MIC. 2.3)
36kA 11

QM-SDE

Set @ 300A 14 12
E E

N L1 L2 L3
1 2
TRIP STATUS

F F

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

Incoming Supply DB-917-N3 SPARE DB-917-N1 DB-917-N2

G
400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W G
Fed From : SWGR-900-412A (900-B906) Cable Size : 4CX185mm2 + 1CX70mm2 (G) Cable Size : N/A Cable Size : 4CX50mm2 + 1CX35mm2 (G) Cable Size : 4CX50mm2 + 1CX35mm2 (G)
Cable Size : 2R-3C+Nx240mm2 + 120mm2

E - 1bx30x5mm

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-02


PR PR 08-02-23
H TITLE: MDB-900-B917-N (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 48 5of
OF 8
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

1X30X10mm Main Bus bar - 400A


R
Y
A B
A
N

1x15x5mm Busbar 1x15x5mm Busbar 1x15x5mm Busbar 1x15x5mm Busbar

1x15x5mm Busbar 1x15x5mm Busbar

B B

C C
C04

C04

C04

C04

C04
N L1 L2 L3 N L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3

11 11 11 11 11

QM-SDE QM-SDE QM-SDE QM-SDE QM-SDE

14 12 14 12 14 12 14 12 14 12

11 12 13 14 15 16 17 18 19 20
N L1 L2 L3 N L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3
TRIP STATUS TRIP STATUS TRIP STATUS TRIP STATUS TRIP STATUS
D D
Q5 Q6 Q7 Q8 Q9 Q4
63AT/100AF 4P 40AT/100AF 4P 40AT/100AF TP 40AT/100AF TP 40AT/100AF TP
MCCB (TMD) MCCB (TMD) MCCB (TMD) MCCB (TMD) MCCB (TMD)
25kA 25kA 25kA 25kA 25kA

E7 E8 E9
E E

T7 T8 T9

F F

N L1 L2 L3 N L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3

SPARE SPARE EWH-01 (INTERMITENT DUTY) EWH-02 (INTERMITENT DUTY) EWH-03 (INTERMITENT DUTY) SPACE (100A)

G
400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W 400V/230V, 60Hz, AC 3ɸ 4W G
Cable Size : N/A Cable Size : N/A Cable Size : 1-3Cx16 mm2 Cable Size : 1-3Cx16 mm2 Cable Size : 1-3Cx16 mm2

E - 1bx30x5mm

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-02


PR PR 08-02-23
H TITLE: MDB-900-B917-N (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 49 6of
OF 8
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

1X30X10mm Main Bus bar - 400A


R
Y
A B
A
N

1FU4(4A)

B B
1
11
TH1 DS-1
THERMOSTAT 12
2

X1 1FU5
L
PL-1
C ACH1
X2
C

T7

CBCT 8

E7
7 9
D S2 S1 D

E7

(FROM MAIN BUSBAR)


AFTER INCOMER
5 8
1

230V AC
2
21
6 9 7 Q7-OF2
E E
24 22

C2
F F
MX
C1
N

TYPICAL CONTROL CIRCUIT FOR ELR WITH CBCT(Q7-Q9)

G G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-02


PR PR 08-02-23
H TITLE: MDB-900-B917-N (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 50 7of
OF 8
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

BILL OF QUANTITY
A ITEM TAG CAT. REF. No. DESCRIPTION RATING QTY MANUFACTURER A

1 QM LV432677 / C40F42D400 + 29450 MCCB 4P 400AT/400AF 36kA with Micrologic 2.3 Trip Unit (Set @ 300A) 400A 1 Schneider Electric
2 Q1,Q2 LV430320 / C16B6TM160C + 29450 Circuit breaker, ComPact NSX160B, 25kA/415VAC, TMD trip unit 160A, 4 poles 3d 160A 2 Schneider Electric
3 Q3,Q5 LV429562 / C10B6TM063C + 29450 Circuit breaker, ComPact NSX100B, 25kA/415VAC, TMD trip unit 63A, 4 poles 3d 63A 2 Schneider Electric
4 Q4 LV429561 / C10B6TM080C + 29450 Circuit breaker, ComPact NSX100B, 25kA/415VAC, TMD trip unit 80A, 4 poles 3d 80A 1 Schneider Electric
B 5 Q6 LV429564 / C10B6TM040C + 29450 Circuit breaker, ComPact NSX100B, 25kA/415VAC, TMD trip unit 40A, 4 poles 3d 40A 1 Schneider Electric B

6 Q7,Q8,Q9 LV429554 / C10B3TM040C + 29450 Circuit breaker, ComPact NSX100B, 25kA/415VAC, TMD trip unit 40A, 3 poles 3d 40A 3 Schneider Electric
7 1HP1-1HP3 XB7EV04MP/05MP/06MP Pilot Light - Integral LED - 230V AC (Red/Yellow/Blue) 230V AC 3 Schneider Electric
8 1FU1-1FU5 A9N15636 SP Control Fuse Carrier 230V AC 5 Schneider Electric
9 TH1 NSYCCOTHC ClimaSys CC - simple thermostat 250V - range of temperature 0…60°C - NC - 230V AC 1 Schneider Electric
C 10 ACH1 NSYCR55WU2 ClimaSys PTC heating resistance 55W, 110-250V 230V AC 1 Schneider Electric C

11 E7-E9 56173 Residual current protection relay, VigiPacT RH99M, 30mA-30A, 220/240VAC 50/60Hz 30mA-30A 3 Schneider Electric
12 T7-T9 50438 Closed toroid A type, VigiPacT, Vigilohm, PA50, inner diameter 50mm, rated current 85A - 3 Schneider Electric
13 Encl NSYSM1812402DP Spacial SM compact enclosure with mounting plate - 1800x1200x400 mm IP55 1 Schneider Electric
14 1CT1-1CT3 - Current Transformer 400/5A 4 Elmex
D 15 A - Analog Ammeter 0-600A, 96mmx96mm 0-400A 1 Elmex D

16 V - Analog Voltmeter 0-500V, 96mmx96mm 0-500V 1 Elmex


17 ASS - Ammeter Selector Switch - 1 Selec
18 VSS - Voltmeter Selector Switch - 1 Selec
19 DS1 - Door Limit Switch - 1 Andeli
E 20 PL1 - Panel Mounted LIght - LED 220V AC, 60Hz - 1 Reputed E

21
22
23
24
F 25 F

26
27
28
29
G 30 G

31
32

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-02


PR PR 08-02-23
H TITLE: MDB-900-B917-N (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 51 8of
OF 8
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

C C

D D

E E

PANEL BOARD FACTORY


F F

PROJECT: PANEL TAG

NEOM GREEN HYDROGEN DB-B917-E1


G PROJECT - U900 (CELL ASSEMBLY BUILDING) G

QTY: 01No.

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-03


PR PR 08-02-23
H TITLE: DB-B917-E1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 52 1of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

POWER SUPPLY APPARATUS DEGREE OF PROTECTION CIRCUIT MARKING


A A
SOURCE : MDB-900-B917-E MOUNTING : INCOMINGOUTGOING PROTECTION : LABELS :
FIXED IP 31 IP 41 IP 54 IP 66 ENGRAVED GRAVOPLY
400/230V, 3PH, 4W, 60Hz
DRAW-OUT ALUMINUM PVC
NO PARALLEL OPERATION PLUG-IN FORM : 1 3B TYPE : 2 4 6 MECHANICAL SCREWED (EXT.)
PARALLEL OPERATION OF OPERATION : RIVETED SELF STICK
2 4B 3 5 7
BEHIND DOOR GLUED (INT.)
ALL SOURCES PARALLEL ENCLOSURES
THROUGH PLATE COLOR : BLACK LETTERS IN WHITE BACKGROUND
B B
NEUTRAL SYSTEM : INTERLOCK Schneider Electric LANGUAGE : ENGLISH
PADLOCKING
Color : RAL 7035 PACKING
DIRECT TO EARTH (TT) EARTHED(TN) SHUTTER
THROUGH DOOR Wall Mounted Type LAND TRANSPORT
ISOLATED (IT) TNS
TERMINAL COVER PRESENTATION :
_______________
DIRECT CURRENT : TO EARTH ISOLATED CONNECTIONS FIXED FRONT TRANSPARENT DOOR
INCOMINGOUTGOING FUNCTIONAL DOOR WITH KEY _______________
C C
DIRECT
BUS BARS PLAIN DOOR PARTICULAR NOTES
TO TERMINAL PADS

MATERIAL : ALUM.
TO LINKS SELECTOR SWITCH/PUSH BUTTONS/LAMPS
COPPER APPARATUS DEFINED
ACCESS :
SYSTEM : PARTIC DIMENSIONS
REAR (CABLING) PUSH BUTTONS :
CONSTANT SECTION H V EXTENSION OF
FRONT (CABLING)
DECREASING H V ON OFF L.TEST RESET
LEFT SIDE/RIGHT SIDE SIMILAR TO
TIN PLATED H V SPECIFICATION
D ENTRY : D
WITH COLOUR CODED PVC SLEEVE LAMPS :
TOP (BY CABLES) DEVIATION
NEUTRAL : PE : BOTTOM (BY CABLES) RED GREEN YELLOW BLUE LOOSE MATERIAL
NOT DISTRIBUTED HORIZONTAL ACCESSORIES :
SCREWS _______________
SAME SECTION AS PHASES VERTICAL SELECTOR SWITCH :
HALF SECTION HALF SECTION GLAND PLATES
HOA ON/OFF AM. SS VM. SS DRAWINGS :
CABLE GLAND
SUPPLY OF AUXILIARIES SHROUDING :
E For Approval AS BUILT E
CABLE ENDS OTHERS :
VOLTAGE : ORIGIN :
FOR PRODUCTION
AUXILIARY WIRING ________________________
-ALL CIRCUITS 230 VAC / 24V DC CONTROL TRANFR.
-CONTROL 230 VAC / 24V DC FROM POWER SUPPLY SEC.VOLTAGE : 2.50 2.50 SQ.MM QUANTITY : 1 No.
-SIGNALLING 230 V AC,60HZ. FROM BUSBAR CURRENT : 2.50 2.50 SQ.MM INDICATING INSTRUMENT (METERS) REMARKS
POWER CKT.: RYB&N Y/G (GROUNDING)
INSTRUMENTS :
F CLIMATIC CONDITION CT: RYB&N F
SIZE 96 X 96 SIZE 72 X 72
ALARM: GRAY
TYPE OF CLIMATE : NORMAL
OTHERS :
TYPE OF ATMOSPHERE : ORDINARY TO SUIT DESERT
MARKING OF CIRCUITS
CONDITIONS
POWER : STAND R,Y,B,N
POLLUTION RISKS :
AUXILIARY : LOCAL END METER RELAY :
-MOUNTING INDOOR OUTDOOR
BOTH ENDS
G -AMBIENT TEMP. 50°C G
COMPOSED
-RELATIVE HUMIDITY 50% AT 50°C

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-03


PR PR 08-02-23
H TITLE: DB-B917-E1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 53 2of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A
LEGENDS & SYMBOL A

S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION

X1
AIR CIRCUIT BREAKER
1 ACB 10 INDICATING LAMP
SURGE PROTECTION DEVICE
(ACB) 19 28
X2

B B
T2 T4 T6
A1
MOULDED CASE CIRCUIT BREAKER
2 (MCCB) 11 CONTACTOR / RELAY COIL 20 CONTROL FUSE 29
A2
T1 T3 T5

MANUAL

AUTO
OFF
HAND/OFF/AUTO
3 MCB 12 CURRENT TRANSFORMER 21
3 3
30
C SELECTOR SWITCH C
4 4

21 A
QM-OF

L3
L2

L1
MCCB AUXILIARY CONTACTS AMMETER

0
4 13 4 10
22 SPACE HEATER 31
24 22
1 3 5 11
WITH SELECTOR SWITCH

D D
C12 V

L3-L1
L2-L3
L1-L2

L1-N
L2-N
L3-N
VOLTMETER
5

0
MCCB SHUNT TRIP CONTACTS
MX 14 4 10

WITH SELECTOR SWITCH


23 THERMOSTAT 32
1 3 5 11
C11

L1 L2 L3

6 CONTACTOR 15 V POWER FACTOR METER


24 EARTH 33
E T1 T2 T3
E

A1 S1 S2 S1 S2 S1 S2
DIGITAL MULTIFUNCTION TERMINALS
7 T1 24H TIMER 16 L1 L2 L3
25 34
MFM METER
A2 V1 V2 V3 VN 0V - +

F F
CBCT

L 1

8 PANEL MOUNTED PHOTOCELL 17 26 35


S2 S1

EARTH LEAKAGE RELAY WITH


5 8
1

2
CBCT
N 2 6 9 7

1 8

XX
9 XX AUXILIARY CONTACTS 18 27 36
480V

230V

CONTROL TRANSFORMER
7 9
G 2 G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-03


PR PR 08-02-23
H TITLE: DB-B917-E1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 54 3of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

DB-B917-N1
(40 0/230 V, 3PH , 4W, 60 Hz)

Busbar Assembly

B B
DANGER ‫ﺧﻄﺮ‬
600

HAZAR D OF EL ECTR IC AL S HOCK OR B URN


TURN O FF POWER TO T HIS EQUI PM ENT
BEF OR E WOR KING I NSIDE
‫ﺧﻄـــﺮ اﻟ ﺼــــﺪ ﻣﺔ اﻟﮑﮫﺮﺑﺎﺋﯿــــﺔ أو ا ﻻﺣــــﺘﺮا ق‬
‫إﻳ ﻘــﺎ ف اﻟﻄﺎﻗــﺔ ﻟﮫــﺬه اﻟﻤﻌـــﺪات‬
‫ﻗﺒــ ﻞ ااﻟﻌﻤـــ ﻞ ﺑﺎﻟـــﺪاﺧ ﻞ‬

Ele ct ric
QM E lec tric
QM
S ch ne id er
Sch ne id e r

E N

C C

500 500 500 200


D FRONT VIEW INTERNAL VIEW INTERNAL VIEW SIDE VIEW D

(WITH FRONT COVER)

E E

GLAND PLATE (CUSTOMIZED)

TOP VIEW BOTTOM VIEW


F F

PANEL BOARD FACTORY: NOTES:


PROJECT : NEOM GREEN HYDROGEN PROJECT - U900
1. BUSBAR : TIN PLATED COPPER
DANGER ‫ﺧﻄﺮ‬ DB-B917-E1
PROJECT NO. : PM210011
HAZAR D OF ELECTRICAL SHOCK OR BURN
PANEL REF. : DB-B917-E1 (CELL ASSEMBLY BUILDING) 2. ENCLOSURE: THICKNESS 1.2mm TURN O FF POWER TO THIS EQUIPMENT (CELL ASSEMBLY BUILDING)
CURRENT RATING : 40A BEFORE WORKING INSIDE
G SYSTEM VOLTAGE : 400/230V,3PH., 4W, 60Hz 3. PANEL WEIGHT : 20Kg (APPX.) G
DEGREE OF PROTECTION : IP 66
‫ﺧﻄـــــﺮ اﻟﺼـــــﺪﻣﺔ اﻟﮑﮫﺮﺑﺎﺋﯿـــــﺔ أو اﻻﺣـــــﺘﺮاق‬
‫إﻳﻘـــﺎف اﻟﻄﺎﻗـــﺔ ﻟﮫـــﺬه اﻟﻤﻌــــﺪات‬ 400/230V,3PH.,4W,60Hz.
PANEL WEIGHT : 25Kg 4. PANEL MOUNTING : SURFACE MOUNTED TYPE ‫ﻗﺒــــﻞ ااﻟﻌﻤــــﻞ ﺑﺎﻟــــﺪاﺧﻞ‬
YEAR OF MANUFACTURE : 2023
MANUFACTURER REF. : NPB-2210009 DANGER LABEL PANEL TAG
(WHITE LETTERS IN RED BACKGROUND)
(BLACK LETTERS IN WHITE BACKGROUND)
NAME PLATE DETAILS

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-03


PR PR 08-02-23
H TITLE: DB-B917-E1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 55 3of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A
LOAD DESCRIPTION BREAKER BREAKER LOAD DESCRIPTION
1 LTG. PRE-ASSEMBLY AREA & CELL WORKSHOP-1 16A SP MCB,10KA 16A SP MCB,10KA LTG. OFF-2, CORRIDOR, AIR LOCK, MALE PRAYER, LUNCH RM, FEMALE PRAYER & TOILET, CHANGE RM 2

EARTH BAR
NEUTRAL BAR

3 LTG. CELL WORKSHOP-2 & SWITCHGEAR ROOM 16A SP MCB,10KA 16A SP MCB,10KA LTG. OFF-1&3 TO 7, TEL. RM & MALE TOILET, AIRLOCK 4
5 LIGHTING STORAGE AREA 16A SP MCB,10KA 16A SP MCB,10KA LTG. - BUILING PRIMETER THROUGH LCP-B917-E1 6
7 SPARE 16A SP MCB,10KA 16A SP MCB,10KA SPARE 8
9 LTG. BUILDING PROMETER THROUGH LCP-B917-E1 16A SP MCB,10KA 16A SP MCB,10KA SPARE 10
11 LTG. BUILDING PROMETER THROUGH LCP-B917-E1 16A SP MCB,10KA 16A SP MCB,10KA LTG. - BUILING PRIMETER THROUGH LCP-B917-E1 12
B B

C C

D D

QM
40AT/100AF TP
MCCB, 25kA
(TMD)
E E

F F

N R Y B
G Incoming Supply G

400V/230V, 60Hz, AC 3ɸ 4W
Fed From : MDB-900-B917-E
Cable Size : 4CX25mm2 + 1CX16mm2 (G)

ISSUE REVISION DATE PROJECT: DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009
NEOM GREEN HYDROGEN PROJECT - U900
01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-03
PR PR 08-02-23
H TITLE: DB-B917-E1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 56 5of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A BILL OF QUANTITY A

ITEM TAG CAT. REF. No. DESCRIPTION RATING QTY MANUFACTURER


1 QM LV429554 / C10B3TM040C Circuit breaker, ComPact NSX100B, 25kA/415VAC, TMD trip unit 40A, 3 poles 3d 40A 1 Schneider Electric
2 Q1-Q12 A9F44116 Acti9 iC60N 1P 16A C Miniature Circuit breaker 16A 12 Schneider Electric
3 Encl NSYCRN65200 + NSYMM65 Spacial CRN plain door w/o mount.plate. H600xW500xD200 IP66 IK10 RAL7035 IP66 1 Schneider Electric
B
4 - - Busbar Assembly - 12 Way SPN - 1 Reputed B

5
6
7
8
C C
9
10

D D

E E

F F

G G

ISSUE REVISION DATE PROJECT: DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009
NEOM GREEN HYDROGEN PROJECT - U900
01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-03
PR PR 08-02-23
H TITLE: DB-B917-E1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 57 6of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

C C

D D

E E

PANEL BOARD FACTORY


F F

PROJECT: PANEL TAG

NEOM GREEN HYDROGEN DB-B917-N1


G PROJECT - U900 (CELL ASSEMBLY BUILDING) G

QTY: 01No.

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-04


PR PR 08-02-23
H TITLE: DB-B917-N1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 58 1of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

POWER SUPPLY APPARATUS DEGREE OF PROTECTION CIRCUIT MARKING


A A
SOURCE : MDB-900-B917-N MOUNTING : INCOMINGOUTGOING PROTECTION : LABELS :
FIXED IP 31 IP 41 IP 54 IP 66 ENGRAVED GRAVOPLY
400/230V, 3PH, 4W, 60Hz
DRAW-OUT ALUMINUM PVC
NO PARALLEL OPERATION PLUG-IN FORM : 1 3B TYPE : 2 4 6 MECHANICAL SCREWED (EXT.)
PARALLEL OPERATION OF OPERATION : RIVETED SELF STICK
2 4B 3 5 7
BEHIND DOOR GLUED (INT.)
ALL SOURCES PARALLEL ENCLOSURES
THROUGH PLATE COLOR : BLACK LETTERS IN WHITE BACKGROUND
B B
NEUTRAL SYSTEM : INTERLOCK Schneider Electric LANGUAGE : ENGLISH
PADLOCKING
Color : RAL 7035 PACKING
DIRECT TO EARTH (TT) EARTHED(TN) SHUTTER
THROUGH DOOR Wall Mounted Type LAND TRANSPORT
ISOLATED (IT) TNS
TERMINAL COVER PRESENTATION :
_______________
DIRECT CURRENT : TO EARTH ISOLATED CONNECTIONS FIXED FRONT TRANSPARENT DOOR
INCOMINGOUTGOING FUNCTIONAL DOOR WITH KEY _______________
C C
DIRECT
BUS BARS PLAIN DOOR PARTICULAR NOTES
TO TERMINAL PADS

MATERIAL : ALUM.
TO LINKS SELECTOR SWITCH/PUSH BUTTONS/LAMPS
COPPER APPARATUS DEFINED
ACCESS :
SYSTEM : PARTIC DIMENSIONS
REAR (CABLING) PUSH BUTTONS :
CONSTANT SECTION H V EXTENSION OF
FRONT (CABLING)
DECREASING H V ON OFF L.TEST RESET
LEFT SIDE/RIGHT SIDE SIMILAR TO
TIN PLATED H V SPECIFICATION
D ENTRY : D
WITH COLOUR CODED PVC SLEEVE LAMPS :
TOP (BY CABLES) DEVIATION
NEUTRAL : PE : BOTTOM (BY CABLES) RED GREEN YELLOW BLUE LOOSE MATERIAL
NOT DISTRIBUTED HORIZONTAL ACCESSORIES :
SCREWS _______________
SAME SECTION AS PHASES VERTICAL SELECTOR SWITCH :
HALF SECTION HALF SECTION GLAND PLATES
HOA ON/OFF AM. SS VM. SS DRAWINGS :
CABLE GLAND
SUPPLY OF AUXILIARIES SHROUDING :
E For Approval AS BUILT E
CABLE ENDS OTHERS :
VOLTAGE : ORIGIN :
FOR PRODUCTION
AUXILIARY WIRING ________________________
-ALL CIRCUITS 230 VAC / 24V DC CONTROL TRANFR.
-CONTROL 230 VAC / 24V DC FROM POWER SUPPLY SEC.VOLTAGE : 2.50 2.50 SQ.MM QUANTITY : 1 No.
-SIGNALLING 230 V AC,60HZ. FROM BUSBAR CURRENT : 2.50 2.50 SQ.MM INDICATING INSTRUMENT (METERS) REMARKS
POWER CKT.: RYB&N Y/G (GROUNDING)
INSTRUMENTS :
F CLIMATIC CONDITION CT: RYB&N F
SIZE 96 X 96 SIZE 72 X 72
ALARM: GRAY
TYPE OF CLIMATE : NORMAL
OTHERS :
TYPE OF ATMOSPHERE : ORDINARY TO SUIT DESERT
MARKING OF CIRCUITS
CONDITIONS
POWER : STAND R,Y,B,N
POLLUTION RISKS :
AUXILIARY : LOCAL END METER RELAY :
-MOUNTING INDOOR OUTDOOR
BOTH ENDS
G -AMBIENT TEMP. 50°C G
COMPOSED
-RELATIVE HUMIDITY 50% AT 50°C

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-04


PR PR 08-02-23
H TITLE: DB-B917-N1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 59 2of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A
LEGENDS & SYMBOL A

S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION

X1
AIR CIRCUIT BREAKER
1 ACB 10 INDICATING LAMP
SURGE PROTECTION DEVICE
(ACB) 19 28
X2

B B
T2 T4 T6
A1
MOULDED CASE CIRCUIT BREAKER
2 (MCCB) 11 CONTACTOR / RELAY COIL 20 CONTROL FUSE 29
A2
T1 T3 T5

MANUAL

AUTO
OFF
HAND/OFF/AUTO
3 MCB 12 CURRENT TRANSFORMER 21
3 3
30
C SELECTOR SWITCH C
4 4

21 A
QM-OF

L3
L2

L1
MCCB AUXILIARY CONTACTS AMMETER

0
4 13 4 10
22 SPACE HEATER 31
24 22
1 3 5 11
WITH SELECTOR SWITCH

D D
C12 V

L3-L1
L2-L3
L1-L2

L1-N
L2-N
L3-N
VOLTMETER
5

0
MCCB SHUNT TRIP CONTACTS
MX 14 4 10

WITH SELECTOR SWITCH


23 THERMOSTAT 32
1 3 5 11
C11

L1 L2 L3

6 CONTACTOR 15 V POWER FACTOR METER


24 EARTH 33
E T1 T2 T3
E

A1 S1 S2 S1 S2 S1 S2
DIGITAL MULTIFUNCTION TERMINALS
7 T1 24H TIMER 16 L1 L2 L3
25 34
MFM METER
A2 V1 V2 V3 VN 0V - +

F F
CBCT

L 1

8 PANEL MOUNTED PHOTOCELL 17 26 35


S2 S1

EARTH LEAKAGE RELAY WITH


5 8
1

2
CBCT
N 2 6 9 7

1 8

XX
9 XX AUXILIARY CONTACTS 18 27 36
480V

230V

CONTROL TRANSFORMER
7 9
G 2 G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-04


PR PR 08-02-23
H TITLE: DB-B917-N1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 60 3of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A
DB-B917-N1
(40 0/230 V, 3PH , 4W, 60 Hz)

Busbar Assembly

B E N B

DANGER ‫ﺧﻄﺮ‬
800

HAZAR D OF EL ECTR IC AL S HOCK OR B URN


TURN O FF POWER TO T HIS EQUI PM ENT
BEF OR E WOR KING I NSIDE
‫ﺧﻄـــﺮ اﻟ ﺼــــﺪ ﻣﺔ اﻟﮑﮫﺮﺑﺎﺋﯿــــﺔ أو ا ﻻﺣــــﺘﺮا ق‬
‫إﻳ ﻘــﺎ ف اﻟﻄﺎﻗــﺔ ﻟﮫــﺬه اﻟﻤﻌـــﺪات‬
‫ﻗﺒــ ﻞ ااﻟﻌﻤـــ ﻞ ﺑﺎﻟـــﺪاﺧ ﻞ‬

C C
Ele ct ric
QM E lec tric
S ch ne id er
QM
Sch ne id e r

D D

600 600 600 200


FRONT VIEW INTERNAL VIEW INTERNAL VIEW SIDE VIEW
(WITH FRONT COVER)
E E

GLAND PLATE (CUSTOMIZED)

F BOTTOM VIEW TOP VIEW F

PANEL BOARD FACTORY: NOTES:


PROJECT : NEOM GREEN HYDROGEN PROJECT - U900
1. BUSBAR : TIN PLATED COPPER
DANGER ‫ﺧﻄﺮ‬ DB-B917-N1
PROJECT NO. : PM210011
HAZAR D OF ELECTRICAL SHOCK OR BURN
PANEL REF. : DB-B917-N1 (CELL ASSEMBLY BUILDING) 2. ENCLOSURE: THICKNESS 1.2mm TURN O FF POWER TO THIS EQUIPMENT (CELL ASSEMBLY BUILDING)
CURRENT RATING : 63A BEFORE WORKING INSIDE
SYSTEM VOLTAGE : 400/230V,3PH., 4W, 60Hz 3. PANEL WEIGHT : 65Kg (APPX.)
G DEGREE OF PROTECTION : IP 66
‫ﺧﻄـــــﺮ اﻟﺼـــــﺪﻣﺔ اﻟﮑﮫﺮﺑﺎﺋﯿـــــﺔ أو اﻻﺣـــــﺘﺮاق‬
‫إﻳﻘـــﺎف اﻟﻄﺎﻗـــﺔ ﻟﮫـــﺬه اﻟﻤﻌــــﺪات‬ 400/230V,3PH.,4W,60Hz. G
PANEL WEIGHT : 65Kg 4. PANEL MOUNTING : WALL MOUNTED TYPE ‫ﻗﺒــــﻞ ااﻟﻌﻤــــﻞ ﺑﺎﻟــــﺪاﺧﻞ‬
YEAR OF MANUFACTURE : 2023
MANUFACTURER REF. : NPB-2210009 DANGER LABEL PANEL TAG
(WHITE LETTERS IN RED BACKGROUND)
(BLACK LETTERS IN WHITE BACKGROUND)
NAME PLATE DETAILS

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-04


PR PR 08-02-23
H TITLE: DB-B917-N1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 61 3of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

LOAD DESCRIPTION BREAKER BREAKER LOAD DESCRIPTION


1 LTG. PRE-ASSEMBLY AREA 16A SP MCB,10KA 16A SP MCB,10KA LTG. STORAGE AREA 2

EARTH BAR
A A

NEUTRAL BAR
3 LTG. CELL WORKSHOP-1 16A SP MCB,10KA 16A SP MCB,10KA LTG. OFFICES-1&3 TO 7 AND TELECOM ROOM 4
5 LTG. CELL WORKSHOP-2, UTILITY & SWITCHGEAR ROOM 20A SP MCB,10KA 16A SP MCB,10KA LTG. OFFICES-2, LUNCH ROOM, FEMALE PRAYER & TOILET, CHANGE ROOM 6
7 LTG. MALE PRAYER & TOILET, CORRIDOR 16A SP MCB,10KA 8
9 LTG. MALE PRAYER & TOILET, CORRIDOR 16A SP MCB,10KA 40A TP MCB,10KA EDH-01 (INTERMITTENT, 15.5KW) 10
11 SPARE 16A SP MCB,10KA 12
13 14
15 EDH-04 (INTERMITTENT, 7KW) 32A TP MCB,10KA 32A TP MCB,10KA EDH-02 (INTERMITTENT, 9.6KW) 16
B 17 18 B
19 40A SP MCB,10KA EDH-03 (INTERMITTENT, 5.5KW) 20
21 SPARE 40A TP MCB,10KA 20A SP MCB,10KA SPARE 22
23 16A SP MCB,10KA SPARE 24
25 ROLL UP DOOR ELECTRICALLY OPERATED, D03 IN PRE ASEEMBLY AREA (INTERMITTENT) 16A SP MCB,10KA 16A SP MCB,10KA ROLL UP DOOR ELECTRICALLY OPERATED, D10 IN PRE ASEEMBLY STORAGE AREA (INTERMITTENT) 26
27 ROLL UP DOOR ELECTRICALLY OPERATED, D05 IN CELL WORKSHOP-1 (INTERMITTENT) 16A SP MCB,10KA 16A SP MCB,10KA ROLL UP DOOR ELECTRICALLY OPERATED, D10 IN PRE ASEEMBLY STORAGE AREA (INTERMITTENT) 28
29 ROLL UP DOOR ELECTRICALLY OPERATED, D05 IN CELL WORKSHOP-1 (INTERMITTENT) 16A SP MCB,10KA 16A SP MCB,10KA ROLL UP DOOR ELECTRICALLY OPERATED, D10 IN PRE ASEEMBLY STORAGE AREA (INTERMITTENT) 30
31 ROLL UP DOOR ELECTRICALLY OPERATED, D06 IN CELL WORKSHOP-2 (INTERMITTENT) 16A SP MCB,10KA ROLL UP DOOR ELECTRICALLY OPERATED, D10 IN PRE ASEEMBLY STORAGE AREA (INTERMITTENT)
C 16A SP MCB,10KA 32 C
33 ROLL UP DOOR ELECTRICALLY OPERATED, D06 IN CELL WORKSHOP-2 (INTERMITTENT) 16A SP MCB,10KA 16A SP MCB,10KA ROLL UP DOOR ELECTRICALLY OPERATED, D14 IN UTILITY ROOM (INTERMITTENT) 34
35 SPARE 16A SP MCB,10KA 16A SP MCB,10KA SPARE 36

D D

E E

QM
63AT/100AF TP
MCCB, 25kA
(TMD)

F F

N R Y B
G Incoming Supply G

380/220V,3PH.,4W,60Hz.
Fed From : MDB-900-B917-N
Cable Size : 4CX50mm2 + 1CX35mm2 (G)

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-04


PR PR 08-02-23
H TITLE: DB-B917-N1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 62 5of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

BILL OF QUANTITY
A A
ITEM TAG CAT. REF. No. DESCRIPTION RATING QTY MANUFACTURER
1 QM LV429552 / C10B3TM063C Circuit breaker, ComPact NSX100B, 25kA/415VAC, TMD trip unit 63A, 3 poles 3d 63A 1 Schneider Electric
2 Q1-Q21 A9F44116 Acti9 iC60N 1P 16A C Miniature Circuit breaker 16A 21 Schneider Electric
3 Q22,Q23 A9F44120 Acti9 iC60N 1P 20A C Miniature Circuit breaker 20A 2 Schneider Electric
4 Q24 A9F44140 Acti9 iC60N 1P 40A C Miniature Circuit breaker 40A 1 Schneider Electric
B B
5 Q25,Q26 A9F44332 Acti9 iC60N 3P 32A C Miniature Circuit breaker 32A 2 Schneider Electric
6 Q27,Q28 A9F44340 Acti9 iC60N 3P 40A C Miniature Circuit breaker 40A 2 Schneider Electric
7 Encl NSYCRN86200P Spacial CRN plain door with mount.plate. H800xW600xD200 IP66 IK10 RAL7035 IP66 1 Schneider Electric
8 - - Busbar Assembly - 36 Way SPN - 1 Reputed
9
C C
10

D D

E E

F F

G G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-04


PR PR 08-02-23
H TITLE: DB-B917-N1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 63 6of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

C C

D D

E E

PANEL BOARD FACTORY


F F

PROJECT: PANEL TAG

NEOM GREEN HYDROGEN LCP-B917-E1


G PROJECT - U900 (CELL ASSEMBLY BUILDING) G

QTY: 01No.

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-05


PR PR 08-02-23
H TITLE: LCP-B917-E1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 64 1of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

POWER SUPPLY APPARATUS DEGREE OF PROTECTION CIRCUIT MARKING


A A
SOURCE : DB-B917-E1 MOUNTING : INCOMINGOUTGOING PROTECTION : LABELS :
FIXED IP 31 IP 41 IP 54 IP 65 ENGRAVED GRAVOPLY
400/230V, 3PH, 4W, 60Hz
DRAW-OUT ALUMINUM PVC
NO PARALLEL OPERATION PLUG-IN FORM : 1 3B TYPE : 2 4 6 MECHANICAL SCREWED (EXT.)
PARALLEL OPERATION OF OPERATION : RIVETED SELF STICK
2 4B 3 5 7
BEHIND DOOR GLUED (INT.)
ALL SOURCES PARALLEL ENCLOSURES
THROUGH PLATE COLOR : BLACK LETTERS IN WHITE BACKGROUND
B B
NEUTRAL SYSTEM : INTERLOCK Schneider Electric LANGUAGE : ENGLISH
PADLOCKING
Color : RAL 7035 PACKING
DIRECT TO EARTH (TT) EARTHED(TN) SHUTTER
THROUGH DOOR Wall Mounted Type LAND TRANSPORT
ISOLATED (IT) TNS
TERMINAL COVER PRESENTATION :
_______________
DIRECT CURRENT : TO EARTH ISOLATED CONNECTIONS FIXED FRONT TRANSPARENT DOOR
INCOMINGOUTGOING FUNCTIONAL DOOR WITH KEY _______________
C C
DIRECT
BUS BARS PLAIN DOOR PARTICULAR NOTES
TO TERMINAL PADS

MATERIAL : ALUM.
TO LINKS SELECTOR SWITCH/PUSH BUTTONS/LAMPS
COPPER APPARATUS DEFINED
ACCESS :
SYSTEM : PARTIC DIMENSIONS
REAR (CABLING) PUSH BUTTONS :
CONSTANT SECTION H V EXTENSION OF
FRONT (CABLING)
DECREASING H V ON OFF L.TEST RESET
LEFT SIDE/RIGHT SIDE SIMILAR TO
TIN PLATED H V SPECIFICATION
D ENTRY : D
WITH COLOUR CODED PVC SLEEVE LAMPS :
TOP (BY CABLES) DEVIATION
NEUTRAL : PE : BOTTOM (BY CABLES) RED GREEN YELLOW BLUE LOOSE MATERIAL
NOT DISTRIBUTED HORIZONTAL ACCESSORIES :
SCREWS _______________
SAME SECTION AS PHASES VERTICAL SELECTOR SWITCH :
HALF SECTION HALF SECTION GLAND PLATES
HOA ON/OFF AM. SS VM. SS DRAWINGS :
CABLE GLAND
SUPPLY OF AUXILIARIES SHROUDING :
E For Approval AS BUILT E
CABLE ENDS OTHERS :
VOLTAGE : ORIGIN :
FOR PRODUCTION
AUXILIARY WIRING ________________________
-ALL CIRCUITS 230 VAC / 24V DC CONTROL TRANFR.
-CONTROL 230 VAC / 24V DC FROM POWER SUPPLY SEC.VOLTAGE : 2.50 2.50 SQ.MM QUANTITY : 1 No.
-SIGNALLING 230 V AC,60HZ. EXTERNAL CURRENT : 2.50 2.50 SQ.MM INDICATING INSTRUMENT (METERS) REMARKS
POWER CKT.: RYB&N Y/G (GROUNDING)
INSTRUMENTS :
F CLIMATIC CONDITION CT: RYB&N F
SIZE 96 X 96 SIZE 72 X 72
ALARM: GRAY
TYPE OF CLIMATE : NORMAL
OTHERS :
TYPE OF ATMOSPHERE : ORDINARY TO SUIT DESERT
MARKING OF CIRCUITS
CONDITIONS
POWER : STAND R,Y,B,N
POLLUTION RISKS :
AUXILIARY : LOCAL END METER RELAY :
-MOUNTING INDOOR OUTDOOR
BOTH ENDS
G -AMBIENT TEMP. 50°C G
COMPOSED
-RELATIVE HUMIDITY 50% AT 50°C

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-05


PR PR 08-02-23
H TITLE: LCP-B917-E1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 65 2of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A
LEGENDS & SYMBOL A

S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION

X1
AIR CIRCUIT BREAKER
1 ACB 10 INDICATING LAMP
SURGE PROTECTION DEVICE
(ACB) 19 28
X2

B B
T2 T4 T6
A1
MOULDED CASE CIRCUIT BREAKER
2 (MCCB) 11 CONTACTOR / RELAY COIL 20 CONTROL FUSE 29
A2
T1 T3 T5

MANUAL

AUTO
OFF
HAND/OFF/AUTO
3 MCB 12 CURRENT TRANSFORMER 21
3 3
30
C SELECTOR SWITCH C
4 4

21 A
QM-OF

L3
L2

L1
MCCB AUXILIARY CONTACTS AMMETER

0
4 13 4 10
22 SPACE HEATER 31
24 22
1 3 5 11
WITH SELECTOR SWITCH

D D
C12 V

L3-L1
L2-L3
L1-L2

L1-N
L2-N
L3-N
VOLTMETER
5

0
MCCB SHUNT TRIP CONTACTS
MX 14 4 10

WITH SELECTOR SWITCH


23 THERMOSTAT 32
1 3 5 11
C11

L1 L2 L3

6 CONTACTOR 15 V POWER FACTOR METER


24 EARTH 33
E T1 T2 T3
E

A1 S1 S2 S1 S2 S1 S2
DIGITAL MULTIFUNCTION TERMINALS
7 T1 24H TIMER 16 L1 L2 L3
25 34
MFM METER
A2 V1 V2 V3 VN 0V - +

F F
CBCT

L 1

8 PANEL MOUNTED PHOTOCELL 17 26 35


S2 S1

EARTH LEAKAGE RELAY WITH


5 8
1

2
CBCT
N 2 6 9 7

1 8

XX
9 XX AUXILIARY CONTACTS 18 27 36
480V

230V

CONTROL TRANSFORMER
7 9
G 2 G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-05


PR PR 08-02-23
H TITLE: LCP-B917-E1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 66 3of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

PL-1
LCP-B917-E1
(40 0/230 V,3 PH .,4W ,6 0Hz.)
DS-1
ACH
Earth Stud

B B
H
O
A
ON OFF E N
R G

500
DANGER ‫ﺧﻄﺮ‬
HAZAR D OF EL ECTR IC AL S HOCK OR B URN
TURN O FF POWER TO T HIS EQUI PM ENT
BEF OR E WOR KING I NSIDE

‫ﺧﻄـــﺮ اﻟ ﺼــــﺪ ﻣﺔ اﻟﮑﮫﺮﺑﺎﺋﯿــــﺔ أو ا ﻻﺣــــﺘﺮا ق‬


‫إﻳ ﻘــﺎ ف اﻟﻄﺎﻗــﺔ ﻟﮫــﺬه اﻟﻤﻌـــﺪات‬
‫ﻗﺒــ ﻞ ااﻟﻌﻤـــ ﻞ ﺑﺎﻟـــﺪاﺧ ﻞ‬
TH

KM1 KM1
F1 F2 PC1
C C

400 400 200


FRONT VIEW INTERNAL VIEW SIDE VIEW
D D

GLAND PLATE (CUSTOMIZED)


325
E E

BOTTOM VIEW TOP VIEW

F F

NOTES:
1. BUSBAR : TIN PLATED COPPER
DANGER ‫ﺧﻄﺮ‬ LCP-B917-E1
HAZAR D OF ELECTRICAL SHOCK OR BURN
PANEL BOARD FACTORY: 2. ENCLOSURE: THICKNESS 1.2mm TURN O FF POWER TO THIS EQUIPMENT (CELL ASSEMBLY BUILDING)
BEFORE WORKING INSIDE
PROJECT : NEOM GREEN HYDROGEN PROJECT - U900 3. PANEL WEIGHT : 18Kg (APPX.)
PROJECT NO. : PM210011
‫ﺧﻄـــــﺮ اﻟﺼـــــﺪﻣﺔ اﻟﮑﮫﺮﺑﺎﺋﯿـــــﺔ أو اﻻﺣـــــﺘﺮاق‬
‫إﻳﻘـــﺎف اﻟﻄﺎﻗـــﺔ ﻟﮫـــﺬه اﻟﻤﻌــــﺪات‬ 400/230V,3PH.,4W,60Hz.
PANEL REF. : LCP-B917-E1 (CELL ASSEMBLY BUILDING) 4. PANEL MOUNTING : WALL MOUNTED TYPE ‫ﻗﺒــــﻞ ااﻟﻌﻤــــﻞ ﺑﺎﻟــــﺪاﺧﻞ‬

CURRENT RATING : 25A


G SYSTEM VOLTAGE : 400/230V,3PH., 4W, 60Hz
DANGER LABEL PANEL TAG G
DEGREE OF PROTECTION : IP 65 (WHITE LETTERS IN RED BACKGROUND)
PANEL WEIGHT : 18Kg
(BLACK LETTERS IN WHITE BACKGROUND)
YEAR OF MANUFACTURE : 2023
MANUFACTURER REF. : NPB-2210009

NAME PLATE DETAILS

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-05


PR PR 08-02-23
H TITLE: LCP-B917-E1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 67 3of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Incoming Supply From DB-B917-E1 (CELL ASSEMBLY BUILDING)


220V, 1Ph. 60Hz

A A

Circuit-11

Circuit-12
Circuit-6

Circuit-9
1 3 5 7

B B

FU1
4A
1 3 5 7
C C

A1 1/L1 3/L2 5/L3 A1 1/L1 3/L2 5/L3

D KM1 KM2 D
A2 2/T1 4/T2 6/T3 A2 2/T1 4/T2 6/T3

HAND

AUTO
OFF
FU2
1 3

2 4 13 13 21 21
S1
KM1 KM2 KM1 KM2
2
2 4 6 8 PC
PHOTO CELL 14 14 22 22 1
PC TH1
11
E L 1 THERMOSTAT 12
DS-1
E
1 2

N 2

X1

A1 A1 X1 X1
PL-1
ACH1
KM1 KM2 X2

F A2 A2 X2 X2 F
N

2 4 6 8
Circuit-11

Circuit-12
Circuit-6

Circuit-9

G G
TO LIGHTING CIRCUITS
N

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-05


PR PR 08-02-23
H TITLE: LCP-B917-E1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 68 5of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A BILL OF QUANTITY A

ITEM TAG CAT. REF. No. DESCRIPTION RATING QTY MANUFACTURER


1 KM1, KM2 LC1D25M7 Contactor, TeSys Deca, 3P(3 NO), AC-3 440V, 25A, 220VAC 50/60Hz coil 25A 2 Schneider Electric
2 FU1,2 A9N15636 SP Control Fuse Carrier 4A 2 Schneider Electric
3 1HP1,1HP2 XB7EV03MP/04MP Pilot Light - Integral LED - 230V AC (Green/Red) 20A 2 Schneider Electric
B 4 TH1 NSYCCOTHC ClimaSys CC - simple thermostat 250V - range of temperature 0…60°C - NC - 230V AC 1 Schneider Electric B

5 ACH1 NSYCR55WU2 ClimaSys PTC heating resistance 55W, 110-250V 230V AC 1 Schneider Electric
6 S1 XB5AD33 Selector switch, Harmony XB5 black, 22mm, 3 positions, stay put, 2 NO - 1 Schneider Electric
7 PC1 1IC 7051 Panel Mounted photocell Module, IP65 - 1 Perry
8 Encl NSYCRN54200 + NSYMM54 Spacial CRN plain door with mount.plate. H500xW400xD200 IP66 IK10 RAL7035 IP66 1 Schneider Electric
C 9 DS1 - Door Limit Switch - 1 Andeli C

10 PL1 - Panel Mounted LIght - LED 220V AC, 60Hz - 1 Reputed

D D

E E

F F

G G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-05


PR PR 08-02-23
H TITLE: LCP-B917-E1 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 69 5of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

C C

D D

E E

PANEL BOARD FACTORY


F F

PROJECT: PANEL TAG

NEOM GREEN HYDROGEN DB-B917-N2


G PROJECT - U900 (CELL ASSEMBLY BUILDING) G

QTY: 01No.

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-06


PR PR 08-02-23
H TITLE: DB-B917-N2 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 70 1of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

POWER SUPPLY APPARATUS DEGREE OF PROTECTION CIRCUIT MARKING


A A
SOURCE : MDB-900-B917-N MOUNTING : INCOMINGOUTGOING PROTECTION : LABELS :
FIXED IP 31 IP 41 IP 54 IP 66 ENGRAVED GRAVOPLY
400/230V, 3PH, 4W, 60Hz
DRAW-OUT ALUMINUM PVC
NO PARALLEL OPERATION PLUG-IN FORM : 1 3B TYPE : 2 4 6 MECHANICAL SCREWED (EXT.)
PARALLEL OPERATION OF OPERATION : RIVETED SELF STICK
2 4B 3 5 7
BEHIND DOOR GLUED (INT.)
ALL SOURCES PARALLEL ENCLOSURES
THROUGH PLATE COLOR : BLACK LETTERS IN WHITE BACKGROUND
B B
NEUTRAL SYSTEM : INTERLOCK Schneider Electric LANGUAGE : ENGLISH
PADLOCKING
Color : RAL 7035 PACKING
DIRECT TO EARTH (TT) EARTHED(TN) SHUTTER
THROUGH DOOR Wall Mounted Type LAND TRANSPORT
ISOLATED (IT) TNS
TERMINAL COVER PRESENTATION :
_______________
DIRECT CURRENT : TO EARTH ISOLATED CONNECTIONS FIXED FRONT TRANSPARENT DOOR
INCOMINGOUTGOING FUNCTIONAL DOOR WITH KEY _______________
C C
DIRECT
BUS BARS PLAIN DOOR PARTICULAR NOTES
TO TERMINAL PADS

MATERIAL : ALUM.
TO LINKS SELECTOR SWITCH/PUSH BUTTONS/LAMPS
COPPER APPARATUS DEFINED
ACCESS :
SYSTEM : PARTIC DIMENSIONS
REAR (CABLING) PUSH BUTTONS :
CONSTANT SECTION H V EXTENSION OF
FRONT (CABLING)
DECREASING H V ON OFF L.TEST RESET
LEFT SIDE/RIGHT SIDE SIMILAR TO
TIN PLATED H V SPECIFICATION
D ENTRY : D
WITH COLOUR CODED PVC SLEEVE LAMPS :
TOP (BY CABLES) DEVIATION
NEUTRAL : PE : BOTTOM (BY CABLES) RED GREEN YELLOW BLUE LOOSE MATERIAL
NOT DISTRIBUTED HORIZONTAL ACCESSORIES :
SCREWS _______________
SAME SECTION AS PHASES VERTICAL SELECTOR SWITCH :
HALF SECTION HALF SECTION GLAND PLATES
HOA ON/OFF AM. SS VM. SS DRAWINGS :
CABLE GLAND
SUPPLY OF AUXILIARIES SHROUDING :
E For Approval AS BUILT E
CABLE ENDS OTHERS :
VOLTAGE : ORIGIN :
FOR PRODUCTION
AUXILIARY WIRING ________________________
-ALL CIRCUITS 230 VAC / 24V DC CONTROL TRANFR.
-CONTROL 230 VAC / 24V DC FROM POWER SUPPLY SEC.VOLTAGE : 2.50 2.50 SQ.MM QUANTITY : 1 No.
-SIGNALLING 230 V AC,60HZ. FROM BUSBAR CURRENT : 2.50 2.50 SQ.MM INDICATING INSTRUMENT (METERS) REMARKS
POWER CKT.: RYB&N Y/G (GROUNDING)
INSTRUMENTS :
F CLIMATIC CONDITION CT: RYB&N F
SIZE 96 X 96 SIZE 72 X 72
ALARM: GRAY
TYPE OF CLIMATE : NORMAL
OTHERS :
TYPE OF ATMOSPHERE : ORDINARY TO SUIT DESERT
MARKING OF CIRCUITS
CONDITIONS
POWER : STAND R,Y,B,N
POLLUTION RISKS :
AUXILIARY : LOCAL END METER RELAY :
-MOUNTING INDOOR OUTDOOR
BOTH ENDS
G -AMBIENT TEMP. 50°C G
COMPOSED
-RELATIVE HUMIDITY 50% AT 50°C

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-06


PR PR 08-02-23
H TITLE: DB-B917-N2 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 71 2of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A
LEGENDS & SYMBOL A

S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION

X1
AIR CIRCUIT BREAKER
1 ACB 10 INDICATING LAMP
SURGE PROTECTION DEVICE
(ACB) 19 28
X2

B B
T2 T4 T6
A1
MOULDED CASE CIRCUIT BREAKER
2 (MCCB) 11 CONTACTOR / RELAY COIL 20 CONTROL FUSE 29
A2
T1 T3 T5

MANUAL

AUTO
OFF
HAND/OFF/AUTO
3 MCB 12 CURRENT TRANSFORMER 21
3 3
30
C SELECTOR SWITCH C
4 4

21 A
QM-OF

L3
L2

L1
MCCB AUXILIARY CONTACTS AMMETER

0
4 13 4 10
22 SPACE HEATER 31
24 22
1 3 5 11
WITH SELECTOR SWITCH

D D
C12 V

L3-L1
L2-L3
L1-L2

L1-N
L2-N
L3-N
VOLTMETER
5

0
MCCB SHUNT TRIP CONTACTS
MX 14 4 10

WITH SELECTOR SWITCH


23 THERMOSTAT 32
1 3 5 11
C11

L1 L2 L3

6 CONTACTOR 15 V POWER FACTOR METER


24 EARTH 33
E T1 T2 T3
E

A1 S1 S2 S1 S2 S1 S2
DIGITAL MULTIFUNCTION TERMINALS
7 T1 24H TIMER 16 L1 L2 L3
25 34
MFM METER
A2 V1 V2 V3 VN 0V - +

F F
CBCT

L 1

8 PANEL MOUNTED PHOTOCELL 17 26 35


S2 S1

EARTH LEAKAGE RELAY WITH


5 8
1

2
CBCT
N 2 6 9 7

1 8

XX
9 XX AUXILIARY CONTACTS 18 27 36
480V

230V

CONTROL TRANSFORMER
7 9
G 2 G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-06


PR PR 08-02-23
H TITLE: DB-B917-N2 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 72 3of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A DB-B917-N2
(40 0/2 30V, 3PH, 4W, 60 Hz) A

Busbar Assembly

B B

E N
1000

DA NG ER ‫ﺧﻄﺮ‬
HA ZA RD O F E LEC TRIC A L SH OC K O R B URN
TURN OFF PO WER TO T HIS EQ UIPME NT
BE FORE WO RK ING INS ID E

‫ﺧﻄـــــﺮ اﻟﺼـــــﺪﻣﺔ اﻟﮑﮫﺮﺑﺎﺋﯿـــــﺔ أو اﻻﺣـــــﺘﺮاق‬


‫إﻳﻘـــﺎف اﻟﻄﺎﻗـــﺔ ﻟﮫــــﺬه اﻟﻤﻌــــﺪات‬
‫ﻗﺒــــﻞ ااﻟﻌﻤــــﻞ ﺑﺎﻟــــﺪاﺧﻞ‬

C C

Electric
QM Electric QM
Schneider
Schneider

D D

600 600 600 250


FRONT VIEW INTERNAL VIEW INTERNAL VIEW SIDE VIEW
(WITH FRONT COVER)
E E

GLAND PLATE (CUSTOMIZED)

F F
BOTTOM VIEW TOP VIEW

NOTES:
PANEL BOARD FACTORY: 1. BUSBAR : TIN PLATED COPPER
DANGER ‫ﺧﻄﺮ‬ DB-B917-N2
HAZAR D OF ELECTRICAL SHOCK OR BURN
PROJECT
PANEL REF.
:
:
NEOM GREEN HYDROGEN PROJECT - U900
DB-B917-N2 (CELL ASSEMBLY BUILDING)
2. ENCLOSURE: THICKNESS 1.2mm TURN O FF POWER TO THIS EQUIPMENT (CELL ASSEMBLY BUILDING)
BEFORE WORKING INSIDE
PROJECT NO. : PM210011 3. PANEL WEIGHT : 95Kg (APPX.)
G CURRENT RATING : 80A
‫ﺧﻄـــــﺮ اﻟﺼـــــﺪﻣﺔ اﻟﮑﮫﺮﺑﺎﺋﯿـــــﺔ أو اﻻﺣـــــﺘﺮاق‬
‫إﻳﻘـــﺎف اﻟﻄﺎﻗـــﺔ ﻟﮫـــﺬه اﻟﻤﻌــــﺪات‬ 400/230V,3PH.,4W,60Hz. G
SYSTEM VOLTAGE : 400/230V,3PH., 4W, 60Hz 4. PANEL MOUNTING : SURFACE MOUNTED TYPE ‫ﻗﺒــــﻞ ااﻟﻌﻤــــﻞ ﺑﺎﻟــــﺪاﺧﻞ‬
DEGREE OF PROTECTION : IP 41
PANEL WEIGHT : 95Kg DANGER LABEL PANEL TAG
YEAR OF MANUFACTURE : 2023 (WHITE LETTERS IN RED BACKGROUND)
MANUFACTURER REF. : NPB-2210009 (BLACK LETTERS IN WHITE BACKGROUND)
NAME PLATE DETAILS

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-06


PR PR 08-02-23
H TITLE: DB-B917-N2 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 73 3of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

LOAD DESCRIPTION BREAKER BREAKER LOAD DESCRIPTION


1 SOCKET OUTLETS - PRE ASSEMBLY AREA, OFFICE-2 20A 30mA SP RCBO,10KA 20A 30mA SP RCBO,10KA SOCKET OUTLETS - STORAGE AREA 2

EARTH BAR
A A

NEUTRAL BAR
3 SOCKET OUTLETS - WORKSHOP-2 20A 30mA SP RCBO,10KA 20A 30mA SP RCBO,10KA SOCKETS OUTLETS - STORAGE AREA & SWITCHGEAR ROOM 4
5 SOCKET OUTLETS - CELL WORKSHOP-1&2 20A 30mA SP RCBO,10KA 20A 30mA SP RCBO,10KA SOCKETS OUTLETS - STORAGE, UTILITY RM, MALE PRAYER & TOILET 6
7 SOCKET OUTLETS - OFFICE-5,6&7 20A 30mA SP RCBO,10KA 20A 30mA SP RCBO,10KA SOCKETS OUTLETS - LUNCH ROOM, FEMALE TOILETS, CHANGING ROOM 8
9 SOCKET OUTLETS - OFFICE-3&7, TELECOM ROOM 20A 30mA SP RCBO,10KA 16A SP MCB,10KA PORTABLE COMPRESSOR (INTERMITTENT) 10
11 SOCKET OUTLETS - OFFICE-1, CORRIDOR & FEMALE PRAYER 20A 30mA SP RCBO,10KA 16A SP MCB,10KA SPARE 12
13 14
15 3 TON OVERHEAD CRANE FOR STORAGE AREA 32A TP MCB,10KA 32A TP MCB,10KA 0.5 TON OVERHEAD CRANE FOR CELL WORKSHOP - 1 16
B 17 18 B
19 20
21 DEMIN WATER PUMP CONTROL PANEL 32A TP MCB,10KA 32A TP MCB,10KA 0.5 TON OVERHEAD CRANE FOR CELL WORKSHOP - 2 22
23 24
25 SPARE 20A SP MCB,10KA 26
27 SPARE 20A SP MCB,10KA 32A TP MCB,10KA SPARE 28
29 3KVA UPS FOR IT 20A SP MCB,10KA 30
31 EXHAUST FAN (EF-02) 16A SP MCB,10KA EXHAUST FAN (EF-04)
C 16A SP MCB,10KA 32 C
33 SPARE 16A SP MCB,10KA 16A SP MCB,10KA SPARE 34
35 EXHAUST FAN (EF-03) 16A SP MCB,10KA 16A 30mA SP RCBO,10KA HOT WATER CIRCULATING PUMP (HWRP-01) (INTERMITTENT) 36
37 32A SP MCB,10KA 5KVA UPS FOR PAGA 38
39 EXHAUST FAN (EF-01A) 20A TP MCB,10KA 20A SP MCB,10KA SPARE 40
41 32A SP MCB,10KA SPARE 42
43 16A SP MCB,10KA SPARE 44
45 EXHAUST FAN (EF-01B) 20A TP MCB,10KA 20A SP MCB,10KA SPARE 46
D D
47 20A SP MCB,10KA SPARE 48

E E

QM
80AT/100AF TP
MCCB, 25kA
(TMD)

F F

N R Y B
G Incoming Supply G

380/220V,3PH.,4W,60Hz.
Fed From : MDB-900-B917-N
Cable Size : 4CX50mm2 + 1CX35mm2 (G)

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-06


PR PR 08-02-23
H TITLE: DB-B917-N2 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 74 5of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A BILL OF QUANTITY A

ITEM TAG CAT. REF. No. DESCRIPTION RATING QTY MANUFACTURER


1 QM LV429551 / C10B3TM080C Circuit breaker, ComPact NSX100B, 25kA/415VAC, TMD trip unit 80A, 3 poles 3d 80A 1 Schneider Electric
2 Q1-Q8 A9F44116 Acti9 iC60N 1P 16A C Miniature Circuit breaker 16A 8 Schneider Electric
3 Q9-Q14 A9F44120 Acti9 iC60N 1P 20A C Miniature Circuit breaker 20A 6 Schneider Electric
B B
4 Q15,Q16 A9F44132 Acti9 iC60N 1P 32A C Miniature Circuit breaker 32A 2 Schneider Electric
5 Q17,Q18 A9F44320 Acti9 iC60N 3P 20A C Miniature Circuit breaker 20A 2 Schneider Electric
6 Q19-Q23 A9F44332 Acti9 iC60N 3P 32A C Miniature Circuit breaker 32A 5 Schneider Electric
7 Q24 A9D11816 / A9D14816 Acti9 iC60H RCBO, 1P+Ns, 16A, 30mA, A type 16A 30mA 1 Schneider Electric
8 Q25-Q34 A9D11820 / A9D14820 Acti9 iC60H RCBO, 1P+Ns, 20A, 30mA, A type 20A 30mA 10 Schneider Electric
C C
9 Encl NSYCRN106250P Spacial CRN plain door with mount.plate. H1000xW600xD250 IP66 IK10 RAL7035 IP66 1 Schneider Electric
10 - - Busbar Assembly - 48 Way SPN - 1 Reputed

D D

E E

F F

G G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-06


PR PR 08-02-23
H TITLE: DB-B917-N2 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 75 6of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

C C

D D

E E

PANEL BOARD FACTORY


F F

PROJECT: PANEL TAG

NEOM GREEN HYDROGEN DB-B917-N3


G PROJECT - U900 (CELL ASSEMBLY BUILDING) G

QTY: 01No.

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-07


PR PR 08-02-23
H TITLE: DB-B917-N3 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 76 1of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

POWER SUPPLY APPARATUS DEGREE OF PROTECTION CIRCUIT MARKING


A A
SOURCE : MDB-900-B917-N MOUNTING : INCOMINGOUTGOING PROTECTION : LABELS :
FIXED IP 31 IP 41 IP 54 IP 66 ENGRAVED GRAVOPLY
400/230V, 3PH, 4W, 60Hz
DRAW-OUT ALUMINUM PVC
NO PARALLEL OPERATION PLUG-IN FORM : 1 3B TYPE : 2 4 6 MECHANICAL SCREWED (EXT.)
PARALLEL OPERATION OF OPERATION : RIVETED SELF STICK
2 4B 3 5 7
BEHIND DOOR GLUED (INT.)
ALL SOURCES PARALLEL ENCLOSURES
THROUGH PLATE COLOR : BLACK LETTERS IN WHITE BACKGROUND
B B
NEUTRAL SYSTEM : INTERLOCK Schneider Electric LANGUAGE : ENGLISH
PADLOCKING
Color : RAL 7035 PACKING
DIRECT TO EARTH (TT) EARTHED(TN) SHUTTER
THROUGH DOOR Wall Mounted Type LAND TRANSPORT
ISOLATED (IT) TNS
TERMINAL COVER PRESENTATION :
_______________
DIRECT CURRENT : TO EARTH ISOLATED CONNECTIONS FIXED FRONT TRANSPARENT DOOR
INCOMINGOUTGOING FUNCTIONAL DOOR WITH KEY _______________
C C
DIRECT
BUS BARS PLAIN DOOR PARTICULAR NOTES
TO TERMINAL PADS

MATERIAL : ALUM.
TO LINKS SELECTOR SWITCH/PUSH BUTTONS/LAMPS
COPPER APPARATUS DEFINED
ACCESS :
SYSTEM : PARTIC DIMENSIONS
REAR (CABLING) PUSH BUTTONS :
CONSTANT SECTION H V EXTENSION OF
FRONT (CABLING)
DECREASING H V ON OFF L.TEST RESET
LEFT SIDE/RIGHT SIDE SIMILAR TO
TIN PLATED H V SPECIFICATION
D ENTRY : D
WITH COLOUR CODED PVC SLEEVE LAMPS :
TOP (BY CABLES) DEVIATION
NEUTRAL : PE : BOTTOM (BY CABLES) RED GREEN YELLOW BLUE LOOSE MATERIAL
NOT DISTRIBUTED HORIZONTAL ACCESSORIES :
SCREWS _______________
SAME SECTION AS PHASES VERTICAL SELECTOR SWITCH :
HALF SECTION HALF SECTION GLAND PLATES
HOA ON/OFF AM. SS VM. SS DRAWINGS :
CABLE GLAND
SUPPLY OF AUXILIARIES SHROUDING :
E For Approval AS BUILT E
CABLE ENDS OTHERS :
VOLTAGE : ORIGIN :
FOR PRODUCTION
AUXILIARY WIRING ________________________
-ALL CIRCUITS 230 VAC / 24V DC CONTROL TRANFR.
-CONTROL 230 VAC / 24V DC FROM POWER SUPPLY SEC.VOLTAGE : 2.50 2.50 SQ.MM QUANTITY : 1 No.
-SIGNALLING 230 V AC,60HZ. FROM BUSBAR CURRENT : 2.50 2.50 SQ.MM INDICATING INSTRUMENT (METERS) REMARKS
POWER CKT.: RYB&N Y/G (GROUNDING)
INSTRUMENTS :
F CLIMATIC CONDITION CT: RYB&N F
SIZE 96 X 96 SIZE 72 X 72
ALARM: GRAY
TYPE OF CLIMATE : NORMAL
OTHERS :
TYPE OF ATMOSPHERE : ORDINARY TO SUIT DESERT
MARKING OF CIRCUITS
CONDITIONS
POWER : STAND R,Y,B,N
POLLUTION RISKS :
AUXILIARY : LOCAL END METER RELAY :
-MOUNTING INDOOR OUTDOOR
BOTH ENDS
G -AMBIENT TEMP. 50°C G
COMPOSED
-RELATIVE HUMIDITY 50% AT 50°C

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-07


PR PR 08-02-23
H TITLE: DB-B917-N3 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 77 2of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A
LEGENDS & SYMBOL A

S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION

X1
AIR CIRCUIT BREAKER
1 ACB 10 INDICATING LAMP
SURGE PROTECTION DEVICE
(ACB) 19 28
X2

B B
T2 T4 T6
A1
MOULDED CASE CIRCUIT BREAKER
2 (MCCB) 11 CONTACTOR / RELAY COIL 20 CONTROL FUSE 29
A2
T1 T3 T5

MANUAL

AUTO
OFF
HAND/OFF/AUTO
3 MCB 12 CURRENT TRANSFORMER 21
3 3
30
C SELECTOR SWITCH C
4 4

21 A
QM-OF

L3
L2

L1
MCCB AUXILIARY CONTACTS AMMETER

0
4 13 4 10
22 SPACE HEATER 31
24 22
1 3 5 11
WITH SELECTOR SWITCH

D D
C12 V

L3-L1
L2-L3
L1-L2

L1-N
L2-N
L3-N
VOLTMETER
5

0
MCCB SHUNT TRIP CONTACTS
MX 14 4 10

WITH SELECTOR SWITCH


23 THERMOSTAT 32
1 3 5 11
C11

L1 L2 L3

6 CONTACTOR 15 V POWER FACTOR METER


24 EARTH 33
E T1 T2 T3
E

A1 S1 S2 S1 S2 S1 S2
DIGITAL MULTIFUNCTION TERMINALS
7 T1 24H TIMER 16 L1 L2 L3
25 34
MFM METER
A2 V1 V2 V3 VN 0V - +

F F
CBCT

L 1

8 PANEL MOUNTED PHOTOCELL 17 26 35


S2 S1

EARTH LEAKAGE RELAY WITH


5 8
1

2
CBCT
N 2 6 9 7

1 8

XX
9 XX AUXILIARY CONTACTS 18 27 36
480V

230V

CONTROL TRANSFORMER
7 9
G 2 G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-07


PR PR 08-02-23
H TITLE: DB-B917-N3 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 78 3of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A DB-B917-N3
(40 0/2 30V, 3PH, 4W, 60 Hz) A
Busbar Assembly

B E N B
1000

DA NG ER ‫ﺧﻄﺮ‬
HA ZA RD O F E LEC TRIC A L SH OC K O R B URN
TURN OFF PO WER TO T HIS EQ UIPME NT
BE FORE WO RK ING INS ID E

‫ﺧﻄـــــﺮ اﻟﺼـــــﺪﻣﺔ اﻟﮑﮫﺮﺑﺎﺋﯿـــــﺔ أو اﻻﺣـــــﺘﺮاق‬


‫إﻳﻘـــﺎف اﻟﻄﺎﻗـــﺔ ﻟﮫــــﺬه اﻟﻤﻌــــﺪات‬
‫ﻗﺒــــﻞ ااﻟﻌﻤــــﻞ ﺑﺎﻟــــﺪاﺧﻞ‬

C C
Electric
QM Electric
Schneider
QM
Schneider

D D

600 600 600 250


FRONT VIEW INTERNAL VIEW INTERNAL VIEW SIDE VIEW
(WITH FRONT COVER)
E E

GLAND PLATE (CUSTOMIZED)

F F
BOTTOM VIEW TOP VIEW

NOTES:
PANEL BOARD FACTORY: 1. BUSBAR : TIN PLATED COPPER
DANGER ‫ﺧﻄﺮ‬ DB-B917-N3
HAZAR D OF ELECTRICAL SHOCK OR BURN
PROJECT
PROJECT NO.
:
:
NEOM GREEN HYDROGEN PROJECT - U900
PM210011
2. ENCLOSURE: THICKNESS 1.2mm TURN O FF POWER TO THIS EQUIPMENT (CELL ASSEMBLY BUILDING)
BEFORE WORKING INSIDE
PANEL REF. : DB-B917-N3 (CELL ASSEMBLY BUILDING) 3. PANEL WEIGHT : 85Kg (APPX.)
G
CURRENT RATING : 160A
‫ﺧﻄـــــﺮ اﻟﺼـــــﺪﻣﺔ اﻟﮑﮫﺮﺑﺎﺋﯿـــــﺔ أو اﻻﺣـــــﺘﺮاق‬
‫إﻳﻘـــﺎف اﻟﻄﺎﻗـــﺔ ﻟﮫـــﺬه اﻟﻤﻌــــﺪات‬ 400/230V,3PH.,4W,60Hz. G
SYSTEM VOLTAGE : 400/230V,3PH., 4W, 60Hz 4. PANEL MOUNTING : SURFACE MOUNTED TYPE ‫ﻗﺒــــﻞ ااﻟﻌﻤــــﻞ ﺑﺎﻟــــﺪاﺧﻞ‬
DEGREE OF PROTECTION : IP 66
PANEL WEIGHT : 85Kg DANGER LABEL PANEL TAG
YEAR OF MANUFACTURE : 2023 (WHITE LETTERS IN RED BACKGROUND)
MANUFACTURER REF. : NPB-2210009 (BLACK LETTERS IN WHITE BACKGROUND)
NAME PLATE DETAILS

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-07


PR PR 08-02-23
H TITLE: DB-B917-N3 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 79 3of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

LOAD DESCRIPTION BREAKER BREAKER LOAD DESCRIPTION


1 DOOR AIR CURTAIN IN STORAGE AREA (DAC-03) 16A SP MCB,10KA 16A SP MCB,10KA DOOR AIR CURTAIN IN STORAGE AREA (DAC-03) 2

EARTH BAR
A A

NEUTRAL BAR
3 DOOR AIR CURTAIN IN STORAGE AREA (DAC-01) 16A SP MCB,10KA 16A SP MCB,10KA DOOR AIR CURTAIN IN STORAGE AREA (DAC-01) 4
5 DOOR AIR CURTAIN IN STORAGE AREA (DAC-03) 16A SP MCB,10KA 16A SP MCB,10KA DOOR AIR CURTAIN IN STORAGE AREA (DAC-03) 6
7 DOOR AIR CURTAIN IN CELL WORKSHOP-1 (DAC-01) 16A SP MCB,10KA 16A SP MCB,10KA DOOR AIR CURTAIN IN CELL WORKSHOP-1 (DAC-01) 8
9 DOOR AIR CURTAIN IN CELL WORKSHOP-1 (DAC-03) 16A SP MCB,10KA 16A SP MCB,10KA DOOR AIR CURTAIN IN CELL WORKSHOP-1 (DAC-03) 10
11 DOOR AIR CURTAIN IN CELL WORKSHOP-2 (DAC-03) 16A SP MCB,10KA 16A SP MCB,10KA DOOR AIR CURTAIN IN CELL WORKSHOP-2 (DAC-01) 12
13 DOOR AIR CURTAIN IN CELL AIRLOCK-106 (DAC-02) 16A SP MCB,10KA 16A SP MCB,10KA DOOR AIR CURTAIN IN CELL AIRLOCK-116 (DAC-02) 14
15 SPARE 16A SP MCB,10KA 16A SP MCB,10KA SPARE 16
B 17 SPARE 16A SP MCB,10KA 16A SP MCB,10KA SPARE 18 B
19 20
21 WELDING SOCKET OUTLET IN CELL WORKSHOP-1 (WO-01) 63A TP MCB,10KA 63A TP MCB,10KA WELDING SOCKET OUTLET IN CELL WORKSHOP-1 (WO-02) 22
23 24
25 26
27 WELDING SOCKET OUTLET IN CELL WORKSHOP-2 (WO-03) 63A TP MCB,10KA 63A TP MCB,10KA WELDING SOCKET OUTLET IN CELL WORKSHOP-2 (WO-04) 28
29 30
31
C 32 C
33 WELDING SOCKET OUTLET IN PAN ASSEMBLY AREA (WO-05) 63A TP MCB,10KA 63A TP MCB,10KA WELDING SOCKET OUTLET IN PAN ASSEMBLY AREA (WO-06) 34
35 36
37 38
39 SPARE 63A TP MCB,10KA 63A TP MCB,10KA SPARE 40
41 42
43 DOOR AIR CURTAIN 16A SP MCB,10KA 16A SP MCB,10KA DOOR AIR CURTAIN 44
45 DOOR AIR CURTAIN 16A SP MCB,10KA 16A SP MCB,10KA DOOR AIR CURTAIN 46
D D
47 DOOR AIR CURTAIN 16A SP MCB,10KA 16A SP MCB,10KA DOOR AIR CURTAIN 48

E E

QM
160AT/160AF TP
MCCB, 25kA
(TMD)
F F

N R Y B
G Incoming Supply G

380/220V,3PH.,4W,60Hz.
Fed From : MDB-900-B917-N
Cable Size : 4CX185mm2 + 1CX70mm2 (G)

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-07


PR PR 08-02-23
H TITLE: DB-B917-N3 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 80 5of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A
BILL OF QUANTITY A

ITEM TAG CAT. REF. No. DESCRIPTION RATING QTY MANUFACTURER


1 QM LV430310 / C16B3TM160C Circuit breaker, ComPact NSX160B, 25kA/415VAC, TMD trip unit 160A, 3 poles 3d 160A 1 Schneider Electric
2 Q1-Q24 A9F44116 Acti9 iC60N 1P 16A C Miniature Circuit breaker 20A 24 Schneider Electric
3 Q25-Q32 A9F44363 Acti9 iC60N 3P 63A C Miniature Circuit breaker 63A 8 Schneider Electric

B 4 Encl NSYCRN106250P Spacial CRN plain door with mount.plate. H1000xW600xD250 IP66 IK10 RAL7035 IP66 1 Schneider Electric B
5 - - Busbar Assembly - 48 Way SPN - 1 Reputed
6
7
8
C 9 C
10

D D

E E

F F

G G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-07


PR PR 08-02-23
H TITLE: DB-B917-N3 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 81 6of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B

C C

D D

E E

PANEL BOARD FACTORY


F F

PROJECT: PANEL TAG

NEOM GREEN HYDROGEN DB-B917-E2


G PROJECT - U900 (CELL ASSEMBLY BUILDING) G

QTY: 01No.

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-08


PR PR 08-02-23
H TITLE: DB-B917-E2 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 82 1of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

POWER SUPPLY APPARATUS DEGREE OF PROTECTION CIRCUIT MARKING


A A
SOURCE : MDB-900-B917-E MOUNTING : INCOMINGOUTGOING PROTECTION : LABELS :
FIXED IP 31 IP 41 IP 54 IP 66 ENGRAVED GRAVOPLY
400/230V, 3PH, 4W, 60Hz
DRAW-OUT ALUMINUM PVC
NO PARALLEL OPERATION PLUG-IN FORM : 1 3B TYPE : 2 4 6 MECHANICAL SCREWED (EXT.)
PARALLEL OPERATION OF OPERATION : RIVETED SELF STICK
2 4B 3 5 7
BEHIND DOOR GLUED (INT.)
ALL SOURCES PARALLEL ENCLOSURES
THROUGH PLATE COLOR : BLACK LETTERS IN WHITE BACKGROUND
B B
NEUTRAL SYSTEM : INTERLOCK Schneider Electric LANGUAGE : ENGLISH
PADLOCKING
Color : RAL 7035 PACKING
DIRECT TO EARTH (TT) EARTHED(TN) SHUTTER
THROUGH DOOR Wall Mounted Type LAND TRANSPORT
ISOLATED (IT) TNS
TERMINAL COVER PRESENTATION :
_______________
DIRECT CURRENT : TO EARTH ISOLATED CONNECTIONS FIXED FRONT TRANSPARENT DOOR
INCOMINGOUTGOING FUNCTIONAL DOOR WITH KEY _______________
C C
DIRECT
BUS BARS PLAIN DOOR PARTICULAR NOTES
TO TERMINAL PADS

MATERIAL : ALUM.
TO LINKS SELECTOR SWITCH/PUSH BUTTONS/LAMPS
COPPER APPARATUS DEFINED
ACCESS :
SYSTEM : PARTIC DIMENSIONS
REAR (CABLING) PUSH BUTTONS :
CONSTANT SECTION H V EXTENSION OF
FRONT (CABLING)
DECREASING H V ON OFF L.TEST RESET
LEFT SIDE/RIGHT SIDE SIMILAR TO
TIN PLATED H V SPECIFICATION
D ENTRY : D
WITH COLOUR CODED PVC SLEEVE LAMPS :
TOP (BY CABLES) DEVIATION
NEUTRAL : PE : BOTTOM (BY CABLES) RED GREEN YELLOW BLUE LOOSE MATERIAL
NOT DISTRIBUTED HORIZONTAL ACCESSORIES :
SCREWS _______________
SAME SECTION AS PHASES VERTICAL SELECTOR SWITCH :
HALF SECTION HALF SECTION GLAND PLATES
HOA ON/OFF AM. SS VM. SS DRAWINGS :
CABLE GLAND
SUPPLY OF AUXILIARIES SHROUDING :
E For Approval AS BUILT E
CABLE ENDS OTHERS :
VOLTAGE : ORIGIN :
FOR PRODUCTION
AUXILIARY WIRING ________________________
-ALL CIRCUITS 230 VAC / 24V DC CONTROL TRANFR.
-CONTROL 230 VAC / 24V DC FROM POWER SUPPLY SEC.VOLTAGE : 2.50 2.50 SQ.MM QUANTITY : 1 No.
-SIGNALLING 230 V AC,60HZ. FROM BUSBAR CURRENT : 2.50 2.50 SQ.MM INDICATING INSTRUMENT (METERS) REMARKS
POWER CKT.: RYB&N Y/G (GROUNDING)
INSTRUMENTS :
F CLIMATIC CONDITION CT: RYB&N F
SIZE 96 X 96 SIZE 72 X 72
ALARM: GRAY
TYPE OF CLIMATE : NORMAL
OTHERS :
TYPE OF ATMOSPHERE : ORDINARY TO SUIT DESERT
MARKING OF CIRCUITS
CONDITIONS
POWER : STAND R,Y,B,N
POLLUTION RISKS :
AUXILIARY : LOCAL END METER RELAY :
-MOUNTING INDOOR OUTDOOR
BOTH ENDS
G -AMBIENT TEMP. 50°C G
COMPOSED
-RELATIVE HUMIDITY 50% AT 50°C

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-08


PR PR 08-02-23
H TITLE: DB-B917-E2 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 83 2of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A
LEGENDS & SYMBOL A

S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION S.NO SYMBOL DESCRIPTION

X1
AIR CIRCUIT BREAKER
1 ACB 10 INDICATING LAMP
SURGE PROTECTION DEVICE
(ACB) 19 28
X2

B B
T2 T4 T6
A1
MOULDED CASE CIRCUIT BREAKER
2 (MCCB) 11 CONTACTOR / RELAY COIL 20 CONTROL FUSE 29
A2
T1 T3 T5

MANUAL

AUTO
OFF
HAND/OFF/AUTO
3 MCB 12 CURRENT TRANSFORMER 21
3 3
30
C SELECTOR SWITCH C
4 4

21 A
QM-OF

L3
L2

L1
MCCB AUXILIARY CONTACTS AMMETER

0
4 13 4 10
22 SPACE HEATER 31
24 22
1 3 5 11
WITH SELECTOR SWITCH

D D
C12 V

L3-L1
L2-L3
L1-L2

L1-N
L2-N
L3-N
VOLTMETER
5

0
MCCB SHUNT TRIP CONTACTS
MX 14 4 10

WITH SELECTOR SWITCH


23 THERMOSTAT 32
1 3 5 11
C11

L1 L2 L3

6 CONTACTOR 15 V POWER FACTOR METER


24 EARTH 33
E T1 T2 T3
E

A1 S1 S2 S1 S2 S1 S2
DIGITAL MULTIFUNCTION TERMINALS
7 T1 24H TIMER 16 L1 L2 L3
25 34
MFM METER
A2 V1 V2 V3 VN 0V - +

F F
CBCT

L 1

8 PANEL MOUNTED PHOTOCELL 17 26 35


S2 S1

EARTH LEAKAGE RELAY WITH


5 8
1

2
CBCT
N 2 6 9 7

1 8

XX
9 XX AUXILIARY CONTACTS 18 27 36
480V

230V

CONTROL TRANSFORMER
7 9
G 2 G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-08


PR PR 08-02-23
H TITLE: DB-B917-E2 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 84 3of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB-B917-E2
(40 0/230 V, 3PH , 4W, 60 Hz)

A A

QSPD SPD F1 F1

Busbar Assembly
B B
1000

E N

DANGER ‫ﺧﻄﺮ‬
HAZAR D OF EL ECTR IC AL S HOCK OR B URN
TURN O FF POWER TO T HIS EQUI PM ENT
BEF OR E WOR KING I NSIDE
‫ﺧﻄـــﺮ اﻟ ﺼــــﺪ ﻣﺔ اﻟﮑﮫﺮﺑﺎﺋﯿــــﺔ أو ا ﻻﺣــــﺘﺮا ق‬
‫إﻳ ﻘــﺎ ف اﻟﻄﺎﻗــﺔ ﻟﮫــﺬه اﻟﻤﻌـــﺪات‬
‫ﻗﺒــ ﻞ ااﻟﻌﻤـــ ﻞ ﺑﺎﻟـــﺪاﺧ ﻞ‬

C C

Ele ct ric
QM E lec tric
QM
S ch ne id er
Sch ne id e r

D D

600 600 600 250


E FRONT VIEW INTERNAL VIEW INTERNAL VIEW SIDE VIEW E

(WITH FRONT COVER)

GLAND PLATE (CUSTOMIZED)


F F

BOTTOM VIEW TOP VIEW


PANEL BOARD FACTORY:
PROJECT : NEOM GREEN HYDROGEN PROJECT - U900 NOTES:
PROJECT NO.
PANEL REF.
:
:
PM210011
DB-B917-E2 (CELL ASSEMBLY BUILDING) 1. BUSBAR : TIN PLATED COPPER
DANGER ‫ﺧﻄﺮ‬ DB-B917-E2
CURRENT RATING : 63A HAZAR D OF ELECTRICAL SHOCK OR BURN
G SYSTEM VOLTAGE : 400/230V,3PH., 4W, 60Hz 2. ENCLOSURE: THICKNESS 1.2mm TURN O FF POWER TO THIS EQUIPMENT (CELL ASSEMBLY BUILDING) G
BEFORE WORKING INSIDE
DEGREE OF PROTECTION : IP 41
3. PANEL WEIGHT : 78Kg (APPX.)
PANEL WEIGHT
YEAR OF MANUFACTURE
:
:
78Kg
2023
‫ﺧﻄـــــﺮ اﻟﺼـــــﺪﻣﺔ اﻟﮑﮫﺮﺑﺎﺋﯿـــــﺔ أو اﻻﺣـــــﺘﺮاق‬
‫إﻳﻘـــﺎف اﻟﻄﺎﻗـــﺔ ﻟﮫـــﺬه اﻟﻤﻌــــﺪات‬ 400/230V,3PH.,4W,60Hz.
4. PANEL MOUNTING : SURFACE MOUNTED TYPE ‫ﻗﺒــــﻞ ااﻟﻌﻤــــﻞ ﺑﺎﻟــــﺪاﺧﻞ‬
MANUFACTURER REF. : NPB-2210009
DANGER LABEL PANEL TAG
NAME PLATE DETAILS (WHITE LETTERS IN RED BACKGROUND)
(BLACK LETTERS IN WHITE BACKGROUND)

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-08


PR PR 08-02-23
H TITLE: DB-B917-E2 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 85 3of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

LOAD DESCRIPTION BREAKER BREAKER LOAD DESCRIPTION


1 SPU-OU-01A (DUTY) 32A 30mA SP RCBO,10KA 32A 30mA SP RCBO,10KA SPU-OU-01B (STANDBY) 2

EARTH BAR
A A

NEUTRAL BAR
3 SPU-OU-02A (DUTY) 32A 30mA SP RCBO,10KA 32A 30mA SP RCBO,10KA SPU-OU-02B (STANDBY) 4
5 SPU-OU-03A (DUTY) 32A 30mA SP RCBO,10KA 32A 30mA SP RCBO,10KA SPU-OU-03C (STANDBY) 6
7 SPU-OU-03B (DUTY) 32A 30mA SP RCBO,10KA 32A 30mA SP RCBO,10KA SPU-OU-03D (STANDBY) 8
9 TORQUE TOOLS (INTERMITTENT) 16A SP MCB,10KA 20A SP MCB,10KA DDC PANEL (STANDBY) 10
11 SPARE 32A SP MCB,10KA 20A SP MCB,10KA 2KVA UPS FOR DDC 12
13 14
15 TILTING DEVICE (INTERMITTENT) 32A TP MCB,10KA 32A TP MCB,10KA + 40A 30mA 4P RCCB AHU-01B (STANDBY) 16
B 17 18 B
19 20
21 AHU-01B (STANDBY) 32A TP MCB,10KA + 40A 30mA 4P RCCB 32A TP MCB,10KA SPARE 22
23 24
25 16A SP MCB,10KA MOTORIZED GAS TIGHT DAMPERS 26
27 SPARE 32A TP MCB,10KA 16A SP MCB,10KA MOTORIZED VOLUME CONTROL DAMPERS 28
29 20A SP MCB,10KA SPARE 30

C C

QSPD
63A 3P Fuse

D D

SPD1

QM
63AT/100AF TP
MCCB, 25kA
E (TMD) E

F F

N R Y B
G Incoming Supply G

380/220V,3PH.,4W,60Hz.
Fed From : MDB-900-B917-E
Cable Size : 4CX50mm2 + 1CX35mm2 (G)

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-08


PR PR 08-02-23
H TITLE: DB-B917-E2 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 86 5of
OF 6
154
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A BILL OF QUANTITY A

ITEM TAG CAT. REF. No. DESCRIPTION RATING QTY MANUFACTURER


1 QM LV429552 / C10B3TM063C Circuit breaker, ComPact NSX100B, 25kA/415VAC, TMD trip unit 63A, 3 poles 3d 63A 1 Schneider Electric
2 Q1-Q3 A9F44116 Acti9 iC60N 1P 16A C Miniature Circuit breaker 16A 3 Schneider Electric
3 Q4-Q6 A9F44120 Acti9 iC60N 1P 20A C Miniature Circuit breaker 20A 3 Schneider Electric
B B
4 Q7 A9F44132 Acti9 iC60N 1P 32A C Miniature Circuit breaker 32A 1 Schneider Electric
5 Q8-Q15 A9D14832 / A9D11832 iC60H - earth leakage circuit breaker - 1P + N - C curve - 32 A - 30 mA - 240 V 32A 30mA 8 Schneider Electric
6 Q16-Q20 A9F44332 Acti9 iC60N 3P 32A C Miniature Circuit breaker 32A 5 Schneider Electric
7 F1,F2 A9R71440 Residual current circuit breaker (RCCB), Acti9 iID, 4P, 40A, AC type, 30mA 40A 30mA 2 Schneider Electric
8 QSPD TD00-D + 63NHG000B 63A 500 Volts gG/gL NH Fuse With 3-pole NH Bases - 1 Eaton
C
9 SPD1 HSA-320/3+1 MS Panel Mounted Surge Arrester - 50KA - 1 Hakel C

10 Encl NSYCRN106250P Spacial CRN plain door with mount.plate. H1000xW600xD250 IP66 IK10 RAL7035 IP66 1 Schneider Electric
11 - - Busbar Assembly - 30 Way SPN - 1 Reputed
12
13
D D
14

E E

F F

G G

ISSUE REVISION DATE PROJECT: NEOM GREEN HYDROGEN PROJECT - U900 DESIGNED BY: DRAWN BY: DATE REF. NO: NPB-2210009

01 For Approval 08-02-23 PANEL BOARD FACTORY DWG NO: NPB-DWG-2210009-08


PR PR 08-02-23
H TITLE: DB-B917-E2 (CELL ASSEMBLY BUILDING) H
02 Revised As Per Comments 05-03-23 P.O. BOX NO. 3402, AL KHOBAR, SCALE: N.T.S
CHECKED BY: APPROVED BY: DATE
03 Revised As Per Comments 16-07-23 SAUDI ARABIA CLIENT: NEOM GREEN HYDROGEN COMPANY SHEET NO.
TELEPHONE NO. +966-3-8350371 GH GH
CONTRACTOR: 08-02-23
NESMA UNITED IND. - BLD
FAX NO. +966-3-865 6126 PM210011-NUI900-ESE-00001_02 87 6of
OF 6
154
1 2 3 4 5 6 7 8
3

Product Catalogues

PM210011-NUI900-ESE-00001_02 88 of 154
Spacial Thalassa ClimaSys Actassi

Catalogue 2022
Universal Enclosures
More than 60 years protecting your equipment

se.com/enclosures

PM210011-NUI900-ESE-00001_02 89 of 154
Introduction

Steel Wall-Mounted Enclosures Spacial CRN - CRNG, Introduction

2
CRN Enclosure for indoor
non-clean industrial environment
This range can be configured according to your needs

4 differents services available:

CRN

Assemble Mounting CRNG


to order of standard
accessories

Painting Machining

Built to last Sealed


• Industrial welding process. • Door glazed with tempered glass, water-
• Epoxy-polyester painting. and dust-tight, IP66 and IK08 protection
• Molded polyurethane gasket.
These features ensure quality as well as water
and dust tightness for years. Front folded
gutter prevents the entry of water, oil or liquids,
ensuring IP66 protection

Safe Practical
For people: • 4 welded M8 x 15 back studs with 10-mm
• Two welded M6 x 15 earth studs welded to collar for direct installation of mounting
the back and one M6 x 15 stud on the door plate
For your installation:
• Water and dust tightness IP66
• Ruggedness IK10 to protect your
components from external impact
• Concealed hinges to prevent removal
of the door

Smart Convenient
• Welded door reinforcement profile allowing • Large embedded cable-entry plate with
the fixing of equipment in models from a neoprene gasket, flush with the back of
500 mm in height the enclosure
• Direct fixing or using the brackets fixed
from outside

See page 546 for details or consult


our web site www.se.com

PM210011-NUI900-ESE-00001_02 90 of 154
Characteristics

Spacial CRN - CRNG, Characteristics

2
CRN

Characteristics Spacial CRN Spacial CRNG


39 dimensions for this metal monobloc. • 17 dimensions with three-point locking system for
Back piece joined to the sides using a special this metal construction suite of enclosures
profile forming a protected sealed area. • All Spacial CRNG models include a
three-point locking system
Material Steel
Finish Structured finish, epoxy-polyester powder
Color RAL 7035 grey
Ingress protection rating • IP66 for one-door enclosures
• IP55 for two-door enclosures according to IEC 60529
Mechanical protection IK10 for plain door and IK08 for glazed door according to IEC 62262
rating
Standards IEC 62208
Certifications • UL (cULus), CUL
• Rating according UL50E :Types 4, and 13 for NSYCRN enclosures, and Types 4, and 13 for single doors NSYCRNG enclosures.
• Types 12 and 13 for double-door enclosures according UL50E
• RoHS compliance
Installation • Given their strength, metal enclosures are particularly well suited to indoor areas where they may experience impacts
Supply Body Body
• 4 holes for direct fixing • 4 holes for direct fixing
• Wall-fixing drill holes sealed with plastic plugs to ensure • Wall-fixing drill holes sealed with plastic plugs to ensure
the degree of protection (supplied as standard) water and dust tightness (supplied as standard)
• Wall-fixing bracket fixed from outside • Wall-fixing bracket fixed from outside, specific for large
(brackets to be ordered separately) dimensions (to be ordered separatly).
• Direct cable entry • Built-in cable-entry plate, flush with the back of the enclosure
• Built-in cable-entry plate, flush with the back of the enclosure (without foamed-in gasket to facilitate machining)
(without foamed-in gasket to facilitate machining) • Easy to equip with 4 welded back studs shouldered
• Insulated cable entries with knock-outs, available as an 10 mm (6 for widths of 1000 mm and 1200 mm)
accessory
• Easy to equip with 4 welded back studs shouldered 10 mm Door
• Three-point locking system for one and two doors.
Door Standard 5-mm double-bar lock
• 3-mm standard double-bar lock as standard. • Door-centering piece on two-door enclosures to ensure
(Wide choice of inserts as accessories) proper door alignment
• Foamed-in polyurethane gasket on the doors to guarantee • Foamed-in polyurethane gasket on the doors to guarantee
water and dust tightness water and dust tightness
• Easily reversible door, fixed with two or three invisible metal • Reinforcement on plain doors with welded perforated door
hinges allowing the door to open to 120° profiles for equipment fixing
• Reinforcement on plain doors with welded perforated door • Delivered with a reusable packaging and technical
profiles for equipment fixing from models NSYCRN54150 instructions
• Welded earth studs on door and body • Easily reversible door, fixed with two or three invisible
• Delivered with a reusable packaging metal hinges allowing the door to open to 120°
and technical instructions • Welded earth studs on door and body

PM210011-NUI900-ESE-00001_02 91 of 154
Spacial CRN, Selection guide

CRN Steel Wall-Mounted Enclosures Spacial CRN, Selection Guide

2 Enclosures Mounting plates


CRN

Dimensions
Height Width Depth Doors IP Weight with plain door, with plain door, with glazed door, Plain Silkscreened Micro ­ Telequick
(A) (B) (C) (kg) (1) with mounting without mounting with mounting perforated
(mm) (mm) (mm) plate plate plate
200 200 150 1 66 2.5 - NSYCRN22150 (2) - NSYMM22 - - -
200 300 150 1 66 3.9 - NSYCRN23150 (2) - NSYMM32 - NSYMF32 -

250 200 150 1 66 3.2 NSYCRN252150P NSYCRN252150 - NSYMM2520 - - -

300 250 150 1 66 4.2 NSYCRN325150P NSYCRN325150 NSYCRN325150T NSYMM3025 - - NSYMR3025


300 250 200 1 66 4.9 NSYCRN325200P NSYCRN325200 NSYCRN325200T NSYMM3025 - - NSYMR3025
300 300 150 1 66 5.0 NSYCRN33150P NSYCRN33150 NSYCRN33150T NSYMM33 - NSYMF33 NSYMR33
300 300 200 1 66 6.0 NSYCRN33200P NSYCRN33200 NSYCRN33200T NSYMM33 - NSYMF33 NSYMR33
300 400 200 1 66 6.4 - NSYCRN34200 NSYCRN34200T NSYMM43 NSYMS43 NSYMF43 NSYMR34
300 450 150 1 66 6.7 - NSYCRN345150 - NSYMM3045 - - -

400 300 150 1 66 6.0 NSYCRN43150P NSYCRN43150 NSYCRN43150T NSYMM43 NSYMS43 NSYMF43 NSYMR43
400 300 200 1 66 6.8 NSYCRN43200P NSYCRN43200 NSYCRN43200T NSYMM43 NSYMS43 NSYMF43 NSYMR43
400 400 200 1 66 8.0 NSYCRN44200P NSYCRN44200 NSYCRN44200T NSYMM44 NSYMS44 NSYMF44 NSYMR44
400 600 250 1 66 10.0 NSYCRN46250P NSYCRN46250 NSYCRN46250T NSYMM64 NSYMS64 NSYMF64 NSYMR46
400 600 300 1 66 11.2 - NSYCRN46300 NSYCRN46300T NSYMM64 NSYMS64 NSYMF64 NSYMR46

500 400 150 1 66 8.7 NSYCRN54150P NSYCRN54150 NSYCRN54150T NSYMM54 NSYMS54 NSYMF54 NSYMR54
500 400 200 1 66 9.8 NSYCRN54200P NSYCRN54200 NSYCRN54200T NSYMM54 NSYMS54 NSYMF54 NSYMR54
500 400 250 1 66 11.0 NSYCRN54250P NSYCRN54250 NSYCRN54250T NSYMM54 NSYMS54 NSYMF54 NSYMR54
500 500 250 1 66 12.8 NSYCRN55250P NSYCRN55250 NSYCRN55250T NSYMM55 NSYMS55 NSYMF55 NSYMR55

600 400 150 1 66 9.3 NSYCRN64150P NSYCRN64150 NSYCRN64150T NSYMM64 NSYMS64 NSYMF64 NSYMR64
600 400 200 1 66 10.8 NSYCRN64200P NSYCRN64200 NSYCRN64200T NSYMM64 NSYMS64 NSYMF64 NSYMR64
600 400 250 1 66 12.3 NSYCRN64250P NSYCRN64250 NSYCRN64250T NSYMM64 NSYMS64 NSYMF64 NSYMR64
600 500 150 1 66 11.3 NSYCRN65150P NSYCRN65150 NSYCRN65150T NSYMM65 - NSYMF65 NSYMR65
600 500 200 1 66 14.3 NSYCRN65200P NSYCRN65200 NSYCRN65200T NSYMM65 - NSYMF65 NSYMR65
600 500 250 1 66 16.2 NSYCRN65250P NSYCRN65250 NSYCRN65250T NSYMM65 - NSYMF65 NSYMR65
600 600 200 1 66 16.3 NSYCRN66200P NSYCRN66200 NSYCRN66200T NSYMM66 NSYMS66 NSYMF66 NSYMR66
600 600 250 1 66 18.2 NSYCRN66250P NSYCRN66250 NSYCRN66250T NSYMM66 NSYMS66 NSYMF66 NSYMR66
600 600 300 1 66 19.8 NSYCRN66300P NSYCRN66300 NSYCRN66300T NSYMM66 NSYMS66 NSYMF66 NSYMR66
600 800 300 1 66 26.0 - NSYCRN68300 NSYCRN68300T NSYMM86 NSYMS86 NSYMF86 NSYMR68

700 500 200 1 66 17.3 NSYCRN75200P NSYCRN75200 NSYCRN75200T NSYMM75 NSYMS75 NSYMF75 NSYMR75
700 500 250 1 66 19.3 NSYCRN75250P NSYCRN75250 NSYCRN75250T NSYMM75 NSYMS75 NSYMF75 NSYMR75

800 600 200 1 66 21.8 NSYCRN86200P NSYCRN86200 NSYCRN86200T NSYMM86 NSYMS86 NSYMF86 NSYMR86
800 600 250 1 66 24.8 NSYCRN86250P NSYCRN86250 NSYCRN86250T NSYMM86 NSYMS86 NSYMF86 NSYMR86
800 600 300 1 66 26.3 NSYCRN86300P NSYCRN86300 NSYCRN86300T NSYMM86 NSYMS86 NSYMF86 NSYMR86
800 800 200 1 66 29.5 NSYCRN88200P NSYCRN88200 NSYCRN88200T NSYMM88 - NSYMF88 NSYMR88
800 800 300 1 66 32.5 NSYCRN88300P NSYCRN88300 NSYCRN88300T NSYMM88 - NSYMF88 NSYMR88

1000 600 250 1 66 28.4 NSYCRN106250P NSYCRN106250 NSYCRN106250T NSYMM106 - NSYMF106 NSYMR106
1000 600 300 1 66 30.6 NSYCRN106300P NSYCRN106300 NSYCRN106300T NSYMM106 - NSYMF106 NSYMR106
1000 800 250 1 66 34.5 NSYCRN108250P NSYCRN108250 NSYCRN108250T NSYMM108 - NSYMF108 NSYMR108
1000 800 300 1 66 37.4 NSYCRN108300P NSYCRN108300 NSYCRN108300T NSYMM108 - NSYMF108 NSYMR108
(1)
Enclosure without mounting plate.


(2)
Two cable gland plates, one on the top, one on the bottom.


PM210011-NUI900-ESE-00001_02 92 of 154
Characteristics

Spacial S3D, Characteristics

2
S3D

S3D
Characteristics Spacial S3D
Three steel enclosure configurations are available:
• Enclosure with plain door.
• Enclosure with plain door delivered with a galvanized plain mounting plate, not installed.
• Enclosure with glazed door, 4 mm-thick Securit ® glass.
Personnel protection • Earth connection: Spacial S3D steel enclosures are equipped with M6 x 16 earth studs welded in the body
and the door for equipotential connection. Earth braid to be ordered separately (see page 323).
• Closing the enclosure: The enclosures are equipped from the height of 600 mm with three locking points with
linkage, with a single control point, helping prevent the enclosures from being left ajar. Locks and inserts, page 85.
Material Steel
Finish Structured finish, epoxy polyester powder
Color RAL 7035 grey
Ingress protection rating • IP66 for the single-door enclosures and IP55 for the double-door enclosures, according to IEC 60529.
• cUL : Types 4, 4x and 13 for single-door enclosure and 12 and 13
Mechanical protection IK10 for the plain-door enclosures and IK08 for the glazed-door enclosures according to IEC 62262
rating Types 4, 4X and 13 for single-door and Types 12 and 13 according UL508A and CAN C22.2 No 14
Standards Compliance with enclosure standards IEC 62208
The Spacial S3D wall-mounted enclosures are compliant with the RoHS directive
Certifications • UL (cULus), BVM, DNV, LR. For Atex see page 496
(see page 712) • Types 4, 4X and 13 for the single-door enclosures and Types 12, 13 for the double-door enclosures.
according to UL508A. Information on NEMA and UL classification on page 717 and 718
Nuclear decontamination: RAL 7035 grey and AFNOR A550 tests available on demand.
More information on painting properties on page 719 and 720
• Seismic behavior: 2.5G or 3G (details page 104)
Fixing 4 (or 6 studs for widths 1000 and 1200 (see page 102 and 103)) M8 x 25 collared studs
for installing mounting plates and step slides, leaving a space of 10 mm behind them.
Supply Body
• Single-piece body (cross-shaped structure). Gutter-shaped front profile with double fold.
Flat rear
• M6 x 16 earthing screws for equipotential connection between the door and the body of the enclosure
• Cable gland plate with marking for easy drilling and to enable the maximum access surface; Delivered with the enclosure.
This plate is flush with the body of the enclosure (detail and other options on page 89)
• Direct wall-mounted (4 Ø 10 holes for the sealing plugs for the the IP) or with the help of fixing
lugs installed from the outside (to be ordered separately, see page 79)
Door
• Wall-mounted enclosure supplied with 3-mm double-bar lock as standard
• Polyurethane door gasket
• M6 x 16 earthing screws for equipotential connection between the door and the body of the enclosure
• Easily removable and reversible, with 20 mm return with double thickness granting excellent rigidity,
opening to 120°, equipped with 2 or 3 invisible hinges (from the height of 800 mm)
• Door opening to 180° with optional hinges (page 88)
• For heights from 600 mm, three locking points with linkage, with a single control point.
Simple reversal of linkage. Maximum load: 50 kg/m²
• A handle is delivered which provides 2 functions:
- Operating key
- Tool for loosening the stud protection caps.


This handle can be solidly attached to the locking system by means of a captive element
• Perforated rails on the door, with drill holes with a diameter of 4.2 mm in steps of 25 mm:
- 2 vertical rails from the height of 400 mm
- 2 vertical rails and 2 horizontal rails from the width of 800 mm

PM210011-NUI900-ESE-00001_02 93 of 154
Selection guide

S3D Steel Wall-Mounted Enclosures Spacial S3D, Selection Guide

2 • Ingress protection rating: IP66 for the single-door enclosures and IP55 for • Rating according UL50E: Types 4, 4X and 13 for single-door enclosures
S3D the double-door enclosures, according to IEC 60529. and Types 12 and 13 for double-door enclosures.

Door Mounting plates

Dimensions (1)
Height Width Depth Doors IP Weight Plain without Plain with Glazed without Plain Silkscreened (3) Microperforated
­

(mm) (mm) (mm) (kg) (2) mounting plate mounting plate mounting plate

300 200 150 1 66 3.02 NSYS3D3215 NSYS3D3215P - NSYMM32 - NSYMF32


300 250 150 1 66 3.48 NSYS3D32515 NSYS3D32515P NSYS3D32515T NSYMM3025 - -
300 300 150 1 66 3.90 NSYS3D3315 NSYS3D3315P NSYS3D3315T NSYMM33 - NSYMF33
300 300 200 1 66 4.50 NSYS3D3320 NSYS3D3320P NSYS3D3320T NSYMM33 - NSYMF33
300 400 150 1 66 4.82 NSYS3D3415 NSYS3D3415P NSYS3D3415T NSYMM43 NSYMS43 NSYMF43
300 400 200 1 66 5.60 NSYS3D3420 NSYS3D3420P NSYS3D3420T NSYMM43 NSYMS43 NSYMF43

400 300 150 1 66 4.90 NSYS3D4315 NSYS3D4315P NSYS3D4315T NSYMM43 NSYMS43 NSYMF43
400 300 200 1 66 5.00 NSYS3D4320 NSYS3D4320P NSYS3D4320T NSYMM43 NSYMS43 NSYMF43
400 400 200 1 66 6.50 NSYS3D4420 NSYS3D4420P NSYS3D4420T NSYMM44 NSYMS44 NSYMF44
400 600 200 1 66 10.50 NSYS3D4620 NSYS3D4620P NSYS3D4620T NSYMM64 NSYMS64 NSYMF64
400 600 250 1 66 12.00 NSYS3D4625 NSYS3D4625P NSYS3D4625T NSYMM64 NSYMS64 NSYMF64

500 300 200 1 66 7.50 NSYS3D5320 NSYS3D5320P NSYS3D5320T NSYMM53 NSYMS53 NSYMF53
500 400 200 1 66 9.30 NSYS3D5420 NSYS3D5420P NSYS3D5420T NSYMM54 NSYMS54 NSYMF54
500 400 250 1 66 10.20 NSYS3D5425 NSYS3D5425P NSYS3D5425T NSYMM54 NSYMS54 NSYMF54
500 500 200 1 66 11.18 NSYS3D5520 NSYS3D5520P NSYS3D5520T NSYMM55 NSYMS55 NSYMF55
500 500 250 1 66 12.06 NSYS3D5525 NSYS3D5525P NSYS3D5525T NSYMM55 NSYMS55 NSYMF55

600 400 200 1 66 11.00 NSYS3D6420 NSYS3D6420P NSYS3D6420T NSYMM64 NSYMS64 NSYMF64
600 400 250 1 66 12.00 NSYS3D6425 NSYS3D6425P NSYS3D6425T NSYMM64 NSYMS64 NSYMF64
600 500 250 1 66 16.20 NSYS3D6525 NSYS3D6525P NSYS3D6525T NSYMM65 - NSYMF65
600 600 200 1 66 14.00 NSYS3D6620 NSYS3D6620P NSYS3D6620T NSYMM66 NSYMS66 NSYMF66
600 600 250 1 66 15.00 NSYS3D6625 NSYS3D6625P NSYS3D6625T NSYMM66 NSYMS66 NSYMF66
600 600 300 1 66 17.00 NSYS3D6630 NSYS3D6630P NSYS3D6630T NSYMM66 NSYMS66 NSYMF66
600 600 400 1 66 19.00 NSYS3D6640 NSYS3D6640P NSYS3D6640T NSYMM66 NSYMS66 NSYMF66
600 800 300 1 66 25.50 NSYS3D6830 NSYS3D6830P NSYS3D6830T NSYMM86 NSYMS86 NSYMF86

700 500 250 1 66 15.00 NSYS3D7525 NSYS3D7525P NSYS3D7525T NSYMM75 NSYMS75 NSYMF75

800 600 200 1 66 21.00 NSYS3D8620 NSYS3D8620P NSYS3D8620T NSYMM86 NSYMS86 NSYMF86
800 600 250 1 66 23.00 NSYS3D8625 NSYS3D8625P NSYS3D8625T NSYMM86 NSYMS86 NSYMF86
800 600 300 1 66 25.00 NSYS3D8630 NSYS3D8630P NSYS3D8630T NSYMM86 NSYMS86 NSYMF86
800 600 400 1 66 29.00 NSYS3D8640 NSYS3D8640P NSYS3D8640T NSYMM86 NSYMS86 NSYMF86
800 800 250 1 66 30.00 NSYS3D8825 NSYS3D8825P NSYS3D8825T NSYMM88 - NSYMF88
800 800 300 1 66 32.00 NSYS3D8830 NSYS3D8830P NSYS3D8830T NSYMM88 - NSYMF88
800 1000 300 1 66 38.00 NSYS3D81030 NSYS3D81030P - NSYMM108 - NSYMF108
800 1000 300 2 55 43.50 NSYS3D81030D NSYS3D81030DP - NSYMM108 - NSYMF108
800 1200 300 2 55 46.00 NSYS3D81230D NSYS3D81230DP - NSYMM128 - NSYMF128

1000 600 250 1 66 28.00 NSYS3D10625 NSYS3D10625P NSYS3D10625T NSYMM106 - NSYMF106


1000 600 300 1 66 30.60 NSYS3D10630 NSYS3D10630P NSYS3D10630T NSYMM106 - NSYMF106
1000 600 400 1 66 33.00 NSYS3D10640 NSYS3D10640P NSYS3D10640T NSYMM106 - NSYMF106
1000 800 250 1 66 35.00 NSYS3D10825 NSYS3D10825P NSYS3D10825T NSYMM108 - NSYMF108
1000 800 300 1 66 38.00 NSYS3D10830 NSYS3D10830P NSYS3D10830T NSYMM108 - NSYMF108
1000 800 400 1 66 42.00 NSYS3D10840 NSYS3D10840P NSYS3D10840T NSYMM108 - NSYMF108
1000 1000 300 1 66 46.00 NSYS3D101030 NSYS3D101030P NSYS3D101030T NSYMM1010 - NSYMF1010
1000 1000 300 2 55 46.00 NSYS3D101030D NSYS3D101030DP NSYS3D101030DT NSYMM1010 - NSYMF1010
1000 1200 300 2 55 53.00 NSYS3D101230D NSYS3D101230DP - NSYMM1210 - NSYMF1210
1000 1200 400 2 55 60.00 NSYS3D101240D NSYS3D101240DP - NSYMM1210 - NSYMF1210

1200 600 300 1 66 37.00 NSYS3D12630 NSYS3D12630P NSYS3D12630T NSYMM126 - NSYMF126


1200 600 400 1 66 42.00 NSYS3D12640 NSYS3D12640P NSYS3D12640T NSYMM126 - NSYMF126
1200 800 300 1 66 45.00 NSYS3D12830 NSYS3D12830P NSYS3D12830T NSYMM128 - NSYMF128
1200 800 400 1 66 49.00 NSYS3D12840 NSYS3D12840P NSYS3D12840T NSYMM128 - NSYMF128
1200 1000 300 1 66 53.00 NSYS3D121030 NSYS3D121030P NSYS3D121030T NSYMM1210 - NSYMF1210
1200 1000 300 2 55 54.00 NSYS3D121030D NSYS3D121030DP NSYS3D121030DT NSYMM1210 - NSYMF1210
1200 1000 400 2 55 61.00 NSYS3D121040D NSYS3D121040DP - NSYMM1210 - NSYMF1210
1200 1200 300 2 55 64.00 NSYS3D121230D NSYS3D121230DP - NSYMM1212 - 2x NSYMF126 (4)
1200 1200 400 2 55 90.00 NSYS3D121240D NSYS3D121240DP - NSYMM1212 - 2x NSYMF126 (4)

1400 1000 300 2 55 80.00 NSYS3D141030D NSYS3D141030DP - NSYMM1410 - -


(1)
For other dimensions, see our application offer, page 16. (5)
Order nuts ref. NSYAMCSF. Steel siderail ref. NSYMDVR12.
(2)
Enclosure without mounting plate. (6)
When width ≥ 1000 ref. NSYEMR is mandatory (see on page 102).
(3)
In inverted use, the marking is inverted. (7)
Possible assembling to ref. NSYDLM84 or NSYDLM112.
(4)
Order NSYCRNGSDR for double mounting of the mounting plates

PM210011-NUI900-ESE-00001_02 94 of 154
Spacial SM, Characteristics

Steel Floor-Standing Enclosures Spacial SF, Characteristics

SM
Characteristics Compact enclosures Spacial SM
• Compact body with a front rigid frame with welded corners and rear panel supports
installed in depth to adjust and fix the equipment with a pitch of 25 mm

Basic composition • The double doors are overlapping, with system for fixing the left door
• Door reversible, 120° opening
• Welded rear panel
• System with 4 locking points with handle and 5-mm double-bar insert
• Cable gland plate 1 entry
• Mounting plate support brackets

Versions / Configurations • Compact enclosure with plain door and mounting plate
• Compact enclosure with plain door and without mounting plate
• Compact enclosure with transparent Securit ® glass door and without mounting plate

Protection of personnel Earthing accessories needed to ensure the grounding continuity, page 323
Material Steel
Finish Structured finish, epoxy polyester powder
Color RAL 7035 grey
Ingress protection rating IP55 according to IEC 60529
Mechanical protection rating IK10 for plain door and IK08 for transparent door according to IEC 62262
Standards Compliance with enclosure standard IEC 62208 and the RoHS and REACH directive
Certifications BVM, UL (cULus), Rating according UL50E : single-door enclosures : Types 1, 2, 3R, 5 and 13. double-door enclosures Types 1, 12
Installation * Compliant with IEC 62208 regarding type tests specified in §9.12 (resistance to UV radiation) and §9.13 (resistance to corrosion)
Canopy needed to avoid water stagnation on the upper part of the enclosure, page 135
Maximum load 500 kg
Options • Plinths, heights 100 mm and 200 mm, page 126
• Lifting eyebolts, page 134
• Internal door, page 139
• Door accessories, page 141
• Other locking options, page 144
• Mounting plates and Telequick system, page 265

PM210011-NUI900-ESE-00001_02 95 of 154
Spacial SF, Characteristics

SF SF kit

Suitable enclosures Spacial SF - supplied assembled Suitable enclosures Spacial SF - supplied as kit
• Structure made up of vertical uprights joined with top and bottom frames
• Panels and doors built into the structure
• Formed from a single section and perforated structure with a pitch of 25 mm
• Front door with a reinforcement frame (horizontal rails height-adjustable) • Front door with a reinforcement frame (horizontal rails height-adjustable)
• The double doors are overlapping, with system for fixing the left door • The double doors are overlapping, with system for fixing the left door
• Door reversible, 120° opening • Door reversible, 120° opening
• Rear panel screwed on with captive screws • Rear panel to be screwed on with captive screws
• Removable roof • Removable roof delivered with top frame
• System with 4 locking points with handle and 5-mm double-bar insert • System with 4 locking points with handle and 5-mm double-bar insert
• Mounting plate support brackets (for widths from 600 mm) • Mounting plate support brackets delivered with top and bottom frames kit
• Mounting plate sliding rails (for widths from 600 mm) (for widths from 600 mm)
• 2 quick-fixing cross-rails • Mounting plate sliding rails delivered with top and bottom frames kit
(for heights from 1800 mm, widths from 600 mm and depths from 500 mm) (for widths from 600 mm)
• 2 quick-fixing cross-rails delivered with top and bottom frames kit
(for frames with widths from 600 mm and depths from 500 mm)
• Modular enclosure with plain door and mounting plate • Uprights kit
• Modular enclosure with plain door and without mounting plate • Top and bottom frames kit
• Modular enclosure with transparent Securit ® glass door and • Rear panel kit
without mounting plate • Door kit (plain or transparent)
Earthing accessories needed to ensure the grounding continuity
Steel
Structured finish, epoxy polyester powder
RAL 7035 grey
IP55 according to IEC 60529 (with side panels and cable entry plates)
IK10 for plain door and IK08 for transparent door according to IEC 62262
Compliance with enclosure standard IEC 62208 and the RoHS and REACH directive
BV, BVM, DNV, UL (cULus) Rating according UL50E : Types 1, 3R, 12

1000 kg
• Side panels options, page 122 • Side panels options, page 122
• Enclosure suites options, page 123 • Enclosure suites options, page 123
• Plinths, heights 100 mm and 200 mm, page 124 • Plinths, heights 100 mm and 200 mm, page 124
• Cable gland plates, page 130 • Cable gland plates, page 130
• Lifting systems, page 134 • Lifting systems, page 134
• Roof options, page 136 • Roof options, page 136
• Door accessories, page 141 • Other locking options, page 144
• Other locking options, page 144 • Mounting plates and Telequick system, page 265
• Mounting plates and Telequick system, page 265

PM210011-NUI900-ESE-00001_02 96 of 154
Selection guide

SM Steel Floor-Standing Enclosures Spacial SM, Selection Guide

Enclosures Plinth (H 100 mm)

3
Dimensions

Height Width Depth Doors Plain door, Plain door, Transparent door, Front kit (corners Side panels,
(mm) (mm) (mm) without mounting plate with mounting plate without mounting plate + front panels) 2 u.
1200 800 300 1 NSYSM12830 NSYSM12830P - NSYSPF8100 NSYSPS3100
1200 1000 300 2 NSYSM1210302D NSYSM1210302DP - NSYSPF10100 NSYSPS3100
1200 1200 400 2 NSYSM1212402D NSYSM1212402DP - NSYSPF12100 NSYSPS4100

1400 600 300 1 NSYSM14630 NSYSM14630P - NSYSPF6100 NSYSPS3100


1400 600 400 1 NSYSM14640 NSYSM14640P - NSYSPF6100 NSYSPS4100
1400 800 300 1 NSYSM14830 NSYSM14830P - NSYSPF8100 NSYSPS3100
1400 800 400 1 NSYSM14840 NSYSM14840P NSYSM14840T NSYSPF8100 NSYSPS4100
1400 1000 400 2 NSYSM1410402D NSYSM1410402DP - NSYSPF10100 NSYSPS4100
1400 1200 400 2 NSYSM1412402D NSYSM1412402DP - NSYSPF12100 NSYSPS4100

1600 600 300 1 NSYSM16630 NSYSM16630P - NSYSPF6100 NSYSPS3100


1600 600 400 1 NSYSM16640 NSYSM16640P NSYSM16640T NSYSPF6100 NSYSPS4100
1600 800 300 1 NSYSM16830 NSYSM16830P NSYSM16830T NSYSPF8100 NSYSPS3100
1600 800 400 1 NSYSM16840 NSYSM16840P NSYSM16840T NSYSPF8100 NSYSPS4100
1600 1000 300 2 NSYSM1610302D NSYSM1610302DP - NSYSPF10100 NSYSPS3100
1600 1000 400 2 NSYSM1610402D NSYSM1610402DP - NSYSPF10100 NSYSPS4100
1600 1200 300 2 NSYSM1612302D NSYSM1612302DP - NSYSPF12100 NSYSPS3100
1600 1200 400 2 NSYSM1612402D NSYSM1612402DP - NSYSPF12100 NSYSPS4100

1800 600 300 1 NSYSM18630 NSYSM18630P - NSYSPF6100 NSYSPS3100


1800 600 400 1 NSYSM18640 NSYSM18640P NSYSM18640T NSYSPF6100 NSYSPS4100
1800 600 500 1 NSYSM18650 NSYSM18650P - NSYSPF6100 NSYSPS5100
1800 800 300 1 NSYSM18830 NSYSM18830P NSYSM18830T NSYSPF8100 NSYSPS3100
1800 800 400 1 NSYSM18840 NSYSM18840P NSYSM18840T NSYSPF8100 NSYSPS4100
1800 800 500 1 NSYSM18850 NSYSM18850P NSYSM18850T NSYSPF8100 NSYSPS5100
1800 800 600 1 NSYSM18860 NSYSM18860P - NSYSPF8100 NSYSPS6100
1800 1000 400 1 NSYSM181040 NSYSM181040P - NSYSPF10100 NSYSPS4100
1800 1000 400 2 NSYSM1810402D NSYSM1810402DP - NSYSPF10100 NSYSPS4100
1800 1000 500 2 NSYSM1810502D NSYSM1810502DP - NSYSPF10100 NSYSPS5100
1800 1200 400 2 NSYSM1812402D NSYSM1812402DP - NSYSPF12100 NSYSPS4100
1800 1200 500 2 NSYSM1812502D NSYSM1812502DP - NSYSPF12100 NSYSPS5100
1800 1600 400 2 NSYSM1816402D NSYSM1816402DP - NSYSPF16100 NSYSPS4100
1800 1600 500 2 NSYSM1816502D NSYSM1816502DP - NSYSPF16100 NSYSPS5100

2000 600 300 1 NSYSM20630 NSYSM20630P - NSYSPF6100 NSYSPS3100


2000 600 400 1 NSYSM20640 NSYSM20640P NSYSM20640T NSYSPF6100 NSYSPS4100
2000 600 500 1 NSYSM20650 NSYSM20650P - NSYSPF6100 NSYSPS5100
2000 800 300 1 NSYSM20830 NSYSM20830P NSYSM20830T NSYSPF8100 NSYSPS3100
2000 800 400 1 NSYSM20840 NSYSM20840P NSYSM20840T NSYSPF8100 NSYSPS4100
2000 800 500 1 NSYSM20850 NSYSM20850P NSYSM20850T NSYSPF8100 NSYSPS5100
2000 800 600 1 NSYSM20860 NSYSM20860P NSYSM20860T NSYSPF8100 NSYSPS6100
2000 1000 400 2 NSYSM2010402D NSYSM2010402DP - NSYSPF10100 NSYSPS4100
2000 1000 500 2 NSYSM2010502D NSYSM2010502DP - NSYSPF10100 NSYSPS5100
2000 1200 400 2 NSYSM2012402D NSYSM2012402DP - NSYSPF12100 NSYSPS4100
2000 1200 500 2 NSYSM2012502D NSYSM2012502DP - NSYSPF12100 NSYSPS5100
2000 1200 600 2 NSYSM2012602D NSYSM2012602DP - NSYSPF12100 NSYSPS6100
2000 1600 400 2 NSYSM2016402D NSYSM2016402DP - NSYSPF16100 NSYSPS4100
2000 1600 500 2 NSYSM2016502D NSYSM2016502DP - NSYSPF16100 NSYSPS5100
2000 1600 600 2 NSYSM2016602D NSYSM2016602DP - NSYSPF16100 NSYSPS6100

PM210011-NUI900-ESE-00001_02 97 of 154
Spacial SF und Spacial SM

SF Steel Floor-Standing Enclosures Spacial SF, Selection Guide

Enclosures Side panels Cable entry plates

3 Dimensions
(A) (B) (C)
Height Width Depth Doors Plain door, without Plain door, with Transparent door, Plain Plain 1 entry 2 entries
(mm) (mm) (mm) mounting plate mounting plate without mounting plate
1200 600 400 1 NSYSF12640 NSYSF12640P - NSY2SP124 NSYEC64 NSYEC641 -
1200 600 600 1 NSYSF12660 NSYSF12660P - NSY2SP126 NSYEC66 NSYEC661 NSYEC662
1200 800 400 1 NSYSF12840 NSYSF12840P - NSY2SP124 NSYEC84 NSYEC841 -
1200 800 600 1 NSYSF12860 NSYSF12860P - NSY2SP126 NSYEC86 NSYEC861 NSYEC862

1400 600 400 1 NSYSF14640 NSYSF14640P - NSY2SP144 NSYEC64 NSYEC641 -


1400 800 400 1 NSYSF14840 NSYSF14840P - NSY2SP144 NSYEC84 NSYEC841 -

1600 600 600 1 NSYSF16660 NSYSF16660P - NSY2SP166 NSYEC66 NSYEC661 NSYEC662


1600 600 800 1 NSYSF16680 NSYSF16680P - NSY2SP168 NSYEC68 NSYEC681 NSYEC682
1600 800 600 1 NSYSF16860 NSYSF16860P - NSY2SP166 NSYEC86 NSYEC861 NSYEC862
1600 800 800 1 NSYSF16880 NSYSF16880P - NSY2SP168 NSYEC88 NSYEC881 NSYEC882

1800 400 400 1 NSYSF18440 - - NSY2SP184 NSYEC44 NSYEC441 -


1800 400 500 1 NSYSF18450 - - NSY2SP185 NSYEC45 NSYEC451 -
1800 400 600 1 NSYSF18460 - - NSY2SP186 - NSYEC461 NSYEC462
1800 600 400 1 NSYSF18640 NSYSF18640P NSYSF18640T NSY2SP184 NSYEC64 NSYEC641 -
1800 600 500 1 NSYSF18650 NSYSF18650P NSYSF18650T NSY2SP185 NSYEC65 NSYEC651 -
1800 600 600 1 NSYSF18660 NSYSF18660P - NSY2SP186 NSYEC66 NSYEC661 NSYEC662
1800 600 800 1 - - NSYSF18680T NSY2SP188 NSYEC68 NSYEC681 NSYEC682
1800 800 400 1 NSYSF18840 NSYSF18840P NSYSF18840T NSY2SP184 NSYEC84 NSYEC841 -
1800 800 500 1 NSYSF18850 NSYSF18850P NSYSF18850T NSY2SP185 NSYEC85 NSYEC851 -
1800 800 600 1 NSYSF18860 NSYSF18860P NSYSF18860T NSY2SP186 NSYEC86 NSYEC861 NSYEC862
1800 800 600 2 NSYSF188602D NSYSF188602DP - NSY2SP186 NSYEC86 NSYEC861 NSYEC862
1800 1000 400 1 NSYSF181040 NSYSF181040P - NSY2SP184 NSYEC104 NSYEC1041 -
1800 1000 400 2 NSYSF1810402D NSYSF1810402DP - NSY2SP184 NSYEC104 NSYEC1041 -
1800 1000 500 1 NSYSF181050 NSYSF181050P - NSY2SP185 NSYEC105 NSYEC1051 -
1800 1000 600 1 NSYSF181060 NSYSF181060P - NSY2SP186 NSYEC106 NSYEC1061 NSYEC1062
1800 1000 600 2 NSYSF1810602D NSYSF1810602DP - NSY2SP186 NSYEC106 NSYEC1061 NSYEC1062
1800 1200 400 2 NSYSF1812402D NSYSF1812402DP - NSY2SP184 NSYEC124 NSYEC1241 -
1800 1200 500 2 NSYSF1812502D NSYSF1812502DP - NSY2SP185 NSYEC125 NSYEC1251 -
1800 1200 600 2 NSYSF1812602D NSYSF1812602DP - NSY2SP186 NSYEC126 NSYEC1261 NSYEC1262

2000 300 500 1 NSYSF20350 - - NSY2SP205 NSYEC35 NSYEC351 -


2000 300 600 1 NSYSF20360 - - NSY2SP206 NSYEC36 NSYEC361 -
2000 300 800 1 NSYSF20380 - - NSY2SP208 - NSYEC381 -
2000 400 400 1 NSYSF20440 - - NSY2SP204 NSYEC44 NSYEC441 -
2000 400 500 1 NSYSF20450 - - NSY2SP205 NSYEC45 NSYEC451 -
2000 400 600 1 NSYSF20460 - - NSY2SP206 NSYEC64 NSYEC461 NSYEC462
2000 400 800 1 NSYSF20480 - - NSY2SP208 NSYEC84 NSYEC481 NSYEC482
2000 600 400 1 NSYSF20640 NSYSF20640P NSYSF20640T NSY2SP204 NSYEC64 NSYEC641 -
2000 600 500 1 NSYSF20650 NSYSF20650P NSYSF20650T NSY2SP205 NSYEC65 NSYEC651 -
2000 600 600 1 NSYSF20660 NSYSF20660P - NSY2SP206 NSYEC66 NSYEC661 NSYEC662
2000 600 800 1 NSYSF20680 NSYSF20680P - NSY2SP208 NSYEC68 NSYEC681 NSYEC682
2000 800 400 1 NSYSF20840 NSYSF20840P NSYSF20840T NSY2SP204 NSYEC84 NSYEC841 -
2000 800 500 1 NSYSF20850 NSYSF20850P NSYSF20850T NSY2SP205 NSYEC85 NSYEC851 -
2000 800 600 1 NSYSF20860 NSYSF20860P NSYSF20860T NSY2SP206 NSYEC86 NSYEC861 NSYEC862
2000 800 600 2 NSYSF208602D NSYSF208602DP - NSY2SP206 NSYEC86 NSYEC861 NSYEC862
2000 800 800 1 NSYSF20880 NSYSF20880P NSYSF20880T NSY2SP208 NSYEC88 NSYEC881 NSYEC882
2000 1000 400 1 NSYSF201040 NSYSF201040P NSYSF201040T NSY2SP204 NSYEC104 NSYEC1041 -
2000 1000 400 2 NSYSF2010402D NSYSF2010402DP - NSY2SP204 NSYEC104 NSYEC1041 -
2000 1000 500 1 NSYSF201050 NSYSF201050P NSYSF201050T NSY2SP205 NSYEC105 NSYEC1051 -
2000 1000 500 2 NSYSF2010502D NSYSF2010502DP - NSY2SP205 NSYEC105 NSYEC1051 -
2000 1000 600 1 NSYSF201060 NSYSF201060P NSYSF201060T NSY2SP206 NSYEC106 NSYEC1061 NSYEC1062
2000 1000 600 2 NSYSF2010602D NSYSF2010602DP - NSY2SP206 NSYEC106 NSYEC1061 NSYEC1062
2000 1000 800 1 NSYSF201080 NSYSF201080P - NSY2SP208 NSYEC108 NSYEC1081 NSYEC1082
2000 1200 400 2 NSYSF2012402D NSYSF2012402DP - NSY2SP204 NSYEC124 NSYEC1241 -
2000 1200 500 2 NSYSF2012502D NSYSF2012502DP - NSY2SP205 NSYEC125 NSYEC1251 -
2000 1200 600 2 NSYSF2012602D NSYSF2012602DP - NSY2SP206 NSYEC126 NSYEC1261 NSYEC1262
2000 1200 800 2 NSYSF2012802D NSYSF2012802DP - NSY2SP208 NSYEC128 NSYEC1281 NSYEC1282
2000 1600 400 2 NSYSF2016402D NSYSF2016402DP - NSY2SP204 NSYEC164 NSYEC1641 -
2000 1600 500 2 NSYSF2016502D NSYSF2016502DP - NSY2SP205 NSYEC165 NSYEC1651 -
2000 1600 600 2 NSYSF2016602D NSYSF2016602DP - NSY2SP206 NSYEC166 NSYEC1661 NSYEC1662

2200 400 600 1 NSYSF22460 - - NSY2SP226 - NSYEC461 -


2200 600 600 1 NSYSF22660 NSYSF22660P - NSY2SP226 NSYEC66 NSYEC661 NSYEC662
2200 600 800 1 NSYSF22680 NSYSF22680P - NSY2SP228 NSYEC68 NSYEC681 NSYEC682
2200 800 600 1 NSYSF22860 NSYSF22860P - NSY2SP226 NSYEC86 NSYEC861 NSYEC862
2200 800 800 1 NSYSF22880 NSYSF22880P NSYSF22880T NSY2SP228 NSYEC88 NSYEC881 NSYEC882
2200 1000 600 1 NSYSF221060 NSYSF221060P - NSY2SP226 NSYEC106 NSYEC1061 NSYEC1062
2200 1200 600 2 NSYSF2212602D NSYSF2212602DP - NSY2SP226 NSYEC126 NSYEC1261 NSYEC1262
2200 1200 800 2 NSYSF2212802D NSYSF2212802DP - NSY2SP228 NSYEC128 NSYEC1281 NSYEC1282

PM210011-NUI900-ESE-00001_02 98 of 154
Functions Introduction
and characteristics General characteristics of the
Compact NSX range

Compliance with standards


DB112018

Compact NSX circuit breakers and auxiliaries comply with the following:
1 b international recommendations:
2 v IEC 60947-1: general rules
v IEC 60947-2: circuit breakers
NSX250 H 3 v IEC 60947-3: switch-disconnectors
v IEC 60947-4: contactors and motor starters
4 v IEC 60947-5.1 and following: control circuit devices and switching elements;
100 100
automatic control components
70 70 5
65 65 b European (EN 60947-1 and EN 60947-2) and corresponding national standards:
50 50 6 v France NF
35 35
10 10 v Germany VDE
v United Kingdom BS
v Australia AS
7 v Italy CEI
b the specifications of the marine classification companies (Veritas, Lloyd's Register
8 of Shipping, Det Norske Veritas, etc.), standard NF C 79-130 and recommendations
9 issued by the CNOMO organisation for the protection of machine tools.
100
65 10 For U.S. UL, Canadian CSA, Mexican NOM and Japanese JIS standards, please
35
consult us.

Standardised characteristics indicated on the rating plate: Pollution degree


1 Type of device: frame size and breaking capacity class Compact NSX circuit breakers are certified for operation in pollution-degree III
2 Ui: rated insulation voltage. environments as defined by IEC standards 60947-1 and 60664-1 (industrial
3 Uimp: rated impulse withstand voltage. environments).
4 Ics: service breaking capacity.
5 Icu: ultimate breaking capacity for various values of the
rated operational voltage Ue Climatic withstand
6 Ue: operational voltage. Compact NSX circuit breakers have successfully passed the tests defined by the
7 Colour label indicating the breaking capacity class.
following standards for extreme atmospheric conditions:
8 Circuit breaker-disconnector symbol.
9 Reference standard. b IEC 60068-2-1: dry cold (-55 °C)
10 Main standards with which the device complies. b IEC 60068-2-2: dry heat (+85 °C)
Note: when the circuit breaker is equipped with an extended b IEC 60068-2-30: damp heat (95 % relative humidity at 55 °C)
rotary handle, the door must be opened to access the rating b IEC 60068-2-52 severity level 2: salt mist.
plate.

Environment
Compact NSX respects the European environment directive EC/2002/95 concerning
the restriction of hazardous substances (RoHS).
Product environment profiles (PEP) have been prepared, describing the
environmental impact of every product throughout its life cycle, from production to
the end of its service life.
All Compact NSX production sites have set up an environmental management
system certified ISO 14001.
Each factory monitors the impact of its production processes. Every effort is made to
prevent pollution and to reduce consumption of natural resources.

Ambient temperature
b Compact NSX circuit breakers may be used between -25 °C and +70 °C. For
temperatures higher than 40°C (65°C for circuit breakers used to protect motor
feeders), devices must be derated (pages B-8 and B-9).
b Circuit breakers should be put into service under normal ambient, operating-
temperature conditions. Exceptionally, the circuit breaker may be put into service
when the ambient temperature is between -35 °C and -25 °C.
b The permissible storage-temperature range for Compact NSX circuit breakers in
the original packing is -50 °C (1) and +85 °C.

(1) -40 °C for Micrologic control units with an LCD screen.

PM210011-NUI900-ESE-00001_02 99 of 154

559EN.indb 4 27/05/2009 10:10:03


Electromagnetic compatibility
Compact NSX devices are protected against:
b overvoltages caused by circuit switching (e.g. lighting circuits)
b overvoltages caused by atmospheric disturbances
b devices emitting radio waves such as mobile telephones, radios, walkie-talkies,
radar, etc.
b electrostatic discharges produced by users.
Immunity levels for Compact NSX comply with the standards below.
b IEC/EN 60947-2: Low-voltage switchgear and controlgear, part 2: Circuit
breakers:
v Annex F: Immunity tests for circuit breakers with electronic protection
v Annex B: Immunity tests for residual current protection
b IEC/EN 61000-4-2: Electrostatic-discharge immunity tests
b IEC/EN 61000-4-3: Radiated, radio-frequency, electromagnetic-field immunity
tests
b IEC/EN 61000-4-4: Electrical fast transient/burst immunity tests
b IEC/EN 61000-4-5: Surge immunity tests
b IEC/EN 61000-4-6: Immunity tests for conducted disturbances induced by radio-
frequency fields
b CISPR 11: Limits and methods of measurement of electromagnetic disturbance
characteristics of industrial, scientific and medical (ISM) radio-frequency equipment.

Discrimination
Compact NSX reinforces the discrimination capabilities of the Compact NS range by
applying the rapid calculation capacity of the Micrologic trip units.
Total discrimination is now possible between NSX100 and modular Multi 9 circuit
breakers rated y 63 A (see page A-8).

Suitable for isolation with positive contact


PB103578-53

indication
All Compact NSX circuit breakers are suitable for isolation as defined in IEC
standard 60947-2:
b The isolation position corresponds to the O (OFF) position.
b The operating handle cannot indicate the OFF position unless the contacts are
effectively open.
b Padlocks may not be installed unless the contacts are open.
Installation of a rotary handle or a motor mechanism does not alter the reliability of
the position-indication system.
The isolation function is certified by tests guaranteeing:
b the mechanical reliability of the position-indication system
b the absence of leakage currents
b overvoltage withstand capacity between upstream and downstream connections.
The tripped position does not insure isolation with positive contact indication.
Only the OFF position guarantees isolation.
DB112093

Installation in class II switchboards


All Compact NSX circuit breakers are class II front face devices. They may be
installed through the door of class II switchboards (as per IEC standards 61140 and
60664-1) without downgrading switchboard insulation. Installation requires no
special operations, even when the circuit breaker is equipped with a rotary handle or
a motor mechanism.

Degree of protection
The following indications are in accordance with standards IEC 60529 (IP degree of
protection) and IEC 62262 (IK protection against external mechanical impacts).
Bare circuit breaker with terminal shields
b With toggle: IP40, IK07.
b With standard direct rotary handle / VDE: IP40 IK07
Circuit breaker installed in a switchboard
b With toggle: IP40, IK07.
b With direct rotary handle:
v standard / VDE: IP40, IK07
v MCC: IP43 IK07
v CNOMO: IP54 IK08
b With extended rotary handle: IP56 IK08
b With motor mechanism: IP40 IK07.

PM210011-NUI900-ESE-00001_02 100 of 154

559EN.indb 5 27/05/2009 10:10:03


Functions Introduction
and characteristics Characteristics and performance of
Compact NSX circuit breakers
from 100 to 630 A
PB103354-40

Common characteristics
Rated voltages
Insulation voltage (V) Ui 800
Impulse withstand voltage Uimp 8
(kV)
Operational voltage (V) Ue AC 50/60 Hz 690
Suitability for isolation IEC/EN 60947-2 yes
Utilisation category A
Pollution degree IEC 60664-1 3

Circuit breakers
Breaking capacity levels
Electrical characteristics as per IEC 60947-2
Rated current (A) In 40 °C
Number of poles
Compact NSX100/160/250. Breaking capacity (kA rms)
lcu AC 50/60 Hz 220/240 V
380/415 V
440 V
PB103279-44

500 V
525 V
660/690 V
Service breaking capacity (kA rms)
lcs AC 50/60 Hz 220/240 V
380/415 V
440 V
500 V
525 V
660/690 V
Durability (C-O cycles) Mechanical
Electrical 440 V In/2
In
690 V In/2
In
Characteristics as per Nema AB1
Breaking capacity (kA rms) AC 50/60 Hz 240 V
480 V
600 V
Characteristics as per UL 508
Breaking capacity (kA rms) AC 50/60 Hz 240 V
480 V
Compact NSX400/630.
600 V
Protection and measurements
Short-circuit protection Magnetic only
Overload / short-circuit protection Thermal magnetic
Electronic
with neutral protection (Off-0.5-1-OSN) (1)
with ground-fault protection
with zone selective
interlocking (ZSI) (2)
Display / I, U, f, P, E, THD measurements / interrupted-current measurement
Options Power Meter display on door
Operating assistance
Counters
Histories and alarms
Metering Com
Device status/control Com
Earth-leakage protection By Vigi module
By Vigirex relay
Installation / connections
Dimensions and weights
Dimensions (mm) Fixed, front connections 2/3P
WxHxD 4P
Weight (kg) Fixed, front connections 2/3P
4P
(1) OSN: Over Sized Neutral protection for neutrals carrying Connections
high currents (e.g. 3rd harmonics). Connection terminals Pitch With/without spreaders
(2) ZSI: Zone Selective Interlocking using pilot wires.
(3) 2P circuit breaker in 3P case for B and F types, only with Large Cu or Al cables Cross-section mm²
thermal-magnetic trip unit.

PM210011-NUI900-ESE-00001_02 101 of 154

559EN.indb 6 27/05/2009 10:10:05


Common characteristics
Control
Manual With toggle b
With direct or extended rotary handle b
Electrical With remote control b
Versions
Fixed b
Withdrawable Plug-in base b
Chassis b

NSX100 NSX160 NSX250 NSX400 NSX630


B F N H S L B F N H S L B F N H S L F N H S L F N H S L

100 160 250 400 630


2 (3), 3, 4 2 (3), 3, 4 2 (3), 3, 4 3, 4 3, 4

40 85 90 100 120 150 40 85 90 100 120 150 40 85 90 100 120 150 40 85 100 120 150 40 85 100 120 150
25 36 50 70 100 150 25 36 50 70 100 150 25 36 50 70 100 150 36 50 70 100 150 36 50 70 100 150
20 35 50 65 90 130 20 35 50 65 90 130 20 35 50 65 90 130 30 42 65 90 130 30 42 65 90 130
15 25 36 50 65 70 15 30 36 50 65 70 15 30 36 50 65 70 25 30 50 65 70 25 30 50 65 70
- 22 35 35 40 50 - 22 35 35 40 50 - 22 35 35 40 50 20 22 35 40 50 20 22 35 40 50
- 8 10 10 15 20 - 8 10 10 15 20 - 8 10 10 15 20 10 10 20 25 35 10 10 20 25 35

40 85 90 100 120 150 40 85 90 100 120 150 40 85 90 100 120 150 40 85 100 120 150 40 85 100 120 150
25 36 50 70 100 150 25 36 50 70 100 150 25 36 50 70 100 150 36 50 70 100 150 36 50 70 100 150
20 35 50 65 90 130 20 35 50 65 90 130 20 35 50 65 90 130 30 42 65 90 130 30 42 65 90 130
7.5 12.5 36 50 65 70 15 30 36 50 65 70 15 30 36 50 65 70 25 30 50 65 70 25 30 50 65 70
- 11 35 35 40 50 - 22 35 35 40 50 - 22 35 35 40 50 10 11 11 12 12 10 11 11 12 12
- 4 10 10 15 20 - 8 10 10 15 20 - 8 10 10 15 20 10 10 10 12 12 10 10 10 12 12
50000 40000 20000 15000 15000
50000 20000 20000 12000 8000
30000 10000 10000 6000 4000
20000 15000 10000 6000 6000
10000 7500 5000 3000 2000

40 85 90 100 120 150 40 85 90 100 120 150 40 85 90 100 120 150 40 85 100 120 150 40 85 100 120 150
20 35 50 65 90 130 20 35 50 65 90 130 20 35 50 65 90 130 30 42 65 90 130 30 42 65 90 130
- 8 20 35 40 50 - 20 20 35 40 50 - 20 20 35 40 50 - 20 35 40 50 - 20 35 40 50

- 85 85 85 - - - 85 85 85 - - - 85 85 85 - - 85 85 85 - - 85 85 85 - -
- 25 50 65 - - - 35 50 65 - - - 35 50 65 - - 35 50 65 - - 35 50 65 - -
- 10 10 10 - - - 10 10 10 - - - 15 15 15 - - 20 20 20 - - 20 20 20 - -

b b b b b
b b b - -
b b b b b
b b b b b
b b b b b
b b b b b

b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b

105 x 161 x 86 105 x 161 x 86 105 x 161 x 86 140 x 255 x 110 140 x 255 x 110
140 x 161 x 86 140 x 161 x 86 140 x 161 x 86 185 x 255 x 110 185 x 255 x 110
2.05 2.2 2.4 6.05 6.2
2.4 2.6 2.8 7.90 8.13

35/45 mm 35/45 mm 35/45 mm 45/52.5 mm 45/52.5 mm


45/70 mm 45/70 mm
300 300 300 4 x 240 4 x 240

PM210011-NUI900-ESE-00001_02 102 of 154

559EN.indb 7 27/05/2009 10:10:05


3.3

Catalogue numbers NSX100/160/250B:


complete fixed/FC device
Compact NSX100/160/250B
(25 kA 380/415 V)
Compact NSX100/160/250B
With thermal-magnetic trip unit TM-D
DB112222

Compact NSX100B (25 kA at 380/415 V)


Rating 3P 2d 3P 3d 4P 3d 4P 4d
TM16D LV429547 LV429557 LV429567 LV429577
TM25D LV429546 LV429556 LV429566 LV429576
TM32D LV429545 LV429555 LV429565 LV429575
TM40D LV429544 LV429554 LV429564 LV429574
TM50D LV429543 LV429553 LV429563 LV429573
TM63D LV429542 LV429552 LV429562 LV429572
TM80D LV429541 LV429551 LV429561 LV429571
TM100D LV429540 LV429550 LV429560 LV429570
Compact NSX160B (25 kA at 380/415 V)
Rating 3P 2d 3P 3d 4P 3d 4P 4d
TM80D LV430303 LV430313 LV430323 LV430333
TM100D LV430302 LV430312 LV430322 LV430332
TM125D LV430301 LV430311 LV430321 LV430331
TM160D LV430300 LV430310 LV430320 LV430330
Compact NSX250B (25 kA at 380/415 V)
Rating 3P 2d 3P 3d 4P 3d 4P 4d
TM125D LV431103 LV431113 LV431123 LV431133
TM160D LV431102 LV431112 LV431122 LV431132
TM200D LV431101 LV431111 LV431121 LV431131
TM250D LV431100 LV431110 LV431120 LV431130
With electronic trip unit Micrologic 2.2 (LSOI protection)
DB112223

Compact NSX100B (25 kA at 380/415 V)


Rating 3P 3d 4P 3d, 4d, 3d + N/2
40 LV429777 LV429787
100 LV429775 LV429785
Compact NSX160B (25 kA at 380/415 V)
Rating 3P 3d 4P 3d, 4d, 3d + N/2
100 LV430746 LV430751
160 LV430745 LV430750
Compact NSX250B (25 kA at 380/415 V)
Rating 3P 3d 4P 3d, 4d, 3d + N/2
100 LV431142 LV431152
160 LV431141 LV431151
250 LV431140 LV431150
With electronic trip unit Micrologic 5.2 A (LSI protection, ammeter)
DB112224

Compact NSX100B (25 kA at 380/415 V)


Rating 3P 3d 4P 3d, 4d, 3d + N/2, 3d + OSN
40 LV429872 LV429877
100 LV429870 LV429875
Compact NSX160B (25 kA at 380/415 V)
Rating 3P 3d 4P 3d, 4d, 3d + N/2, 3d + OSN
OK
100 LV430871 LV430876
160
Mode

LV430870 LV430875
Compact NSX250B (25 kA at 380/415 V)
Rating 3P 3d 4P 3d, 4d, 3d + N/2, 3d + OSN
100 LV431147 LV431157
160 LV431146 LV431156
250 LV431145 LV431155
With electronic trip unit Micrologic 5.2 E (LSI protection, energy meter)
To be ordered with 2 catalogue numbers: 1 basic frame + 1 trip unit

With electronic trip unit Micrologic 6.2 A (LSIG protection, ammeter)


To be ordered with 2 catalogue numbers: 1 basic frame + 1 trip unit

With electronic trip unit Micrologic 6.2 E (LSIG protection, energy meter)
To be ordered with 2 catalogue numbers: 1 basic frame + 1 trip unit

PM210011-NUI900-ESE-00001_02 103 of 154

559EN.indb 4 27/05/2009 10:18:04


www.se.com
Catalog Numbers
Complete Fixed Device
ComPacT NSX100/160/250B (25 KA 380/415 V)

ComPacT NSX100/160/250B
With thermal-magnetic trip unit TM-D
ComPacT NSX100B (25 kA at 380/415 V)
DB438166.ai

Rating 3P 3d 4P 3d 4P 4d
TM16D C10B3TM016 C10B6TM016 C10B4TM016
TM25D C10B3TM025 C10B6TM025 C10B4TM025
TM32D C10B3TM032 C10B6TM032 C10B4TM032
Ii
Trip

2250
2500

1500
1250
TM25
0D

250 A/40°
C Ir
Ii TM40D C10B3TM040 C10B6TM040 C10B4TM040
TM50D C10B3TM050 C10B6TM050 C10B4TM050
Ir 2000 1750 2.2
ogic
175 MicroL
200
A
250
225

A
Isd 5 6
4 7
Ir .95 .96 3 8
% >105% .94 .97
>90
Io 2
ALARM

Ir 160 175 10
.93
READY

140 200 .98 1.5

TM63D C10B3TM063 C10B6TM063 C10B4TM063


.92 1
125 225 .9 xIr
110 250 xIo
100
(A)

TM80D C10B3TM080 C10B6TM080 C10B4TM080


TM100D C10B3TM100 C10B6TM100 C10B4TM100
ComPacT NSX160B (25 kA at 380/415 V)
Rating 3P 3d 4P 3d 4P 4d
TM80D C16B3TM080 C16B6TM080 C16B4TM080
TM100D C16B3TM100 C16B6TM100 C16B4TM100
TM125D C16B3TM125 C16B6TM125 C16B4TM125
TM160D C16B3TM160 C16B6TM160 C16B4TM160
ComPacT NSX250B (25 kA at 380/415 V)
Rating 3P 3d 4P 3d 4P 4d
TM125D C25B3TM125 C25B6TM125 C25B4TM125
TM160D C25B3TM160 C25B6TM160 C25B4TM160
TM200D C25B3TM200 C25B6TM200 C25B4TM200
TM250D C25B3TM250 C25B6TM250 C25B4TM250
With electronic trip unit MicroLogic 2.2 (LSOI protection)
ComPacT NSX100B (25 kA at 380/415 V)
DB438167.ai

Rating 3P 3d 4P 3d, 4d, 3d + N/2


40 C10B32D040 C10B42D040
100 C10B32D100 C10B42D100
ComPacT NSX160B (25 kA at 380/415 V)
Rating 3P 3d 4P 3d, 4d, 3d + N/2
Micrologic 4.2

100 C16B32D100 C16B42D100


500 1A
300 3A
Trip 100 5A
OFF
30
li=1500A mA
max 500
40V Isd 5 6 150
Ue=4 4 7
50-60Hz Ir .95 .96 60 1000
% >105% 3
>90 .94 8
Dielectric

ALARM

.97
Vigi

0 t(ms)
READY

Ir Io 63 70 2
switch

.93 10
55 80 .98 1.5 xIr

C16B32D160 C16B42D160
50 .92 1

160
90 .9
45 xIo
100
40
(A)

ComPacT NSX250B (25 kA at 380/415 V)


Rating 3P 3d 4P 3d, 4d, 3d + N/2
100 C25B32D100 C25B42D100
160 C25B32D160 C25B42D160
250 C25B32D250 C25B42D250
With electronic trip unit MicroLogic Vigi 4.2 (LSOIR protection)
ComPacT NSX100B (25 kA 380/415V)
DB438168.ai

Rating 3P 3d 4P 4d, 3d + N/2


40 A C10B34V040 C10B44V040
100 A C10B34V100 C10B44V100

Ir

250
225

A
200
175
Ii
Trip

2500

2250

2000 1750

A
1250

1500
TM25
0D

250 A/40°
C Ir
Ii
ComPacT NSX160B (25 kA 380/415V)
Rating 3P 3d 4P 4d, 3d + N/2
F
100 A C16B34V100 C16B44V100
160 A C16B34V160 C16B44V160
ComPacT NSX250B (25 kA 380/415V)
Rating 3P 3d 4P 4d, 3d + N/2
100 A C25B34V100 C25B44V100
160 A C25B34V160 C25B44V160
250 A C25B34V250 C25B44V250
With electronic trip unit MicroLogic Vigi 7.2 E (LSIR protection)
ComPacT NSX100B (25 kA 380/415V)
DB438567.ai

Rating 3P 3d 4P 3d, 4d, 3d + N/2


40 A - C10B47E040
100 A - C10B47E100
ComPacT NSX160B (25 kA 380/415V)
Rating 3P 3d 4P 3d, 4d, 3d + N/2
100 A - C16B47E100
160 A - C16B47E160
ComPacT NSX250B (25 kA 380/415V)
Rating 3P 3d 4P 3d, 4d, 3d + N/2
100 A - C25B47E100
160 A - C25B47E160
250 A - C25B47E250
With electronic trip unit MicroLogic 5.2 E (LSI protection, energy meter)
Only available as separate component or through online configurator (product selector)
With electronic trip unit MicroLogic 6.2 E (LSIG protection, energy meter)
Only available as separate component or through online configurator (product selector)
With electronic trip unit MicroLogic 7.2 E (LSIG protection, energy meter)
Only available as separate component or through online configurator (product selector)

PM210011-NUI900-ESE-00001_02 104 of 154


Catalogue numbers Accessories (cont.)
Compact and Vigicompact
NSX100/160/250 (cont.)

Electrical auxiliaries
Auxiliary contacts (changeover)
OF or SD or SDE or SDV
DB112254

29450
OF or SD or SDE or SDV low level 29452
SDE adapter, mandatory for trip unit TM, MA or Micrologic 2 LV429451

SDx output module for Micrologic


SDx module 24/415 V AC/DC
DB112275

LV429532

SDTAM contactor tripping module (early-break thermal fault signal) for Micrologic 2.2-M/6.2 E-M
SDTAM 24/415 V AC/DC overload fault indication
DB112276

LV429424

Voltage releases
Voltage
DB111454

MX MN
AC 24 V 50/60 Hz LV429384 LV429404
48 V 50/60 Hz LV429385 LV429405
110-130 V 50/60 Hz LV429386 LV429406
220-240 V 50/60 Hz and 208-277 V 60 Hz LV429387 LV429407
380-415 V 50 Hz and 440-480 V 60 Hz LV429388 LV429408
525 V 50 Hz and 600 V 60 Hz LV429389 LV429409
DC 12 V LV429382 LV429402
24 V LV429390 LV429410
30 V LV429391 LV429411
48 V LV429392 LV429412
60 V LV429383 LV429403
125 V LV429393 LV429413
250 V LV429394 LV429414
MN 48 V 50/60 Hz with fixed time delay
DB115631

Composed of: MN 48 V DC LV429412


Delay unit 48 V 50/60 Hz LV429426
MN 220-240 V 50/60 Hz with fixed time delay
Composed of: MN 250 V DC LV429414
Delay unit 220-240 V 50/60 Hz LV429427
MN 48 V DC/AC 50/60 Hz with adjustable time delay
Composed of: MN 48 V DC LV429412
Delay unit 48 V 50/60 Hz 33680
MN110-130 V DC/AC 50/60 Hz with adjustable time delay
Composed of: MN 125 V DC LV429413
Delay unit 110-130 V 50/60 Hz 33681
MN 220-250 V 50/60 Hz with adjustable time delay
Composed of: MN 250 V DC LV429414
Delay unit 220-250 V 50/60 Hz 33682

PM210011-NUI900-ESE-00001_02 105 of 154

559EN.indb 20 27/05/2009 10:18:23


3.2

Catalogue numbers NSX400/630F:


complete fixed/FC device
Compact NSX400/630F
(36 kA 380/415 V)
Compact NSX400/630F
Electronic trip unit Micrologic 2.3 (LSOI protection)
3P 3d 4P 3d, 4d, 3d + N/2
DB111455

Compact NSX400F (36 kA at 380/415 V) 250 A LV432682 LV432683


400 A LV432676 LV432677
Compact NSX630F (36 kA at 380/415 V) 630 A LV432876 LV432877

Electronic trip unit Micrologic 5.3 A (LSI protection, ammeter)


3P 3d 4P 3d, 4d, 3d + N/2, 3d + OSN
DB111456

Compact NSX400F (36 kA at 380/415 V) 400 A LV432678 LV432679


Compact NSX630F (36 kA at 380/415 V) 630 A LV432878 LV432879

OK

Mode

Electronic trip unit Micrologic 1.3-M (I motor protection)


3P 3d
DB111457

Compact NSX400F 1.3-M (36 kA at 380/415V) 320 A LV432748


Compact NSX630F 1.3-M (36 kA at 380/415V) 500 A LV432948

Electronic trip unit Micrologic 2.3-M (LSOI motor protection)


3P 3d
DB111457

Compact NSX400F 2.3-M (36 kA at 380/415V) 320 A LV432775


Compact NSX630F 2.3-M (36 kA at 380/415V) 500 A LV432975

With electronic trip unit Micrologic 5.3 E (LSI protection, energy meter)
To be ordered with 2 catalogue numbers: 1 basic frame + 1 trip unit

With electronic trip unit Micrologic 6.3 A (LSIG protection, ammeter)


To be ordered with 2 catalogue numbers: 1 basic frame + 1 trip unit

With electronic trip unit Micrologic 6.3 E (LSIG protection, energy meter)
To be ordered with 2 catalogue numbers: 1 basic frame + 1 trip unit

With electronic trip unit Micrologic 6.3 E-M (LSIG motor protection, energy meter)
To be ordered with 2 catalogue numbers: 1 basic frame + 1 trip unit

PM210011-NUI900-ESE-00001_02 106 of 154

559EN.indb 30 27/05/2009 10:18:40


Catalog Numbers www.se.com

Complete Fixed Device


ComPacT NSX400/630F (36 KA 380/415 V)

ComPacT NSX400/630F
Electronic trip unit MicroLogic 2.3 (LSOI protection)
3P 3d 4P 3d, 4d, 3d + N/2
DB438189.ai

ComPacT NSX400F (36 kA at 380/415 V) 250 A C40F32D250 C40F42D250


400 A C40F32D400 C40F42D400
ComPacT NSX630F (36 kA at 380/415 V) 630 A C63F32D630 C63F42D630

rip

.95 .96
.94 .97
.93
.98
.92 1
.9
x Io

Electronic trip unit MicroLogic Vigi 4.3 (LSOIR protection)


3P 3d 4P 4d 3d + N/2
DB438190.ai

ComPacT NSX400F (36 kA at 380/415 V) 400 A C40F34V400 C40F44V400


ComPacT NSX630F (36 kA at 380/415 V) 570 A C63F34V570 C63F44V570

rip
MicroLogic 4.3

3A 5A
1A
10A
500
>105%
>90% OFF
ALARM

Ir 300
READY

mA

li=4800A
150 500
Isd
5 6
4 7 60 1000
Ir
.95 .96 3 0 t(ms)
.94 8
Io .97
250 280 2
.93 10
230 320 .98 1.5 xIr
200 .92 1
360 .9
xIo
180 400
160 (A)
50-60Hz

0V max
Ue=44

Electronic trip unit MicroLogic Vigi 7.3 E (LSIR protection + embedded energy management)
3P 3d 4P 4d, 3d + N/2
DB438568.ai

ComPacT NSX400F (36 kA at 380/415V) 400 A C40F37E400 C40F47E400


ComPacT NSX630F (36 kA at 380/415V) 570 A C63F37E570 C63F47E570

Electronic trip unit MicroLogic 1.3 M (I motor protection)


3P 3d
DB438191.ai

ComPacT NSX400F 1.3 M (36 kA at 380/415V) 320 A C40F31M320

F ComPacT NSX630F 1.3 M (36 kA at 380/415V) 500 A C63F31M500

rip

Electronic trip unit MicroLogic 2.3 M (LSOI motor protection)


3P 3d
DB438192.ai

ComPacT NSX400F 2.3 M (36 kA at 380/415V) 320 A C40F32M320


ComPacT NSX630F 2.3 M (36 kA at 380/415V) 500 A C63F32M500

rip

With electronic trip unit MicroLogic 5.3 E (LSI protection, energy meter)
Only available as separate component or through online configurator (product selector)
With electronic trip unit MicroLogic 6.3 E (LSIG protection, energy meter)
Only available as separate component or through online configurator (product selector)
With electronic trip unit MicroLogic 6.3 E-M (LSIG motor protection, energy meter)
Only available as separate component or through online configurator (product selector)
With electronic trip unit MicroLogic 7.3 E (LSIG protection, energy meter)
Only available as separate component or through online configurator (product selector)

PM210011-NUI900-ESE-00001_02 107 of 154


Catalogue numbers Accessories (cont.)
Compact and Vigicompact
NSX400/630 (cont.)

Electrical auxiliaries
Auxiliary contacts (changeover)
OF or SD or SDE or SDV
DB112254

29450
OF or SD or SDE or SDV low level 29452

SDx output module for Micrologic electronic trip unit


SDx module 24/415 V AC/DC
DB112275

LV429532

SDTAM contactor tripping module (early-break thermal fault signal) for Micrologic 2.3-M/6.3 E-M
SDTAM 24/415 V AC/DC overload fault indication
DB112276

LV429424

Voltage releases
Voltage
DB111454

MX MN
AC 24 V 50/60 Hz LV429384 LV429404
48 V 50/60 Hz LV429385 LV429405
110-130 V 50/60 Hz LV429386 LV429406
220-240 V 50/60 Hz and 208-277 V 60 Hz LV429387 LV429407
380-415 V 50 Hz and 440-480 V 60 Hz LV429388 LV429408
525 V 50 Hz and 600 V 60 Hz LV429389 LV429409
DC 12 V LV429382 LV429402
24 V LV429390 LV429410
30 V LV429391 LV429411
48 V LV429392 LV429412
60 V LV429383 LV429403
125 V LV429393 LV429413
250 V LV429394 LV429414
MN 48 V 50/60 Hz with fixed time delay
DB115631

Composed of: MN 48 V DC LV429412


Delay unit 48 V 50/60 Hz LV429426
MN 220-240 V 50/60 Hz with fixed time delay
Composed of: MN 250 V DC LV429414
Delay unit 220-240 V 50/60 Hz LV429427
MN 48 V DC/AC 50/60 Hz with adjustable time delay
Composed of: MN 48 V DC LV429412
Delay unit 48 V 50/60 Hz 33680
MN110-130 V DC/AC 50/60 Hz with adjustable time delay
Composed of: MN 125 V DC LV429413
Delay unit 110-130 V 50/60 Hz 33681
MN 220-250 V 50/60 Hz with adjustable time delay
Composed of: MN 250 V DC LV429414
Delay unit 220-250 V 50/60 Hz 33682

PM210011-NUI900-ESE-00001_02 108 of 154

559EN.indb 42 27/05/2009 10:18:57


Protection iC60N circuit breakers
Circuit protection
(curve B, C, D)

CEI/EN 60947-2
DB116619

BS/EN 60898-1
bb Disbo iC60N circuit breakers are multi-standard circuit breakers which combine
the following functions:
vv circuit protection against short-circuit currents,
vv circuit protection against overload currents,
vv suitable for industrial isolation according to IEC/EN 60947-2, standard.
vv fault tripping indication by a red mechanical indicator in circuit breaker front face. A
Alternating current (AC) 50/60 Hz
PB111066-40

PB111070-40

Breaking capacity (Icu) according to IEC/EN 60947-2 Service


Voltage (Ue) breaking
capacity
Ph/Ph (2P, 3P, 4P) 12 to 133 V 220 to 240 V 380 to 415 V 440 V
(Ics)
Ph/N (1P, 1P+N) 12 to 60 V 100 to 133 V 220 to 240 V -
Rating (In) 0.5 to 4 A 50 kA 50 kA 50 kA 25 kA 100 % of Icu
6 to 63 A 36 kA 20 kA 10 kA 6 kA 75 % of Icu
Breaking capacity (Icn) according to IEC/EN 60898-1
Voltage (Ue)
Ph/Ph 400 V
Ph/N 230 V
Rating (In) 0.5 to 63 A 6000 A

Direct current (DC)


Breaking capacity (Icu) according to IEC/EN 60947-2 Service
Voltage (Ue) breaking
capacity
Between +/- 12 to 48 V 72 V 100 to 133 V 220 to 250 V
(Ics)
Number of poles 1P 2P (in series) 3P (in series) 4P (in series)
Rating (In) 1 to 63 A 15 kA 6 kA 6 kA 15 kA 6 kA 100 % of Icu

Catalogue numbers
Disbo iC60N circuit breaker
Type 1P 2P
E45092

E45094

Auxiliaries See page E-2 and F-22 See page E-2 and F-22
Rating (In) Curve Curve
B C D B C D
0.5 A A9F43170 A9F44170 A9F45170 A9F43270 A9F44270 A9F45270
1A A9F43101 A9F44101 A9F45101 A9F43201 A9F44201 A9F45201
2A A9F43102 A9F44102 A9F45102 A9F43202 A9F44202 A9F45202
3A A9F43103 A9F44103 A9F45103 A9F43203 A9F44203 A9F45203
4A A9F43104 A9F44104 A9F45104 A9F43204 A9F44204 A9F45204
6A A9F43106 A9F44106 A9F45106 A9F43206 A9F44206 A9F45206
10 A A9F43110 A9F44110 A9F45110 A9F43210 A9F44210 A9F45210
16 A A9F43116 A9F44116 A9F45116 A9F43216 A9F44216 A9F45216
20 A A9F43120 A9F44120 A9F45120 A9F43220 A9F44220 A9F45220
25 A A9F43125 A9F44125 A9F45125 A9F43225 A9F44225 A9F45225
32 A A9F43132 A9F44132 A9F45132 A9F43232 A9F44232 A9F45232
40 A A9F43140 A9F44140 A9F45140 A9F43240 A9F44240 A9F45240
50 A A9F43150 A9F44150 A9F45150 A9F43250 A9F44250 A9F45250
63 A A9F43163 A9F44163 A9F45163 A9F43263 A9F44263 A9F45263
Width in 9-mm modules 2 4
Accessories See page E-2 and E-10 See page E-2 and E-10

PM210011-NUI900-ESE-00001_02 109 of 154


Protection iC60N circuit breakers
Circuit protection
(curve B, C, D) (cont.)

bb Insulated terminals IP20


Visi-trip window
bb Fault tripping is indicated by a red
mechanical indicator on the front face

Positive contact indication


bb Suitable for industrial isolation according to
IEC/EN 60947-2 standard.
bb The presence of the green strip guarantees
physical opening of the contacts and allows
operations to be performed on the downstream
bb Large circuit
circuit in complete safety
labelling area

bb Insulated terminals IP20

bb Clip for dismounting

bb Increased product service life thanks to:


vv overvoltage resistance by high level of industrial performances conception
(pollution degree, rated impulse withstand voltage and insulation voltage),
vv high performance limitation (see limitation curves),
vv fast closing independent of the speed of actuation of the toggle.
bb Remote indication, open/closed/tripped, by optional auxiliary contacts.
bb Top or bottom electrical feeding.

3P 4P
E45095

E45097

See page E-2 and F-22 See page E-2 and F-22
Curve Curve
B C D B C D
A9F43370 A9F44370 A9F45370 A9F43470 A9F44470 A9F45470
A9F43301 A9F44301 A9F45301 A9F43401 A9F44401 A9F45401
A9F43302 A9F44302 A9F45302 A9F43402 A9F44402 A9F45402
A9F43303 A9F44303 A9F45303 A9F43403 A9F44403 A9F45403
A9F43304 A9F44304 A9F45304 A9F43404 A9F44404 A9F45404
A9F43306 A9F44306 A9F45306 A9F43406 A9F44406 A9F45406
A9F43310 A9F44310 A9F45310 A9F43410 A9F44410 A9F45410
A9F43216 A9F44316 A9F45316 A9F43416 A9F44416 A9F45416
A9F43220 A9F44320 A9F45320 A9F43420 A9F44420 A9F45420
A9F43225 A9F44325 A9F45325 A9F43425 A9F44425 A9F45425
A9F43232 A9F44332 A9F45332 A9F43432 A9F44432 A9F45432
A9F43240 A9F44340 A9F45340 A9F43440 A9F44440 A9F45440
A9F43250 A9F44350 A9F45350 A9F43450 A9F44450 A9F45450
A9F43263 A9F44363 A9F45363 A9F43463 A9F44463 A9F45463
6 8
See page E-2 and E-10 See page E-2 and E-10

PM210011-NUI900-ESE-00001_02 110 of 154


Protection iC60N circuit breakers
Circuit protection
(curve B, C, D) (cont.)

Connection Without accessory With accessories


Rating Tightening Copper cables 50 mm² Screw-on Multi-cables terminal
DB405585

torque Rigid Flexible Al connection Rigid Flexible


14 mm
6.5 mm or ferrule terminal for ring cables cables
terminal
PZ2

DB122945

DB122946

DB122935

DB118789

DB118787
A
0.5 to 25 A 2 N.m 1 to 25 mm2 1 to 16 mm2 - Ø 5 mm - -
32 to 63 A 3.5 N.m 1 to 35 mm2 1 to 25 mm2 50 mm2 3 x 16 mm2 3 x 10 mm2
DB123310

Technical data
Main characteristics
According to IEC/EN 60947-2
Insulation voltage (Ui) 500 V AC
Pollution degree 3
Rated impulse withstand voltage (Uimp) 6 kV
Clip on DIN rail 35 mm.
Thermal tripping Reference temperature 50 °C
DB405583

Temperature derating See the Technical Guide


Magnetic tripping B curve 4 In ± 20 %
C curve 8 In ± 20 %
D curve 12 In ± 20 %
Utilization category A
According to IEC/EN 60898-1
Limitation class 3
Rated making and breaking capacity of an Icn1 = Icn
individual pole (Icn1)
Additional characteristics
Breaking capacity 40 A 4 kA
under 1 pole with IT 50/63 A 3 kA
Installation on Fishbone. 380-415 V isolated
neutral system
(case of double fault)
DB123312

Degree of protection Device only IP20


(IEC 60529) Device in modular IP40
enclosure Insulation classe II
Endurance (O-C) Electrical 10,000 cycles
Mechanical 20,000 cycles
Overvoltage category (IEC 60364) IV
Indifferent position of installation. Operating temperature -35°C to +70°C
Storage temperature -40°C to +85°C
Tropicalization (IEC 60068-1) Treatment 2 (relative humidity 95 % to 55°C)
IP20 IP40
DB123314

Dimensions (mm) Weight (g)


DB405584

Circuit-breaker
Type Disbo iC60N
1P 125
2P 250
3P 375
4P 500

PM210011-NUI900-ESE-00001_02 111 of 154


Protect iC60H RCBO
Circuit protection 30 and 100 mA

IEC 61009-1,
IEC 61009-2-2

bb The single-phase iC60H RCBO’s self-contained residual current device carries


PB110075-70

out complete protection of final circuits:


vv protection against short-circuits and cable overloads
vv protection of persons against electric shock by direct contact
(30 mA sensitivities),
vv protection of persons against electric shock by indirect contact
(100 mA sensitivity),
vv protection of equipment against fires set by leakage currents
(100 mA sensitivity).
bb The neutral is not interrupted when the device is tripped. Hence iC60H RCBO can
be used on most circuits, except for the ones operating under TT or IT earthing
systems.

Alternating current (AC) 50/60 Hz


Breaking capacity (Icn) according to IEC 61009-1
Voltage (Ue)
Ph/N 110 V 240 V
Rating (In) 6 to 45 A 10000 A 10000 A

Accessory
Padlocking device
bb Used to lock the toggle in the "open" or "closed" position by 4 mm diameter
padlock (not supplied).

Catalogue numbers
iC60H RCBO 10000
1P+N A Width in 9-mm
modules
B curve Voltage rating (V) Sensitivity (IΔn) 30 mA 100 mA
240 Rating 6A A9D34806 - 2
DB405038

(In) 10 A A9D34810 -
16 A A9D34816 -
20 A A9D34820 -
25 A A9D34825 -
32 A A9D34832 -
40 A A9D34840 -
45 A A9D34845 -
C curve Voltage rating (V) Sensitivity (IΔn)
240 Rating 6A A9D14806 A9D15806 2
DB405038

(In) 10 A A9D14810 A9D15810


16 A A9D14816 A9D15816
20 A A9D14820 A9D15820
25 A A9D14825 A9D15825
32 A A9D14832 A9D15832
40 A A9D14840 A9D15840
45 A A9D14845 A9D15845
Operating frequency 50…60 Hz
Auxiliaries See pages E-2 and F-2

Accessory
Type
Padlocking device (bag of 10 pieces) A9A27049

PM210011-NUI900-ESE-00001_02 112 of 154


Protect iC60 RCBO
Circuit protection 10, 30 and 100 mA

Technical data
Main characteristics iC60N RCBO iC60H RCBO iC60H2 RCBO
Insulation voltage (Ui) 400 V AC
Rated impulse withstand voltage (Uimp) 4 kV
Rated residual operating current (IΔn) 30 mA 10, 30, 100 mA 30 mA
Thermal tripping Reference temperature 50°C
Temperature derating See the Technical Guide
Limitation class 3
Surge current withstand (8/20 μs) without tripping 250 Â
Rated nominal breaking capacity (Icn) 6,000 A 10,000 A 10,000 A
Phase/earth rated residual breaking and making capacity (IΔm) 6,000 A 7,500 A 7,500 A
Additional characteristics
Degree of protection Device only IP20
Device in modular enclosure IP40
Endurance (O-C) Electrical 5,000 cycles
Mechanical 20,000 cycles
Operating temperature -15°C to +60°C
Storage temperature -40°C to +85°C
Tropicalization Treatment 2 (relative humidity: 95 % at 55°C)

IP20 IP40
DB404953
DB123309

DB123313

Clip on DIN rail 35 mm.


B
Installation on Fishbone.
DB123311

Weight (g)
Indifferent position of installation.
iC60 RCBO
iC60N RCBO 205
iC60H RCBO 205
iC60H2 RCBO 332

Dimensions (mm)
DB405565

iC60N RCBO, iC60H RCBO iC60H2 RCBO

PM210011-NUI900-ESE-00001_02 | 113 of 154


Protection iID residual current
Earth leakage protection
circuit breakers (AC type)

IEC/EN 61008-1
DB116619

bb The iID residual current circuit breakers provide:


PB104472-40

PB104473-40

vv protection of persons against electric shock by direct contact (y 30 mA),


vv protection of persons against electric shock by indirect contact (u 100 mA),
vv protection of installations against the risk of fire (300 mA or 500 mA).

Catalogue numbers
iID residual current circuit breakers
Type AC Width in 9 mm
Product iID module
Auxiliaries See page E-2 and F-2
2P Sensitivity 10 mA 30 mA 100 mA 300 mA 500 mA 300 mA s 500 mA s
Rating 16 A A9R10216 - - - - - - 4
DB122476

25 A
40 A
A9R10225
-
A9R71225
A9R71240
-
A9R12240
A9R74225
A9R74240
A9R16225
A9R16240
-
-
-
-
B
63 A - A9R71263 A9R12263 A9R74263 A9R16263 A9R15263 -
80 A - A9R11280 A9R12280 A9R14280 - A9R15280 -
100 A - A9R11291 A9R12291 A9R14291 - A9R15291 -

4P Sensitivity 10 mA 30 mA 100 mA 300 mA 500 mA 300 mA s 500 mA s


Rating 25 A - A9R71425 - A9R74425 A9R16425 - - 8
DB122477

40 A - A9R71440 A9R12440 A9R74440 A9R16440 A9R15440 A9R17440


63 A - A9R71463 A9R12463 A9R74463 A9R16463 A9R15463 A9R17463
80 A - A9R11480 A9R12480 A9R14480 A9R16480 A9R15480 A9R17480
100 A - A9R11491 A9R12491 A9R14491 - A9R15491 -

Voltage rating (Ue) 2P 230 - 240 V


4P 400 - 415 V
Operating frequency 50/60 Hz
Accessories See pages E-2 and E-10

PM210011-NUI900-ESE-00001_02 114 of 154


TeSys D Contactors
0.06…75 kW

Connections
■ screw clamp terminals or connectors
Rated operational voltage 690 V
Rated operational current Ie max AC-3 (Ue ≤ 440V) 9A 12 A 18 A 25 A 32 A 38 A
Ie AC-1 (θ ≤ 60° C) 25 A 32 A 40 A 50 A
Rated operational power 220/240 V 2.2 kW 3 kW 4 kW 5.5 kW 7.5 kW 9 kW
in category AC3 380/400 V 4 kW 5.5 kW 7.5 kW 11 kW 15 kW 18.5 kW
415/440 V 4 kW 5.5 kW 9 kW 11 kW 15 kW 18.5 kW
500 V 5.5 kW 7.5 kW 10 kW 15 kW 18.5 kW 18.5 kW
660/690 V 5.5 kW 7.5 kW 10 kW 15 kW 18.5 kW 18.5 kW
1000 V – – – – – –
Contactor type * LC1-D09 LC1-D12 LC1-D18 LC1-D25 LC1-D32 LC1-D38
Reversing contactor type * with mechanical interlock LC2-D09 LC2-D12 LC2-D18 LC2-D25 LC2-D32 LC2-D38
(1)
■ spring terminals
Add the figure 3 before the voltage code. Example LC1-D09P7 becomes LC1-093P7
(2)
■ lug-clamps
Add the figure 6 before the voltage code. Example LC1-D09P7 becomes LC1-096P7
■ Faston connectors (3)
2 x 6.35 (power) and 1 x 6.35 (control) up to D12 only
Add the figure 9 before the voltage code. Example LC1-D09P7 becomes LC1-099P7
* Basic reference to be completed by adding the coil voltage

(1) (2) (3)

Standard control circuit voltages


a supply
Volts 24 42 48 110 115 220 230 240 380 400 415 440 500
Contactors LC1-D09…D150 (coils D115 and D150 with integral suppression device fitted as standard)
50/60 Hz B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7 S7
Contactors LC1-D80…D115
50 Hz B5 D5 E5 F5 FE5 M5 P5 U5 Q5 V5 N5 R5 S5
60 Hz B6 - E6 F6 - M6 - U6 Q6 - - R6 -
c supply
Volts 12 24 36 48 60 72 110 125 220 250 440
Contactors LC1-D09…D65A (coils with integral suppression device fitted as standard)
U 0.75…1.25 Uc JD BD CD ED ND SD FD GD MD UD RD
Contactors LC1-D80…D95
U 0.85…1.1 Uc JD BD CD ED ND SD FD GD MD UD RD
U 0.75…1.2 Uc JW BW CW EW - SW FW - MW - -
Contactors LC1-D115 and D150 (coils with integral suppression device fitted as standard)
U 0.75…1.2 Uc - BD - ED ND SD FD GD MD UD RD
Low consumption
Contactors LC1-D09…D38 (coils with integral suppression device fitted as standard)
Volts c 5 12 20 24 48 110 120 250
U 0.7…1.25 Uc AL JL ZL BL EL FL ML UL
Example of complete reference LC1-D09P7
PM210011-NUI900-ESE-00001_02 115 of 154
Product datasheet A9N15636
Characteristics Acti 9 - fuse-disconnector STI - 1 pole - 25 A - for
fuse 10.3 x 38 mm

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range Acti 9
Product name Acti 9 STI
Product or component type Fuse-disconnector
Device short name STI
Poles description 1P

Complementary
[In] rated current 2A
4A
6A
10 A
16 A
20 A
25 A
Fuse curve AM
GG
Fuse size 10.3 x 38 mm
[Ue] rated operational voltage 500 V AC
[Ui] rated insulation voltage 500 V AC 50/60 Hz
Mounting mode Clip-on
Mounting support DIN rail
9 mm pitches 2
Height 81 mm
Width 18 mm
Depth 75 mm
Colour White
Connections - terminals Screw clamp terminals1 cable(s) 0.75…10 mm² rigid
Screw clamp terminals1 cable(s) 0.5…6 mm² flexible
Screw clamp terminals2 cable(s) 0.75…4 mm² rigid
Screw clamp terminals2 cable(s) 0.5…6 mm² flexible
PM210011-NUI900-ESE-00001_02 116 of 154
Wire stripping length 12 mm
Tightening torque 2 N.m

Environment
Standards IEC 60269-1/2
IEC EN 60947-3
IP degree of protection IP20
Pollution degree 3
Ambient air temperature for operation -20…60 °C
Ambient air temperature for storage -40…80 °C

Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
REACh free of SVHC Yes
EU RoHS Directive Compliant
EU RoHS Declaration
Toxic heavy metal free Yes
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure Product Environmental Profile
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins

PM210011-NUI900-ESE-00001_02 117 of 154


Presentation Control and signaling units Ø 22
Harmony XB7, monolithic
Pushbuttons, switches and pilot lights

Presentation
The Harmony® XB7 range of plastic control and signaling units is a monolithic range
designed for use in the industrial, tertiary and building sectors. It is simple to use
and quick to install.

b This range includes:


b

v Pushbuttons and switches designed for Start/Stop control of machines and


v

installations, adjustment and parametering (contact functions): Pushbuttons,


selector/key switches, Emergency stop or Emergency switching off pushbuttons
v Pilot lights designed for visual signaling (signaling functions)
v

v Illuminated pushbuttons designed for control and signaling (contact functions +


v

signaling functions)

b The range comprises complete units, with round plastic bezel, and 6 pilot light
b

colors.

b The pushbutton and switch control offer comprises:


b

v Flush and projecting spring return pushbuttons, with or without marking


v

v Flush latching pushbuttons, without marking


v

v Projecting spring return or latching illuminated pushbuttons


v

v Emergency stop trigger action and mechanically latching mushroom head


v

pushbuttons (conforming to standards EN/IEC 60204-1 and EN/ISO 13850)


v Emergency switching off mechanically latching mushroom head pushbuttons
v

(conforming to standard IEC 60364-5-53)


v Selector switches, with standard black handle, and key switches
v

v Legends and legend holders


v

v Accessories and spare parts


v

b The pilot light signaling offer includes:


b

v Pilot lights with integral LED


v

v Pilot lights for BA 9s base fitting bulbs


v

The two types of pilot lights are for direct supply or with resistor.

Installation
b Harmony XB7 products are both simple and quick to install:
b

v Mounting by single installer


v

v Fixing by a single locking nut


v

b Two types of connection are available:


b

v Screw clamp terminals


v

v Faston connectors (only for pilot lights)


v

Environment
The performance features of the XB7 range meet the following specifications:

b International standards and approvals:


b

v For the entire range: EN/IEC 60947-1, EN/IEC 60947-5-1, EN/IEC 60947-5-4,
v

UL 508, CSA C22-2 no. 14, GB 14048.5


v For Emergency stop pushbuttons: EN/IEC 60947-5-5, EN/ISO 13850 and
v

EN/IEC 60204-1
v For Emergency switching off pushbuttons: EN/IEC 60364-5-53
v

b International certifications: UL, CSA, CCC, GOST.


b

b Degrees of protection:
b

v Front face: IP 65 (IP 54 for Emergency switching off pushbuttons)


v

v Rear face: IP 20 (protection against direct contact)


v

For more technical information, please refer to our website www.schneider-electric.com.

PM210011-NUI900-ESE-00001_02 118 of 154


References (continued) Control and signaling units Ø 22
Harmony XB7, monolithic
Pushbuttons, switches and pilot lights

Pilot lights
With integral LED
Shape of Type of light Color of Sold in Unit reference by supply voltage (1) Weight
head source lens lots of 24 V a/c 120 V a 230 V a kg/lb
(included)
PF100406

Integral LED Green 10 XB7EV03BP XB7EV03GP XB7EV03MP 0.020/0 044


.

Red 10 XB7EV04BP XB7EV04GP XB7EV04MP 0.020/0 044


.

XB7EV08BP
Yellow 10 XB7EV05BP XB7EV05GP XB7EV05MP 0.020/0 044
.

Blue 10 XB7EV06BP XB7EV06GP XB7EV06MP 0.020/0 044


.

Clear 10 XB7EV07BP XB7EV07GP XB7EV07MP 0.020/0 044


.

Orange 10 XB7EV08BP XB7EV08GP XB7EV08MP 0.020/0 044


.

With BA 9s base fitting


Shape of Supply Color of Sold in Unit reference (1) Weight
head lens lots of With bulb Without bulb kg/lb
PF100407

With resistor, Green 10 XB7EV73P XB7EV730P 0.020/0 044


.

for 130 V,
2.6 W bulb Red 10 XB7EV74P XB7EV740P 0.020/0 044
XB7EV75P Supply voltage:
.

230 V a,
Yellow 10 XB7EV75P XB7EV750P 0.020/0 044
50-60 Hz
.

Blue 10 XB7EV76P XB7EV760P 0.020/0 044


.

Clear 10 XB7EV77P XB7EV770P 0.020/0 044


.

Orange 10 XB7EV78P XB7EV780P 0.020/0 044


.

Direct for BA 9s Green 10 – XB7EV63P 0.020/0 044


.

base fitting
incandescent Red 10 – XB7EV64P 0.020/0 044
bulb
.

Supply voltage:
Yellow 10 – XB7EV65P 0.020/0 044
y 250 V
.

(2)
Blue 10 – XB7EV66P 0.020/0 044
.

Clear 10 – XB7EV67P 0.020/0 044


.

Orange 10 – XB7EV68P 0.020/0 044


.

Selector switches and key switches


Shape of Type of operator Type of contact Number and type of Sold in lots of Unit reference Weight
head positions (3) kg/lb
NO NC
PF100409

Standard handle, 1 – 2, stay put 10 XB7ND21 0.026/0 057


.

black
1 1 2, stay put 10 XB7ND25 0.026/0 057
.

XB7ND21
2 – 3, stay put 10 XB7ND33 0.026/0 057
.

Key 1 – 2, key 10 XB7NG21 0.050/0 110


.

(key no 455) withdrawal


PF100410

in LH position
2 – 3, key 10 XB7NG33 0.050/0 110
.

withdrawal
XB7NG33 in centre
position
(1) For Faston connection version (1 x 6.35 mm/0.04 x 0.24 in. and 2 x 2.8 mm/0.08 x 0.11 in. ), add the number “3” to the end of
the reference.
Example: XB7EV07BP becomes XB7EV07BP3.
(2) Bulb characteristics for direct supply pilot lights: 250 V, 2.6 W.
(3) The symbol “ ” indicates key withdrawal position.

PM210011-NUI900-ESE-00001_02 119 of 154


Presentation (continued) Control and signaling units
Harmony XB5, plastic
Pushbuttons, switches, and pilot lights

Configurable display: Harmony Display Module


Harmony display units are used to configure the machines through touch panels
and have following offers :

Harmony Display is a configurable display module with Ø 22 mm mounting in the


front of a control panel or directly on the front of a machine. With ZBSD01 SD card,
you can configure TM221C16R into an IO Block which is compatible with Harmony
Display. The offer provides features as below:
Harmony Display Module b No programmation needed : just configure it on the touch screen
b 2 analog displays 0...10V, 4...20 mA from physical analog input in the
representation of numerical, bar graph, and meter
b Threshold notification via relay output and background color change
b 8 digital status display, counters, or hour meters
b 1 CAM switch function of 7 steps and 5 outputs
b Harmony Display has an IP65 protective rating on the front face and the operating
temperature can be between 0..50 degrees celsius
b As options, 2 temperature inputs, 2 analog inputs, or 2 analog outputs can be
added

Installation
Harmony XB5 products are both simple and quick to install:
b Mounting by single installer (self-maintaining head in its cut-out)
b Clip-together component system (head, body, contact blocks, and LED)
b Anti-loosening system for screw clamp terminals on contact blocks

Harmony XB5 standard mounting products are installed with or without a notch in a
Ø 22 mm/0.866 in. hole, thanks to the self-cleavable orientation pin.

For installation of Harmony XB5 For installation of Harmony XB5 flush


standard mounting products mounting products

Harmony XB5 flush mounting products are installed without a notch in a Ø 30 mm/
1.181 in. hole. This gives flush mounting products the same actuating area as that
of standard mounting products, offering optimized ergonomics for operators even
when wearing gloves.

Flush solutions mounted in a Ø 22 mm/0.866 in. hole can be achieved using the
Harmony XB6 range. Please refer to the Harmony XB6 catalog for details.

Environment
The performance of the Harmony XB5 range meets some of the most demanding
international standards and approvals:

b Certified and approved for meeting requirements worldwide:


EN/IEC, CE marking, UL, CSA, CCC, EAC, JIS, NEMA, and marine approvals
b Protection against the ingress of solid foreign objects, dust, and water: IP 66, 67,
69, 69K, type 4X
b Operating temperature range from -40 °C to +70 °C/-40 °F to +158 °F for outdoor
applications
b High chemical robustness
b Shock protection level up to IK03
b High vibration resistance with shakeproof connection screws (periodic
retightening unnecessary)

PM210011-NUI900-ESE-00001_02 120 of 154


References Control and signaling units
Harmony XB5, plastic
Assembly of other products using: Selector switches with standard handle
Body/contact assemblies: see page 78
Accessories: see page 90

Selector switches with standard handle (1)


Screw clamp terminal connections (Schneider Electric anti-loosening system)
Shape Type of Type of contact Positions Reference Weight
of head operator Number Type kg/lb

NO NC For black bezel For gray bezel


(2)
106201

Complete units (3)


Standard 1 – 2-position Stay put XB5AD21 XB5AD21C0 0.043/0.095
handle, 90° (ZB5AZ101 + (ZB5AZ101 +
black ZB5AD2) ZB5AD2C0)
XB5AD33
1 – Spring XB5AD41 XB5AD41C0 0.046/0.101
return from (ZB5AZ101 + (ZB5AZ101 +
right ZB5AD4) ZB5AD4C0)
to left
1 1 Stay put XB5AD25 XB5AD25C0 0.043/0.095
(ZB5AZ105 + (ZB5AZ105 +
ZB5AD2) ZB5AD2C0)
XB5_633_CPMFS18072

2 – 3-position Stay put XB5AD33 XB5AD33C0 0.043/0.095


± 45° (ZB5AZ103 + (ZB5AZ103 +
ZB5AD3) ZB5AD3C0)

Spring XB5AD53 XB5AD53C0 0.043/0.095


XB5AD33C0
return to (ZB5AZ103 + (ZB5AZ103 +
center ZB5AD5) ZB5AD5C0)

Heads only (3)


Standard handle, black 2-position Stay put ZB5AD2 ZB5AD2C0 0.017/0.037
90°
106215

Spring ZB5AD4 ZB5AD4C0 0.020/0.044


return from
ZB5AD2 right
to left
3-position Stay put ZB5AD3 ZB5AD3C0 0.017/0.037
± 45°

Spring ZB5AD5 ZB5AD5C0 0.017/0.037


return to
center

Spring ZB5AD7 ZB5AD7C0 0.017/0.037


return from
left to center

Spring ZB5AD8 ZB5AD8C0 0.017/0.037


return from
right to
center
Heads only with other colored handles (2) (3)
Standard handle, white Add suffix 01 to the reference, for example: ZB5AD201 ZB5AD201C0
IOP107728

Standard handle, green Add suffix 03 to the reference, for example: ZB5AD203 ZB5AD203C0

Standard handle, red Add suffix 04 to the reference, for example: ZB5AD204 ZB5AD204C0

ZB5AD204 Standard handle, yellow Add suffix 05 to the reference, for example: ZB5AD205 ZB5AD205C0

Standard handle, blue Add suffix 06 to the reference, for example: ZB5AD206 ZB5AD206C0

(1) For recommended maximum number of contacts and sequence of contacts constituting the body (fixing collar and contact)
associated with the head, see page 22.
(2) For white color plated bezel replace C0 with C1, and for other color plated bezels using the web customization tool, see page 5.
(3) To add customized markings on these references using the web customization tool, see page 5.

PM210011-NUI900-ESE-00001_02 121 of 154


ClimaSys CC

Thermal Management System ClimaSys CC, Introduction

Mechanical thermostats

Thermostat Thermostat Thermostat Double Thermostat


with NC contact with NO contact with NO/NC contact
Characteristics NSYCCOTHC NSYCCOTHO NSYCCOTHI NSYCCOTHD
(NSYCCOTHCF) (NSYCCOTHOF) (NSYCCOTHDF)
Thermostat with NC Contact:
• To control the stopping of a resistance heater when the temperature exceeds the displayed value.
Thermostat with NO Contact:
• To control the starting of a fan when the temperature exceeds the displayed maximum value,
• To control the temperature inside the enclosure by only starting the fan when necessary,
thus increasing the service life of the fan and reducing the clogging of the filter.
Button color Red Blue Black Red and blue
Ingress protection rating IP20 IP20 IP20 IP20
Sensor element Bimetal Bimetal Bimetal Bimetal
Contact NC, forced rupture NC, forced rupture Inverse,forced rupture NO/NC, forced rupture
Contact resistance < 10 mΩ < 10 mΩ < 10 mΩ < 10 mΩ
Service life > 100,000 cycles > 100,000 cycles > 100,000 cycles > 100,000 cycles
Switching capacity • 250 V AC; 10 A • 250 V AC; 10 A • 250 V AC; 10 A • 250 V AC; 10 A
(resistive load) (resistive load) (resistive load) (resistive load)
• 120 V AC; 15 A • 120 V AC; 15 A • 120 V AC; 15 A
(resistive load) (resistive load) (resistive load)
• 250 V AC/120 V AC 2 A • 250 V AC/120 V AC 2 A • 250 V AC/120 V AC 2 A
(inductive load cos = 0.6) (inductive load cos = 0.6) (inductive load cos = 0.6)
• 30 W DC • 30 W DC • 30 W DC
Max interrupting capacity with NC NO 250 V AC 4 A NA
direct current (inductive load cos = 0.6)
30 W DC
Connection Two 2.5-mm² terminals Two 2.5-mm² terminals Four 2.5-mm² terminals Six 2.5-mm² terminals
Mounting By clip on 35-mm DIN rail By clip on 35-mm DIN rail By clip on 35-mm DIN rail By clip on 35-mm DIN rail
Enclosure UL 94 V-0 plastic, light grey UL 94 V-0 plastic, light grey UL 94 V-0 plastic, light grey UL 94 V-0 plastic, light grey
Dimensions 60 x 33 x 43 mm 60 x 33 x 43 mm 67 x 50 x 44 mm 60 x 33 x 43 mm
Weight 40 g 40 g 100 g 40 g
Mounting position Indifferent Indifferent Indifferent Indifferent
Operating temperature -20...+80 ºC (-4...+176 ºF) -20...+80 ºC (-4...+176 ºF) -20...+80 ºC (-4...+176 ºF) -20...+80 ºC (-4...+176 ºF)
Hysteresis 7K 7K 7K 7K
Temperature setting range 0...+60 ºC 0...+60 ºC +5...+60 ºC 0...+60 ºC
Display °C (°F) °C (°F) °C (°F) °C (°F)
Max. command intensity 10 A 250 V 10 A 250 V (NO) 5 A (NC) 10 A (NO) 5 A (NC) 10 A

Thermal control

Mechanical and electronic Operational temperature range


thermostats • For mechanical thermostats: 0 ºC ... +60 ºC
• Large range of temperature control. • For electronic thermostats: -40 ºC ... +80 ºC
• Small dimensions.
• Easily accessible terminals.

14
CC LED display
• Display visible even in the dark.

PM210011-NUI900-ESE-00001_02 122 of 154


Thermal Management System ClimaSys CR

Aluminum PTC heaters


• Extruded aluminum body.
• Surface temperature limited to 75 ºC when the ambient temperature is -5 ºC.
• Heaters equipped with a power cable with a length of 500 mm with silicon insulation, or with a connection terminal block.
Conditions of use:
• The heaters must be installed with a thermal controller to control
the temperature or the humidity inside the enclosure
• The enclosure must be sealed to prevent the entry of air from the outside
• An electrical protection device must be installed on the supply side of the unit

Characteristics Power (W) Voltage (V) References


Aluminum PTC heater 10 12-24 DC NSYCR10WU1
Aluminum PTC heater 10 110-250 AC NSYCR10WU2
Aluminum PTC heater 20 12-24 DC NSYCR20WU1
Aluminum PTC heater 20 110-250 AC NSYCR20WU2
Aluminum PTC heater 20 270-420 AC NSYCR20WU3
NSYCR10WU1 Aluminum PTC heater 55 12-24 DC NSYCR55WU1
Aluminum PTC heater 55 110-250 AC NSYCR55WU2
Aluminum PTC heater 55 270-420 AC NSYCR55WU3
Aluminum PTC heater 90 12-24 DC NSYCR100WU1
Aluminum PTC heater 90 110-250 AC NSYCR100WU2
Aluminum PTC heater 90 270-420 AC NSYCR100WU3
Aluminum PTC heater 150 12-24 DC NSYCR150WU1
Aluminum PTC heater 150 110-250 AC NSYCR150WU2
Aluminum PTC heater 150 270-420 AC NSYCR150WU3
Aluminum PTC heater with fan 250 115 AC NSYCR250W115VV
Aluminum PTC heater with fan 250 230 AC NSYCR250W230VV
Aluminum PTC heater with fan 400 115 AC NSYCR400W115VV
Aluminum PTC heater with fan 400 230 AC NSYCR400W230VV
Resistive heater 200 230 AC NSYCRS200W230V
NSYCR250W115VV

Thermofan

160
Combination of a resistance heater and an axial
fan to ensure uniform heating of the enclosure.
• Fixing by clip on a DIN rail.
• Thermostat adjustable from 0…+60 ºC.
• Visual operation indicator. 97 120

Characteristics Power (W) Voltage (V) References


Thermofan 350/550 120 AC NSYCRP1W120VTVC
NSYCRP1W120VTVC Thermofan 350/550 230 AC NSYCRP1W230VTVC

14
CR

PM210011-NUI900-ESE-00001_02 123 of 154


RH21 with local manual fault reset
System to be protected LV y 1000 V RH21M RH21P

DB126090.eps

DB126091.eps
1P
x RH2

Vigire

RH21M

Vigirex

DIN-rail mount. Front-panel mount.

Sensitivity 0.03 A - instantaneous


Sensitivity 0.3 A - instantaneous or with 0.06 s time delay
Power supply 12 to 24 V AC - 12 to 48 V DC 50/60 Hz 56160 56260
48 V AC 50/60 Hz 56161
110 to 130 V AC 50/60 Hz 56162 56262
220 to 240 V AC 50/60/400 Hz 56163 56263
380 to 415 V AC 50/60 Hz 56164 56264
440 to 525 V AC 50/60 Hz 56165 56265
RH99 with local manual fault reset
System to be protected LV y 1000 V RH99M RH99P

DB126092.eps

DB126093.eps
9P
x RH9

Vigire

RH99M

Vigirex

DIN-rail mount. Front-panel mount.

Sensitivity 0.03 A to 30 A - instantaneous or with 0 to 4.5 s time delay


Power supply 12 to 24 V AC - 12 to 48 V DC 50/60 Hz 56170 56270
48 V AC 50/60 Hz 56171 56271
110 to 130 V AC 50/60 Hz 56172 56272
220 to 240 V AC 50/60/400 Hz 56173 56273
380 to 415 V AC 50/60 Hz 56174 56274
440 to 525 V AC 50/60 Hz 56175 56275
RH197 with local manual or automatic fault reset (1)
System to protected LV y 1000 V RH197M RH197P
DB403206.eps

DB126094.eps
on
Fault

50%
97P
x RH1

Vigire 40%

30%

20%

.5 1
.25 2.5
.1 .15
.15 5
.075 .2
0
.05 .3
.03
x1

/M
60947-2
IEC

Test

Reset

DIN-rail mount. Front-panel mount.

Alarm: 50 % of fault threshold - instantaneous


Fault: sensitivity 0.03 A to 30 A - instantaneous or with 0 to 4.5 s time delay
Single-phase power supply 48 V AC - 24 to 130 V DC 50/60 Hz 56515 56505
110 to 130 V AC (2) 50/60 Hz 56516 56506
220 to 240 V AC (2) 50/60/400 Hz 56517 56507
380 to 415 V AC (2) 50/60 Hz 56518 56508
Alarm: 100 % of fault threshold - instantaneous
Fault: sensitivity 0.03 A to 30 A - instantaneous or with 0 to 4.5 s time delay
Single-phase power supply 48 V AC - 24 to 130 V DC 50/60 Hz 56515 56510
110 to 130 V AC (2) 50/60 Hz 56516 56511
220 to 240 V AC (2) 50/60/400 Hz 56517 56512
380 to 415 V AC (2) 50/60 Hz 56518 56513
(1) Selected via a switch.
(2) RH197M: 110 V, 230 V, 400 V.

PM210011-NUI900-ESE-00001_02 124 of 154

433E.indb 3 13/10/2011 15:56:32


Toroids and rectangular sensors,
communication module

Sensors
Closed toroids, A-type
Type Ie (A) Inside diameter (mm)
DB126098.eps

rated operational current


TA30 65 30 50437
PA50 85 50 50438
IA80 160 80 50439
MA120 250 120 50440
SA200 400 200 50441
GA300 630 300 50442
Accessory for closed toroids
Magnetic ring For TA30 toroid 56055
For PA50 toroid 56056
DB107032.eps

For IA80 toroid 56057


For MA120 toroid 56058

Split toroids, OA-type


Type Ie (A) Inside diameter (mm)
DB126099.eps

rated operational current


POA 85 46 50485
GOA 250 110 50486

Rectangular sensors
Inside dimensions (mm) Ie (A)
DB126100.eps

280 x 115 1600 56053


470 x 160 3200 56054

Communication module
DC150 data concentrator 50823
DB403922.eps

110-240 V AC / 115-125 V DC

DC150 BBus JBus


OK com. com.

error 24V error

9600
19200
5
3 7
1 9
N°1 N°2 N°1
15
13
5
3 7
1 9 N°2
15
13

Note: sensor-relay link: twisted cable not supplied (see “Installation and connection” chapter).

PM210011-NUI900-ESE-00001_02 125 of 154

433E.indb 5 13/10/2011 15:56:35


PHOTOCELL LIGHTING CONTROL SWITCHES

1IC 7242
Photocell lighting control switch for wall-mounting and/or pole installation
• Power supply 230V a.c. 50 / 60Hz • Intervention threshold adjustment trimmer, 2 - 200 Lux
• Outdoor installation • Threshold signalling LED
• Output 1 polarized NO contact: 16 (2) A / 250Va.c. • Anti-UV opaline housing
• Connection with cables up to 2.5 mm2 • Protection degree IP 54
• Wiring with shielded cable diameter 4-9 mm • Dimensions (Ø L x W x H) Ø 82 x 97 x 101 mm

1IC 7243
Photocell lighting control switch with replaceable control module for wall-mounting and/or pole installation
Product being particularly suitable to facilitate system maintenance personnel: the control part that can be removed
from the base of the contacts allows a quick intervention in the product without disconnecting the load
• Power supply 230V a.c. 50/60Hz • Intervention threshold adjustment trimmer, 2 - 200 Lux
• Outdoor installation • Threshold signalling LED
• Output 1 polarized NO contact: 16 (2) A / 250Va.c. • Anti-UV opaline housing
• Connection with cables up to 2.5 mm2 • Protection degree IP 65
• Wiring with shielded cable diameter 7-11 mm • Dimensions (L x W x H) 72 x 37.5 x 147 mm
• Pre-calibrated at the factory at 10 Lux ± 20%

1PR 7243M Spare module for photocell lighting control switch item 7243
• Power supply 230V a.c. 50/60Hz • Intervention threshold adjustment trimmer, 2 - 200 Lux
• Outdoor installation • Threshold signalling LED Anti-UV opaline housing
• Output 1 polarized NO contact: 16 (2) A / 250Va.c. • Dimensions (L x W x H) 72 x 37.5 x 80 mm
• Pre-calibrated at the factory at 10 Lux ± 20%

1IC 7245
Photocell lighting control switch model “FEBO” for wall-mounting and/or pole installation
The factory 10 LUX calibration prevents difficult interventions by the installer
• Power supply 230V a.c. 50 / 60Hz • Intervention threshold adjustment trimmer, 2 - 200 Lux
• Outdoor installation • Threshold signalling LED
• Output 1 polarized NO contact: 16 (2) A/250Va.c. • Anti-UV opaline housing
• Connection with cables up to 2.5 mm2 • Protection degree IP 65
• Wiring with shielded cable diameter 7-11 mm • Dimensions (L x W x H) 55 x 45 x 106 mm
• Pre-calibrated at the factory at 10 Lux ± 20%

1IC 7051
Photocell lighting control switch with adjustment 2-10.000Lux, 2 DIN
It allows progressively lighting street tunnels

• Power supply 230V a.c. 50 / 60Hz DIN assembly plus • Threshold calibration signalling LED
outdoor probe • Operation signalling LED Intervention threshold
• Output 1 changeover contact, potential-free: adjustment trimmer
16 (2) A / 250V a.c. • Dimensions DIN (L x W x H) 35 x 60 x 90 mm
• Connection with cables up to 2.5 mm2
• Adjustment range 2-100 / 2-1000 / EXTERNAL PROBE
2-10.000 Lux (3 scales) • Anti-UV opaline housing
• Activation delay 8 sec ± 10% • Protection degree IP 65
• Deactivation delay 38 sec ± 10% • Dimensions of the probe (L x W x H) 28 x 48 x 56 mm

1IC 7052
Photocell lighting control switch with adjustment 2-200 Lux, 2 DIN
Provided with hysteresis and activation / deactivation delays to prevent false switching
• Power supply 230V a.c. 50 / 60Hz DIN assembly plus • Operation signalling LED Intervention threshold
outdoor probe adjustment trimmer
• Output 1 changeover contact, potential-free: • Dimensions DIN (L x W x H) 35 x 60 x 90 mm
16 (2) A / 250V a.c.
• Connection with cables up to 2.5 mm2 EXTERNAL PROBE
• Adjustment range 2-200 Lux adjustable • Anti-UV opaline housing
• Activation delay 8 sec ± 10% • Protection degree IP 65
• Deactivation delay 38 sec ± 10% • Dimensions of the probe (L x W x H) 28 x 48 x 56 mm
• Threshold calibration signalling LED

PM210011-NUI900-ESE-00001_02 126 of 154


PM210011-NUI900-ESE-00001_02 127 of 154
PM210011-NUI900-ESE-00001_02 128 of 154
Product data sheet
Specifications

EasyLogic PM2130, Power &


Energy meter, up to the 31st
harmonic, LED display, RS485,
class 0.5S
METSEPM2130

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range EasyLogic

Product name EasyLogic PM2100

Device short name PM2130

Product or component type Power meter

Complementary
Device application Sub billing
Power monitoring

Power quality analysis total harmonic distortion


up to the 31st harmonic

Type of measurement Apparent power min/max, total


Active and reactive power min/max, total
Current min/max, avg
Voltage min/max, avg
Frequency min/max, avg
Total current harmonic distortion THD (I) per phase
Total voltage harmonic distortion THD (U) per phase
Power factor min/max, avg
Apparent energy total
Active and reactive energy total

Metering type Peak demand currents


Active power P, P1, P2, P3
Demand power P, Q, S
Reactive power Q, Q1, Q2, Q3
Apparent power S, S1, S2, S3
Active, reactive, apparent energy (signed, four quadrant)
Voltage U, U21, U32, U13, V, V1, V2, V3
Current I, I1, I2, I3
Calculated neutral current
Unbalance current
Peak demand power PM, QM, SM

Accuracy class Class 1 reactive energy conforming to IEC 62053-24


Class 0.5S active energy conforming to IEC 62053-22
Class 5 harmonic distorsion (I THD & U THD)

Measurement accuracy Apparent power +/- 0.5 %


Active energy +/- 0.5 %
Reactive energy +/- 1 %
Active power +/- 0.5 %
Voltage +/- 0.5 %
Power factor +/- 0.01
Current +/- 0.5 %
Frequency +/- 0.05 %

Measurement current 5…6000 mA

Measurement voltage 35…480 V AC 50/60 Hz between phases


20…277 V AC 50/60 Hz between phase and neutral
480…999000 V AC 50/60 Hz with external VT

Frequency measurement range 45…65 Hz

PM210011-NUI900-ESE-00001_02 129 of 154


[Us] rated supply voltage 80...277 V AC 45...65 Hz +/- 10 %
100...277 V DC +/- 10 %

Network frequency 50 Hz
60 Hz

Ride-through time 50 ms 120 V AC typical


50 ms 230 V AC typical
50 ms 125 V DC typical

[In] rated current 1A


5A

Maximum power consumption in 8 VA at 277 V AC


VA

Maximum power consumption in 3.3 W (power lines (AC))


W 3.3 W at 277 V (power lines (DC))

Input impedance Current (impedance <= 0.3 mOhm)


Voltage (impedance > 5 MOhm)

Tamperproof of settings Protected by access code

Display type 7 segments LED

Display colour Red

Messages display capacity 3 fields of 4 characters

Display digits 12 digit(s) - 14.2 mm in height

Demand intervals Configurable from 1 to 60 min

Information displayed Demand current (past value)


Demand current (present value)
Demand power (past value)
Demand power (present value)
Voltage
Current
Frequency
Energy consumption
Harmonic distortion
Power factor
Active power
Apparent power
Reactive power
Unbalanced in %

Control type 3 x button

Local signalling Red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh)
Green LED: module operation and integrated communication

Number of inputs 0

Number of outputs 0

Communication port protocol Modbus RTU at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation
2500 V

Communication port support Screw terminal block: RS485

Data recording Power logs


Time stamping
Energy consumption logs
Min/max for 8 parameters

Function available Real time clock

Sampling rate 64 samples/cycle

Cybersecurity Enable/disable communication ports

Communication service Remote monitoring

Product certifications CE conforming to IEC 61010-1


CULus conforming to UL 61010-1
CULus conforming to CSA C22.2 No 61010-1
RCM
EAC
C-Tick

Mounting mode Clip-on

Mounting position Vertical

Mounting support Framework

PM210011-NUI900-ESE-00001_02 130 of 154


Provided equipment 1 x installation guide

Measurement category Category III 480 V


Category II 480…600 V

Electrical insulation class Class II


Double insulation

Flame retardance V-0 conforming to UL 94

Connections - terminals Current transformer: screw connection (bottom) 6


Voltage inputs: screw connection (top) 4

Material Polycarbonate

Width 96 mm

Depth 76.09 mm total:


61.64 mm embedded:

Height 96 mm

Net weight 300 g

Compatibility code PM2130

Environment
Service life 7 year(s)

IP degree of protection IP54 front: conforming to IEC 60529


IP30 body: conforming to IEC 60529

Relative humidity 5…95 % at 50 °C

Pollution degree 2

Ambient air temperature for -10…60 °C


operation

Ambient air temperature for -25…70 °C


storage

Operating altitude <= 2000 m

Electromagnetic compatibility Electrostatic discharge conforming to IEC 61000-4-2


Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
Surge immunity test conforming to IEC 61000-4-5
Conducted RF disturbances conforming to IEC 61000-4-6
Magnetic field at power frequency conforming to IEC 61000-4-8
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Emission tests conforming to FCC part 15 class A

Overvoltage category III

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 11.5 cm

Package 1 Width 8.7 cm

Package 1 Length 12.0 cm

Package 1 Weight 404.0 g

Unit Type of Package 2 S03

Number of Units in Package 2 18

Package 2 Height 30.0 cm

Package 2 Width 30.0 cm

Package 2 Length 40.0 cm

Package 2 Weight 7.71 kg

Unit Type of Package 3 P12

PM210011-NUI900-ESE-00001_02 131 of 154


Number of Units in Package 3 432

Package 3 Height 80.0 cm

Package 3 Width 80.0 cm

Package 3 Length 120.0 cm

Package 3 Weight 197.112 kg

Offer Sustainability
Sustainable offer status Green Premium product

REACh Regulation REACh Declaration

EU RoHS Directive Compliant


EU RoHS Declaration

Mercury free Yes

China RoHS Regulation China RoHS declaration

RoHS exemption information Yes

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

PM210011-NUI900-ESE-00001_02 132 of 154


PM210011-NUI900-ESE-00001_02 133 of 154
BUSSMANN
Technical Data 10163
Effective August 2017
Supersedes May 2016 SERIES

Bussmann series
NH Bases
Product description
Eaton’s Bussmann series NH Bases have been
designed with thermoplastic bodies DIN-Rail
and/or screw mounting (size 4 screw mounting
only).
This range comes with a accessories including
phase barriers: IP20 finger safe protection kits
and neutral links.
Microswitch also available for remote signaling
of fuse link operation.

Standard features
• Complies with IEC 60269-1 and 2 fuse
system A (NH Base), manufacturers type test
certificates of compliance available.
• 3-pole integral NH00 Base available with
reduced width
• Clip-in phase barriers, terminal shrouds and
fuse covers available
• Vibration tested to IEC 60068-2-6 for marine
use

PM210011-NUI900-ESE-00001_02 134 of 154


Technical Data 10163 Bussmann series
Effective August 2017 NH Bases

Catalogue symbol
• 1-pole DIN-Rail and screw mounting: SD(size)-D
• 1-pole screw mounting only: SD(size)-S
• 3-pole DIN-Rail and screw mounting: TD(size)-D
• 3-pole Integral DIN-Rail and screw mounting: TD00-DxI (see
catalogue numbers for details)

Technical data
• Rated voltage: 690 V a.c.
• Rated current: 160 to 1600 A
• Rated for fuse links with breaking capacity of 120 kA

Standard/Approvals
• IEC 60269-1 and 2
• VDE 0636-1 and 2

Packaging
• 1-pole: 3
• 3-pole and SD4: 1

Technical data
SD00-D
TD00-D SD1-D SD2-D SD3-D
Fuse base catalogue numbers TD00-DI TD1-D TD2-D TD3-D SD4-S SD4-S1600
Base Glass filled PBT
Contacts Silver plated copper
Screw, nuts and washers Zinc clear plated steel
 35°C 1 1 1 1 1 1
Derating temperature factors for 40°C 0.95 0.95 0.95 0.95 0.95 0.95
maximum current
50°C 0.85 0.85 0.85 0.85 0.85 0.85
Maximum power acceptance 12W 32W 45W 60W 110W 145W
Degree of protection with covers fitted IP20 IP20 IP20 IP20 - -
Terminal screw M8 M10 M10 M12 M16 M16
Maximum tightening torque terminal screw 10N•m 32N•m 32N•m 32N•m 56N•m 56N•m
DIN-Rail      
Fixing
Screw      
With microswitch 16A/250V Fuse operated signal      
Operating temperature range -20 to 70°C
Storage temperature range -40 to 80°C

PM210011-NUI900-ESE-00001_02 135 of 154


BUSSMANN
Effective September 2015
Technical Data 10164 Supersedes February 2015 SERIES

Bussmann series
500 Volts gG/gL NH Fuse links
Product description
Eaton’s Bussmann series 500 Volts NH square
bodied industrial fuse links are suitable for a
wide variety of applications.

Standard features
• Reliable dual indicator system
• Low temperature rise
• Globally compliant
• Compatible with Bussmann series PV NH
base range (see data sheet 10163)

PM210011-NUI900-ESE-00001_02 136 of 154


Technical Data 10164 Bussmann series
Effective September 2015 500 Volts gG/gL NH Fuse links

Catalogue symbol: Fuse holders (ordered separately)


• (amp)NHG(size)B • Fuse bases:
• DIN-Rail mounting and screw mounting:
1-pole SD(size)-D, 3-pole TD(size)-D
Fuse size:
• Screw mounting only: SD(size)-S
• 000 to 4
• Fuse rails - vertical: BFR Series
• Fuse switch disconnectors vertical: BFD Series
Technical data:
• Fuse switch disconnectors horizontal: BFH Series
• Volts: 500 V a.c.
• Amps: 2 to 1250 A
• Breaking capacity: 120 kA AC
• Operating frequency: 45-62 Hz
• Class of operation: gG/gL

Standards/Approvals:
• IEC 60269
• VDE 0636
• DIN 43620
• CE

Microswitches:
• 170H0236
• BVL50

Packaging:
• Sizes 000 to 3: 3 per carton
• Size 4: 1 per carton

Size - mm

Table 1. NH Sizes

Size a1 a2 a3 a4 b c1 c2 d e1 e2 e3 e4 f
(max) (max) (max) (max) (max)

000 78.5 ± 1.5 54 45±1.5 49±1.5 15 35 10 2±0.5 41 21 16 6 8


00 78.5 ± 1.5 54 45±1.5 49±1.5 15 35 11 2±0.5 48 30 25 6 15
0 125±2.5 68 +3
-1.5 62 +3
-1.5 68 15 35 11 2.5±0.5 48 30 25 6 15
01 135±2.5 75 62±2.5 68±2.5 15 40 11 2.5±0.5 48 30 25 6 15
1 135±2.5 75 62±2.5 68±2.5 20 40 11 2.5±0.5 53 40 25 6 15
02 150±2.5 75 62±2.5 68±2.5 20 48 11 2.5±0.5 53 40 25 6 15
2 150±2.5 75 62±2.5 68±2.5 25 48 11 2.5±0.5 61 53 25 6 15
03 150±2.5 75 62±2.5 68±2.5 25 60 11 2.5±0.5 61 53 25 6 15
3 150±2.5 75 62±2.5 68±2.5 32 60 11 3±0.5 75 70 25 6 18
4 200±3 84 62±2.5 90±3 50 85 10 3±0.5 102 87 25 8 30

PM210011-NUI900-ESE-00001_02 137 of 154


Bussmann series Technical Data 10164
500 Volts gG/gL NH Fuse links Effective September 2015

Table 2. Part numbers sizes 000 to 01

Size Rated Rated gG/gL dual indicator Pack


current voltage Voltage conducting Insulated metal quantity
(Amps) (V a.c.) metal gripping lugs gripping lugs
000 2 500 2NHG000B 2NHG000BI 3
000 4 4NHG000B 4NHG000BI
000 6 6NHG000B 6NHG000BI
000 10 10NHG000B 10NHG000BI
000 16 16NHG000B 16NHG000BI
000 20 20NHG000B 20NHG000BI
000 25 25NHG000B 25NHG000BI
000 32 32NHG000B 32NHG000BI
000 35 35NHG000B 35NHG000BI
000 40 40NHG000B 40NHG000BI
000 50 50NHG000B 50NHG000BI
000 63 63NHG000B 63NHG000BI
000 80 80NHG000B 80NHG000BI
000 100 100NHG000B 100NHG000BI
00 50 50NHG00B 50NHG00BI*
00 63 63NHG00B 63NHG00BI*
00 80 80NHG00B 80NHG00BI*
00 100 100NHG00B 100NHG00BI*
00 125 125NHG00B 125NHG00BI
00 160 160NHG00B 160NHG00BI
0 6 6NHG0B -
0 10 10NHG0B -
0 16 16NHG0B -
0 20 20NHG0B -
0 25 25NHG0B -
0 32 32NHG0B -
0 35 35NHG0B -
0 40 40NHG0B -
0 50 50NHG0B -
0 63 63NHG0B -
0 80 80NHG0B -
0 100 100NHG0B -
0 125 125NHG0B -
0 160 160NHG0B -
01 6 6NHG01B 6NHG01BI
01 10 10NHG01B 10NHG01BI
01 16 16NHG01B 16NHG01BI
01 20 20NHG01B 20NHG01BI
01 25 25NHG01B 25NHG01BI
01 32 32NHG01B 32NHG01BI
01 35 35NHG01B 35NHG01BI
01 40 40NHG01B 40NHG01BI
01 50 50NHG01B 50NHG01BI
01 63 63NHG01B 63NHG01BI
01 80 80NHG01B 80NHG01BI
01 100 100NHG01B 100NHG01BI
01 125 125NHG01B 125NHG01BI
01 160 160NHG01B 160NHG01BI

* Available upon request

PM210011-NUI900-ESE-00001_02 138 of 154


Lightning arresters T1

HLA50-255/4+0
Lightning impulse current arresters type T1 ensure the Installed as close as possible the overhead line enters the building
equipotential bonding and eliminate the effects of lightning i.e. the electric power substation, electrometer or the main
current in single-phase and three-phase power supply systems. distribution boards.
Products contain multiple non-exhausting spark gaps, thanks to If the product contains two PE (or PEN) terminals, it must not be
which they are able to discharge the highest lightning impulse used as a PE (PEN) bridge.
current. LED indication specifies a version with LED fault signalisation.
Suitable for objects with considerable levels of protection LPL I S indication specifies a version with remote monitoring and LED
and LPL II, such as big industrial complexes and properties of fault signalisation.
particular importance – hospitals, banks, power plants.

Type HLA50-255/4+0
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) T1
System TN-S
Number of poles 4
Rated operating AC voltage UN 230 V
Maximum continuous operating voltage AC UC 255 V
Impulse discharge current for class I test (10/350) Iimp 50 kA
Charge Q 25 As
Specific energy for class I test W/R 625 kJ/Ω
Total discharge current (10/350) L1+L2+L3+N->PE ITotal 200 kA
Nominal discharge current for class II test (8/20) In 50 kA
Voltage protection level at Iimp Up < 2 kV
Temporary overvoltage test (TOV) for tT = 5 s UT 337 V
Temporary overvoltage test (TOV) for tT = 120 min UT 440 V
Response time tA < 100 ns
Maximal back-up fuse 500 A gL/gG
Short-circuit current rating at maximum back-up fuse ISCCR 25 kArms
Follow current interrupt rating Ifi 25 kArms
Lightning protection zone LPZ 0-1, LPZ 1-2
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ -40 ÷ 70 °C
Humidity range RH 5 ÷ 95 %
Minimum cross-section of connected Cu conductors accord. to HD 60364-5-53:2022 S 6 mm² (L, N)
(doesn't apply to „V“ connection) for T1 16 mm² (PE, PEN)
Clamp fastening range (solid conductor) 2.5 ÷ 25 mm2
Clamp fastening range (stranded conductor) 2.5 ÷ 16 mm2
Tightening moment 4 Nm
Installation On DIN rail 35 mm

HLA50-255/4+0 – page 1/2 HAKEL spol. s r.o. | Bratri Stefanu 980, 500 03 Hradec Kralove, Czech Republic
Datasheet generated on 2023-06-24 20:47:49 Phone: +420 494 942 314 | e-mail: info@hakel.com
PM210011-NUI900-ESE-00001_02 139| of
www.hakel.com
154
Lightning arresters T1

Type HLA50-255/4+0
Modular width 8 TE
Operating position Any
Product placement environment Internal
Signalling at the device None
Remote signalling No
Modular design No
Lifetime > 100 000 h

Designed according to standards


Requirements and test methods for SPDs connected to low-voltage power systems IEC 61643-11:2011
Safety of Flammability of Plastic Materials UL 94

Application standards
Protection against lightning IEC 62305:2010
Selection and erection of electrical equipment – Switchgear and controlgear HD 60364-5-53:2022
Selection and application principles for SPDs connected to low-voltage power systems CLC/TS 61643-12:2009

Ordering, packaging and additional data


Mass m 920 g
Mass (including the packaging) m 964 g
Packaging dimensions (H x W x D) 71 x 177 x 106 mm
Packaging value V 1.33 dm3
ETIM group EG000021
ETIM class EC000381
Customs tariff no. 85363010
EAN code 8590681114810
Art. number 10 973

The link in the QR code leads to the online presentation of the HLA50-255/4+0.
There, in addition to the always up-to-date data sheet, you will also find all diagrams
and drawings, declarations of conformity, or 2D or 3D models and other necessary materials.
For more information, visit www.hakel.com 8590681114810

Application wiring diagram (installation) Internal diagram

HLA50-255/4+0 – page 2/2 HAKEL spol. s r.o. | Bratri Stefanu 980, 500 03 Hradec Kralove, Czech Republic
Datasheet generated on 2023-06-24 20:47:49 Phone: +420 494 942 314 | e-mail: info@hakel.com
PM210011-NUI900-ESE-00001_02 140| of
www.hakel.com
154

Powered by TCPDF (www.tcpdf.org)


Surge arresters T2+T3

HSA-320/4+0 M S
Surge arresters type T2+T3 ensure the equipotential bonding and Installed at the boundaries of LPZ 1 – LPZ 3 into subsidiary
reduce switching, induced and residual overvoltage in LV power switchboards and control panels.
supply systems. If the product contains two PE (or PEN) terminals, it must not be
The products consist of varistors with big discharge ability. used as a PE (PEN) bridge.
Configurations 1+1 and 3+1 are additionally combined with a gas M indication specifies a type of construction with removable
discharge tube which ensures zero leakage current through the PE module.
conductor. S indication specifies a version with remote monitoring.

Type HSA-320/4+0 M S
Test class according to EN 61643-11:2012 (IEC 61643-11:2011) T2, T3
System TN-S
Number of poles 4
Rated operating AC voltage UN 230 V
Maximum continuous operating voltage AC UC 320 V
Maximum discharge current (8/20) Imax 50 kA
Nominal discharge current for class II test (8/20) In 20 kA
Open circuit voltage of the combination wave generator UOC 6 kV
Total discharge current (8/20) L1+L2+L3+N->PE ITotal 200 kA
Voltage protection level at In Up < 1.4 kV
Voltage protection level at UOC Up < 0.95 kV
Temporary overvoltage test (TOV) for tT = 5 s UT 337 V
Temporary overvoltage test (TOV) for tT = 120 min UT 440 V
Response time tA < 25 ns
Maximal back-up fuse 160 A gL/gG
Residual current IPE ≤ 400 µA
Short-circuit current rating at maximum back-up fuse ISCCR 60 kArms
Lightning protection zone LPZ 1-2, LPZ 2-3
Housing material Polyamid PA6, UL94 V-0
Degree of protection IP20
Operating temperature ϑ -40 ÷ 70 °C
Humidity range RH 5 ÷ 95 %
Minimum cross-section of connected Cu conductors accord. to HD 60364-5-53:2022 S 2.5 mm² (L, N)
(doesn't apply to „V“ connection) for T2 6 mm² (PE, PEN)
Clamp fastening range (solid conductor) 1.5 ÷ 25 mm2
Clamp fastening range (stranded conductor) 1.5 ÷ 16 mm2
Tightening moment 3 Nm
Installation On DIN rail 35 mm
Modular width 4 TE

HSA-320/4+0 M S – page 1/2 HAKEL spol. s r.o. | Bratri Stefanu 980, 500 03 Hradec Kralove, Czech Republic
Datasheet generated on 2023-06-24 20:50:05 Phone: +420 494 942 314 | e-mail: info@hakel.com
PM210011-NUI900-ESE-00001_02 141| of
www.hakel.com
154
Surge arresters T2+T3

Type HSA-320/4+0 M S
Operating position Any
Product placement environment Internal
Signalling at the device Optic
Importance of local signaling OK – clear target
FAULT – red target
Remote signalling Yes
Potential free signal contact (S) (recommended cross-section of remote monitoring AC: 250 V / 1.5 A, DC: 250 V / 0.1 A
max. 1 mm2)
Modular design Yes
Article number of spare module 27 192
Lifetime > 100 000 h

Designed according to standards


Requirements and test methods for SPDs connected to low-voltage power systems IEC 61643-11:2011
Safety of Flammability of Plastic Materials UL 94

Application standards
Protection against lightning IEC 62305:2010
Selection and erection of electrical equipment – Switchgear and controlgear HD 60364-5-53:2022
Selection and application principles for SPDs connected to low-voltage power systems CLC/TS 61643-12:2009

Ordering, packaging and additional data


Mass m 476 g
Mass (including the packaging) m 504 g
Packaging dimensions (H x W x D) 74 x 112 x 73 mm
Packaging value V 0.61 dm3
ETIM group EG000021
ETIM class EC000941
Customs tariff no. 85363010
EAN code 8590681116548
Art. number 27 529

The link in the QR code leads to the online presentation of the HSA-320/4+0 M S.
There, in addition to the always up-to-date data sheet, you will also find all diagrams
and drawings, declarations of conformity, or 2D or 3D models and other necessary materials.
For more information, visit www.hakel.com 8590681116548

Application wiring diagram (installation) Internal diagram

HSA-320/4+0 M S – page 2/2 HAKEL spol. s r.o. | Bratri Stefanu 980, 500 03 Hradec Kralove, Czech Republic
Datasheet generated on 2023-06-24 20:50:05 Phone: +420 494 942 314 | e-mail: info@hakel.com
PM210011-NUI900-ESE-00001_02 142| of
www.hakel.com
154

Powered by TCPDF (www.tcpdf.org)


4

Sample Test Certificates

PM210011-NUI900-ESE-00001_02 143 of 154


PM210011-NUI900-ESE-00001_02 144 of 154
PANEL BOARD FACTORY

INSPECTION CHECKLIST

Project Client :
Panel name Job No :
Pos. Description Result
1. Enclosure
1.1. Enclosure type (degree of protection)
1.2. Dimension / measurement
1.3. Doors and cover fit properly, no sound no resistance while opening
1.4. Lifting angles and base channel properly assembled / secured
1.5. Finish kind, color, appearance, paint condition
1.6. Enclosure conform to general characteristics
1.7. Incoming and outgoing cable (space)
1.8. Bolts and nuts
1.9 Enclosure Clean
2. Electrical conductors
2.1. Size with thickness and quantity per phase of bus bar
2.2. Size of wire (incoming, outgoing and controls)
2.3. Alignment and bus bar support spacing/Insulators
2.4. Control Transformer Rating
2.5. Torque marks
2.6. Control wiring properly wired
2.7. Connection of LV cable to transformer
2.8. Phase, earth circuit continuity
2.9. Point–to-point / continuity test
2.10 Electrical conduct clean
3. Components layout and service specification
3.1. Arrangement of components as per approved drawing
4. Conformity of components
4.1. Components rating as per drawing
4.2. Component installed must conform to drawing list
4.3. Nameplates and components label
5. Mechanical operation test
5.1. Closing and opening of circuit breaker
5.2.
All handles, interlocks, switches operate freely and are accessible
PM210011-NUI900-ESE-00001_02 145 of 154
5.3
Components clean
6. Electrical test
6.1. MEGGER test
6.2. Dielectric test
7. Functional test
7.1. Component device electrical operation test
7.2. Confirmation of electrical interlock
7.3. Electrical operation of circuit breaker on / off
7.4. Verification of panel heater and lighting (if fitted)
7.5. ATS operation test (automatic / manual)
8. Protection test
8.1. Relay operate satisfactory
8.2. All protection relay functional confirmation
9. Metering
9.1. Test for correct polarity of connection (correct direction of movement)

REMARKS:

RESULTS: OK – conformed (requirements are met); N/A - not applicable

Inspected by: Approved by: Witnessed / Received by


QC Factory Manager Clients Representative

Name : Name : Name :

Date &Signature Date &Signature Date &Signature

PM210011-NUI900-ESE-00001_02 146 of 154


Type of enclosure: eMDB/MSB/MV/LV
MDB

Procedures: Check-in conformity of drawing with IEC 61439-1 Edition 1.0 2009-01

Client: Job Order No.:


Project: Item No.:
Panel ref.: Inspection ref.:
Drawing No./rev.: Project Engineer:
THE CHECK LIST Status

1. Aspect and presentation

2. Layout
3. Service specifications
3.1.Voltage: ………..…. V; phase: …….….; wires: ………..….; frequency: ………. Hz; temp: …..…. °C
4. Conformity of components
4.1. Enclosures
4.1.1. Dimensions (HxWxD): ………..….. x ………..….. x ………..….. mm
4.1.2. No. of sections: ………..….…….. No. of modules: ………..….……..
4.1.3. Degree of protection: IP ………..…
4.2. Control and protection units
4.2.1. Main breaker: rating ………. A, ………. P; 4.2.3. Main breaker: rating: ………. A, ………. P
- type: - type:
4.2.2. Main breaker: rating: ………. A, ………. P; 4.2.4. Main breaker: rating: ………. A, ………. P
- type: - type:

4.2.5. Branch breakers (see drawing):


4.2.6. Control relays (types: ……..…..……….. , …………..….…….. , ……..…..….…….. )
4.2.7. Protection relays (types: ………....….…….. , ………..…….….... , …...……..….…….. )

4.2.8. Fixation of components:


4.2.9. Components’ labeling:

4.3. Metering
in / out in / out in / out in / out in / out in / out
CT rating A A A A A A
Ammeter rating A A A A A A
Ammeter selector switch : pos. pos. pos. pos. pos. pos.
Volt. transformer rating v v v v v v
Voltmeter rating v v v v v v
Voltmeter selector switch pos. pos. pos. pos. pos. pos.

4.4. Main Busbars


4.4.1.Size: ………….. x ………….. mm (L1, L2, L3) qty: …………..
………….. x ………….. mm (N) qty: …………..
………….. x ………….. mm (E) qty: …………..
4.4.2. Material: tin-plated copper insulated copper bare copper
4.4.3. Isc: …..…..KA/ …………SEC
4.4.4. Busbar Space clearance and supports

PM210011-NUI900-ESE-00001_02 147 of 154


4.4.5. Busbar sizes in accordance with approved drawings
4.4.6. Tightness of connecting bolts:

4.4.7. Main busbar labelling

4.5. Mechanical check of breakers (5 times opening and closing)

4.6. Cables / Busbars


4.6.1 Power cables / busbar of branch breakers
(Selection done according to Prisma Technical guide, see table below)
Copper cable
Copper Cable IP  30 IP  31
cross section Bundle Bundle Qty. of ckt.
mm² Amps Amps
1.5 14 15
2.5 22 20
4 28 24
6 36 33
10 55 50 Bundle = 6 to 8 power
16 80 70 cables held together
25 100 93 by ties
35 125 120
50 165 135
70 207 175
Insulated flexible copper strip
Cross Section l max (A)
No. of elements IP  30 IP  31 Qty. of ckt.
20 x 2 mm 275 240
20 x 3 " 300 275
24 x 5 " 490 450
32 x 5 " 630 570
32 x 8 " 800 720

Copper busbars Crimping


Cross Section Qty. of ckt.
1515
x 10
x 5mm
mm
2020
x 10
x 5 mm
mm
2525
x5x 5mm
mm
3032 x 5 mm
x 10 mm
4040
x 10
x 5 mm
mm
5050
x 5x 5
mmmm
6063 x 5mm
x 10 mm
8080 x 5mm
x 10 mm
100x x105 mm
100 mm
125x x105 mm
125 mm
(for busbar rating please refer to the Prisma Guide)
Power cable / busbar marking
4.6.2. Control wiring
- size: …..…. ; especially: current circuit: …..…. mm²; voltage circuit: …..….. mm²

PM210011-NUI900-ESE-00001_02 148 of 154


Control cable marking:
4.7. Neutral Circuit: distributed not distributed TNS TNC

4.7.1. Neutral CT:


4.7.2. Primary injection: ………. A across L Trip: Yes No
………. A across L in series to N; Trip: Yes No

4.8. Earth Circuit Continuity

4.9. Cable Entry / Bus Duct / Cable Duct


4.9.1. Incoming: top bottom
4.9.2. Outgoing: top bottom

4.10. Cable Connection Access

4.10.1. Incoming: front rear side


4.10.2. Outgoing: front rear side

4.11. Interlocking
4.11.1. In-comers / feeders / bus couplers
4.11.2. Type: mech. electr. key (See Panel Drawing for Details)

4.12. Auto changeover facility Yes No

5. Phase continuity test

6. Phase sequence test

7. Dielectric test

7.1. Insulation resistance test (Megger test) 1 kVDC / 1 min Insulation [MΩ]
(Satisfactory if the insulation resistance L1 - L2
between circuits and exposed conductive L2 - L3
parts is at least 1000 Ohms/V per circuit L3 - L1
referred to nominal voltage to earth of L- N
these circuits) L- E
N -E

7.2. Dielectric test (for main circuits) 2.5 kVAC / 1 Sec Passed / Failed
(Passed if no puncture or flash-over) L1 - L2
L2 - L3
L3 - L1
L- N
L- E
N -E

PM210011-NUI900-ESE-00001_02 149 of 154


PANEL BOARD FACTORY

PANEL TEST REPORT

7.3.1.Continuity Test

7.3.2.ƵdžŝůŝĂƌLJΘŽŶƚƌŽůŝƌĐƵŝƚ

8. Protection TEST (if applicable)


8.1. Relay operation satisfactory

8.2 Protection relay functioning properly

9. Equipment type used for testing


MULTIMETER FLUKE-179 POWER SOCKET PANEL 380/220V AC
5KV INSULATION TESTER FLUKE-1550C HIPOT TESTER ZEAL 5KV
TORQUE WRENCH

Status codes : OK - conformed; N/C - not conformed; N/A - not applicable

REMARKS

Inspected by: Noted by: Witnessed/Received by: Approved by:


QCI Production Supervisor Client Representative Factory Manager
Name: Name: Name: Name:
Ullas Joseph Sudharsanan V Georges Hajj
Date Signature: Date Signature: Date Signature: Date Signature:

PM210011-NUI900-ESE-00001_02 150 of 154


Type of enclosure: SMDB

Procedures: Check-in conformity of drawing with IEC 61439-1 1.0 2009-01

Client: Job Order No.:


Project: Item No.:
Panel ref.: Inspection ref.:
Drawing No./rev.: Project Engineer:
THE CHECK LIST Status

1. Layout
2. Service specifications
2.1.Voltage: ………..…. V; phase: …….….; wires: ………..….; frequency: ………. Hz; temp: …..…. °C
3. Conformity of components
3.1. Enclosures
3.1.1. Dimensions (HxWxD): ………..…..x………..…..x………..….. mm
3.1.2. No. of sections: ………..….…….. No. of modules: ………..….……..
3.1.3. Degree of protection: IP ………..…
3.1.2. Mounting Type: Flush
Floor mounted:
Mounted SurfaceMounted
Surface mounted:
3.1.5. Number of ways:
3.1.6. Entry: Bottom: Top:
3.1.7. Optional accessories: Lock: Gasket: Earth Bar: Tinplated Busbar
4. INSPECTION OF MECHANICAL PART
4.1
4.1.1 Step 1 Result 4.1.2 Step 2 Result
4.1.1.1 Tightening of the bolts 4.1.2.1 Alignment of branch breakers
4.1.1.2 Fixation of the neutral Busbar 4.1.2.2 Door hinges
4.1.1.3 Provision of phase insulator 4.1.2.3 Door locking fixtures
4.1.1.4 Phase marking 4.1.2.4 Fixation of the earth Busbar
4.1.1.5 Branch breakers fixation 4.1.2.5 Cleanness of the parts
4.1.1.6 Labels : Panel name: Earth: Neutral:
Note: 1. Bolt tightening torques for bus-bar fixation and electrical assembly – 13.5 Nm; 2. Mark upon the joints by a red paint when checked
4.2 Protection
4.2.1. Main Breaker: Type: Rating:
4.2.2. Branch Breakers (see drawing):
4.3. Main Busbars
4.4.1.Size: ………….. x………….. mm (L1, L2, L3) qty: …………..
………….. x………….. mm (N) qty: …………..
………….. x………….. mm (E) qty: …………..
4.4.2. Material: tin-plated copper insulated copper bare copper
5 Metering
in / out in / out in / out in / out in / out in / out
CT rating A A A A A A
Ammeter rating A A A A A A
Ammeter selector switch : pos. pos. pos. pos. pos. pos.
Voltmeter rating v v v v v v
Voltmeter selector switch pos. pos. pos. pos. pos. pos.

PM210011-NUI900-ESE-00001_02 151 of 154


6 Cables / Busbars
6.1 Power cables / busbar of branch breakers
(Selection done according to Prisma Technical guide, see table below)
Copper cable
Copper Cable IP  30 IP  31
cross section Bundle Bundle Qty. of ckt.
mm² Amps Amps
1.5 14 15
2.5 22 20
4 28 24
6 36 33
10 55 50 Bundle = 6 to 8 power
16 80 70 cables held together
25 100 93 by ties
35 125 120
50 165 135
95 232 207
6.2 Insulated flexible copper strip
Cross Section l max (A)
No. of elements IP  30 IP  31 Qty. of ckt.
20 x 2 mm 275 240
20 x 3 “ 300 275
24 x 5 “ 490 450
32 x 5 “ 630 570
32 x 8 “ 800 720

6.3 Copper busbars


Cross Section Qty. of ckt.
15 15
x 10
x 5mm
mm
2020
x 10
x 5mm
mm
2525
x 5x mm
5 mm
3032
x 10x 5mm
mm
4040
x 10x 5mm
mm
5050
x 5xmm
5 mm
60 x 105mm
63 x mm
8080 x 5mm
x 10 mm
100
100 x 5mm
x 10 mm
125
125 x 5mm
x 10 mm
(for busbar rating please refer to the Prisma Guide)
- power cable / busbar marking
Control wiring
- size: …..…. ; especially: current circuit: …..…. mm²; voltage circuit: …..….. mm²
- control cable marking:

PM210011-NUI900-ESE-00001_02 152 of 154


PANEL BOARD FACTORY

PANEL TEST REPORT

8 Functional tests
8.1 Megger test – Application of 1kv / 1 Min
Phase L1 – L2 L2 – L3 L3 – L1 L1 - N L2 - N L3 - N L1- E L2 - E L3 - E N-E
Result

8.1.1 Continuity and phase sequence


8.1.2 Closing and opening of MCB and MCCB – 5 times
9 MEASURING DEVICES
Name Serial No. Name Serial No.
9.1 MULTIMETER FLUKE-179 9.3 TORQUE WRENCH

9.2 5KV INSULATION TESTER FLUKE-1550 C 9.4 POWER SOCKET PANEL 380/220V AC

Inspected by: Noted by: Witnessed/Received by: Approved by:


QCI Production Supervisor Client Representative Factory Manager
Name: Name: Name: Name:
Ullas Joseph Sudharsanan V Georges Hajj
Date Signature: Date Signature: Date Signature: Date Signature:

PM210011-NUI900-ESE-00001_02 153 of 154


PANEL BOARD FACTORY

PANEL TEST REPORT

Type of Enclosure: CONTROL DB


PANEL

Procedures: Check conformity with the drawings and IEC 61439-1 Edition 1.0 2009-01

Client: Job Order No.:


Project: Panel ref. No.:
Item No.: Inspection ref. No.:
1 INSPECTION OF MECHANICAL PART
1.1 Step 1 Result 1.2 Step 2 Result
1.1.1 Tightening of the bolts 1.2.1 Alignment of branch breakers
1.1.2 Fixation of the neutral bars 1.2.2 Door hinges
1.1.3 Provision of phase insulator 1.2.3 Door locking fixtures
1.1.4 Phase marking 1.2.4 Fixation of the earth bar/terminal
1.1.5 Branch breakers fixation 1.2.5 Cleanness of the parts
Note: 1. Bolt tightening torques for bus-bar fixation and electrical assembly – 13.5 Nm; 2. Mark upon the joints by a red paint when checked

2 FINAL INSPECTION
2.1 Aspect and presentation OK
2.2 Conformity of components
2.2.1 Mounting type: FlushMounted
Wall mounted Control Transformer :
2.2.2 Number of ways: Enclosure Size : IP-
2.2.3 Entry: bottom
Bottom Enclosure Color :
2.2.4 Main breaker: type Rating :
2.2.5 Branch breaker(s) Supplied loose
Fitted Drawing No. :
2.2.6 Optional Ronis lock Gasket Tin-plated
Tin - Plated Bus Bar
accessories -
2.3 Functional tests
2.3.1 Dielectric test – Application of 1kv / 1 Min
Phase L1 – L2 L2 – L3 L3 – L1 L1 - N L2 - N L3 - N L1- E L2 - E L3 - E N-E
Result

2.3.2 Continuity and phase sequence


2.3.3 Closing and opening of MCB and MCCB – 5 times
2.4 Labels
2.4.1 Circuit directory/As-Built 2.4.2 Labels: panel name, earth, neutral
2.4.3 Cable Sizes: 2.4.4 Busbar Sizes:

3 MEASURING DEVICES
Name Serial No. Name Serial No.
3.1 MULTIMETER FLUKE-179 3.3 TORQUE WRENCH
3.2 5KV INSULATION TESTER FLUKE-1550C 3.4 POWER SOCKET PANEL 380/220V AC

Inspected by: Noted by: Witnessed/Received by: Approved by:


QCI Production Supervisor Client Representative Factory Manager
Name: Name: Name: Name:
Georges Hajj
Date Signature : Date Signature: Date Signature: Date Signature:
NPBF/DOC/QCI/003 Issue 0

PM210011-NUI900-ESE-00001_02 154 of 154