2250cfm FS

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Date 1/19/2017 Kruger Ventilation Industries Pte Ltd

Company - No. 17 Tuas Avenue 10


Attention - Singapore 639141
Project -
Reference Tel: +65 6861 1577 Fax: +65 6861 3577
Email: mktg@krugerasia.com

Fan Selection
Fan Type
Unit BDB315/CM (I)
Operating Conditions Ducted
Air Volume 2,250 cfm
Static Pressure 150 mmwg
Velocity Pressure 2.60 mmwg
Total Pressure 153 mmwg
Outlet Velocity 6.51 m/s
Fan Total Efficiency 68.9 %
Fan Static Efficiency 67.8 %
Fan Speed 2919 rpm
Air Temperature 20 °C
Altitude 0m
Fan Absorbed Power 2.31 kW
Motor Selection
Recommended Motor D100L (3.00 kW)
Motor Speed 2900 rpm
Service Factor 5%
Belt Selection
Fan Pulley / Bush / Shaft 112 mm / 1610 / 25 mm
Motor Pulley / Bush / Shaft 118 mm / 1610 / 28 mm
Belt Length 1432 mm
Number of Belts / f 1 x SPA
Static Belt Tension/Belt 548 N / 421 N
Belt Deflection 12 mm / 15 mm
Belt Speed (<40m/s) 17.1 m/s
Bearing Lift (L10/L50) 983546 / 3934183 hour
Starting Torque 1.08 kgm
Hz 63 125 250 500 1k 2k 4k 8k Overall
Operating Limits
Lwi(Lin) 83 90 88 92 82 78 74 70 96 dB
Max. Absorbed Power 4.00 kW
Lwi(A) 57 74 79 89 82 79 75 69 91 dB(A)
Max. Fan Speed 3100 rpm
Lpi(A) 46 64 69 78 71 69 65 58 80 dB(A)
Temperature (Min-Max) -20° to 85°C * Sound data is for the inlet side * Sound Pressure Level 1.5m, Room Conditions

C H KG L W
542 618 34 900 630

Version: 1.16.11.91 (Database: 30) (OEM) Date: 1/19/2017 Time: 9:43 AM