Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

TITLE Hydraulic & Pump Calculation DATE 17/09/2023

PROJECT STP - SIP CAPACITY 1,200 m3/d

Ridgewood OWNER Elsewedy T&D REV. 0


Group
CONSULTANT Cosmos RWG22-001
PROJECT NO.

Hydraulic & Pump Calculation


Note
3
For STP - 1200 m /day

Doc Title Hydraulic & Pump Calculation Doc No. RWG22-001-001


0 Issued for Approval 21/06/2023 KHA KHA
Rev. No Description Date Prepared Checked By Approved By
TITLE Hydraulic & Pump Calculation DATE 17/09/2023

PROJECT STP - SIP CAPACITY 1,200 m3/d

Ridgewood OWNER Elsewedy T&D REV. 0

Group CONSULTANT Cosmos PROJECT NO. RWG22-001

Design Basis
Qaverage 1200.0 m3/d
0.014 m3/s
50.0 m3/h
Peak factor considered 3.0
Q peak 150.0 m3/h

The Peak Hydraulic flow has been considered while designing all the parts of the inlet works and balancing tank. While average
flow were considered for the rest of the plant structures. Such as for the aeration tank and final sedimentation tank

1 Inlet Pumping Station Sizing :


a- Sump Size:
This sizing is preliminary and shall be revised after finalizing:
- pump model (to be based on actual motor power and number of pump starts / hours)
- invert level of inlet pipe
Number of duty pumps = 2
Over all number of pumps = 3 (2 duty / 1 standby)
Flow per pump = 75 m3/h
Estimated pump motor power (based on 15 mt
head) = 7.5 kW
Allowable number of start stops for motors up to
= 20 Times/ hour
20 kW\ ECP

For average flow 50 m3/hr - one pump shall be in duty and 2 in standby - The total number of start stop allowed will be 60
Total numbers of starts/ stop allowed (N) = 60 Times/ hour
Minimum water volume is sump Qav/N = 0.83 m3

For peak flow 150 m3/hr - two pumps shall be in duty and 1 in standby - The total number of start stop allowed will be 60
Total numbers of starts/ stop allowed (N) = 60 Times/ hour
Water volume is sump Qpeak/N = 2.5 m3

For operation safety and for installation reasons (three parallel pumps installation) - the volume of the sump shall be 50 m3
Selected sump volume (V) = 50 m3

Invert level of inlet pipe (Lp) = -1 m As per T&D confirmation

Sump length = 4 m
Sump width = 4 m
Effective water depth (ds = V / Area) = 3.125 m
Minimum water level for safe pump operation (L (to be confirmed in
= 0.5 m Engineering phase)
op)
Overall depth of pump sump ((-Lp) + ds + Lop) = 4.625 m

1 of 11
TITLE Hydraulic & Pump Calculation DATE 17/09/2023

PROJECT STP - SIP CAPACITY 1,200 m3/d

Ridgewood OWNER Elsewedy T&D REV. 0

Group CONSULTANT Cosmos PROJECT NO. RWG22-001

b- Pump head:
i. Static head
Inlet pipe level to STP (Lf) = 5.4 m
Minimum water level in sump (Ls) = -4.125 m
Static Head (Lf - Ls) = 9.525 m

ii. Piping size


Delivery pump of each pump
Flow per pump Q = 75 m3/h
Velocity in pipe V = 1.5 m/s
Pipe area: Q / V = 0.0139 m2
Diameter = 0.133 m
Take pipe diameter = 150 mm
Commen header flow Q = 150 m3/h
Velocity in pipe V = 1.5 m/s
Pipe area: Q / V = 0.0278 m2
Diameter = 0.188 m
Take common header diameter = 200 mm

iii. Friction losses and total pump head


Friction losses shall be calculated using Hazen William Equation (Hf) = (10.6 L/D 4.87) (Q/C) 1.85
First: riser pipe losses
Flow = 75 m3/h
Diameter = 150 mm
Area = 0.018 m2
Velocity = 1.178 m/s
Length = 4.0 m
C (Friction Coeff) = 120 Old Pipes Cond.
Hf = 0.048 m
2
Secondary losses  k (V /2g)
Description Secondary losses Coeff / unit (k) Quantity Total second. losses
Pipe inlet = 0.5 0 0
Pipe Exit = 1.0 0 0
Elbow 90 = 0.9 2 1.8
Elbow 45 = 0.5 0 0
Tee (Through run) = 0.6 0 0
Tee (Through Branch) = 1.8 1 1.8
Reducer = 0.5 1 0.5
Gate Valve open = 0.2 1 0.2
NR Valve = 2.5 1 2.5
Butterfly Valve = 0.6 0 0
Others = 0 0
k 6.8
2
Hsec.  k (V /2g) 0.482
Total losses in riser pipe (Hf + Hsec) = 0.530 m (a)

2 of 11
TITLE Hydraulic & Pump Calculation DATE 17/09/2023

PROJECT STP - SIP CAPACITY 1,200 m3/d

Ridgewood OWNER Elsewedy T&D REV. 0

Group CONSULTANT Cosmos PROJECT NO. RWG22-001

Second: Common header & main pipe till STP entrance losses
Flow = 150 m3/h
Diameter = 200 mm
Area = 0.031 m2
Velocity = 1.326 m/s
Length = 20.0 m
C (Friction Coeff) = 120 Old Pipes Cond.
Hf = 0.214 m
2
Secondary losses  k (V /2g)
Description Secondary losses Coeff / unit (k) Quantity Total second. losses
Pipe inlet = 0.5 1 0.5
Pipe Exit = 1.0 0 0
Elbow 90 = 0.9 4 3.6
Elbow 45 = 0.5 0 0
Tee (Through run) = 0.6 0 0
Tee (Through Branch) = 1.8 0 0
Reducer = 0.5 0 0
Gate Valve open = 0.2 1 0.2
NR Valve = 2.5 0 0
Butterfly Valve = 0.6 0 0
Others = 0 0
k 4.3
2
Hsec.  k (V /2g) 0.386
Total losses in main pipe (Hf + Hsec) = 0.600 m (b)

Total Friction & Secondary losses in riser & pipe till plant entry = (a) + (b)= 1.130 m
Static head 9.525 m
Residual head at plant entrance (recommended) 2 m
Calculated pump head for lifting station pumps 12.655 m
Selected pump head 15 m
Lifting station pumps shall be 75 m3/hr @ 15 mt head

3 of 11
TITLE Hydraulic & Pump Calculation DATE 17/09/2023

PROJECT STP - SIP CAPACITY 1,200 m3/d

Ridgewood OWNER Elsewedy T&D REV. 0

Group CONSULTANT Cosmos PROJECT NO. RWG22-001

2 Weir between Inlet Chamber & Screen Channel :

Flow rate Qpeak 150.0 m3/h


Weir type Rectangular H = (1.5*Q/(C*b)*((2g)^0.5)))^2/3

Weir length b 700.0 mm

Weir Discharge Coeff. C 0.6


Head 0.104 mt.

Take losses in weir 0.11 mt

Water level in inlet Chamber 4.8 mt


Water level in screen channel 4.69 mt

3 Losses in Manual Screen

Losses through screen (from process calc) 0.002 mt


Assume losses through screen 0.1 mt

Water level before screen 4.69 mt


Water level after screen 4.59 mt

4 Losses in orfice at end of grit removal channel

Flow rate Qpeak 150.0 m3/h


Orfice dimension Length 700.0 mm
Width 350.0 mm
Head losses through orifice 𝐻𝑙 𝑐𝑑 𝑣2/2𝑔

Discharge coefficient Cd 0.6


Velocity through orfice Q / Area of orific 0.17 m/s

Hl 0.001 m

Take losses through orfice 0.005 m


Water level before orfice 4.59 mt
Water level after orfice 4.585 mt

4 of 11
TITLE Hydraulic & Pump Calculation DATE 17/09/2023

PROJECT STP - SIP CAPACITY 1,200 m3/d

Ridgewood OWNER Elsewedy T&D REV. 0

Group CONSULTANT Cosmos PROJECT NO. RWG22-001

5 Losses through weir between grit channel & balancing tank

Flow rate Qpeak 150.0 m3/h


Weir type Rectangular H = (1.5*Q/(C*b)*((2g)^0.5)))^2/3

Weir length b 1000.0 mm

Weir Discharge Coeff. C 0.6


Head 0.082 mt.

Take losses in weir 0.1 mt

Water level at end of grit channel 4.585 mt


Water level in balancing tank 4.485 mt

Take water level in balancing tank 4.30 mt

6 Balancing Tank Pumps:

As the funcition of the balancing tank is to absorb the difference between peak flow and average flow, balancing tank pumps
should be sized based on average flow rate of the plant - this mean total flow rate of balancing tank pumps should be 50 m3/hr.

a- Pump flow rate


Flow rate of balancingt tank pumps 25 m3/h per pump
Number of duty pumps 2 Nos.
Number of standby pumps 1 No.
b- Pump head
i. Static head
Aeration tank pipe inlet level = 4.8 m
Minimum water level in balancing tank(Ls) = 0.5 m
Static Head (Lf - Ls) = 4.3 m

5 of 11
TITLE Hydraulic & Pump Calculation DATE 17/09/2023

PROJECT STP - SIP CAPACITY 1,200 m3/d

Ridgewood OWNER Elsewedy T&D REV. 0

Group CONSULTANT Cosmos PROJECT NO. RWG22-001

ii. Piping size


Delivery pump of each pump
Flow per pump Q = 25 m3/h
Velocity in pipe V = 1 m/s
Pipe area: Q / V = 0.0069 m2
Diameter = 0.094 m
Take pipe diameter = 100 mm
Commen header flow Q = 50 m3/h
Velocity in pipe V = 1 m/s
Pipe area: Q / V = 0.0139 m2
Diameter = 0.133 m
Take common header diameter = 150 mm

iii. Friction losses and total pump head


Friction losses shall be calculated using Hazen William Equation (Hf) = (10.6 L/D 4.87) (Q/C) 1.85
First: riser pipe losses
Flow = 25 m3/h
Diameter = 100 mm
Area = 0.008 m2
Velocity = 0.884 m/s
Length = 4.3 m
C (Friction Coeff) = 120 Old Pipes Cond.
Hf = 0.007 m
2
Secondary losses  k (V /2g)
Description Secondary losses Coeff / unit (k) Quantity Total second. losses
Pipe inlet = 0.5 0 0
Pipe Exit = 1.0 0 0
Elbow 90 = 0.9 2 1.8
Elbow 45 = 0.5 0 0
Tee (Through run) = 0.6 0 0
Tee (Through Branch) = 1.8 1 1.8
Reducer = 0.5 1 0.5
Gate Valve open = 0.2 1 0.2
NR Valve = 2.5 1 2.5
Butterfly Valve = 0.6 0 0
Others = 0 0
k 6.8
2
Hsec.  k (V /2g) 0.271
Total losses in riser pipe (Hf + Hsec) = 0.278 m (a)

6 of 11
TITLE Hydraulic & Pump Calculation DATE 17/09/2023

PROJECT STP - SIP CAPACITY 1,200 m3/d

Ridgewood OWNER Elsewedy T&D REV. 0

Group CONSULTANT Cosmos PROJECT NO. RWG22-001

Second: Common header & main pipe to aeration tank entrance


Flow = 50 m3/h
Diameter = 150 mm
Area = 0.018 m2
Velocity = 0.786 m/s
Length = 6.0 m
C (Friction Coeff) = 120 Old Pipes Cond.
Hf = 0.034 m
2
Secondary losses  k (V /2g)
Description Secondary losses Coeff / unit (k) Quantity Total second. losses
Pipe inlet = 0.5 1 0.5
Pipe Exit = 1.0 0 0
Elbow 90 = 0.9 2 1.8
Elbow 45 = 0.5 0 0
Tee (Through run) = 0.6 0 0
Tee (Through Branch) = 1.8 0 0
Reducer = 0.5 0 0
Gate Valve open = 0.2 0 0
NR Valve = 2.5 0 0
Butterfly Valve = 0.6 0 0
Others = 0 0
k 2.3
2
Hsec.  k (V /2g) 0.072
Total losses in main pipe (Hf + Hsec) = 0.107 m (b)

Total Friction & Secondary losses in riser & pipe to aertion tank entry = (a) + (b)= 0.384 m
Static head 4.3 m
Residual head at tank entrance (recommended) 2 m
Calculated pump head for balancing tank pumps 6.684 m
Selected pump head 7 m
Balancing tank pumps shall be 25 m3/hr @ 7 mt head

7 of 11
TITLE Hydraulic & Pump Calculation DATE 17/09/2023

PROJECT STP - SIP CAPACITY 1,200 m3/d

Ridgewood OWNER Elsewedy T&D REV. 0

Group CONSULTANT Cosmos PROJECT NO. RWG22-001

7 Inlet from aeration to settling tank

No. of settling tank 4 Nos.


Total average flow 50.0 m3/h
Flow per settling tank 12.5 m3/h

Opening between aeration tank and settling tank 300.0 mm


Weir type Rectagular H = (1.5*Q/(C*b)*((2g)^0.5)))^2/3

Weir length b 300.0 mm

Weir Discharge Coeff. C 0.6


Head 0.088 mt.

Take losses in weir 0.1 mt

Water level in aeration tank 4.30 mt


Water level in settling tank 4.20 mt

Take water level in settling tank 4.20 mt

7 Weir on settling tank collecting channel

No. of settling tank 4 Nos.

Total average flow 50.0 m3/h


Flow per settling tank 12.5 m3/h

Weir length 5000.0 mm


Weir type Rectangular H = (1.5*Q/(C*b)*((2g)^0.5)))^2/3

Weir length b 5000.0 mm

Weir Discharge Coeff. C 0.6


Head 0.014 mt.

Take losses in weir 0.02 mt

Water level in settling tank 4.20 mt


Water level in settling tank channel 4.18 mt

8 of 11
TITLE Hydraulic & Pump Calculation DATE 17/09/2023

PROJECT STP - SIP CAPACITY 1,200 m3/d

Ridgewood OWNER Elsewedy T&D REV. 0

Group CONSULTANT Cosmos PROJECT NO. RWG22-001

Take water level in Effluent channel 4.15 mt

9 of 11
TITLE Hydraulic & Pump Calculation DATE 17/09/2023

PROJECT STP - SIP CAPACITY 1,200 m3/d

Ridgewood OWNER Elsewedy T&D REV. 0

Group CONSULTANT Cosmos PROJECT NO. RWG22-001

8 Settling tank efflunet channel

No. of settling tank 4 Nos.

Total average flow 50.0 m3/h


Flow per settling tank 12.5 m3/h

Channel dimensions Depth 400.0 mm


Water depth 200.0 mm
Width 400.0 mm
Length 5000.0 mm

Water velocity 0.043 m/sec


Hyd. Radius 0.10 mt
n (Rouhness factor) (for Manning Formula) 0.03 Ideally 0.015 should be used for concrete
C (Chezy Coeff) 33.7
Hlosses in channel 0.00008 mt
Required slope in effluent channel is not signficant, however 0.025 mt shall be considered.

Overall slop for all 4 effluent channels 0.1 mt


Water level at beginning of effluent channel 4.15 mt
Level at channel end before inlet to
chlorine contact tank 4.05 mt

9 Weir inlet to chlorine contact tank

Total average flow for all settling tanks 50.0 m3/h

Weir length 300.0 mm


Weir type Rectangular H = (1.5*Q/(C*b)*((2g)^0.5)))^2/3

Weir length b 300.0 mm

Weir Discharge Coeff. C 0.6


Head 0.088 mt.

Take losses in weir 0.1 mt

Water level at the end of settling tank channel 4.05 mt


Water level in chlorine contact tank 3.95 mt

Take water level in chlorine contact tank 3.90 mt

10 of 11
TITLE Hydraulic & Pump Calculation DATE 17/09/2023

PROJECT STP - SIP CAPACITY 1,200 m3/d

Ridgewood OWNER Elsewedy T&D REV. 0

Group CONSULTANT Cosmos PROJECT NO. RWG22-001

11 of 11

You might also like