Product description
Digital Energy™ Uninterruptible Power Supply
VH Series UPS
700 - 1000 - 1500 - 2000 - 3000VA
Contents:
1. Introduction ............................................................................................................... 2
2. Functional explanation........................................................................................ 2
2.1 Principles of operation
2.2 Normal conditions
2.3 Mains failure
2.4 Bypass operation
3. External description............................................................................................... 4
3.1 Front and rear panel
3.2 Enclosure
3.3 Dimensions
3.4 Weight
4. Electrical specifications....................................................................................... 5
4.1 Ratings
4.2 Input converter
4.3 Output converter
4.4 Bypass
4.5 General design criteria
5. Performance characteristics............................................................................ 6
5.1 Efficiency
5.2 Environment
5.3 Runtimes
5.4 Overload capability
5.5 Standard features
7. Batteries....................................................................................................................... 8
8. Options.......................................................................................................................... 9
8.1 USB / RS232 / Relay interface card
8.2 Longer runtimes (VH Series 1000 -3000VA)
9. Transport / storage..............................................................................................10
© General Electric. Data subject to change without prior notice. All brands and product names are Trademarks or Registered Trademarks of their respective owners.
Reproduction only upon written consent by GE.
2 - Functional explanation
2.1 Principles of operation
The UPS stores electric energy in batteries housed in the unit. This allows the UPS to supply output power even when
the incoming mains power is cut off completely. Energy is stored as Direct Current (DC), while input and output
energy are Alternating Current (AC) in sine wave form. Therefore the UPS contains an input converter (AC to DC) and
an output converter (DC to AC) (See fig.1).
BYPASS
RFI
FROM FILTER
MAINS INPUT OUTPUT
RFI CONVERTER CONVERTER
FILTER
AUTOMATIC APPLIANCE OUTLETS
BYPASS
BATTERY BATTERY
OPTIONAL CHARGER BOOSTER
USB
RJ11
BATTERY FRONT PANEL
ON OFF
BATTERY
USB
EXTENSION
RS232
MICRO-PROCESSOR CONTROL Relay
(optional)
RFI
FILTER
INPUT OUTPUT
RFI CONVERTER CONVERTER
FILTER
AUTOMATIC APPLIANCE OUTLETS
BYPASS
BATTERY BATTERY
OPTIONAL CHARGER BOOSTER
USB
RJ11
BATTERY FRONT PANEL
ON OFF
BATTERY
USB
EXTENSION
RS232
MICRO-PROCESSOR CONTROL Relay
(optional)
In the event of an extended mains failure, the output converter will stop when the battery energy has been used up. At
this point, the UPS is no longer able to power the connected equipment.
When the mains is re-established within tolerance, the input converter will be supplied again by the mains and the
batteries will be recharged, making them ready to support future power failures.
FRONT REAR
3.2 Enclosure
Construction : steel/plastic
Colour : RAL 9005 (black)
Protection : IP 20
3.3 Dimensions
Dimensions UPS tower (hxwxd, mm) : 440x87x472 440x87x547
Shipping dimensions (hxwxd, mm) : 205x545x540 205x545x655
Dimension battery pack (hxwxd, mm) : 36Vdc: 440x87x472; 72Vdc: 440x87x547
Shipping dims batt. pack (hxwxd, mm) : 36Vdc: 205x545x540; 72Vdc: 205x545x655
3.4 Weight
Weight UPS (kg) : 18.3 18.3 19.3 31.1 33.1
Weight 36V / 72V battery pack (kg) : 29 / 47
Shipping weight UPS (kg) : 21.6 21.6 22.6 34.8 36.8
Shipping weight 36V / 72V batt. pack (kg) : 32.3 / 50.7
4.4 Bypass
AC input voltage range : selected output voltage +15% -10%
Frequency tracking rate : 2 Hz/sec.
Frequency tracking range : nominal ± 10%
Phase difference : < 7°
Transfer time, msec : 1
Note: The VH Series UPS is intended for use in normal domestic and office situations (see Safety: EN 62040-1-1)
5.2 Environment
Ambient temperature : -10 to +40°C
Audible noise at 1 meter : < 45dB(A), load and temperature dependent
Max. relative humidity : 95% (non-condensing)
6.2 RJ 11 port
The RJ 11 port is a plug-in contact interface port.
Pin # Function
1 Mains failure
2 General alarm 1)
3 Battery low
4 On bypass
5 Remote UPS shutdown
6 GND
fig. 6.2
1)
Active if the output voltage of the UPS is no longer guaranteed due to other circumstances than already indicated by pin
1-3-4:
• General fault
• Overload
• Overtemperature
• Output out of tolerance
• Charger failure
• Bypass out of limits
• Replace battery
1000VA
std. UPS 36 / 7 7 7 / 18
1 pack: 36 / 14 21 32 / 70
2 packs: 36 / 14+14 35 59 / 97
1500VA
std. UPS 36 / 9 9 6 / 15
1 pack: 36 / 14 23 21 / 54
2 packs: 36 / 14+14 37 41 / 76
2000VA
std. UPS 72 / 7 7 7 / 18
1 pack: 72 / 14 21 32 / 70
2 packs: 72 / 14+14 35 59 / 97
3000VA
std. UPS 72 / 9 9 6 / 15
1 pack: 72 / 14 23 21 / 54
2 packs: 72 / 14+14 37 41 / 76
Store the UPS in a dry location with the batteries in a fully charged state.
Storage temperature must be within -20 +45 °C. If the unit is stored for a period exceeding 3 months, optimal battery
lifetime is obtained if the storage temperature does not exceed 25°C.
If the unit is stored for an extended period of time, the batteries must be recharged periodically. Be sure that the
batteries are connected to the UPS. Subsequently connect the unit to a wall outlet and recharge the batteries for 24
hours:
- if the storage temperature is within -20 and +30°C: every 3 months,
- if the storage temperature is within -20 and +45°C: every month.