Type, Size, Capacity & Protection of Conductors - Update-1
Type, Size, Capacity & Protection of Conductors - Update-1
Type, Size, Capacity & Protection of Conductors - Update-1
BYA
450/750V
(Plain Annealed Copper Conductor, Single Core, PVC Insulated, Non-sheathed Cables)
Derated value of
No. and Approximat
Cross-Sectional Current Rating Ampacity of
Approximate e Outer
Area of 35 C ambient
o
Conductor for ECC-size
Diameter of Diameter
Conductor temperature in air Selecting CB/Fuse
Wires
Sizes
No./mm. Mm mm2 A A mm2
1/1.38 6.6 1 x 1.5 re 22 16 3.243
1/1.78 7.2 1 x 2.5 re 30 21 3.243
7/0.85 8.2 1 x 4 rm 39 27 4
7/1.05 8.7 1 x 6 rm 50 35 6
7/1.35 9.7 1 x 10 rm 69 48 10
7/1.71 10.7 1 x 16 rm 94 66 16
7/2.13 12.4 1 x 25 rm 125 88 16
19/1.53 13.7 1 x 35 rm 160 112 16
19/1.83 15.6 1 x 50 rm 195 156 25
19/2.17 17.3 1 x 70 rm 245 196 35
19/2.52 19.4 1 x 95 rm 300 240 50
37/2.03 21.0 1 x 120 rm 350 280 70
37/2.27 23.1 1 x 150 rm 405 324 95
37/2.52 25.6 1 x 185 rm 460 368 95
61/2.24 28.6 1 x 240 rm 555 444 120
61/2.50 31.3 1 x 300 rm 640 512 150
61/2.89 35.3 1 x 400 rm 770 616 240
61/3.23 39.2 1 x 500 rm 900 720
127/2.52 43.2 1 x 630 rm 1030 824
NYY
600/1000V
(Plain Annealed Copper Conductor, PVC Insulated and PVC-sheathed Cables)
Three Core
Current
Rating at
35o C
Clipped to a
Overall Nominal Cross- surface or Derated Ampacity
No. and Nominal
Diameter Sectional Area on a cable for Selecting ECC-size
Diameter of Wires
of Conductor tray CB/Fuse Sizes
bunched &
unenclosed
two cables
single phase
No./inch. No./mm. mm mm2 A A mm2
1/0.044 1/1.12 3.03 1.00 16 11 3.243
3/0.029 3/0.74 3.43 1.30 20 14 3.243
3/0.036 3/0.91 3.88 1.95 25 18 3.243
7/0.029 7/0.74 4.11 2.98 31 22 3.243
7/0.036 7/0.91 4.90 4.55 41 29 6
7/0.044 7/1.12 5.51 6.85 51 36 10
7/0.052 7/1.32 6.12 9.58 65 46 10
7/0.064 7/1.63 7.03 14.53 83 58 16