Building 1 E2

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

SCHEDULE OF LOADS

PANEL BOARD: PB

CKT TOTAL VOLTAGE CURRENT CIRCUIT BREAKER VOLTAGE


LOAD DESCRIPTION QTY WIRE CONDUIT LENGTH (ft) % DROP
NO. VA (V) (A) DROP
POLES TRIP

1 LIGHTING OUTLET 16 800 230 3.48 2 - 3.5mm2 THHN + 1-3.5mm2 TW GRND 20MM Ø 2P 20AT 263.00 3.614 1.57%

2 CONVENIENCE OUTLET 4 720 230 3.13 2 - 3.5mm2 THHN + 1-3.5mm2 TW GRND 20MM Ø 2P 20AT 115.00 1.422 0.62% SERVICE ENTRANCE
3 CONVENIENCE OUTLET 4 720 230 3.13 2 - 3.5mm2 THHN + 1-3.5mm2 TW GRND 20MM Ø 2P 20AT 132.00 1.633 0.71%

4 CONVENIENCE OUTLET 4 720 230 3.13 2 - 3.5mm2 THHN + 1-3.5mm2 TW GRND 20MM Ø 2P 20AT 83.00 1.027 0.45%

5 REFRIGERATOR 1 800 230 3.48 2 - 3.5mm2 THHN + 1-3.5mm2 TW GRND 20MM Ø 2P 20AT 50.00 0.687 0.30%

6 RANGE 1 1500 230 6.52 2 - 3.5mm2 THHN + 1-3.5mm2 TW GRND 20MM Ø 2P 20AT 53.00 1.366 0.59%

7 SPARE 230

8 SPARE 230 KWH


TOTAL 5260 22.87

IPB = 22.87 + 0.25(3.48) = 23.74 A TOTAL LOAD IN KVA:


FEEDER SIZE: 2 - 14 sq.mm THWN & 1 - 5.5 sq.mm TW (Gnd) in 25mm dia. Conduit KVA = 23.74 x 230/1000 = 5.46
CB: 60AT, 100AF Circuit Breaker, 230 V, 2P, 60 Hz

MAIN FEEDER VOLTAGE DROP CALCULATION FAULT CURRENT CALCULATIONS:

MAIN DISTRIBUTION PANEL VOLTAGE DROP CALCULATION:


PB
CONSIDER THE VOLTAGE IS 230V FROM SOCOTECO 2.

FOR SINGLE PHASE, THE VOLTAGE DROP CAN BE CALCULATED USING 60A, 2P
THE FOLLOWING EQUATION:
20A 20A
VD = 2(K)(I)(L)/CM;
1 2
CONSIDERING THE LINE FROM THE SERVICE CONNECTION TO THE MAIN 1
20A 20A
PANEL, THE FOLLOWING DATA IS KNOWN:
3 4
WIRE SIZE = 2 - 14MM2 THWN WIRE
20A 20A
I = 23.74 A
L = 150 FT 5 6
K = 12.9 OHMS-CMIL/FT (FROM CHAPTER 9, TABLE 8 OF NEC,
FOR COPPER)
CM = 26240 CIRCULAR MILS (FROM CHAPTER 9, TABLE 8 OF 7 8
NEC)

THUS,

GROUND
VD = 2(12.9)(23.74)(150)/26240
VD = 3.5

VOLTAGE DROP PERCENTAGE = 3.5 / 230


= 1.5%

VOLTAGE AT THE MAIN PANEL BOARD = 230V - 3.5V


= 226.5 V
SINGLE LINE DIAGRAM
SCALE: NTS

PROFESSIONAL ELECTRICAL ENGINEER: PROJECT: REPUBLIC ACT 9266, RULE IV ,Section 33, DRAWN BY: OWNER: SHEET #

Drawings and Specifications & other contract documents duly signed,stamped


or sealed,as instruments of service,are the intelectual property & documents of
SCALE:
Architect, whether the object for which they are made is executed or not. It
shall be unlawfull for any person to duplicate or to make copies of said
LOCATION: documents for use in the repitition of & for other projects or buildings,whether
PRC executed partly or in whole,without the written consent of architect or author
of said documents.
P.T.R PROJECT #
T.I.N ISSUED AT: