PANEL BOARD: PB
1 LIGHTING OUTLET 16 800 230 3.48 2 - 3.5mm2 THHN + 1-3.5mm2 TW GRND 20MM Ø 2P 20AT 263.00 3.614 1.57%
2 CONVENIENCE OUTLET 4 720 230 3.13 2 - 3.5mm2 THHN + 1-3.5mm2 TW GRND 20MM Ø 2P 20AT 115.00 1.422 0.62% SERVICE ENTRANCE
3 CONVENIENCE OUTLET 4 720 230 3.13 2 - 3.5mm2 THHN + 1-3.5mm2 TW GRND 20MM Ø 2P 20AT 132.00 1.633 0.71%
4 CONVENIENCE OUTLET 4 720 230 3.13 2 - 3.5mm2 THHN + 1-3.5mm2 TW GRND 20MM Ø 2P 20AT 83.00 1.027 0.45%
5 REFRIGERATOR 1 800 230 3.48 2 - 3.5mm2 THHN + 1-3.5mm2 TW GRND 20MM Ø 2P 20AT 50.00 0.687 0.30%
6 RANGE 1 1500 230 6.52 2 - 3.5mm2 THHN + 1-3.5mm2 TW GRND 20MM Ø 2P 20AT 53.00 1.366 0.59%
7 SPARE 230
FOR SINGLE PHASE, THE VOLTAGE DROP CAN BE CALCULATED USING 60A, 2P
THE FOLLOWING EQUATION:
20A 20A
VD = 2(K)(I)(L)/CM;
1 2
CONSIDERING THE LINE FROM THE SERVICE CONNECTION TO THE MAIN 1
20A 20A
PANEL, THE FOLLOWING DATA IS KNOWN:
3 4
WIRE SIZE = 2 - 14MM2 THWN WIRE
20A 20A
I = 23.74 A
L = 150 FT 5 6
K = 12.9 OHMS-CMIL/FT (FROM CHAPTER 9, TABLE 8 OF NEC,
FOR COPPER)
CM = 26240 CIRCULAR MILS (FROM CHAPTER 9, TABLE 8 OF 7 8
NEC)
THUS,
GROUND
VD = 2(12.9)(23.74)(150)/26240
VD = 3.5