Professional Documents
Culture Documents
Third Order Integral Terminal Sliding Control For DC-DC Converter Voltage Stability
Third Order Integral Terminal Sliding Control For DC-DC Converter Voltage Stability
Third Order Integral Terminal Sliding Control For DC-DC Converter Voltage Stability
Abstract—In DC bus, constant power loads (CPLs) are control systems, however, could not ascertain the stability of
connected in DC distribution networks (DCDNs) which causes the DDBC feeding load of the CPL. Two improved linear
the system instability due to the negative impedance properties quadratic regulator (LQR) control systems, m-LQR and M-
of CPLs. To ensure system stability, a third-order integral LQR, had been claimed in [8] to deal with all of the
terminal sliding mode controller (3-ITSMC) is proposed using aforementioned issues. These two control strategies, however,
an improved quick-reaching law. In this proposed control could not be sufficient to compensate for the impedance
scheme, an improved reaching law is used to mitigate chattering characteristics of CPLs which had a bad impact on the overall
from the system and tackles the underlying issue of the non- system stability. Fuzzy logic (FL), sliding mode (SM), and
minimum phase in DC-DC boost converters (DDBCs). Through
model predictive control (MPC) schemes are just a few of the
the Lyapunov stability theory, 3-ITSMC controller can ensure
the stability of the entire system which is the main aim of this
examples of nonlinear control mechanisms that the
proposed 3-ITSMC. The performance of the proposed control researchers had developed in some research works to get over
scheme is validated through the simulation investigations these constraints [9-11].
implemented in MATLAB/Simulink under major fluctuations To ensure the whole system's stability, the adaptive energy
demonstrating that it enhances the stability of DCDNs in every shaping (AES) control method has been proposed in [12].
aspect as compared to the existing sliding mode controllers. However, the AES control method could not ensure a fast
After the simulation, the tracking error of 3-ITSMC is 20% for
dynamic response as well as fewer dynamic tracking errors in
DC voltage variation. Additionally, for the variations in CPLs’
the whole system. In [11], the author presented an explicit
power, the tracking error of 3-ITSMC is 18%.
MPC (eMPC) for assurance of a fast dynamic response. If the
Keywords—constant power load, DC distribution networks, system characteristics were not exactly comprehended, then
DC-DC boost converters, third-order integral terminal sliding the MPC controller could not work effectively. To resolve this
mode controller, Lyapunov stability criteria limitation, a backstepping controller (BSC) was proposed in
[13] to alleviate and enhance the DC bus voltage stability in
I. INTRODUCTION DCDNs. A new nonlinear integral BSC scheme was proposed
Power electronics converter (PEC) sources generally by Andalibi et al. [14] to ensure a fast dynamic response.
employ renewable energy sources (RES) such as solar power However, the BSC could not ensure the tracking error and the
generation systems (SPGs) and wind power generation transient response of the output DC bus voltage if the user-
systems (WPGs). PECs are extensively used because of their defined constants were improperly chosen by trial-and-error
adaptability, versatile voltage management at present, high approaches.
efficiency, and output voltage stability [1]. DC-DC boost By inspiring the above mentioned works and for
converters (DDBCs) are utilized in such instances for stabilizing the DC bus voltage of DDBCs feeding CPLs, a 3-
coupling the RES to the DC bus [2]. The DC bus in a DC ITSMC method is presented. This proposed control scheme is
distribution network (DCDN) has an enormous number of developed by making use of improved quick-reaching law
loads attached to it. One of them is the constant power load theories and third-order integral terminal sliding mode control
(CPL), has been set up to consume a constant volume of power (3-ITSMC). To lessen chattering in the overall system, this
[3]. As a result, research has concentrated on enhancing the research use a third-order integral terminal sliding mode
reliability and sustainability of DCDNs with CPLs [4]. surface. The overall stability of the entire system is
Feeding CPLs in DDBCs present two major challenges: investigated by employing the Lyapunov stability theory.
regulating DDBCs to achieve desirable DC bus voltage and Finally, the performance is compared to that of the existing
reducing the negative impedance characteristics of CPLs. This sliding mode controller to show its positive consequences.
type of impedance of CPLs causes the voltage to drop And the simulation results under various circumstances and
exponentially with increasing current, which significantly disturbances based on real-life scenarios are shown such as
impacts the stability of the power systems. Negative reference DC bus voltage and reference power of CPLs'
incremental impedance of the constant power loads results in fluctuations in a certain time range.
significant power system instability [5]. The work is structured as follows: Section II covers
Usually, linear controllers have been employed; however, problem formulation and system modeling, while Section III
the nonlinear system feeding CPLs cannot be controlled via explains the recommended controller design process using
conventional techniques [6]. Direct model reference adaptive appropriate equations. In Section IV, the simulated results and
control based on the PI linear control scheme was proposed in its analysis are given. The conclusion and future works are
[7] to deal with this issue. All of the aforementioned linear described in Section V.
where, RCPL indicates the equivalent internal impedance of where, c1 and c2 are positive constants which satisfy the
conditions of c1 > 0 and c2 > 0. And α is a positive constant
CPLs and I CPL is the steady-state current value at the
which satisfies the condition of < α < 1.
equilibrium point under small signal disturbances. Because of
the negative impedance characteristics of CPLs, it poses a Therefore, dynamic errors are determined as follows:
negative impact on system stability under load variations
which is seen in Eq. (1) and Eq. (2). e1 = Vdc − Vdc ( ref ) (6)
B. Modeling of the DDBC Feeding CPLs
e2 = iL − iL ( ref ) (7)
In Fig. 2, the DC voltage supply Vg is attached to the main
where, with Ϛ > 0. From Eq. (6), it is obtained as,
DC bus, which serves as the main source through a DDBC,
and the resistive load is connected in parallel to the main DC • •
bus through the CPLs. e1 = Vdc (8)
Authorized licensed use limited to: M S RAMAIAH INSTITUTE OF TECHNOLOGY. Downloaded on March 27,2024 at 09:10:00 UTC from IEEE Xplore. Restrictions apply.
Step 2: Determining the main control law, IV. SIMULATION RESULT AND ANALYSIS
• •
α On the MATLAB/Simulink platform, a primitive
S = c1 e 2 + c 2 e 2 sign ( e 2 ) (11) simulation model, depicted in Fig. 2, has been constructed to
illustrate the effectiveness of the designed controller. Table I
Switching rules are well known for their significance in contains a list of the system parameters. The following gain
reducing chattering and achieving finite-time convergence. To parameters are chosen to run the simulation: c=4, c1=0.09,
meet this control objective and reduce the limitations of c2=0.009, c3=0.67, a=0.0001, α=0.2, and ϛ=5.01. Several
conventional reaching law, a novel improved quick-reaching trials and errors are conducted to find an appropriate gain
law can be represented as follows: parameter for each parameter.
•
S = − c (b
S
− 1) sign ( S ) − c 3 S sign ( S )
a
(12) This proposed control scheme shows strong performance
when considering the alteration of the DC bus voltage and the
where, c, c3, a, and b are positive constants that satisfy all the variation of the reference power of CPLs. Both are discussed
in more detail below.
c3
conditions such as c > 0, c3 > 0, 0 < a < 1, and b = 1 + . A. DC Bus Voltage Variation
c
By equating Eq. (11) and Eq. (12), the following expression Initially, the controller's performance is evaluated through
can be written: fluctuations in the DC bus voltage of DDBC. As a result, a DC
bus voltage of 120 V is initially evaluated, and it is
•
α S a subsequently raised from 120 V to 130 V at t = 1.5 sec. Fig. 3
c1e2 +c2 e2 sign(e2 ) = −c(b −1)sign(S) − c3 S sign(S) (13)
(a) depicts all the possibilities described. On the other hand,
• the supply voltage is 60 V, and the reference power of CPLs
Putting the values of e2 and e2 in Eq. (13) and the main is assumed to be 1800 W respectively. The main DC bus
voltage stability with reduced tracking error and a quicker
control law of the proposed control scheme from Eq. (13) can settling time cannot be assured by the existing sliding mode
be expressed as follows: controller when the reference DC bus voltage of a DC-DC
1 1 P V − Vdc α
boost converter fluctuates, as is seen in Fig. 3 (b). On the other
µ= [ς (iL − CPL ) − c1 ( g ) − c2 e2 sign(e2 ) hand, the proposed 3-ITSMC can offer a quick dynamic
Vdc i C Vdc L
(c1 +ς L ) reaction and a quick settling time with minimized tracking
L C errors.
S a
− c(b − 1) sign( S ) − c3 S sign( S )]
(14)
Inserting the value into Eq. (11) will yield as,
•
S a
S = − c (b − 1) sign ( S ) − c 3 S sign ( S ) (15)
•
Since c > 0 , c3 < 0 , and W ≤ 0 are with the designed
control law, the whole system stability is assured. The control
law is represented in Eq. (14). In the following section, the
simulation results are employed to validate the efficacy of the
proposed 3-ITSMC.
Authorized licensed use limited to: M S RAMAIAH INSTITUTE OF TECHNOLOGY. Downloaded on March 27,2024 at 09:10:00 UTC from IEEE Xplore. Restrictions apply.
controller is less than 17% which means the difference ITSMC is superior to the existing sliding mode controller in
between the measured DC bus voltage and the reference DC terms of settling time and dynamic tracking error.
bus voltage is 0.17. On the other hand, the tracking error for
the existing sliding mode controller is greater than 97% for the V. CONCLUSION AND FUTURE WORK
DC bus voltage response which also means that the difference The negative impedance properties of CPLs, which lead to
value of the measured DC bus voltage and the reference DC system instability, are tackled in this research via a third-order
bus voltage is 0.97. Additionally, the proposed control integral terminal sliding mode controller. The Lyapunov
method's reaction time for the DC bus voltage is significantly theory guarantees the system’s overall stability. It can be
less than the response for the existing sliding mode control determined that the suggested 3-ITSMC is more efficient than
scheme. the existing sliding mode controller, when the reference power
B. Variation in CPLs’s Reference Power of the CPL and system DC bus voltage fluctuates in terms of
settling time and dynamic tracking errors. The contribution of
To demonstrate the influence of this real-life scenario on the proposed controller is verified through the simulated
DCDNs, the reference power of CPLs is set to 1850 W at the results. It is obtained from the simulation outcomes that the
beginning. The power is decreased from 1850 W to 1800 W proposed controller can ensure a more stable DC bus voltage
at t = 1.9 sec, as illustrated in Fig. 4 (a). This type of under different conditions. In future work, another type of
circumstance is regularly observed in practical life scenarios. advanced reaching law can be used to reduce chattering from
In contrast, the reference DC bus voltage is 120 V while the whole system feed CPLs.
DDBC’s rated input voltage is 60 V. As shown in Fig. 4 (b),
3-ITSMC can offer main DC bus voltage traceability with a REFERENCES
shorter settling time and smaller tracking error when the [1] J. Hu and K. W. E. Cheng, “Predictive control of power electronics
reference power of CPLs is altered. Conversely, the existing converters in renewable energy systems,” Energies, vol. 10, no. 4, p.
sliding mode controller is unable to ensure a quick dynamic 515, 2017.
reaction and minimal tracking error. The suggested controller [2] T. K. Roy, M. A. Mahmud, A. M. T. Oo, M. E. Haque, K. M. Muttaqi,
beats the existing controller in terms of tracking error and and N. Mendis, “Nonlinear Adaptive Backstepping Controller Design
settling time when the reference power of CPLs is altered. for Islanded DC Microgrids,” IEEE Trans. Ind. Appl., vol. 54, no. 3,
pp. 2857-2873, 2018.
[3] C. D. Korkas, S. Baldi, I. Michailidis, and E. B. Kosmatopoulos,
“Occupancy-based demand response and thermal comfort optimization
in microgrids with renewable energy sources and energy storage,”
Appl. Energy, vol. 163, pp.93-104, 2016.
[4] M. Nasir, H. A. Khan, A. Hussain, L. Mateen, and N. A. Zaffar, “Solar
PV-Based Scalable DC Microgrid for Rural Electrification in
Developing Regions,” IEEE Trans. Sustainable Energy, vol. 9, no. 1,
pp. 390-399, 2018.
[5] N. Sarafan, J. Zarei, R. Razavi-Far, M. Saif, and M. H. Khooban, “A
Novel On-Board DC/DC Converter Controller Feeding Uncertain
Constant Power Loads,” IEEE J. Emerging Sel. Top. Power Electron.,
vol. 9, no. 2, pp. 1233-1240, 2021.
[6] L.Ardhenta and R. K. Subroto, “Application of direct MRAC in PI
(a) Reference power of CPLs′ fluctuation.
controller for DC-DC boost converter,” Int. J. Power Electron. Drive
Syst., vol. 11, No. 2, p. 851, 2020.
[7] N. Agrawal, S. Samanta, and S. Ghosh, “Modified LQR Technique for
Fuel-Cell-Integrated Boost Converter,” IEEE Trans. Ind. Electron.,
vol. 68, no. 7, pp. 5887-5896, 2021.
[8] A. R. Nikhar, S. M. Apte, and R. Somalwar, “Review of various control
techniques for DC-DC interleaved boost converters,” Int. Conf. Global
Trends in Signal Process. Inf. Comput. Commun., pp. 432-437, 2016.
[9] C. S. Sachin and S. G. Nayak, “Design and simulation for sliding mode
control in DC-DC boost converter,” 2017 2nd Int. Conf. Commun.
Electron. Syst., pp. 440-445, 2017.
[10] K. Swathy, S. Jantre, Y. Jadhav, S. M. Labde, and P. Kadam, “Design
and Hardware Implementation of Closed Loop Buck Converter Using
Fuzzy Logic Controller”, 2018 Second Int. Conf. Electron. Commun.
Aerosp. Technol., pp. 175-180, 2018.
(b) DC bus voltage response. [11] O. Andrés-Martínez, A. Flores-Tlacuahuac, O. F. Ruiz-Martinez, and
J. C. Mayo-Maldonado, “Nonlinear model predictive stabilization of
Fig. 4. Dynamic response of the entire system with the reference power
DC–DC boost converters with constant power loads,” IEEE J.
variation of the CPL. Emerging Sel. Top. Power Electron., vol. 9, no. 1, pp. 822-830, 2020.
[12] W. He and R. Ortega, “Design and implementation of adaptive energy
From Fig. 4(b), the proposed 3-ITSMC controller shaping control for DC–DC converters with constant power loads,”
performs better in terms of tracking errors than the existing IEEE Trans. Ind. Inf., vol. 16, no. 8, pp. 5053-5064, 2019.
works. When the reference power of CPL is varied at 1.9 sec, [13] Q. Xu, W. Jiang, F. Blaabjerg, C. Zhang, X. Zhang, and T. Fernando,
the tracking error for the proposed controller is less than 18% “Backstepping Control for Large Signal Stability of High Boost Ratio
which means the difference between the measured DC bus Interleaved Converter Interfaced DC Microgrids With Constant Power
voltage and the reference DC bus voltage is 0.18. In contrast, Loads,” IEEE Trans. Power Electron., vol. 35, no. 5, pp. 5397-5407,
2020.
the tracking error for the existing sliding mode controller is
[14] M. Andalibi, M. Hajihosseini, M. Gheisarnejad, J. Boudjadar, M. H.
greater than 98% for the DC bus voltage response where the Khooban, and T. Dragicevic, “A new nonlinear controller for
difference value of the measured DC bus voltage and the multilevel DC/DC boost converter,” In 2020 IEEE 11th Int. Symp.
reference DC bus voltage is 0.98. Therefore, the suggested 3- Power Electron. Distrib. Gener. Syst., pp. 276-280, 2020.
Authorized licensed use limited to: M S RAMAIAH INSTITUTE OF TECHNOLOGY. Downloaded on March 27,2024 at 09:10:00 UTC from IEEE Xplore. Restrictions apply.
[15] S. Singh, D. Fulwani, and V. Kumar, “Robust sliding‐mode control of Controllers to Stabilize the DC-Bus Voltage for DC–DC Converters
dc/dc boost converter feeding a constant power load,” IET Power Feeding CPLs,” Energies, vol. 14, no. 20, p. 6753, 2021.
Electron., pp. 1230-1237, 2015.
[16] S. K. Ghosh, T. K. Roy, M. A. H. Pramanik, and M. A. Mahmud,
“Design of Nonlinear Backstepping Double-Integral Sliding Mode
Authorized licensed use limited to: M S RAMAIAH INSTITUTE OF TECHNOLOGY. Downloaded on March 27,2024 at 09:10:00 UTC from IEEE Xplore. Restrictions apply.