NFPA 10 | TYPES OF FIRE

• Not all fires are


the same.

• Fires are
classified into
different Class

• Right fire
extinguishing
system to be
selected for the
hazard.
Honeywell Confidential - ©2019 by Honeywell International Inc. All rights reserved. 3
FIRE TRIANGLE | HEAT ABSORPTION

Ideal Applications

 Removal of Fuel is not possible – Cables

 Removal of Oxygen is dangerous - Manned application

 Water / Powder based systems like


 Sprinklers
 Deluge Systems
 ABC Powders may damage critical assets like
Servers

 Application cannot afford downtime

 Valuable assets

Remove any one element and Fire is


“EXTINGUISHED”
Honeywell Confidential - ©2019 by Honeywell International Inc. All rights reserved. 4
Clean Agent| Most Commonly Used

new
telecom Eco-friendly Product

need
need of
Clean Agent
The hour

Oil & gas go green Safe environment friendly


CONTROL ROOM environment friendly

SYNTHETIC Inert
IG55

1950’s
HFC-227ea 1990
Argonite

Most
Method of Extinguishment Method of Extinguishment
*Buy absorption of heat principle Commonly *Buy reducing oxygen level
Fire is suppress.
used Clean Fire is suppress. (13 ~ 11 %)

Agent
FK-1230TH IG541
2004

1990’s
(FK-5-1-12)
CLEAN AGENT | TYPES & CRITERIA
CF3CF2C(O)CF(CF3) 2 FK-5112 HFC-227ea
Description

Ozone Depletion Potential 0.0 0.0


FK 1230® 42 Bar 1979 1987
(FK-5-1-12)
Global Warming Potential 1 3220

1994 2016
Atmospheric Lifetime (Years) 0.014 34.2

25 Bar HFC-227ea & FK-1230 is


• Clean - Colorless - Odorless
• Electrically non-conductive - Non-Toxic
Clean
Agent Comparison for 200CU.M Class C Hazard
FK-1230® 4.5% 131 kg. - 1 x 120ltr.

HFC-227ea 7.0% 110 kg. - 1 x 120ltr.

CONCENTRATION

HFC-227ea 42 Bar FK-1230® HFC-227ea

10,5
10

10
9
7
4,5
25 Bar
CF3CHFCF3 DESIGN NOAEL LOAEL
CONCENTRATION
(CLASS C)
CLEAN AGENT FIRE SUPPRESSION | APPLICATIONS

DATA CENTRES TELECOMMUNICATIONS CONTROL ROOM

OIL AND GAS INDUSTRY MUSEUMS MARINE INDUSTRY

Honeywell Confidential - ©2019 by Honeywell International Inc. All rights reserved.


STRUCTURE| DESIGN CONCEPTS

• Total Flooding Fire Protection System


• Must have an enclosure
• Agent mixes with atmosphere to protect entire
volume
• Agent mixing performed by nozzles
• No Local application
• Discharge Time
• Must be 10 seconds or less
• Software will issue a warning

Honeywell Confidential - ©2019 by Honeywell International Inc. All rights reserved.


STRUCTURE| MINIMUM DESIGN CONCENTRATION
FK-1230® (FK-5-1-12) HFC-227ea
5 8
Hepptane
4,5 MEC
0,66 7 Hepptane
4 1,2
1,8 MEC
3,5 0,54 6 1,5
3 5
2,5 4
Unit

Unit
2
3,3 3,3 3
1,5 5,2 5,2
1 2
0,5 1
0 0
Class A Class C Class A Class C
MEC Safety Factor Column1 MEC Safety Factor

MEC *Safety Concen MEC *Safety Concen


Factor tration Factor tration
Class A 3.3 1.2 % 4.5 Class A 5.2 1.2 % 6.7
Class C 3.3 1.35 % 4.5 Class C 5.2 1.35 % 7.0

Note : Class A fire safety factor is 1.2 or min. extinguishing concentration of Hepptane as determined from 5.4.2.1,
STRUCTURE| Comparison FK-1230 Vs HFC-227ea

𝑉𝑉 𝑐𝑐
𝑊𝑊 = 𝑋𝑋
𝑠𝑠 100 − 𝑐𝑐
c = agent concentration [ vol %]
W = installed quantity of agent [ lb (kg) ]
s = specific volume of the agent [ ft3/lb (m3/kg) ]
V = volume of enclosure [ ft3 (m3) ]

specific volume FK-1230 (FK-5-1-12) specific volume HFC-227ea

Imperial Units Imperial Units


s = 0.9856 + 0.002441t, Where t is (0F) s = 1.885 + 0.0046t, Where t is (0F)
Metric Units Metric Units
s = 0.0664 + 0.0002741t, Where t is (0C) s = 0.1269 + 0.0005t, Where t is (0C)
STRUCTURE| Calculate Volume
• Dimensions taken during analysis
• OK to subtract permanent volume
reductions
• RCC Columns
• RCC Beam
• Platforms

• Do NOT subtract for equipment


and moveable objects

Calculate Volume
STRUCTURE| MDQ calculation Example

• Enclosure is 5m (W) x 5m (L) x 4m (H)

• Min Ambient Temperature = 21 °C

• Class C Hazard (Fire that involve energized


electrical equipment)
STRUCTURE| MDQ calculation Answer

• Enclosure is 5m (W) x 5m (L) x 4m (H)


• Min Ambient Temperature = 21°C
• Class C Hazard (Fire that involve energized electrical equipment)

• HFC-227ea :- • FK 1230® :-
Volume (V) : 5 x 5 x 4 = 100 Cu.M. Volume (V) : 5 x 5 x 4 = 100 Cu.M.
s : 0.1269 + (0.0005x21) = 0.1374 s : 0.0664 + (0.0002741x21) = 0.07215
W : (100/0.1374) x [7/(100-7)] = 54.78 Kg W : (100/0.0721) x [4.5/(100-4.5)] = 65.30 Kg
- Or - - Or -
Flooding Factor Flooding Factor
(7.0 %, 21°C) = 0.5486 Kg/Cu.M (4.5 %, 21°C) = 0.6530 Kg/Cu.M
= 100 x 0.5486 = 100 x 0.6530
= 54.78 Kg = 65.30 Kg
STRUCTURE| BASIC STRUCTURE OF A SYSTEM

• Agent Cylinder
• Seamless & DOT Cylinder
• Control Heads
• Mounted directly on the cylinder
• Electrical, Manual and pressure
• Discharge piping network
• M.S. Seamless Pipe
• Discharge Nozzles
System Components | Cylinder

SEAMLESS CYLINDER
Capacity Valve Size Storage Agent Agent Fill Range Height Diameter
Pressure (Kg)
34 Liter 1.5” 25 & 42 Bar HFC & FK 16.0 to 38.0 1118 mm Ø 232
80 Liter 2” & 1.5” 25 & 42 Bar HFC & FK 39.0 to 90.0 1842 mm Ø 267
120 Liter 2” & 1.5” 25 & 42 Bar HFC & FK 58.0 to 135.0 1642 mm Ø 356
140 Liter 2” & 1.5” 25 & 42 Bar HFC & FK 67.0 to 157.0 1867 mm Ø 356

DOT CYLINDER
Capacity Valve Size Storage Agent Agent Fill Height Diameter
Pressure Range (Kg)
15 Liter 1.5” 25 Bar HFC & FK 7.0 to 16.2 488.3 mm Ø 254
29 Liter 1.5 25 Bar HFC & FK 14.0 to 32.5 790.0 mm Ø 254
49 Liter 1.5” 25 Bar HFC & FK 23.6 to 54.9 83.6 mm Ø 324
80 Liter 2” 25 Bar HFC & FK 38.5 to 89.7 1258 mm Ø 324
104 Liter 2” 25 Bar HFC & FK 50.2 to 117.1 794.6 mm Ø 508
148 Liter 2” 25 Bar HFC & FK 71.3 to 166.5 1023 mm Ø 508
227 Liter 3” 25 Bar HFC & FK 109.0 to 254.6 1478 mm Ø 508
369 Liter 3” 25 Bar HFC & FK 177.2 to 414.0 1643 mm Ø 610
System Components | SUPER PRESSURIZED WITH NITROGEN

N2

HFC/FK
System Components | Cylinder Valve

Honeywell Confidential - ©2019 by Honeywell International Inc. All rights reserved. 18


System Components | Electrical cum Manual Actuator

Honeywell Confidential - ©2019 by Honeywell International Inc. All rights reserved. 19


System Components | Agent Discharge Nozzles

180° Nozzle 360° Nozzle


Coverage 13 x 13 M. Coverage 13 x 13 M.
Placed 0.3 m from wall Orifices aimed away Placed as close to center of hazard as
from the wall possible
As close to center of the wall as possible Honeywell Confidential - ©2019 by Honeywell International Inc. All rights reserved. 20
System Components | Hoses

Honeywell Confidential - ©2019 by Honeywell International Inc. All rights reserved. 21


System Components | Pneumatic Actuator

Honeywell Confidential - ©2019 by Honeywell International Inc. All rights reserved. 22


System Components | Manifold Pressure Switch

Honeywell Confidential - ©2019 by Honeywell International Inc. All rights reserved. 23


System Components | Manifold Check Valve
Description : Manifold Check Valve installed at the discharge manifold to allow removal of any
Clean Agent cylinder from the manifold while still retaining a closed system.

Available Sizes
1.5” P/N : H4-060-000
2” P/N : H4-061-000
3” P/N : H4-083-000

Honeywell Confidential - ©2019 by Honeywell International Inc. All rights reserved. 24


System Components | Typical installation

Honeywell Confidential - ©2019 by Honeywell International Inc. All rights reserved.


SYSTEM PRESSURE | BENEFITS OF 42 BAR

BENEFITS OF 42 BAR OVER 25 BAR SYSTEM

 High Cylinder Agent Fill


High pressure Low pressure
 Less Cylinders or Smaller size Cylinders
42 bar / N2 25bar / N2
 Supports larger & complex pipe network
 Smaller Pipe Size
Filling ratio:  Dependency on cylinder location eliminated
HP – 0.6 to 0.9 kg per litre  Better evaporation – Faster extinguishing
LP – 0.4 t0 0.7 kg per litre  Lower System Cost
Footer, Arial Bold 10pt Honeywell Confidential - ©2019 by Honeywell International Inc. All rights reserved. 26
HONEYWELL GAS SUPPRESSION SYSTEM | USP’S
a ll
HFC-227ea Clean Agent System
 UL listed gas suppression system for both 25bar & 42bar
FK-5-1-12 Clean Agent System
applications
 ISO Certified, UL Listed & PESO approved Filling station in India
25 42  PESO approved seamless gas filled cylinders
BAR BAR  Best in class UL Listed nozzle coverage area (13m*13m)
 2 in 1 manually/electronically operated Electric Control Head
(Solenoid Value) with Supervision
 UL Listed Flow Calculation Software. Entire clean agent
extinguishing agent system is in compliance with NFPA 2001 & UL
2166
 3 years’ warranty on mechanical components
 Training, Design, Pre & Post sales support end to end offered by
Honeywell
 One stop shop for solutions in Fire Safety Market

Honeywell Confidential - ©2019 by Honeywell International Inc. All rights reserved.