Professional Documents
Culture Documents
Imm Technical Manual
Imm Technical Manual
For product improvement, contents in this book may be subject to change without prior notice.
—1—
IMM TECHNICAL MANUAL
CONTENTS
1.SYSTEM INTRODUCTION....................................................................................................................... 5
2.FUNCTIONS ........................................................................................................................................... 6
3.HARDWARE ........................................................................................................................................... 8
—2—
IMM TECHNICAL MANUAL
5.SOFTWARE .......................................................................................................................................... 25
—3—
IMM TECHNICAL MANUAL
8.APPENDIX ............................................................................................................................................ 75
—4—
IMM TECHNICAL MANUAL
1.System introduction
1.1 System composition
IMM system is the short name of Intelligent Manager of Midea. It consists of four parts:
IMM software (one set), M‐interface web gateway (4 sets at most), V4+ outdoor unit
refrigerant system and dongle. IMM software provides user operation function, can be
installed in the PC. M‐INTERFACE based on WEB; connect to Midea Central Air‐conditioning
devices through the M‐net terminal. Under the auto topology mode, it can connect 4
refrigerant systems at most (can insert 256 sets indoor units and 16 sets outdoor units);
under the manual topology mode, it can connect. The IMM software can communicate
with network and M‐INTERFACE gateway, to control and manage the refrigerant system.
1) Projects which do not need power consumption: can freely connect D3、D4、D4+、V4、
—5—
IMM TECHNICAL MANUAL
V4+ units.
2) Projects which need power consumption: The indoor units and the outdoor units of the
same refrigerant system must be connected in the same M-interface.
3) The new outdoor units and the old outdoor units can not be mixed connected to the
same M‐net port of the M‐interface.
For more information, please contact Midea technical support.
2.Functions
2.1 Function introduction
The user can access WEB page and IMM software to control and manage the
air‐conditioning system. WEB page and IMM software offer different functions.
WEB screen has “Control”, “Map”, “Setting”, “DevInfo”, “Upgrade”, “CommLog” and “Help”
and so on functions.
Control‐‐Device monitoring
Offer indoor and outdoor units’ operating details and control the indoor unit.
Map ‐‐System mapping
Display the entire situation of refrigerant system; include quantities of indoor and outdoor
units in refrigerant system, ammeter quantity and communication quality between single
device and M‐INTERFACE gateway.
—6—
IMM TECHNICAL MANUAL
Setting
Offer the centralize controller configuration, time setting, IP setting and User management
etc. functions.
DevInfo ‐‐Device information
Display and amend detail information of indoor and outdoor devices in air‐conditioning
system.
Upgrade ‐‐Software upgrade
Offer the M‐INTERFACE gateway software upgrade function.
CommLog ‐‐Communication log
Offer the M‐INTERFACE gateway communication log.
Help
Offer helping information for user.
—7—
IMM TECHNICAL MANUAL
Dev.Management‐‐Device management
Offers the group division function of air‐conditioning device.
Statistical‐‐Data statistics
Provides the status changing records of indoor unit, outdoor unit and M‐INTERFACE
gateway.
Log
Offers all the records of the client‐side operations which operated by the user.
Setting
Offers project information configuration and electricity price configuration functions.
Account management
Offers amending account password function.
Refrigerant system
Display the indoor and outdoor units’ information in the refrigerant system, respond the
system mapping relation.
Search device
Search the air‐conditioners and gateway devices in the network.
3.Hardware
3.1 System architecture instruction
The air‐conditioner should connect to the M‐net port of the M‐INTERFACE gateway, and
the gateway through LAN port to communicate with IMM software. Use Type 5 network wire,
the longest should be 100 meters. M‐net port communication wire should use the twisted
three‐core shielding wire, the longest should be 1000 meters.
—8—
IMM TECHNICAL MANUAL
Under auto topology mode, one M‐INTERFACE gateway can connect 4 systems at most,
and No.1 system’s indoor and outdoor units insert to the No.1 and No.5 ports of M‐net
separately. No.2 system’s indoor and outdoor units insert to the No.2 and No.6 ports of M‐net
separately. No.3 system’s indoor and outdoor units insert to the No.3 and No.7 ports of M‐net
separately. No.4 system’s indoor and outdoor units insert to the No.4 and No.8 ports of M‐net
separately.
Under the manual topology, one M‐INTERFACE gateway can connect 16 systems at most.
Indoor units in the same system can not connect to several M‐net ports, but one M‐net port can
connect indoor units (different addresses) from several systems. Outdoor units in the same
system can not connect to several M‐net ports, but one M‐net port can connect outdoor units
(different addresses) from several systems.
M‐INTERFACE gateway only can be installed at one side of the bus, and need to add
matched resistance if necessary.
—9—
IMM TECHNICAL MANUAL
As above displayed, 4 M‐net ports in the upper side are indoor unit communication ports,
connect the XYE wires. 4 M‐net ports in the lower side are outdoor unit communication ports,
connect the K1K2E wires.
The gateway should be installed at one side of the bus, and need to use 0.7mm2~1.0mm2
three‐core shielding wire.
—10—
IMM TECHNICAL MANUAL
—11—
IMM TECHNICAL MANUAL
After setting the dial code switch, and take out the button battery from the accessory bag,
and upward side install the positive pole on the mainboard as the following display. System
time synchronization refers to 4.4.
—12—
IMM TECHNICAL MANUAL
3.2.7I/O Port
One UPS can power supply for one computer, one switchboard and 4 sets M‐INTERFACE
gateways at most. None power consumption system could not use UPS.
—13—
IMM TECHNICAL MANUAL
According to UPS BA650‐CH operation instruction, power wire and signal wire separately
connect to the power and computer. Install UPS BK650‐CH power management software.
Note: please carefully read the UPS operation instruction, and safely shut down the
computer when power‐off.
3.4 Dongle
It should insert the dongle to server PC first, and then operate the server software. The
dongle can be inserted to any USB ports of PC; the dongle will be along with the device.
—14—
IMM TECHNICAL MANUAL
Configure single IP
Open the property dialogue box to configure the IP address and subnet cover code, for
example: IP: 192.168.100.44, subnet cover code: 255.255.255.0.
—15—
IMM TECHNICAL MANUAL
Click the “Add” button in IP address bar, add a IP address in the same net area with
“192.168.100.40”, e.g.: IP: 192.168.100.101, subnet cover code: 255.255.255.0, and then click
the “Add” button.
Note: do not set the gateway IP to be: 192.168.100.0/255, otherwise it may occur error
during operation.
In the PC configured static IP, through browser (e.g.: Internet Explorer 9) to enter IP
configuration page of WEB system, and enter as administer, page displays as follow:
After setting click the “OK” button. If several M‐INTERFACE gateways in the same network
segment, the IP addresses can not be repeated.
4.2 login
Type in M‐INTERFACE gateway’s IP address in the address bar of browser, the page will shift
to M‐INTERFACE WEB login interface, administer enter the system follows the below
operations:
1). Double‐click the left mouse button on the icon , it will popup the login typing
frame.
2). Type in password in login frame.
3). Select the display language (Chinese/English).
4). Click the [Ok] button to enter M‐INTERFACE WEB main page.
5). Click [Cancel] button to cancel this typing.
—16—
IMM TECHNICAL MANUAL
Administer can amend the password and 4 common users’ password. The page display as
follow:
The baud rate of serial ports 5‐8 should be set to be the outdoor unit communication baud
rate (V4+ outdoor unit default to be 600), finish amending then click “Ok” button, and
re‐operate the unit to become effective. If the setting baud rate was different from the outdoor
—17—
IMM TECHNICAL MANUAL
unit communication baud rate, then it cannot search air‐conditioning outdoor units under this
port.
Select the time zone, click the “Ok” button, and then click “Time synchronization” button
to carry out the operation.
—18—
IMM TECHNICAL MANUAL
Set the IP address, terminal (Default: 21), login name (Default: test) and password (Default:
123456) of the FTP server (PC address of installing the server software). Click “apply” button
after setting. If set successfully, then it can check the log record on the FTP server.
Under auto topology mode, through the WEB page to carry out the device search function.
Enter the refrigerant system mapping page, as above display, click the “Scan device”
button. M‐INTERFACE gateway begins to search the air‐conditioners.
Under manual topology mode it needs to manual import the system topology documents
(topology document form refers to 8.1), and during the system topology documents importing
process, M‐INTERFACE gateway automatically carry out device search function. Importing
system topology documents page as below display:
—19—
IMM TECHNICAL MANUAL
During the device searching process, check the existing system, indoor unit and outdoor
unit devices.
After searching, WEB page will display the result, display as follow:
—20—
IMM TECHNICAL MANUAL
The page will display the searched indoor unit quantity, indoor unit number, outdoor unit
quantity and numbers etc.
M‐INTERFACE gateway will give out the communication quality between gateway and
single air‐conditioner, display as follow:
Click single device, communication quality bar will display the communication quality
between this device and gateway.
Select the refrigerant system, click the “IndoorInfo”, and the will show up the indoor unit
information display page, as follow:
—21—
IMM TECHNICAL MANUAL
The display contents include: serial port (terminal no. which inserted into), address, physics
location, sales model, fan power, E‐heater power and maintenance status information.
Administer can amend the physical location, sales model, fan power (only when the sales model
is others), electrical heating power (only when the sales model is others) and maintenance
status. After amend the physical location, the corresponding device name will change, other
items’ amending will affect the electricity partition. Finish amending then click the “Save”
button. If set the maintenance status to be “yes”, then it needs to restart the M‐INTERFACE
gateway to be effective. Device under maintenance status will not display in the WEB page. And
if amended the maintenance status attribute of the device, the client‐side software needs to be
searched again. Otherwise, it fails to control, and it can see “Didn’t find the indoor unit address
information” in the prompt message frame, then after search the client‐side software again, the
devices under maintenance status will not display in the client‐side interface.
Select the refrigerant system, click the “OutdoorInfo”, and the will show up the outdoor
unit information display page, as follow:
—22—
IMM TECHNICAL MANUAL
The display contents include: serial port, address, device name, and sales model.
Administer can amend the “Device Name” and “Sales Model” parameters, and click the “Save”
button. After amend the device name, the corresponding device name will change.
M‐INTERFACE gateway can be upgraded through WEB page, the administer login the WEB
page and enter to the software upgrade page, display as follow:
Select the “Upgrade” menu and click “Browse” button in the page and select the upgrade
document, then click the “Upgrade” button. After finish upgrade, the page will popup “Re‐start
—23—
IMM TECHNICAL MANUAL
the M‐INTERFACE” message. After re‐operation, upgrade finished. Upgrade time is about 10
minutes; please do not cut‐off the power during the upgrade process.
Administer login WEB page to check the communication diagnosis information, display as
follow:
Administer can clear the logs, download the logs and the diagnosis information in this page.
4.10 Precautions
1). When change the auto/manual modes of M‐INTERFACE gateway, it must set the dial code
first.
2). If cannot use the sending button in the WEB page, it means the M‐INTERFACE gateway
was locked in the client‐side software, it need to be un‐locked in the client‐side software.
3).After change the system inserted port number, it must to search M‐INTERFACE again.
4).In I/O port, Pin4 and Pin6 ports’ input voltage are higher than 3V and last for 3 seconds,
M‐INTERFACE will carry out emergency stop. All the devices inserted to this M‐INTERFACE
gateway will be stopped.
5). Install the battery before use the M‐INTEFACE gateway.
—24—
IMM TECHNICAL MANUAL
5.Software
5.1 Software installation
5.1.1 Preparation
Before the new software installation, it needs to meet the following requirements:
System requirements
Specification Recommendation Remark
—25—
IMM TECHNICAL MANUAL
Set the time form as the above, after finish setting click “OK” button for saving. Select
“Administrative” and then display as follow:
Click “Change system locale…”, then will popup the following figure:
—26—
IMM TECHNICAL MANUAL
Select “English (United States)”, click OK. And re‐start the computer after modification.
Note: during the IMM software operating process, do not change the region and language
setting, otherwise will lead the electricity partition error.
If the PC is windows7 system, install server and client‐side software in this system, then it
need to do the following setting:
Open the control panel, display as follow:
—27—
IMM TECHNICAL MANUAL
Set to be “Never notify” as the above, click OK. And re‐start the computer after
modification.
Set the following setting for the PC installed client‐side and server software
Take Windows7 system for example:
Open the “Power option” in the control panel, display as follow:
Set the “Turn off the display” and “Put the computer to sleep” to be “Never”. And click
“Change advanced power settings”, display as the following:
—28—
IMM TECHNICAL MANUAL
Set the “Turn off hard disk after” under “Balanced[Active]”to be “Never”, after setting clicks
the “OK” for saving.
Make sure the server PC has opened port 21
If the server PC did not open port 21, then when operate EnergyFTP process, it will popup
prompt information open port 21. Display as follow:
—29—
IMM TECHNICAL MANUAL
Types the adding port number as the above, click the “OK” button.
Note: before install the software in other language system, do not change the region and
language setting of the system.
Install the database software, server software and dongle software in the same computer
(server). The client‐side software can be installed in the other computer. If the server is
Microsoft Windows XP system, then it needs to previous install: NET Framework 3.5 SP1,
Microsoft Windows Installer 4.5,Windows PowerShell 1.0 and dotNetFx40_Full_x86_x64.exe. If
the client‐side is Microsoft Windows XP system, then it needs to previous install NET Framework
3.5 SP1 and dotNetFx40_Full_x86_x64.exe components. Client‐side and server with Microsoft
—30—
IMM TECHNICAL MANUAL
Windows 7 system do not need to install above system software. The following is installation
steps of each component (take Microsoft Windows XP Chinese system for example):
2、 Finish loading components will popup installation dialogue frame, as the following display:
Select “I had read and agree the clause (A)”, and click “Install (I)” button.
3、 “Download and installation process” dialogue.
—31—
IMM TECHNICAL MANUAL
—32—
IMM TECHNICAL MANUAL
2、 Select “Agree (A)” and click “Next” button then will display as follow:
—33—
IMM TECHNICAL MANUAL
—34—
IMM TECHNICAL MANUAL
2、 Click the “Next” as the above figure, then will display the following:
—35—
IMM TECHNICAL MANUAL
—36—
IMM TECHNICAL MANUAL
—37—
IMM TECHNICAL MANUAL
2. Select “I had read and agree the clause (A)”, and click “Install (I)” button, and display as follow:
—38—
IMM TECHNICAL MANUAL
4. Click “Finish” button to exit the installation interface and finish installation.
Find out “SQLEXPRWT_x86_ENU.exe” under Database menu, install as the following steps:
1、 Double‐click “SQLEXPRWT_x86_ENU.exe”, then will display the following:
2、 Click the “New installation or add …..” as the above figure, then will display the following
—39—
IMM TECHNICAL MANUAL
4、 Select “I accept the license terms” , then will display the following:
—40—
IMM TECHNICAL MANUAL
5、 Click the “Install” as the above figure, then will display the following:
6. Select all the options as the above, and click the “Next” button, then display the following:
—41—
IMM TECHNICAL MANUAL
7.Select “Default instance” in the above, and then click “Next”, display the following:
8. Select “NT AUTHORITY/SYSTEM” in the Account Name of SQL Server Database Engine, then
click “Next”. Display as follow:
—42—
IMM TECHNICAL MANUAL
9. Select “Mixed Mode…….”in the above, and type in sa user’s password, default password is
654321, and then click the “Next”. Display as follow:
10. Do not select “Send Windows and SQL Server….”in the above, and click the “Next”, display as
follow:
—43—
IMM TECHNICAL MANUAL
11. Finish installation, click “Close” and close the dialogue frame.
Find out IMMServer_Vx.exe (server installation program) under IMM menu, install as the
following steps:
1、 Double‐click the installation program, then will display the following:
—44—
IMM TECHNICAL MANUAL
3、 Select “I agree to the terms of this license agreement”, click “Next” button
—45—
IMM TECHNICAL MANUAL
5、 Select the software installation menu, it’s recommended to install in the non‐system disk.
E.g.: the operation system was installed in C disk, and then the software should be installed in
D or E disk, for the system safety. Click the “Next” button.
6、 Finish installation, click “Finish” button and exit installation. Find out “IMM Server” software
in the “Start” and “All programs”.
Find out IMMClient_Vx.exe under IMM menu, install as the following steps:
1、 Double‐click the client‐side installation program, then will display the following:
—46—
IMM TECHNICAL MANUAL
3、 Select “I agree to the terms of this license agreement”, click “Next” button
—47—
IMM TECHNICAL MANUAL
5、 Select the software installation menu, it’s recommended to install in the non‐system disk,
confirm the installation menu, and then click “Next” button.
—48—
IMM TECHNICAL MANUAL
Finish installation, click “Finish” button and exit installation. Find out “IMM Client”
software in the “Start” and “All programs”.
Find out dongle driver (MicroDogInstdrv.exe) under Dog Driver, double‐click this program
to install (take XP Chinese system for example). Display as the following:
Select the “USB dog driver”, click the “Install” button in the above, and start to install the
driver. After installation, display as the following:
—49—
IMM TECHNICAL MANUAL
After installation, click the “Exit” button to finish installation. Insert dongle in the PC
installed the driver.
—50—
IMM TECHNICAL MANUAL
In the right of above, right‐click the “SQL Server(MSSQLSERVER)”, and select the
“Property”, and then display as the following:
—51—
IMM TECHNICAL MANUAL
Choose “Built‐in account” and select “Local System”, then click “OK” button.
4、 Open the connected IP address
In the right of above, right‐click the “TCP/IP”, and select the “Property”, and then display as
the following:
Select the “IP Addresses” in the above, open the corresponding IP address. Change the
“Enabled” to be Yes, and TCP Port to be 1433 (must open the 127.0.0.1 address). And then click
the “OK” button.
5、 Re‐start the SQL Service server
In the right of above, right‐click the “SQL Server (MSSQLSERVER)” and select the
“start/restart”, then re‐start the server.
—52—
IMM TECHNICAL MANUAL
The purpose of database initialization is to create a IMM database in the database, and
carry out the initialization operation. The operation steps as follow:
1. Double‐click InitializationDB.exe in the server software installation menu (E.g.: D:\Program
Files\IMMServer), display as follow.
Parameter specifications:
Database Server IP : 127.0.0.1
—53—
IMM TECHNICAL MANUAL
Local default IP (confirm Enabled in address 127.0.0.1 of the forth step in 5.2.1.1 to be Yes )
Port:1433
TCP/IP default port number: 1433
Database Name:IMM
To be created database name (create by this program, default is IMM)
Login Name:sa
Default user: sa
Password:*** sa password typed when installing the database: default 654321
Choose the Database Save Directory:
D:\IMM_Server menu stored the database document, it’s recommended to be none‐system
disk.
After finish the above parameters, click the “Connect to Database” button, if the button turns
to be gray, and display “Connect Successfully”, means connect the database successfully. Then
can carry out the following operations.
3. Initialize the IMM database
Connect to the database successfully, the “Initialize Database” has been activated; click this
button to carry out initialization operation. If initialize database succeed, will display as the
follow.
If initialization failed, please check whether has IMM sql document in the server installation
menu (e.g.: D:\Program Files\IMMServer) and whether database has already in the IMM
database.
2. Select the SQL Server authentication, and use sa account login the database
—54—
IMM TECHNICAL MANUAL
4. Right‐click “Logins” and select “New Login” in the popup frame, display as follow:
—55—
IMM TECHNICAL MANUAL
Type IMM in the Login name, select “SQL Server authentication”, and then type in IMM user
password (default IMMV4). Do not choose the contents in the red frame, and select IMM in
Default database.
5. In the above figure, right‐click the “Server Roles”, display as follow:
Select “sysadmin” in the above and click “OK”. Finish created the database user.
Open the IMMServerSet.exe document under server installation menu (e.g.: D:\Program
Files\IMMServer), display as follow:
—56—
IMM TECHNICAL MANUAL
Operation steps:
1. Click Path right button in the “Collection procedures”, select the server installation menu, e.g.:
this server installation menu: D:\Program Files\IMMServer
2. Click Path right button in the “Electricity”, select the electricity analysis program installation
menu, e.g.: installation menu: D:\Program Files\IMMServer\EnergyFTP.
3. Click “Read” button, display as follow:
—57—
IMM TECHNICAL MANUAL
1). Click the right button in the corresponding frame; select the exiting menu in the frame.
2). Click the “Create Directory” button, auto select the path for it. The follow is the interface of
clicking the “Create Directory” (default selects this method):
5. Click the right button of “Backup Path”, and select the backup document storage path. It’s
recommended to be the same as the initialized database storage menu (refer to the second step
in 5.2.1.2).
6. Click the “Save”. Finish setting, and close the dialogue frame.
7. Finish configuration, double‐click the “IMMServer.exe” in the server software installation menu
(make sure inserted dongle), and the n create a show.txt document in this menu, and then will
display a server operating interface, as follow:
—58—
IMM TECHNICAL MANUAL
1. Open the IMMIp.exe document under server installation menu (e.g.: D:\Program Files\IMM),
display as follow:
Parameter specifications:
Server IP: Server IP address
Data port IP: Database IP address
Ftp IP: FTP server IP address (server IP address)
Server port: Default 7700, must be same with Server port1 of Server Configuration in 5.2.1.4.
Data port: Default 1433, generally cannot change.
Ftp port: Default 21, generally cannot change.
Select language: English/Chinese, change client‐side interface language display.
Finish configuration, click “Save” button. Default these 3 IP to be the same.
2. Double‐click the cursor middle key in the blank place. Then display the follow:
Parameter specifications:
Database name: database name created in 5.2.1.2, default IMM.
Database port: default 1433, generally cannot change.
Database user name: user name created in 5.2.1.2, default IMM.
Database password: user (IMM) password created in 5.2.1.2, default IMMV4.
—59—
IMM TECHNICAL MANUAL
If the left of the interface display “Connect the server successfully”, means configure correct.
The first operate this interface needs to set the language.
The process management is for make sure the program can be operated again after exit
program process. E.g.: the IMMServer is in the process management range, if IMMServer process
stops, then the process management can operate the IMMServer process again.
—60—
IMM TECHNICAL MANUAL
Finish adding then check the corresponding process operating in task management, display
as follow:
—61—
IMM TECHNICAL MANUAL
If needs to display IMMServer and IMMEnergy operating interfaces, then after the program
operated, newly establish show.txt in the corresponding menu.
—62—
IMM TECHNICAL MANUAL
5.4 login
—63—
IMM TECHNICAL MANUAL
2. Cursor left key double‐click the icon , and then double‐click the version information on
the right corner, and then double‐click the right of “user”, display as follow:
Administer select the “service” user name, type in password (default: service). Then select
whether save the password, and click “OK” to login.
—64—
IMM TECHNICAL MANUAL
After administer login the client‐side, select “Account management” under “Advance
function”, display as follow:
Click the corresponding password of account, type new password, and then click “Save”
button. Default password of user/service will be: user/service.
5.6 setting
After administer login the client‐side, select “Setting” under “Advance function”, display as
follow:
—65—
IMM TECHNICAL MANUAL
Configure the report display forms of program information, electricity price and electricity
partition (refers to 7.4). After configuration, click the “OK” to save it .
After administer login the client‐side, select “Device search” under “Advance function”,
display as follow:
Local IP frame displays server IP address. Click “Start search” button, server will carry out
search function, to search specified IP address M‐INTERFACE gateway. The specified IP address
—66—
IMM TECHNICAL MANUAL
can be set in Control IP in 5.2.1.4. If there is connect server or database failed situation during
searching process, it needs to search the devices again. After system installation, it should carry
out search device function as administer.
After administer login the client‐side, select “Refrigerant system” under “Advance function”,
display as follow:
The interface can search all M‐INTERFACE gateway and refrigerant system, the left display
outdoor units under refrigerant system and the system, the upper right display the indoor units
under corresponding refrigerant system, the lower side display the outdoor unit quantity, indoor
unit quantity, outdoor main/slave units’ ID number, outdoor unit corresponding ammeter
readings.
Both IMM software and IMM WEB can be carried out local insert.
If there is a PC or other similar device of same subnet area as M‐INTERFACE in LAN, then
—67—
IMM TECHNICAL MANUAL
type the link address of M‐INTERFACE gateway (e.g.: http://192.168.100.40) on the browser
address bar can visit the M‐INTERFACE WEB interface to operate the air‐conditioning device. The
local visit topology structure as follow display:
The cline‐side can connect to the server through the local network, the local network
connection as the following display:
Under the allowable situation, M‐INTERFACE gateway can set in the office network; the user
can operate the air‐conditioning device through the PC or similar devices. Remote insert should
base on some IT technology and help by the network administrator.
6.2.1.1 Statistic IP
Configure public network address statistic IP address for M‐INTERFACE gateway, and set it in
the internet; directly visit this public network address then can visit the WEB interface. Ask the
local network operator for the public network address. The public network address insert fee will
be charged by operator, and consider the network safety at the same time.
—68—
IMM TECHNICAL MANUAL
If the company has a public network address, then it needs to send a mapping of a terminal
in fire wall to M‐INTERFACE gateway; when the PC or similar device of outside network visit the
M‐INTERFACE, then take http:// public network IP: visit as a terminal. E.g.: http://
203.208.60.72:6080.
Router establishing
M‐INTERFACE gateway might use a same public IP address with other devices, under the
situation of network cannot send terminal mapping to M‐INTERFACE gateway, and then
can use VPN for visiting. As the figure displayed, VPN tunnels establish between routers,
and then can visit WEB interface through VPN tunnels. VPN Server can be established by
—69—
IMM TECHNICAL MANUAL
PC establishing
Establish VPN tunnel by PC is a little difficult for general users. Use VPN client‐side
software and VPN Server to establish VPN tunnel in the user’s PC, then user can visit WEB
interface through VPN tunnel. VPN client‐side software and VPN Server can be achieved
by commercial ways. Its topology structure as follow display:
The client‐side and server also can use the remote network (VPN) connection. VPN has
router establishing and PC establishing methods.
Router establishing
VPN tunnels establish between routers, and then can visit WEB interface through VPN
tunnels. VPN Server can be established by oneself and also can be rented. Its topology
structure as follow display:
PC establishing
Use VPN client‐side software and VPN Server to establish VPN tunnel, then user can visit
the server through VPN tunnel. VPN client‐side software and VPN Server can be achieved
by commercial ways. Its topology structure as follow display:
—70—
IMM TECHNICAL MANUAL
7.Electricity Partition
7.1 electricity partition introduction
M‐INTERFACE gateway will divide the outdoor unit consumed electricity gathered by every
hour to be: outdoor unit operating electricity P1, outdoor unit standby electricity P2 and
outdoor unit abnormal electricity P3. The partition factor β multiply by P1 to get the indoor unit
operating electricity X, P2 divide indoor unit quantity to get the indoor unit operating electricity
Y. M‐INTERFACE gateway will turn X, Y, P1, P2, P3 to be electricity documents then upload to
IMM software.
IMM software will gather the received electricity documents, and accord to the user
selection to produce report of electricity price output in the specified hour.
Settlement 1: IMM software gathered electricity documents, add the indoor unit’s X, Y and
all the outdoor unit abnormal electricity P3, and this summation divide the effective indoor unit
quantity get the value, then to get the consumed electricity W.
—71—
IMM TECHNICAL MANUAL
Settlement 2: IMM software gathered electricity documents, add all indoor units’ X to get
indoor unit operating electricity W1; all the outdoor unit standby electricity P2 and normal
electricity P3’s summation divide the effective indoor unit quantity get the indoor unit
maintenance electricity W2.
Settlement 1 can get the indoor unit consumed electricity W, even if the indoor unit didn’t
operate, W can not be 0. For indoor unit standby electricity Y can not be 0.
Settlement 2 can get the indoor unit operating electricity W1 and maintenance electricity
W2. If indoor unit didn’t operate then W1 is 0. W2 can get through “Air‐conditioner
maintenance cost”.
When the device can not collect the data for power‐off, disconnected, safeguard system is
necessary to avoid electricity loss or serious phenomenon. At that time the reasonableness of
electricity partition will be decreased. It should be handled the device error as soon as possible. If
the following situations came out, the safeguard system will be operated:
1、When total indoor unit quantity of a refrigerant system were 1~5 sets, and disconnected
indoor units in an hour were more than 1 set, classify P1 as P3 electricity;
2、When total indoor unit quantity of a refrigerant system were 6~10 sets, and disconnected
indoor units in an hour were more than 2 sets, classify P1 as P3 electricity;
3 、 When total indoor unit quantity of a refrigerant system were 11~64 sets, and
disconnected indoor units in an hour were more than 3 sets, classify P1 as P3 electricity;
4、When there has produced P1 electricity, but total indoor unit capacity requirements in an
hour were zero, classify P1 as P3 electricity;
5、When it changed the ammeter and the first readings of changed ammeter was larger than
the readings of the former ammeter, then it will produce P3 electricity;
Increase the reasonableness of electricity partition under this situation is: calculate the electricity
report before changing the ammeter and use a new day (begin with 00:00) as the start time of
—72—
IMM TECHNICAL MANUAL
If came out this situation, it needs to find out the electricity readings records of 19:00 and 20:00
in IMM database and manual share the electricity for indoor units to avoid lose.
10、The ammeter readings continue to change, produce P4 electricity. Communication
between outdoor unit and ammeter met the ammeter communication rules, the correctness of
the data transmission was protective, but under some disturbed or ammeter error situations,
sampled ammeter readings may be changed. For low down the correctness of electricity partition,
filter the ammeter changed situation, and the filtering value P4 will be recorded in the electricity
document but not in electricity partition.
11、Electricity produced during IMM WEB software upgrade period (about 8 minutes) will be
classified as P3 electricity.
Note:
P3 electricity will be shared to indoor units according to the effective indoor unit quantity;
Generally it should not use an old ammeter for changing;
When the customer reads ammeter and finds out the ammeter reading is abnormal, that
may cause by ammeter readings changed, it needs to correct the ammeter.
The fan and electrical heater of the indoor unit will consume electricity. The consumed
electricity of indoor unit is the sum of the fan and E‐heater’s consumed electricity. Fan consumed
electricity: fan’s operating hour multiply the fan’s rated power.
E‐heater consumed electricity: electrical heater’s operating hour multiply the electrical
heater’s rated power.
—73—
IMM TECHNICAL MANUAL
The fan and electrical heater might be outputted not as the rated power during operating
process, e.g.: AC fan may be high/med/low three speeds. This situation will cause error. The
estimation value will be more than the actual value. If can not accept this error, then can choose
to install the ammeter at the indoor unit power supply side.
After install the IMM software, through administer rights to select user report way:
1、Output/not output maintenance cost
2、Estimate/not estimate indoor unit consumed electricity
Note:
If the customer does not accept the non‐operating air‐conditioner might cause output cost,
it’s suggested that select “Output maintenance cost”;
If the customer does not accept the error caused by indoor unit consumed electricity
estimation, it’s suggested that select not estimate indoor unit consumed electricity, and install
the ammeter at the indoor unit power supply side.
IMM software can divide the air‐conditioners to be public air‐conditioner and idle
air‐conditioner, this function is suitable for the situations of commercial office building or
apartment‐style hotel. The setting interface is as follow:
—74—
IMM TECHNICAL MANUAL
IMM software will calculate the consumed electricity of public and idle air‐conditioner, and
share to the effective indoor units.
Under the full heat‐exchanger and new fan requirements situations, these two
air‐conditioners can not mix with V4+ indoor units to connect into the refrigerant system. Under
auto topology mode, needs to separate insert to M‐net indoor unit communication connector;
under manual topology mode, needs to establish a single refrigerant system in CSV document
(refer to 8.1).
7.8 Precautions
1. Midea electricity partition method is not through the calculation tools, but through collecting
the data and analysis and calculate the data, then get the result, so this cost report is only for
reference, and should not use for commercial calculation basis.
2. If M‐INTERFACE gateway’s topology structure changes (air‐conditioner quantity change), then
use the changing time as separate point to print the report separately.
3. Indoor unit operation time specification
E.g.: 10 sets indoor units, one indoor unit operation time is not 0, other units are 0(select not
estimate indoor unit electricity), why shares the electricity?
Reason: Operate the fan, or reach the setting temperature, indoor unit operation time will not be
0, but at that time the indoor unit status is the same with other standby indoor units, so share
the electricity.
8.Appendix
8.1 Topology documents specification
System topology document reflects the system mapping relation, the topology document
use CSV form, under manual topology mode, needs manual fill the CSV document.
—75—
IMM TECHNICAL MANUAL
1. Document structure
—76—
IMM TECHNICAL MANUAL
1. Database will auto backup the data of previous 3 months, and carries out backup operation at
02:30 every day. E.g.: Database IMM_12010203 backup is the data of Jan, Feb and Mar in 2012.
2. If carry out database query operation, it only needs configure the database to need connected
database in the client‐side IMMIP.exe dialogue frame. E.g.: if needs to query Apr, May and Jun of
2012’s data, then do the following setting in IMMIP.exe:
Set the database name to be IMM_12040506, and then click “Save” button to finish.
1. Database backup:
—77—
IMM TECHNICAL MANUAL
Right click on the database which needs backup, select “Tasks”,“Bak up…” at the popup
option, then display as follow:
Select the above red frame, click the “Remove” button on the right, and then click “Add”,
then display as follow:
—78—
IMM TECHNICAL MANUAL
Select the saving document path, type the backup document name in “File name” column.
And also can add .bak in the end of the document name (suggested with the suffix). Click the
“OK” in the page until the following come out:
—79—
IMM TECHNICAL MANUAL
The above figure came out, and then finishes backup operation.
2. Restore the database
Close all the connections before restore the database (include IMM client‐side and server),
and delete the data and log documents of waiting restored database (IMM.mdf and
IMM_log.ldf), e.g.: D:\DB\IMM.mdf and D:\DB\IMM_l og.ldf
—80—
IMM TECHNICAL MANUAL
Select the database which needs to backup in the above figure, and right click on the
database which needs to backup, select “Tasks”—>”Restore”‐”File and Filegroups”, then
display as the follow:
2. Click this
button
—81—
IMM TECHNICAL MANUAL
After click the “From device” right button, then display as follow:
—82—
IMM TECHNICAL MANUAL
Select this
—83—
IMM TECHNICAL MANUAL
Make sure the path in the red frame is the same with the save path of the original database
data log documents (the database data log documents’ original saving path is d:\db), make
sure the document name and the suffix are correct. Click “OK” button to finish restoration.
Note: if the red frame path saved the same document name, then it will be error when
restoring other PCs’ backup documents.
—84—
IMM TECHNICAL MANUAL
—85—