Professional Documents
Culture Documents
90-1150-3.2 Eqp System
90-1150-3.2 Eqp System
APPLICATION FEATURES
Eagle Quantum Premier® is a configurable, distributed, intelli- • Hazardous location certification, including ATEX, for field
gent safety system providing flame and/or gas detection, devices
along with alarm signaling, notification, extinguishing agent • Fire detection and alarm
release, and/or deluge operation. All system components are
integrated together on a fault tolerant digital communication • Fire suppression control
network. The system is ideally suited for harsh industrial appli- • Gas detection and alarm
cations that require a hazardous location rated protection sys-
• Optional redundant controller operation
tem. Typical applications include:
• Extensive diagnostics
• Refineries and chemical plants
• Device calibration data and event logging
• Offshore platforms
• Programmable logic
• Pipelines and liquid gas storage
• Real time clock
• Automotive applications
• Four-line, 20 character alphanumeric display
• Turbines / generators / compressors
• LED status indicators
• Aircraft / vehicle maintenance facilities
• Hazardous manufacturing processes • Fault tolerant communication loop
• Power plants • Up to 246 intelligent addressable field devices
• Alternative fuel bus facilities. • FM/CSA/CENELEC/CE
• Certified to ANSI/NFPA 72 National Fire Alarm Code.
Beacon
Cylinder
SYSTEM DESCRIPTION The Eagle Quantum Premier Controller displays current infor-
mation about the system. Twelve LEDs are provided to indi-
The Eagle Quantum Premier system is a third generation haz- cate when an alarm or fault condition exists. A four line 20-
ard protection system that is designed for fire and gas detec- character vacuum fluorescent display (VFD), controlled by
tion, control of notification appliance circuits, and the releasing front panel membrane buttons, can display a variety of status
of various suppression agents. The system utilizes modular- and diagnostic information. Alarm and trouble conditions are
ized field devices on a digital communication loop. All detec- easily identified, along with the associated device tagname.
tion, re-action, and notification activities are coordinated
through a centralized Controller. See Figure 1. The Eagle Quantum Premier system provides operational flexi-
bility through custom designed user logic programs in the
The system has the flexibility to utilize any combination of controller. Over 50 different types of logic functions are avail-
Eagle Quantum Premier field devices. It can be configured as able to allow the system to be optimized for fire and gas appli-
a total gas detection system, a total fire detection system, or a cations.
combination of both fire and gas detection. All devices and
operating parameters are configured through the Controller.
CONTROLLER REDUNDANCY
Third party devices can be integrated into the system either Two EQP controllers can be configured as a redundant pair,
through dry contact closure inputs (using IDCs/DCIOs) or thereby increasing the availability of the system. The con-
through 4 to 20 mA inputs (using DCUs/Analog Input trollers work in “Master” and “Hot Standby” mode. Under nor-
Modules). mal operating conditions, the Standby controller receives the
same inputs and update information as the Master, but has no
Through its centralized control unit, the Eagle Quantum control over the outputs and does not execute user logic. In
Premier system provides an open architecture in which sys- the event of a switchover, a bumpless transfer occurs.
tems can be tied together to share information. PLC, DCS and
human/machine interface (HMI) systems can communicate Controller Redundancy offers the following benefits:
directly with the Eagle Quantum Premier system through sup-
• Automatic configuration of the standby controller
ported communication protocols. The controller supports up
to five serial ports, utilizing Modbus RTU master/slave protocol • Bumpless transfer
and Safety System Software (S3) for configuring the EQP sys- • Forced and automatic switchover
tem. An optional redundant media ControlNet board is also
• No downtime on controller replacement
available.
• Automatic synchronization between controllers
• Increased system availability.
3.2 2 90-1150
EAGLE • Simplex / redundancy operation
QUANTUM • Approved annunciation and releasing device per NFPA 72
PREMIER
• Meets FM/CSA guidelines in an approved gas system
CONTROLLER
• Programmable logic
The microprocessor-
• Up to five available serial ports
based Controller
continuously moni- • Transformer isolation of network ports
tors the field devices • Utilizes MODBUS and Allen Bradley ControlNet protocols
on the Local
Operating Network / Signaling Line Circuit (LON/SLC) and • Eight programmable relay outputs
performs the logic functions needed to generate the appropri- • Eight digital inputs
ate output(s). The Controller performs both static and user • Four-line, 20 character alphanumeric display
programmable logic operations. Static logic controls the face-
plate displays and relay outputs (alarm, trouble and superviso- • LED status indicators
ry) per ANSI/NFPA 72. Static logic also activates built-in • Fault tolerant communication loop
annunciation circuits, consisting of both visible and audible
• Extensive built-in diagnostics
alarms.
• Supports up to 246 field devices
Programmable logic allows the Controller to be customized to • FM/CSA/CENELEC/CE
perform a variety of complex logic operations. Using Det-
Tronics Safety System Software (S3), the Controller can be (For more information refer to Spec Sheet # 90-1148.)
programmed to implement any cross-zone monitoring, voting,
or timed operations that might be needed in a system.
3.2 3 90-1150
EQ3700DCIO INPUT/OUTPUT • Monitors eight independent I/O channels
MODULE (DCIO) • Individual channels are configurable as an Input or Output
The 8 Channel DCIO Module is spe- • Individual point style is configurable as supervised or unsu-
cially designed to expand the input pervised
and output capability of the Det- • Individual point type is configurable for alarm/gas/superviso-
Tronics Eagle Quantum Premier ry/other input styles, notification/releasing/unsupervised out-
System. The unit provides continuous put
and automated fire/gas protection,
while ensuring reliable system opera- • Meets the requirements of NFPA 72
tion through continuous supervision of system Inputs/Outputs • Panel or DIN rail mounting
on the LON/SLC. The DCIO module provides eight channels of
configurable input or output points that can be programmed (For more information refer to Spec Sheet # 90-1149.)
for supervised or unsupervised operation. Each input point
can accept dry contact fire detection devices such as heat,
smoke, or unitized flame detectors. Each output point can be
configured for unsupervised, signaling or releasing output
operation. Each channel on the module is provided with indi-
vidual indicators for active and fault conditions.
The Intelligent Protection Module (IPM) • Supports two conventional “two-wire” smoke/heat zones
is specially designed to monitor, super- including the ability to reset latched zones. Does not
vise and control one fire suppression require the use of “relay bases”
hazard.
(For more information refer to Spec Sheet # 90-1184.)
The IPM is designed to provide continuous and automated
local area fire protection, while monitoring system operation
through continuous supervision of its Inputs/Outputs and Local
Operating Network/Signalling Line Circuit (LON/SLC) connec-
tion to the EQP controller.
3.2 4 90-1150
EQ3720RM EIGHT CHANNEL • Expands the output capabilities of the Det-Tronics Eagle
RELAY MODULE Quantum Premier™ system
The 8 Channel Relay Module is specially • Provides eight independent relay output channels
designed to expand the Output capabili- • Individual channel LEDs indicate Active and Fault status
ty of the Det-Tronics Eagle Quantum • Provides remote output capabilities via LON/SLC
Premier™ System.
• Panel or DIN rail mounting
The unit is designed to provide eight • Power LED display
relay output channels for use with non-supervised devices
• Plug-in wiring connectors
(PLCs, fans, dampers, etc.).
• Immune to RFI and EMI (CE Marked)
X5200 UVIR FLAME • New patented signal processing, TDSA, Arc rejection
DETECTOR • A new level of false alarm rejection
The X5200 meets the most • Responds to a fire in the presence of modulated blackbody
stringent requirements world- radiation (i.e. heaters, ovens, turbines) without false alarm
wide with advanced detection • High speed capability
capabilities and immunity to
extraneous sources, combined • Microprocessor controlled heated optics for increased resis-
with a superior mechanical design. The detector is equipped tance to moisture and ice
with both automatic and manual optical integrity (o i ) test • Automatic or manual optical integrity (oi) testing
capability. The mounting arrangement allows the UV and IR
• Calibrated magnetic manual testing — no test lamp required
sensors to monitor the same hazardous location with a 90
degree cone of vision. When both sensors simultaneously • Tricolor LED indicates normal operation, fire and fault condi-
detect the presence of a flame, an alarm signal is generated. tions
The detector has Division and Zone explosion-proof ratings • Mounting swivel allows easy sighting
and is suitable for use in indoor and outdoor applications. A
• Integral wiring compartment for ease of installation
tri-color LED on the detector faceplate indicates detector sta-
tus condition. • Class A, Style 7 wiring per NFPA-72
• EMI, RFI, EMC Directive Compliant
The X5200 housing is available in aluminum or stainless steel,
with NEMA 4X and IP66 rating. Typical applications include • FM, CSA, DEMKO (ATEX), CE
hangars, munitions, petrochemical applications and turbines. • Built-in data logging / event monitoring
3.2 5 90-1150
X9800 IR FLAME • Unequaled false alarm rejection, TDSA
DETECTOR • High speed capability
The X9800 is the most advanced • Responds to a fire in the presence of modulated blackbody
single frequency infrared flame radiation (i.e. heaters, ovens, turbines) without false alarm
detector with dual signal pro- • Microprocessor controlled heated optics for increased resis-
cessing capability for high tance to moisture and ice
speed response. The detector • Automatic or manual optical integrity (oi) testing
is equipped with both automatic and manual optical integrity
• Calibrated magnetic manual testing — no test lamp required
(oi) test capability. The detector has Division and Zone explo-
sion-proof ratings and is suitable for use in indoor and outdoor • Tricolor LED indicates normal, fire and fault conditions
applications. A tri-color LED on the detector faceplate indicates • Operates under adverse weather conditions and in dirty
detector status condition. environments
• Mounting swivel allows easy sighting
The X9800 housing is available in aluminum or stainless steel,
• Integral wiring compartment for ease of installation
with NEMA 4X and IP66 rating. Typical applications include
turbines, petrochemical applications, automotive applications • Class A, Style 7 wiring per NFPA-72
and dirty environments. • Built-in data logging / event monitoring
• FM, CSA, DEMKO (ATEX), CE
(For more information refer to Spec Sheet # 90-1160.)
3.2 6 90-1150
POINTWATCH ECLIPSE PIRECL • One person non-intrusive calibration
GAS DETECTOR • HART hand-held communication capability
The PIRECL is a stainless steel point IR • EExd, EExe, EExib protection designs
gas detector, providing detection of • FM, CSA, DEMKO (ATEX), CE
flammable hydrocarbon gases in the • Integral LON/SLC interface
lower explosive limit (LEL) range. Integral LON/SLC interface
as well as a HART interrogation port are provided. A tri-color • Alarm setpoints adjustable via network
LED provides visual display of operating status. The weather • Active fault isolation
protection baffle design offers exceptional protection along • Alarm history stored in non-volatile memory
with easy twist-lock removal and installation. The detector is
• Self-diagnostics
ATEX 94/9/EC certified for global certification compliance.
• Internal wiring compartment saves money and time (For more information refer to Spec Sheet # 90-1138.)
• Heated optics
The DCU is approved for use with a variety of • One person, non-intrusive calibration
Det-Tronics sensors including Pointwatch IR • Alarm setpoints adjustable via network
gas detector and hydrogen sulfide (H2S) elec- • Alarm history stored in non-volatile memory
trochemical sensor. It also accepts any sen-
sor/transmitter with a linear 4 to 20 mA output signal and • Calibration history stored in non-volatile memory
allows for one person non-intrusive calibration. The DCU digi- • Active fault isolation
tizes the analog signal and transmits the value to the system
• Self diagnostics
controller.
• Detector can be close-coupled or separated
3.2 7 90-1150
EQ2500SAM SERIES SIGNAL • Each circuit is individually supervised for opens and shorts
AUDIBLE MODULE • Each circuit is individually controlled by user logic
The Signal Audible Module (SAM) provides • Each circuit supports a variety of programmable blink/flash
two Notification Appliance Circuits (NAC) for rates
controlling UL Listed 24 vdc polarized audi- • Current reversal on activation
ble/visual indicating appliances. The SAM is
located on the system LON/SLC and is con- • 2 output channels can be individually activated
trolled by programmable logic in the Eagle Quantum Premier • Each channel is supervised for open circuits
Controller. Each output circuit is independently programmable
• Active fault isolation
to allow annunciation of separate events. In release applica-
tions, signal outputs can be programmed to provide signaling • Self-diagnostics
for pre-release, release, or post-release.
(For more information refer to Spec Sheet # 90-1129.)
• Provides two ANSI/NFPA 72 Class B Style Y output notifica-
tion appliance circuits
The IDC consists of a terminal wiring board and a • Non-volatile alarm history memory
communication module, mounted in an explosion- • Active fault isolation
proof, water-tight enclosure. The IDC accepts two • Each input programmable for fire, supervisory, trouble or
dry contact inputs for use with devices like relays, normal service
pushbuttons, and key switches.
• Accepts inputs from standard contact closure input devices (For more information refer to Spec Sheet # 90-1121.)
such as manual call stations, heat detectors, keyswitches,
and proof of agent release flow switches
LOCAL OPERATING NETWORK / SIGNALING LINE A single open or short on the LON/SLC will not affect system
CIRCUIT (LON/SLC) DEVICES communication between the field devices and the Controller.
System communication to all field devices will continue until
The LON/SLC is a fault tolerant, two wire, digital communica- the wiring problem can be repaired.
tion network, arranged in a loop that starts and ends at the
Controller. In its base configuration, the LON/SLC supports up
to 246 intelligent field devices spread over a distance of up to
2000 meters (up to 10,000 meters using Network Extenders).
WIRING FAULT
Devices on the network can consist of a variety of flame and NODE 4 NODE 5
gas detectors, as well as other input and output devices. NODE 3 NODE 6