Load Schedule Calculation Sheet


Project Name : Shamyaa Haram Extention
Panel Data : Main Feeder Data :
Panel Name : UPP-SH-GF-CR11 Rated Volt : 220 V Feeding Panel Name : UPP/SH-GM-LC-11
Panel Location : GROUND FLOOR Rated Frequency : ###
60 Hz Feeding Panel Location : GROUND MEZZANINE FLOOR
Panel Type : MCB I.C. Current : ###
10 kA Mian Cable Length : 17.00 m.
Mounting : Wall Surface Main Isolator: 40/100 A Cross Sectional Area : 3(1Cx10) mm²
IP Degree : 41 Accumulative V.D%: <3 % Cable Type / Insulation : CU/PVC

NO. LENGTH HOME WIRE PHASE LOAD MCB MCB PHASE LOAD WIRE HOME LENGTH NO.
CT TYPE OF TYPE OF CT
OF V.D.% BETWEEN RUN LOCATION DESIGNATION OF LOAD SIZE Amp. Amp. SIZE DESIGNATION OF LOAD LOCATION RUN BETWEEN V.D.% OF
LOAD Rating Type Type Rating LOAD
NO. POLE UNITS LENGTH mm2 P N mm2 LENGTH UNITS POLE NO.
1 1-P 0.08% 5 13 MSC ELECTRICAL ROOM 02xEO(ACP) 4 1.000 20 C 1 2 C 20 2.000 4 02xEO(SMOKE CURTAIN) CORRIDOR MSC 30 12 0.36% 1-P 2

3 1-P 0.08% 0 30 MSC CORRIDOR 01xEO(CAMERA) 4 0.500 20 C 3 4 C 20 0.500 6 01xEO(CAMERA) PRAYER AREA MSC 87 0 0.15% 1-P 4

5 1-P SPARE 20 C 5 6 C 20 SPARE 1-P 6

7 SPACE 7 8 SPACE 8

9 SPACE 9 10 SPACE 10

11 SPACE 11 12 SPACE 12
Sub. Total Current (A) 1.500 2.500 0.000 0.000 Sub. Total Current (A)

2.500
Total Connected Current (A) 4.000 40/100 AMPS TRIP/FRAME
The Phase Average Current = 4.000 Amps.

% Balance : 100.00 0.00 0.00

Total Connected Power = 0.880 kVA

Total SPARE LOAD Max. Demand Load


Lighting Loads MISCELLANEOUS SOCETES MOTORS Max. Demand Current (A)
(KVA) (KVA) (KVA)
Connected Power (KVA) 0.000 0.880 0.000 0.000 0.880

% Demand Factor 100% 100% 25% 100% 0.220 1.100 5.000


Demand Load Power (KVA) 0.000 0.880 0.000 0.000 0.880

Reference : 739458600.xls - UPP-SH-GF-CR11 03/27/2024 18:03:25