Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

1278 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO.

3, MAY 2008

Unity Power Factor Isolated Three-Phase Rectifier


With Split DC-Bus Based on the Scott Transformer
Alceu André Badin, Student Member, IEEE, and Ivo Barbi, Senior Member, IEEE

Abstract—In this work, the three-phase rectifier with a new con-


nection is presented. The use of the Scott transformer makes a
split dc-bus voltage possible and the rectifier operates with unity
power factor. Using only two active switches, the rectifier is able
to generate symmetrical currents in the line and a balanced split
dc-bus output voltage, which is necessary in several applications.
Pulse width modulation and instantaneous average current control
are used. There are two voltage controls that regulate the output
voltage and the split dc-bus voltage. Complete simulation results
under closed loop operation are given, as well as results of an ex-
perimental setup.
Index Terms—AC–DC converters, power factor corrector (PFC)
converters, power supplies, pulse width modulated (PWM), split
dc-bus voltage, three-phase rectifier.

I. INTRODUCTION

I N recent years, the growth in the use of electrical equipment


has resulted in more stringent international standards and
utility requirements to ensure that the line current harmonic con-
Fig. 1. Unity power factor isolated three-phase rectifier parallel connection.

tent of the equipment connected to the ac mains is limited [1]. If In addition to unity power factor, safety and robustness are
such standards did not exist, then sensitive electrical equipment also important for medium and high power applications. There-
connected to the mains would be damaged as a result of a dis- fore, low frequency isolation is used. Isolated rectifiers have
torted mains voltage. Three-phase ac–dc converters connected been widely used in the electrochemical and petrochemical in-
to the mains have the potential of injecting current harmonics dustries.
into the mains that may cause voltage distortion. These har- Since regulated output voltage is not required, a number of
monics can be significantly reduced if the input power factor is methods have been proposed to lower the harmonics gener-
corrected by shaping the input current in each of the three phases ated by diode rectifier-type utility interfaces [12]–[14]. One
so that it is sinusoidal and in phase with the phase voltage. Due approach is to use a conventional 12-pulse converter which
to this fact, switch-mode rectifiers for power factor correction requires two six-pulse converters connected through isolation
have gained considerable attention. Other reasons for the use of transformers.
power factor corrector (PFC) rectifiers are their adaptability to The three-phase rectifier based on the Scott Transformer
different line voltages and the fact that they pre-regulate the dc (Fig. 1) was proposed in [15] and its practical aspects were
output voltage, which may be supplying a dc–dc converter. analyzed in [16]. The Scott transformer provides galvanic iso-
The analysis of high power factor three-phase rectifiers and lation and sine and cosine secondary voltage waveforms to the
new control techniques are presented in [2]–[9]. These rectifiers high power factor rectifiers, resulting in a perfectly regulated
have three or more active switches. dc output voltage.
In [10] a three-phase switch-mode rectifier employing three In this paper, an unity power factor three-phase rectifier with
single-phase boost PFC circuits with direct output coupling is a split dc-bus based on the Scott transformer is presented. The
presented. This topology uses three power switches but it has a proposed topology is shown in the Fig. 2. This rectifier has a split
high component count and is not isolated. dc-bus and the voltages across the switches are /2. The con-
In [11], a three-phase PFC scheme is proposed using two trol method employed to control the currents of the two boost
single-phase PFC modules. The two-phase system is produced inductors, and , is instantaneous average current control.
by means of a 0.14-pu-rated autotransformer connected to the Each rectifier presents an independent current loop with an in-
three-phase input. However, this topology is not isolated. dividual reference current, generating sinusoidal secondary cur-
rents in phase with their respective secondary voltages.
Manuscript received July 4, 2006; revised August 28, 2007. Recommended
for publication by Associate Editor J. Kolar. II. STEADY-STATE ANALYSIS
The authors are with the Power Electronics Institute, Federal University of
Santa Catarina, Florianopolis 88040-970, Brazil (e-mail: alceu@inep.ufsc.br). The Scott connection is realized by two single phase trans-
Digital Object Identifier 10.1109/TPEL.2008.920878 formers, and . The primary windings are fed by two dif-
0885-8993/$25.00 © 2008 IEEE
BADIN AND BARBI: UNITY POWER FACTOR ISOLATED THREE-PHASE RECTIFIER 1279

Fig. 2. Unity power factor isolated three-phase rectifier with a new series-con-
nection technique.

Fig. 4. Three-phase rectifier equivalent circuit.

The instantaneous average duty cycles of the switches are

(3)

(4)

The purpose of using a boost PFC is to correct the power


factor of the structure by forcing the inductor current to follow
the shape of the rectified secondary voltage. The boost inductor
currents are, therefore, images of the rectified secondary volt-
ages of (1) and (2)

Fig. 3. (a) Scott connection of the single phase transformers and (b) phasor
diagram of the transformer using the Scott connection. (5)
(6)

ferent voltages, and , that are generated from a where is the peak value of the boost inductor current.
symmetrical three-phase system and . The The current through the switch of a boost converter is the cur-
connection is presented in Fig. 3(a). and rep- rent through the boost inductor multiplied by the duty cycle. In
resent a two phase voltage system, with a phase angle 90 be- the same manner, the current through the boost diode is the cur-
tween them. The phasor diagram is presented in Fig. 3(b). rent through the boost inductor multiplied by the complemen-
In the theoretical study of the unity power factor isolated tary duty cycle. Therefore, the currents through the boost diodes
three-phase rectifier, only the secondary circuitry will be taken are defined as
into account. Therefore, the secondary windings of the Scott
transformer are considered to be ideal ac power sources. The (7)
full-bridge diode rectifiers were substituted by power sources (8)
that represent the rectified secondary voltages and
. The topology of Fig. 2 can be reduced to the circuit Substituting (3)–(6) into (7) and (8) yields
of Fig. 4.
The secondary voltages of the Scott transformer are sine and
cosine waveforms. Therefore, the rectified voltages at the inputs (9)
of the boost converters are
(10)

(1) Considering a balanced load, the resulting equivalent circuit


(2) can be seen in Fig. 5.
1280 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 3, MAY 2008

Fig. 5. Equivalent circuit of the output filter.

From the equations of nodes and , the following differ-


ential equations are obtained:

(11)

(12)

Solving the differential equations yields (13) and (14), shown at


the bottom of the page. Fig. 6. Output voltages (a) C =C and (b) C >C .
The total output voltage, , is defined as the sum of the
capacitor voltages of the output filters:
Input voltage harmonics can also cause ripple in the output
(15)
voltage. In this case, the secondary voltages of the Scott trans-
former are not sine and cosine waveforms.
Substituting (13) and (14) into (15) and considering
, we obtain
III. CONTROL STRATEGY
(16) Each boost PFC presents its own current control. The external
voltage loop is shared by both boost PFCs in order to guarantee
The high frequency components of current were discarded by equal power distribution between them. A second voltage loop
considering only the instantaneous average values of the boost acts to guarantee the balance of the split dc-bus voltage. A com-
diode currents. Even so, ideally, the high frequency components plete block diagram of the control loops can be seen in Fig. 7.
of the current would flow through the output capacitor, leaving The common voltage control loop equally distributes the
the dc component free to flow through the load, resulting in a power between the boost PFCs when a balanced load is present.
constant voltage output [Fig. 6(a)]. Furthermore, it has a fast dynamic response to load variations.
If the capacitances of and are different, ripple According to (16), output voltage is constant and does
voltage will be present in voltage . Therefore, identical not present low frequency ripple. However, the dynamic limit
capacitors should be used in order to avoid output ripple. In the of the shared voltage control loop is different from that of the
same manner, if nonidentical or nonlinear loads are connected single-phase boost PFC converter. This is true for a balanced
to the boost rectifiers, low frequency ripple will exist in the power supply without voltage harmonics and for a linear load
output voltage . connected to the output.

(13)

(14)
BADIN AND BARBI: UNITY POWER FACTOR ISOLATED THREE-PHASE RECTIFIER 1281

Fig. 7. Complete block diagram of the control loops.

A load without a neutral point can be connected to the output


of the three-phase rectifier. In this case, the second voltage con- Fig. 8. Open-Loop Bode plot of the current controlled system.
trol loop will balance the voltage across capacitors and
.
In the case of an imbalance in the mains, the second voltage TABLE I
DESIGN SPECIFICATIONS
loop balances the voltage at the dc bus. In this case, the input
currents are unbalanced and present low harmonic distortion.
Where is the reference voltage, and are the
reference currents, is the voltage compensator common
to both boost PFCs, is the voltage compensator of the
balanced split dc-bus, and are the current com-
pensators, and are the shunt resistances,
and are the transfer functions of the
plant, and , are the output voltages of each boost PFC, where and are the gain, pole and zero of the current
and is the output voltage. compensator.
The reference currents ( and ) are defined by
A. Current Loop
(19)
Instantaneous average current control is one of the most (20)
widely methods used to correct the power factor of rectifiers.
This technique consists of monitoring and controlling the boost where is the scaling factor of the input voltage.
inductor current by means of high frequency switching, so that Fig. 8 shows the open loop transfer function step response
current follows a sinusoidal reference with minimum error. using the design specifications of Table I and the compensator
The transfer functions of the converter and parameters presented in Table II. The crossover frequency is
were obtained from Fig. 5 and from [11], and can be seen in approximately 3 kHz.

(17) B. Voltage Loops


To control the voltage, two voltage control loops are used.
The current controller transfer function is defined by A common voltage loop is used to provide each current loop
with the exact same value with which to generate their reference
currents. A second voltage control loop is added to the common
(18)
voltage loop and it is applied to only one of the boost PFCs. The
1282 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 3, MAY 2008

TABLE II The voltage controller transfer function for the second voltage
CURRENT CONTROLLER PARAMETERS loop is defined by

(22)

where and are the gain, pole and zero of the voltage
compensator.
To obtain the transfer function of the shared control loop
, we consider that the parameters of the boost con-
verters are identical. In other words, and are
identically and mutually independent. This assumption is pos-
sible due to the presence of a neutral point at the load which
decouples the two boost converters and make their interaction
weak. Since the systems are in series, transfer function
is given by

(23)

where

(24)

From (23) and (24), (25) is obtained, which represents


transfer function

Fig. 9. Voltage loop block diagram.

(25)
second loop guarantees the balance of the split dc-bus voltage.
A block diagram of the voltage loops can be seen in Fig. 9.
The current loop is considered to be much faster than the The voltage controller transfer function of the plant for the
voltage loop and, therefore, its closed-loop transfer function common voltage loop is defined by
can be simplified and represented as the current sensor conduc-
tance 1/ . This simplification does not compromise the dy- (26)
namics of the voltage loop because the simplified and complete
closed-loop transfer functions of the current loop are identical
at the frequency range of the voltage loop. where and are the gain, pole and zero of the
The transfer function of the plant for the second voltage loop voltage compensator.
was obtained from the model of Fig. 5 and can be seen in (21). Fig. 10 shows the Bode plot using the voltage compensator
The equivalent series resistance ( ) of the output capacitor parameters presented in Table III and the design spec-
was taken into account. However, this resistance is insignificant ifications of Table I. The crossover frequency is approximately
in most cases and can be ignored 17 Hz.
The voltage compensator for the common voltage loop used
the same parameters as those presented in Table III, except that
the static gain and crossover frequency were 1500 and 70 Hz,
respectively (see Table IV).

IV. SIMULATION RESULTS


The results of three simulations are presented to verify the
(21) study until this point. The first simulation aims to verify the
performance of the current loop.
BADIN AND BARBI: UNITY POWER FACTOR ISOLATED THREE-PHASE RECTIFIER 1283

Fig. 11. Line currents i (t); i (t) and i (t).

Fig. 10. Open-loop Bode plot of the voltage controlled system.

Fig. 12. Output voltage v (t); v (t) and v (t)=2.


TABLE III
VOLTAGE CONTROLLER PARAMETERS FOR SECOND VOLTAGE LOOP

TABLE IV
COMPONENT VALUES OF THE RECTIFIER

Fig. 13. Line currents after a 50% reduction (12 kW to 6 kW) and a 50% in-
crease (6 kW to 12 kW) in the load.

The second simulation aims to verify the performance of the


control loops when the rectifier suffers load variations from
100% of the rated load (12 kW) to 50% (6 kW) and from 50%
(6 kW) to 100% (12 kW). The results for the line currents can
be seen in Fig. 13.
Fig. 11 shows line currents and . Fig. 12 The third simulation verifies the voltage loop when the recti-
shows the output voltage of each boost PFC, and , fier suffers a load unbalance in relation to the split dc-bus. Ini-
and output voltage . tially each boost converter processes 3 kW. At 60 ms one of the
1284 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 3, MAY 2008

Fig. 14. Voltages v (t) and v (t) after a 50% increase in one of the loads,
resulting in a load imbalance.

Fig. 16. Phase voltage v (t) and current i (t) (10 A/division and 5 ms/divi-
sion).

Fig. 15. Photograph of the laboratory prototype. Dimensions are


2 2
360 mm 250 mm 120 mm.

rectifiers suffers a load variation and starts processing 6 kW.


The result can be seen in Fig. 14. Fig. 17. Normalized line current harmonics (phase A).

V. EXPERIMENTAL RESULTS
A laboratory prototype of the isolated three-phase rectifier
based on the Scott transformer with a split dc-bus was imple-
mented to prove the theoretical studies. Both of the PFC mod-
ules are controlled by Unitrode UC3854B, [17], [18]. The de-
sign specifications of the prototype can be seen in Table I.
The reference currents are obtained by scaling the measured
rectified secondary voltages of the Scott transformer. These are
the references of the current controller, which determines the
shape of the boost inductor currents. The inductor currents are
measured by Hall sensors.
Fig. 15 presents a photograph of the laboratory prototype. The
Scott Transformer can be seen at the top of the picture and the
rectifier at the bottom of the picture.
Figs. 16, 18, and 20 show the experimental results of the
12 kW prototype. The THD of the line voltages were 3.23%,
3.34% and 3.57%. The THD of the line currents were 4.95%,
5.48%, and 5.61% (Figs. 17, 19, and 21). They are nearly sinu- Fig. 18. Phase voltage v (t) and current i (t) (10 A/division and 5 ms/divi-
soidal in shape. The power factor per phase was: 0.989, 0.985, sion).
and 0.981, respectively.
Fig. 22 shows input currents and of the boost
PFCs, which are 90 phase-shifted from each other with equal Both currents and present distortion at zero
amplitudes, and confirms that the output power of the two boost crossing which is characteristic of single-phase boost PFC con-
PFCs are equal. verters. This distortion propagates through the transformer and
BADIN AND BARBI: UNITY POWER FACTOR ISOLATED THREE-PHASE RECTIFIER 1285

Fig. 19. Normalized line current harmonics (phase B).

Fig. 22. Currents i (t) and i (t) of each boost PFC (20 A/division and
5 ms/division).

Fig. 20. Phase voltage v (t) and current i (t) (10 A/division and 5 ms/divi-
sion).

Fig. 23. Output voltage ripple (5 V/division and 2 ms/division).

in voltages and are out of phase which results in


practically no 120 Hz ripple in output voltage .
Figs. 20 and 24 show the experimental results to verify the
performance of the control loops when the rectifier suffers load
variations from 67% of the rated load to 100%.
Fig. 25 presents output voltages and when the
rectifier suffers a load unbalance in relation to the split dc-bus.
Initially both converters operate at 3.6 kW. After the transient,
Fig. 21. Normalized line current harmonics (phase C). one of the converters operates at 5.6 kW while the other remains
at 3.6 kW. The line currents, after the transient, are presented in
Fig. 26. Note the imbalance among currents and
appears in the primary currents. It is clear from Fig. 16 that the due to the load imbalance of the boost converters. It is
phase A current presents distortion at zero crossing. The zero important to stress that these currents still present low harmonic
crossing distortion is phase shifted in phase currents B and C, distortion.
Figs. 18 and 20, respectively, due to the current interaction in Fig. 27 shows the tested efficiency of the three-phase rectifier
the Scott transformer. for two cases: with transformer losses and without transformer
Fig. 23 presents output voltages and , the losses. The efficiency data were measured for an output power
latter being scaled by a factor of 2. Note that the 120 Hz ripple range of 25% to 95% of 12 kW. A peak efficiency of 97.12% was
1286 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 3, MAY 2008

Fig. 24. Line currents after a 33% increase in the load, 7.2 kW to 11.2 kW. Fig. 26. Line currents for the case of unbalanced loads. (10 A/division and
(20 A/division and 10 ms/division). 10 ms/division).

Fig. 27. Converter efficiency.

quency of operation of the converters to be increased, conse-


quently reducing the losses and volume.
A common voltage control loop for both boost PFCs is nec-
essary to equally distribute the total power between them when
the load is balanced. A second voltage loop is used in order to
Fig. 25. Output voltages after an increase in the load of one of the converters, obtain a balanced split dc-bus.
3.6 kW and 3.6 kW to 3.6 kW and 5.6 kW. (10 V/division and 20 ms/division). A 12 kW laboratory prototype was implemented. The exper-
imental results demonstrate the performance of the proposed
system.
obtained at 11 kW without transformer losses. Higher efficiency The use of the Scott transformer increases the cost of the
could be obtained by changing the iron-core inductors to ferrite- three-phase rectifier and compromises the overall efficiency.
core inductors. However, low frequency isolation is desirable in some appli-
cations due to the robustness and safety it provides. In these
VI. CONCLUSION cases, this rectifier is certainly an option since it presents unity
power factor by using only two active switches and it uses a
In this paper a unity power factor isolated three-phase rec- simple and well-known control strategy.
tifier with a split dc-bus, based on the Scott transformer, and
with a new series-connection was obtained. It presents only two
switches and a balanced split dc-bus. Two standard single-phase REFERENCES
PFC modules, where each module is rated for half of the output [1] IEEE Recommended Practices and Requirements for Harmonics Con-
trol in Electric Power Systems, IEEE Std. 519, 1992.
power, were used. The resulting input line currents are nearly [2] T. Nussbaumer and J. W. Kolar, “Improving mains current quality
sinusoidal in shape. for three-phase three-switch buck-type PWM rectifiers,” IEEE Trans.
The maximum voltage across the switches is half of . This Power Electron., vol. 21, no. 4, pp. 967–973, Jul. 2006.
fact allows the use of switches with lower voltage ratings, which [3] L. C. G. de Freitas, M. G. Simões, C. A. Canesin, and L. C. de Freitas,
“Programmable PFC based hybrid multipulse power rectifier for ultra
could be implemented by power MOSFETs instead of the tra- clean power application,” IEEE Trans. Power Electron., vol. 21, no. 4,
ditional IGBT. This substitution would allow the maximum fre- pp. 959–966, Jul. 2006.
BADIN AND BARBI: UNITY POWER FACTOR ISOLATED THREE-PHASE RECTIFIER 1287

[4] T. Nussbaumer, M. Baumann, and J. W. Kolar, “Comprehensive design [16] S. K. T. Miller and I. Barbi, “Practical aspects of the unity power
of a three-phase three-switch buck-type PWM rectifier,” IEEE Trans. factor isolated three-phase rectifier based on the Scott transformer,” in
Power Electron., vol. 22, no. 2, pp. 551–559, Mar. 2007. Proc. Appl. Power Electron. Conf. (APEC’05), Austin, TX, 2005, pp.
[5] S. Choi, “A three-phase unity-power-factor diode rectifier with active 621–627.
input current shaping,” IEEE Trans. Ind. Electron., vol. 52, no. 6, pp. [17] Texas Instruments, Advanced high-power factor pre-regulator TI, Inc.,
1711–1714, Mar. 2007. Datasheet SLUS 329A, 2008.
[6] V. F. Pires and J. F. Silva, “Three-phase single-stage four-switch PFC [18] P. C. Todd, UC3854 controlled power factor correction circuit design
buck-boost-type rectifier,” IEEE Trans. Ind. Electron., vol. 52, no. 2, Unitrode Corp., Merrimack, NH, Unitrode Application Note U-134,
pp. 444–453, Apr. 2005. 1999.
[7] G. Gong, M. L. Heldwein, U. Drofenik, J. Minibock, K. Mino, and J.
W. Kolar, “Comparative evaluation of three-phase high-power-factor
ac–dc converter concepts for application in future more electric air-
craft,” IEEE Trans. Ind. Electron., vol. 52, no. 3, pp. 727–737, Jun.
2005.
[8] M. Baumann and J. W. Kolar, “A novel control concept for reliable
operation of a three-phase three-switch buck-type unity-power-factor Alceu André Badin (S’07) was born in Maravilha,
rectifier with integrated boost output stage under heavily unbalanced Santa Catarina, Brazil, in 1979. He received the B.S.
mains condition,” IEEE Trans. Ind. Electron., vol. 52, no. 2, pp. and M.S. degrees in electrical engineering from the
399–409, Apr. 2005. Federal University of Santa Catarina, Florianópolis,
[9] R. Garcia-Gil, J. M. Espi, E. J. Dede, and E. Sanchis-Kilders, “A bidi- Brazil, in 2004 and 2006, respectively, where he is
rectional and isolated three-phase rectifier with soft-switching opera- currently pursuing the Ph.D. degree.
tion,” IEEE Trans. Ind. Electron., vol. 52, no. 3, pp. 765–773, Jun. 2005. His research interests include power factor correc-
[10] G. Spiazzi and F. C. Lee, “Implementation of single-phase boost power tion and power quality.
factor-correction circuits in three-phase application,” IEEE Trans. Ind.
Electron., vol. 44, no. 3, pp. 365–371, Jun. 1997.
[11] J. Hahn, P. N. Enjeti, and I. J. Pitel, “A new three-phase power-factor
correction (PFC) scheme using two single-phase PFC modules,” IEEE
Trans. Ind. Appl., vol. 38, no. 1, pp. 123–130, Jan./Feb. 2002.
[12] S. Miyairi et al., “New method for reducing harmonics involved in
input and output of rectifier with interphase transformer,” IEEE Trans. Ivo Barbi (M’76–SM’90) was born in Gaspar,
Ind. Appl., vol. IA-22, no. 5, pp. 790–797, Sep./Oct. 1986. Santa Catarina, Brazil, in 1949. He received the
[13] W. Hammond, “A new approach to enhance power quality for medium B.S. and M.S. degrees in electrical engineering from
voltage drives,” in Proc. IEEE Petroleum Chem. Ind. Technol. Conf., Federal University of Santa Catarina, Florianópolis,
Denver, CO, Sep. 1995, pp. 231–235. Brazil, in 1973 and 1976, respectively, and the Ph.D.
[14] S. Choi, B. S. Lee, and P. N. Enjeti, “New 24-pulse diode rectifier degree from the Institut National Polytechnique de
system for utility interface of high-power AC motor drives,” IEEE Toulouse, France, in 1979.
Trans. Ind. Appl., vol. 33, no. 2, pp. 531–541, Mar./Apr. 1997. He founded the Brazilian Power Electronics So-
[15] A. Rufer and Ch.-B. Andrianirina, “A symmetrical 3-phase 2-switch ciety and the Power Electronics Institute of the Fed-
PFC-power supply for variable output voltage,” in Proc. Eur. Conf. eral University of Santa Catarina. Currently he is Pro-
Power Electron. Appl. Symp. (EPE’95), Sevilla, Spain, 1995, [CD fessor of the Power Electronics Institute of the Fed-
ROM]. eral University of Santa Catarina.

You might also like