Table 12-4
SERVICE FACTORS
Service Factor
Synchronous Speed, Rpm
Hp 3600 1800 1200 900 720 600 514
1/20 1.4 1.4 1.4 1.4 ... ... ...
1/12 1.4 1.4 1.4 1.4 ... ... ...
1/8 1.4 1.4 1.4 1.4 ... ... ... Small
1/6 1.35 1.35 1.35 1.35 ... ... ... Motors
1/4 1.35 1.35 1.35 1.35 ... ... ...
1/3 1.35 1.35 1.35 1.35 ... ... ...
1/2 1.25 1.25 1.25 1.15* ... ... ... Medium
3/4 1.25 1.25 1.15* 1.15* ... ... ... Motors
1 1.25 1.15* 1.15* 1.15* ... ... ...
1-1/2-125 1.15* 1.15* 1.15* 1.15* 1.15* 1.15* 1.15*
150 1.15* 1.15* 1.15* 1.15* 1.15* 1.15* ...
200 1.15* 1.15* 1.15* 1.15* 1.15* ... ...
250 1.0 1.15* 1.15* 1.15* ... ... ...
300 1.0 1.15* 1.15* ... ... ... ...
350 1.0 1.15* 1.15* ... ... ... ...
400 1.0 1.15* ... ... .. ... ...
450 1.0 1.15* ... ... ... ... ...
500 1.0 1.15* ... ... ... ... ...
*In the case of polyphase squirrel-cage motors, these service factors apply only to Design A, B, and C motors. ▲
In those applications requiring an overload capacity, the use of a higher horsepower rating, as given in
10.32.4, is recommended to avoid exceeding the temperature rises for the class of insulation system
used and to provide adequate torque capacity.