VENTILATION CALCULATIONS
Occupancy Based
Occupancy Based on ASHRAE
on Furniture Selected FRESH AIR
SPACE INFORMATION 62.1, Master Report, FM RESIDENTIAL
layout/Report/Cl Occupancy (Based on ASHRAE 62.1, 62.2)
Requirements NO. OF PUBLIC TOILET MINIMUM
ient input ACTUAL FA ACTUAL
No. OF KITCHEN NO. OF WC EXHAUST EXHAUST REQUIRED
SUPPLIED EXHAUST
BEDROOMS RESIDENTIAL (50 L/s/Kitchen for villa (35 L/s/WC) L/s/AREA ACH EXHAUST
AREA (L/s) (L/s)
OCCUPANT PEOPLE OUTDOOR RESIDENTIAL NO. OF RESIDENTIAL and 25 L/s for Apt) (L/s)
AREA CEILING HEIGHT Room OUTDOOR Minimum Required FA
HVAC SYSTEM ROOM NUMBER & NAME ROOM TYPE DENSITY NO. OF PEOPLE NO. OF PEOPLE NO. OF PEOPLE AIR RATE NO. OF WC LAUNDRY/JANITOR/SHOW NO. OF Powder
(m2) (m) Pressure AIR RATE (L/s)
#/100 m2 Rp (L/s.person) (15 L/s./WC) ER (15 L/s/Powder)
Ra (L/s.m2)
(10 L/s/UNIT)
GROUND FLOOR
STUDIO-GF-01-007 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-GF-01-008 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-GF-01-009 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-GF-01-010 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-GF-01-011 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-GF-01-012 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-GF-01-013 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-GF-01-014 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-GF-01-015 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-GF-01-016 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-GF-01-017 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
CORRIDOR-GF-01-039 66.0 2.7 Common Corridors P 0 0 0 0 2.5 0.3 20 20 0 0 0 0 0 0 0 0 0
CLEAN UTILITY-GF-01-037 7.4 2.7 Laundry N 0 1 1 0 2.5 0.6 10 10 0 0 0 0 0 0 0 11 15
ACCESSSIBLE ROOM GF-01-001 23.0 2.7 Bedroom/living Room P 0 1 1 1 2.5 0.3 10 20 1 0 0 0 0 0 0 15 15
GARBAGE ROOM-GF-02-004 14.0 2.7 Trash Room N 0 0 0 0 0 0 0 35 0 0 0 0 0 5 0 70 70
FIRST FLOOR
STUDIO-01-01-108 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-01-01-109 21 2.7 Bedroom/living Room p 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-01-01-110 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-01-01-111 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-01-01-112 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-01-01-113 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-01-01-114 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-01-01-115 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-01-01-116 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
STUDIO-01-01-117 21 2.7 Bedroom/living Room P 0 2 2 1 2.5 0.3 15 30 1 1 0 0 0 0 0 25 25
CORRIDOR-01-01-141 66 2.7 Common Corridors P 0 0 0 0 2.5 0.3 20 20 0 0 0 0 0 0 0 0 0
CLEAN UTILITY-01-01-137 23 2.7 Bedroom/living Room P 0 1 1 1 2.5 0.3 10 20 1 0 0 0 0 0 0 15 15
SUPERVISOR ROOM 01-01-101 10 2.7 Laundry N 0 1 1 0 2.5 0.6 10 10 0 0 0 0 0 0 0 11 15
LINEN STORE-01-01-138 11 2.7 Store P 0 0 0 0 2.5 0.6 10 10 0 0 0 0 0 0 0 0 0
FAHU‐01
Evidence of increase beyond LBI-R1 (ASHRAE 62.1 - 2007)
Minimum ventilation requirements as per ASHRAE 62.1 ‐ 2007 1095
Actual ventilation air supplied to the building 1880
Supplied Outdoor air increase from minimum LBI‐R1 72%
FAHU‐02
Evidence of increase beyond LBI-R1 (ASHRAE 62.1 - 2007)
Minimum ventilation requirements as per ASHRAE 62.1 ‐ 2007 995
Actual ventilation air supplied to the building 1780
Supplied Outdoor air increase from minimum LBI‐R1 79%