Professional Documents
Culture Documents
Investigation of Load Transfer Characteristics of Dowels
Investigation of Load Transfer Characteristics of Dowels
This paper will describe a study being conducted on the load transfer characteristics of
dowels used in airfield pavement expansion joints. Field installation and dowel and slab
instrumentation will be discussed. A specially-designed cart for applying single wheel
loads will be described and data obtained as a result of preliminary tests using a
50,000-pound load will be presented. Plans for application of the data obtained to the
design of a test facility' for evaluation of load transfer devices in general will be de-
scribed.
• ABOUT a year and a half ago, the U. S. structed on a prepared subgrade having a
Naval Civil Engineering Research and Evalu- modulus of subgrade reaction of about 200
ation Laboratory began a study of load pounds per cubic inch as indicated hy bearing
transfer characteristics of dowels across an tests with a 30-inch diameter plate made just
expansion joint in a concrete slab. This paper prior to construction of the slab.
represents a progress report indicating the Each dowel is instrumented with 14 SR-4
general outline of the project, the instru- strain gages to measure shear and moment in
mentation used, and the type of data which the dowels. The moment gages are placed in
has been obtained to date. The Navy has a longitudinal slots inch wide. I f e inch deep,
current need for a realistic method of evalua- and 9 inches long. These slots are placed on
tion of load transfer devices. The method both ends of the dowels to cover the effective
must provide for the interrelation of several embedment of the dowel on both sides of the
of a given device, and it must be applicable to joint. The slots are placed 180° from each
any combination of device spacing and slab other so that when the gages on one end of
thickness. This method, when developed, will the dowel are on the upper side, those on the
eliminate any necessity for in-service evalu- other end are on the lower side. In these slots,
ation tests. strain gages (A-8) are IK",
To piovide fundamental field data from 2}.i", SH", oH", and 7« from the face of
which a realistic evaluation procedure may be the joint on both ends of the dowels. To
developed, loading tests are being made on a measure the shear transmitted across the joint,
Portland cement concrete slab 10 in. thick, 15 strain gages are j^laced on the bar in the joint
ft wide, and 50 f t long. The slab was designed space. One gage is placed on each side of the
according to Navy procedure, and the con- dowel on the neutral axis and is inclined at
crete has a compressive strength of 6160 psi 45°. The moment instrumentation of the
and a rupture modulus of 795 psi based on dowels is shown in Figure 1. From top to
28-day specimens. The slab is built in 25-foot bottom is shown the transition from the
sections joined by dowels across a ^-inch ex- original slotted bar to the finished instrumen-
pansion joint. A transverse weakened plane tation.
joint is ijrovided at the center of each 25-foot Before installation in the field slab, the in-
section. Fifteen lljj-inch diameter steel dowels strumented dowels were loaded at the center
20 inches long are placed on 12-inch centers while supported at the ends as a simple beam.
across the joint and are capped in accordance Moments were calculated for various loads and
with established construction procedure. The were used to calibrate each of the gages for the
effective embedment of the dowels is 9 inches strain readings. Aloment-strain factors have
on each side of the joint. The slab is con- been determined for each gage so that after a
148 DESIGN
field test the strain for a given gage can be a thin, flexible wire which passes through a
multiplied by the moment-strain factor to de- hole in the top of the plastic case. The brass
termine the moment on the dowel at that gage rod, in turn, passes through an aluminum plate
position. The shears across the joint are calcu- at the surface of the subgrade and extends
lated from the strain indicated bj^ the shear about 3 inches into the concrete. The alumi-
gages. Differential transformers with a linear num plate is the top of a bellows which is
range of ±0.15 inch are used to measure slab mounted on the top of the previously-men-
deflections under both static and dynamic tioned pipe casing and which is independent
loads. The transformers are in the subgrade of the free-standing steel rod that supports the
beneath 10 of the dowels on both sides of the transformer case. The aluminum plate can
joint. Economic limitations prevented the use
of transformers under every dowel. The trans-
formers are in specially-made plastic cases
about 4 inches below the surface of the sub-
grade. Each case is mounted on the upper end
of a steel rod which has been driven 10 feet
into the subgrade. The rods are free-standing
inside a pipe casing from an elevation 5 feet
below the surface of the subgrade. The core of
each transformer is attached to a brass rod bv
FlUure 4. S l a b i n s t r u m e n t a t i o n prior to c o n s t r u c t i o n
F i g u r e 2. C a l i b r a t i o n of transformers. of s l a b .
K E E T O N : LOAD TRANSFER CHARACTERISTICS OF DOWELS 149
MOMENT
LOAD SIDE
PRESSURE
SHEAR
SIDE OPPOSITE
THE LOAD
LOAD SIDE
150
K E E T O N : LOAD TRANSFER CHARACTERISTICS OF DOWELS 151
position on the load side because the amount The moment, shear, and deflection data
and direction of the moment from there to the will be used to develop a method of load trans-
cap have not been determined. fer device evaluation based on field values. A
Shear and pressure curves calculated from small slab containing three IJ^^-inch diameter
the moment curve are shown in Figure 8. The
dowels spaced 12 inches on centers will be
shear transmitted across the joint is about
4000 pounds. The maximum pressure on the constructed on a subgrade with a modulus of
load side is 7,400 pounds per lineal inch and 200 pounds per cubic inch. Loads will be varied
on the side opposite the load is 20,400 pounds until the moment, shear, and deflection values
per lineal inch. correspond with those from field tests. Other
Additional static tests are planned using a transfer devices also will be cast in small slabs
50,000-pound load at 200 psi tire pressure with and similar loads applied to observe their per-
the load applied over dowels closer to the formance under the same conditions which
corners of the slab. Dynamic tests using the prevailed in the dowel tests. Moment, shear,
same load will be applied over the same places
and deflection data from field tests will be
that the static loads were appUed. To deter-
mine the effects of higher loads and higher tire used in current theoretical load transfer equa-
pressures, static and dynamic loading tests tions to observe the correlation.
will be made with various combinations of Field testing is continuing and subsequent
loads and tire pressures up to a maximum of data will be released for publication in the
100,000 pounds and 250 psi, respectively. appropriate technical journals.