HD431910002X00
HD431910002X00
TOTAL
CONDUIT
NUMBER
FIBER (F) ; STEEL (S) STL PVC
CABLE /
SERVICE HP T T POWER (P) - CONTROL (C); QTY
"FROM" " TO " COATED (SP) GROUND (G) - INSTRUMENT (I) REMARKS
OR VOLTS FROM Y PVC (P) Y
END END TO P P
KVA
E LENGTH E
INSULATION FEET
SIZE BENDS NO. & SIZE
Ft / m TYPE VOLTS METER
PC-0011 SPARE
PC-0012 POWER 273.1 13800 V CB(B)-325 RISER POLE P 2X(3-1/C 400MM2) XLPE/PVC/CU 12/20KV 720 (2 SETS) ARMOR
KVA AT 208-040-SG-301, BUS "A" CABLE TERMINATION (CT-19) G 1-1/C 240MM2 PVC 120
PC-0013 POWER 6019 13800 V CB(B)-323 RISER POLE P 3-1/C 400MM2 XLPE/PVC/CU 12/20KV 375 ARMOR
KVA AT 208-040-SG-301, BUS "A" CABLE TERMINATION (CT-17) G 1-1/C 240MM2 PVC 125
PC-0014 SPARE
PC-0015 POWER 329 13800 V CB(B)-319 S40-E327, POS A P 3-1/C 400MM2 XLPE/PVC/CU 12/20KV 600 NON-ARMOR
KVA AT 208-040-SG-301, BUS "A" CABLE SPLICE (CS-13) G 1-1/C 240MM2 PVC 200
PC-0016 POWER 656 13800 V CB(B)-317 S40-E317, POS A P 3-1/C 400MM2 XLPE/PVC/CU 12/20KV 600 NON-ARMOR
KVA AT 208-040-SG-301, BUS "A" CABLE SPLICE (CS-11) G 1-1/C 240MM2 PVC 200
PC-0017 POWER 6510 13800 V CB(B)-315 S40-E318, POS D P 3-1/C 400MM2 XLPE/PVC/CU 12/20KV 600 NON-ARMOR
KVA AT 208-040-SG-301, BUS "A" CABLE SPLICE (CS-09) G 1-1/C 240MM2 PVC 200
PC-0018 POWER 1519 13800 V CB(B)-313 S40-E328, POS D P 3-1/C 400MM2 XLPE/PVC/CU 12/20KV 600 NON-ARMOR
KVA AT 208-040-SG-301, BUS "A" CABLE SPLICE (CS-07) G 1-1/C 240MM2 PVC 200
PC-0019 POWER 1669 13800 V CB(B)-311 S40-E329, POS A P 3-1/C 400MM2 XLPE/PVC/CU 12/20KV 600 NON-ARMOR
KVA AT 208-040-SG-301, BUS "A" CABLE SPLICE (CS-05) G 1-1/C 240MM2 PVC 200
PC-0020 POWER 3324 13800 V CB(B)-306 RISER POLE P 2X(3-1/C 400MM2) XLPE/PVC/CU 12/20KV 810 (2 SETS) ARMOR
KVA AT 208-040-SG-301, BUS "B" CABLE TERMINATION (CT-02) G 1-1/C 4MM2 PVC 135
PC-0021 SPARE
PC-0022 POWER 2710 13800 V CB(B)-310 RISER POLE P 3-1/C 400MM2 XLPE/PVC/CU 12/20KV 390 ARMOR
KVA AT 208-040-SG-301, BUS "B" CABLE TERMINATION (CT-06) G 1-1/C 240MM2 PVC 130
PC-0023 POWER 6894 13800 V CB(B)-312 S40-E301, POS A P 3-1/C 400MM2 XLPE/PVC/CU 12/20KV 600 NON-ARMOR
KVA AT 208-040-SG-301, BUS "B" CABLE SPLICE (CS-08) G 1-1/C 240MM2 PVC 200
PC-0024 SPARE
PC-0025 POWER 656 13800 V CB(B)-316 S40-E326, POS A P 3-1/C 400MM2 XLPE/PVC/CU 12/20KV 600 NON-ARMOR
KVA AT 208-040-SG-301, BUS "B" CABLE SPLICE (CS-12) G 1-1/C 240MM2 PVC 200
PC-0026 POWER 3462 13800 V CB(B)-318 S40-E313, POS A P 3-1/C 400MM2 XLPE/PVC/CU 12/20KV 600 NON-ARMOR
KVA AT 208-040-SG-301, BUS "B" CABLE SPLICE (CS-14) G 1-1/C 240MM2 PVC 200
PC-0027 POWER 5780 13800 V CB(B)-320 S40-E307, POS A P 3-1/C 400MM2 XLPE/PVC/CU 12/20KV 600 NON-ARMOR
KVA AT 208-040-SG-301, BUS "B" CABLE SPLICE (CS-16) G 1-1/C 4MM2 PVC 200
PC-0028 POWER 593 13800 V CB(B)-322 S40-E330, POS D P 3-1/C 400MM2 XLPE/PVC/CU 12/20KV 600 NON-ARMOR
KVA AT 208-040-SG-301, BUS "B" CABLE SPLICE (CS-18) G 1-1/C 4MM2 PVC 200
PC-0029 POWER 2405 13800 V CB(B)-324 S40-E334, POS E P 3-1/C 400MM2 XLPE/PVC/CU 12/20KV 600 NON-ARMOR
KVA AT 208-040-SG-301, BUS "B" CABLE SPLICE (CS-20) G 1-1/C 240MM2 PVC 200
PC-0030 POWER 5780 13800 V CB(B)-309 S40-E312, POS A P 3-1/C 400MM2 XLPE/PVC/CU 12/20KV 600 NON-ARMOR
KVA AT 208-040-SG-301, BUS "A" CABLE SPLICE (CS-03) G 1-1/C 240MM2 PVC 200
00 07/28/22 ISSUED FOR CONSTRUCTION PLANT NO. INDEX DRAWING NUMBER SHEET NO. REV. NO.
JOB ORDER / EWO NO. THIS REVISION IS NOT TO BE USED FOR CONSTRUCTION UNTIL
10-10041-0001 CERTIFIED AND DATED 208 P HD-431910 002 00
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER. Saudi Aramco 2864-ENG (11/10)'D' SIZE