R0 HVAC MPMRCL

Total Total
Sl.No. Description Unit
Quantity(Tender) Quantity(GFC)

C.01 AIRCONDITIONING
1.1 VRF UNITS
Supply, installation, testing and commissioning of Air Cooled Variable Refrigerant Flow System
suitable for R410A, 415V, 50 Hz, AC supply. The unit shall consist of indoor units and external
condensing units and other accessories complete in all respects. The unit shall be fully charged with
required volume of gas. Central remote controller shall be provided to control the complete HVAC
system of that particular station.
OUTDOOR UNIT
Supply, installation, testing and commissioning of Modular Type Outdoor Condensing Units
equipped with highly efficient Inverter scroll compressors to work on 415 V, 50 Hz AC supply with
digital/ inverter technology, special acryl precoated heat exchanger, low noise condenser fan with
motor, auto check function for errors in display panel, auto address setting, as per
specifications.COP should be 4.3 minimum at 100% load with 100% Inverter technology.

BMS integration card to be compatible with 3rd party integration through modbus protocol.
The units shall be complete with necessary electrical cabling between MCB and Outdoor unit,
earthing, mounting frames and required accessories.
a 40 HP ( 1Working + 1 Standby) Nos. 0 0
b 38 HP ( 1Working + 1 Standby) Nos. 0 2
c 36 HP ( 1Working + 1 Standby) Nos. 0 1
d 34 HP ( 1Working + 1 Standby) Nos. 0 1
e 32 HP ( 1Working + 1 Standby) Nos. 14 4
f 30 HP ( 1Working + 1 Standby) Nos. 2 0
g 8 HP ( 1Working + 1 Standby) Nos. 0 0
h 6 HP Side Discharge ( 1Working + 1 Standby) Nos. 16 8

Total

1.2INDOOR UNITS
Supply, installation, testing and commissioning of Wall mounted Type Indoor Units each
comprising of cooling coil, blower with motor suitable for operation on 230 volt, 1 phase, 50 Hz, AC
1.2.1.a supply and as per specifications. The rate shall include cost of cordless Remote controller, Top
Plugs, complete length of required size drain pipes and all other accessories required for full-fledged
operation of system.
a 1.6TR Nos. 0 0
b 2.0 TR Nos. 0 0

Supplying, installation, testing and commissioning of ceiling mounted 4-way cassette Type Indoor
Units each complete with coil, filter, drain pump etc. Air conditioners with evaporating unit
comprising of cooling coil, blower with motor suitable for operation on 230 volt, 1 phase, 50 Hz, AC
1.2.1.b
supply and as per specifications. The rate shall include cost of corded Remote controller, Top Plugs,
complete length of required size drain pipes and all other accessories required for full-fledged
operation of system.
Unit to be provided with UV lamp to eliminate microbes/viruses
a 1.0 TR Nos. 33
1.3 TR 17
b 1.6 TR Nos. 0 64
c 2.0 TR Nos. 1
2.6 TR
d 3.2 TR Nos. 0

Supplying, installation, testing and commissioning of Central Remote Controller for integrating and
efficient control of Indoor and Outdoor Units from Station Controller room. Rate shall include all
required and associated accessories for complete functionality of the equipment as per technical
1.2.1.c Set 8 8
specification. The equipment shall have inbuilt compatibility for integration with BMS subsystem
through RS485 communication port with MODBUS protocol. Price to include Modbus controller
and I- manager

Supplying, installation, testing and commissioning of Ceiling suspended Ductable type indoor Units
comprising of cooling coil, blower with motor suitable for operation on 230 volt, 1 phase, 50 Hz, AC
1.2.1.d supply and as per specifications. The rate shall include cost of corded Remote controller, Top Plugs,
complete length of required size drain pipes and all other accessories required for full-fledged
operation of system.
Unit to be provided with UV lamp to eliminate microbes/viruses
a 1.0 TR Nos. 8 0
b 1.3 TR Nos. 24 0
1.6 TR Nos. 0 0
c 2.0 TR Nos. 0 10
2.6 TR Nos. 2 24
d 3.0 TR Nos. 8 0
3.2 TR Nos. 0 6
e 3.5 TR Nos. 28 0
f 4.0 TR Nos. 6 4
g 4.5TR Nos. 32 0
4.6 TR Nos. 0 0

1 of 3 (Revision-0) Stamp/Signature
R0 HVAC MPMRCL

Total Total
Sl.No. Description Unit
Quantity(Tender) Quantity(GFC)

5.5TR Nos. 0 30
h 6.3TR Nos. 16 0
6.4 TR Nos. 0 6
i 8.0TR Nos. 8 0
Total

1.3 REFRIGERANT PIPING


Supply, installation, testing and commissioning of interconnecting refrigerant pipe work with
elastomeric nitrile rubber/closed cell expanded polythene tubular insulation between each set of
indoor & outdoor units as per specifications, all piping should be laid on Galvanized/Powder
Coated tray supported by Galvanized MS Hangers & Clamps. The rate shall include cost of Y-joints/
T-Joints distributer and headers in the refrigeration piping system wherever required and all other
accessories required for full-fledged operation of system.
a 41.3 mm O.D.(insulation - 19 mm thick) Rmt. 0 302
b 34.9 mm O.D.(insulation - 19 mm thick) Rmt. 240 150
c 28.6 mm O.D.(insulation – 19 mm thick) Rmt. 40 238
d 25.4 mm O.D.(insulation – 19 mm thick) Rmt. 0 0
e 22.2 mm O.D.(insulation – 13 mm thick) Rmt. 280 114
f 19.1 mm O.D.(insulation – 13 mm thick) Rmt. 240 1078
g 15.9 mm O.D.(insulation – 13 mm thick) Rmt. 400 473
h 12.7 mm O.D.(insulation – 13 mm thick) Rmt. 2800 1773
i 9.5 mm O.D.(insulation – 13 mm thick) Rmt. 600 718
j 6.4 mm O.D.(insulation – 13 mm thick) Rmt. 2600 1851

1.4 CONTROL CABLING


Supply, installation, testing and commissioning of control cum transmission wiring of 3 core x 1.5
Sq.mm copper FRLSZH, XLPE insulated cable in suitable GI conduits accessories between indoor
a and outdoor units. Necessary securing of conduit shall be made by contractor. After completion of Rmt. 3200 3200
work, wall and floor shall be repaired and brought to its original finish. The rate shall include cost of
laying of GI conduit between indoor and outdoor units.
Total

1.5 AIR DISTRIBUTION SYSTEM


1.5.1 G.I. Sheet Metal Ducts
Supply, installation, testing and commissioning of factory fabricated G.I. Sheet metal ducts with
flanges complete with supports, vanes, links, levers and quadrants etc. as per specifications and
drawings. The rates shall include all materials of the duct and labour for suspension and supporting
arrangement for plenums, ducts, complete with fire retardant flexible connection as required and as
per specifications.
a 0.63mm (24 Gauge) Sqm 400 381
b 0.83 mm thick (22 Gauge) Sqm 0 0
c 1.00 mm thick (20 Gauge) Sqm 0 0
d 1.20 mm thick (18 Gauge) Sqm 0 0
0
1.5.2 Supply/Exhaust Air / Door Transfer Grill
Supply, installation, testing and commissioning of Exhaust air grills with VCD (In various sizes as
a Sqm 8 8
required at site and as approved by Engineer In charge)
Supply, installation, testing and commissioning of Door Transfer grills (In various sizes as required
b Sqm 0 0
at site and as approved by Engineer In charge)

1.5.3 Fresh Air Louver


Supply, installation, testing and commissioning of Exhaust / Fresh air Aluminium Louvers (In various
Sqm 8 8
sizes as required at site and as approved by Engineer In charge)

1.5.4
DAMPER
Dampers complete as per technical specifications.
Supply, installation, testing and commissioning of MOD/MFD frames and other components made of
hot-dipped galvanized mild steel shall conform to BS/EN-10142. Damper blades shall be fabricated
1.5.4.1
of galvanized steel conforming to BS/EN-10142. All unprotected edges shall be touched up with an
Approved paint-on type zinc-based protective coating.
a Motor Operated Dampers SQM 0 0
b Motorized Fire Dampers SQM 0 0
c Fire Dampers with fusible link SQM 0 0
d
1.5.4.2 Supply, installation, testing and commissioning of duct volume control dampers SQM 4 4
1.5.4.3 Supply, installation, testing and commissioning of duct (Non return type) dampers SQM 0 0

1.5.5 Supply & fixing of fire retardant canvas SQM 256 223

1.5.6 Supply & fixing of Aluminium powder coated Linear Grille SQM 48 32

Total

2 of 3 (Revision-0) Stamp/Signature
R0 HVAC MPMRCL

Total Total
Sl.No. Description Unit
Quantity(Tender) Quantity(GFC)

1.6 VENTILATION FANS

1.6.1 Inline Fans


Supply, installation, testing and commissioning of Inline fans with Blower, motor, flanges, flexible
connections, back draft damper etc., with Class 'F' insulation suitable for operating at 1phase, 230V,
50hz power supply.
a 340 CMH-20 mm ESP With MERV-8 filter for Fresh air - Kruger make Nos. 8 8
b 255 CMH-20 mm ESP for Exhaust - Kruger make Nos. 0 56
c 4930 CMH-20 mm ESP for fresh air - Kruger make Nos. 0 8
d 5000 CMH-20 mm ESP for Exhaust Nos. 8 0

1.6.2 Propeller Type Fans


Supply, Installation, testing and commissioning of Propeller type fan complete with motor suitable for
240 volt, 1 phase, 50 Hz AC supply, mounting frames and Gravity shutters and complete as per
specifications.
a Size 300 mm dia fuel tank- Kruger make Nos. 62 8
b Size 450 mm dia DG room- Kruger make Nos. 0 16
c Size 630 mm dia (3 Phase) for ASS-TSS room)- Kruger make Nos. 52 52

1.6.3 Temperature Based Fan Control System & Panel


a Supply, installation, testing & commissioning of temperature based fan control system of ASS Room
for automatic ON/OFF based on temperature of the ASS room for controlling propeller fans,
consisting of temperature sensor, control panel with 63 A MCCB, 25 kA as incomer and outgoing as
Set 8 8
8 nos. 20A DP MPCB with 20A contactor, on/off indication lamps and one controller to start /stop
fans with help of temperature sensor, necessary control wiring etc. as per control philosophy in
Technical Specification. The system shall be BMS compatible.

Total

GRAND TOTAL WITHOUT TAXES


a TOTAL FOR VRF UNITS
b TOTAL FOR INDOOR UNITS
c TOTAL FOR LOW SIDE WORKS (REF PIPE&CABLES)
d TOTAL FOR LOW SIDE WORKS ( DUCTS & AIR DISTRIBUTION PRODUCTS)
e TOTAL FOR VENTILATION FANS

NOTES
i All Toilet Door Grilles & external wall Louver shall be in civil contractors Scope of Work
ii Any Civil pedestral for installing Ventilation fans shall be in civil contractors Scope of Work
iii Necessary isolator with required MCCB/ELCB shall be provided next to VRF outdoor units &
Ventilation electrical panel by electrical contractor
iv Necessary 3 Pin Socket shall be provided next to all VRF Indoor units & ventilation fans by electrical
contractor
v Necessary Potential free contact box to be provided for all ventilation fans by BMS contractor to
monitor & control units through BMS
vii Necessary DOL starters for axial fans shall be provided by electrical contractor
viii Civil works such as opening and closing of walls to take the pipes and ducts, etc. shall be in civil
contractors Scope of Work

3 of 3 (Revision-0) Stamp/Signature