Download as pdf or txt
Download as pdf or txt
You are on page 1of 36

1997

STANDARD for

ELECTRICAL/
ELECTRONIC
DIAGRAMS

Standard 120

4301 NORTH FAIRFAX DRIVE ! ARLINGTON, VIRGINIA 22203


IMPORTANT

SAFETY RECOMMENDATIONS

It is strongly recommended that the product be designed, constructed, assembled and installed in accordance with
nationally recognized safety requirements appropriate for products covered by this standard.

ARI, as a manufacturers' trade association, uses its best efforts to develop standards employing state-of-the-art and
accepted industry practices. However, ARI does not certify or guarantee safety of any products, components or
systems designed, tested, rated, installed or operated in accordance with these standards or that any tests conducted
under its standards will be non-hazardous or free from risk.

Note:

This standard supersedes ARI Standard 120-90.

Price $20.00 (M) $40.00 (NM) ©Copyright 1997, by Air-Conditioning and Refrigeration Institute
Printed in U.S.A. Registered United States Patent and Trademark Office
TABLE OF CONTENTS

SECTION PAGE

Section 1. Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Section 2. Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Section 3. Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Section 4. Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Section 5. Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

5.1 Schematic Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

5.2 Connection (Wiring) Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

5.3 Interconnection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Section 6. Voluntary Conformance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

FIGURES

Figure 1. Line Conventions for Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Figure 2. Functional or Device Designations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Figure 3. Complete Reference Designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Figure 4. Used and Omitted Reference Designations . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Figure 5. Terminal Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Figure 6. Typical Legend Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Figure 7. Abbreviations for Colors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Figure 8. Schematic Diagram With Reference Designations . . . . . . . . . . . . . . . . . . . . . . 8

Figure 9. Schematic Diagram With Functional Designations . . . . . . . . . . . . . . . . . . . . 10

Figure 10. Schematic Diagram With Functional Description . . . . . . . . . . . . . . . . . . . . . 12

Figure 11. Electrical Path Connection (Junctions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Figure 12. Interrupted Electrical Path . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13


Figure 13. Terminal Markings on Terminal Boards, Strip or Relays . . . . . . . . . . . . . . . . 14

Figure 14. Point to Point Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Figure 15. Highway Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Figure 16. Highway Feed Line Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Figure 17. Interrupted Line Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Figure 18. Tabular Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Figure 19. Point to Point Interconnection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Figure 20. Highway Interconnection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Figure 21. Interrupted Line Interconnection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Figure 22. Diagrammatic Cabling Interconnection Diagram . . . . . . . . . . . . . . . . . . . . . . 31

Figure 23. Tabular Cabling Interconnection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

APPENDICES

Appendix A. References - Normative . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Appendix B. References - Informative . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32


ARI STANDARD 120-97

ELECTRICAL/ELECTRONIC DIAGRAMS
Section 1. Purpose 3.5 Electrical/Electronic Diagram (Diagram). A diagram
which takes the form of one or more of the types as defined
1.1 Purpose. The purpose of this standard is to establish below.
for air-conditioning and refrigerating equipment: a format
for electrical/electronic diagrams. 3.5.1 Connection Diagram (Writing Diagram). A
diagram which shows the connections of an installation
1.1.1 Intent. This standard is intended for the or its devices. It may cover internal or external
guidance of the industry, including manufacturers, connections, or both, and contains such detail as is
engineers, installers, contractors, and users. needed to make or trace connections that are involved.
The connection diagram usually shows general physical
1.1.1.1 This standard is intended to eliminate arrangement of the devices.
divergent electrical and electronics diagram
techniques. 3.5.2 Interconnection Diagram. A diagram which
shows only external connections between assemblies or
1.1.1.2 This standard is not intended to limit or equipment. The internal connections of the assemblies
inhibit advancement in the art of electrical or or equipment are usually omitted.
mechanical engineering.
3.5.3 Schematic Diagram (Elementary or Ladder
1.1.2 Review and Amendment. This standard is Diagram). A diagram which shows, by means of
subject to review and amendment as technology graphic symbols, the electrical connections and
advances. functions of a specific circuit arrangement. The
schematic diagram facilitates tracing the circuit and its
functions without regard to the actual physical size,
Section 2. Scope shape, or location of the device.

2.1 Scope. This standard applies to electrical/electronic 3.6 Equipment. An assembly or any combination of
diagrams for air-conditioning and refrigerating equipment, devices, subassemblies and assemblies mounted together,
including related accessories and controls as defined in normally capable of independent operation in a variety of
Section 3. situations. For purposes of this Standard such independent
operation may be air cleaning, heating, ventilating, air-
conditioning or other refrigeration functions.
Section 3. Definitions
3.7 Functional Description. Words used on a diagram to
3.1 Definitions. All terms in this document will follow describe the function of the device.
the standard industry definitions established in the current
edition of ASHRAE Terminology of Heating, Ventilation, 3.8 Functional Designation. Abbreviations, or
Air Conditioning and Refrigeration, unless otherwise meaningful number-letter combinations derived from the
defined in this section. function of a device, used on diagrams to identify and refer
to the device.
3.2 Assembly (Unit). A number of devices or
subassemblies or any combination thereof joined together 3.9 Reference Designation. A combination of letters and
to perform a specific function and is capable of numbers used on diagrams to identify and refer to a device
disassembly. without regard to its function.

3.3 Class Letter. A letter or combination of letters used 3.10 "Shall," "Should," "Recommended" or "It is
to classify a device. Recommended."

3.4 Device. One or more pieces joined together which are 3.10.1 Shall. Where "shall" or "shall not" is used
not normally subject to disassembly without destruction of for a provision specified, that provision is mandatory if
designed use. Typically designed to serve a special purpose compliance with the standard is claimed.
or a special function.

1
ARI STANDARD 120-97

3.10.2 Should, Recommended, or It is 4.1.5 Line Convention.


Recommended. "Should," "recommended," or "it is
recommended" is used to indicate provisions which are 4.1.5.1 Line thickness and lettering size shall
not mandatory, but which are desirable as good take into account the diagram size and the
practice. reproduction process, when it is felt that legibility
may be affected.
3.11 Subassembly. Two or more devices which form a
portion of an assembly but having a device or devices which 4.1.5.2 Solid lines shall represent factory wiring
are individually replaceable. and dashed lines shall represent field wiring when
both are shown on the same diagram (see Figure
3.12 Test Point. a designated location for testing of the 1). If additional line conventions are used, they
device or assembly. shall be identified in the legend.

Section 4. Requirements FACTORY WIRING _____________


FIELD WIRING --------------------
4.1 General Requirements. The following covers basic
criteria which are applicable to all diagrams.
Figure 1. Line Conventions For Diagrams
4.1.1 Graphic symbols used for electrical/electronic
diagrams shall be as described in ARI Standard 130.
If no suitable symbol is listed in ARI Standard 130, 4.1.6 Representation of Electrical Contacts. Limit,
ANSI/IEEE Standards 315 & 315A shall be used. pressure, float, flow, temperature-sensitive and similar
Symbols which do not appear in ARI Standard 130 switch symbols shall be shown on the diagram in
shall be defined on the diagram. accordance with ARI Standard 130.

4.1.1.1 Graphic symbols shall be drawn to any 4.1.7 Abbreviations. Abbreviations used on
proportional size that suits a particular diagram, electrical/electronic diagrams shall conform with
provided the selection of sizes takes into account ANSI/ASME Standard Y1.1. If no suitable
the anticipated reproduction process. abbreviation exists, a special abbreviation or acronym
may be used, but shall be defined on the diagram.
4.1.1.2 Symbols or parts of symbols (except
letters and numbers) which lend themselves to Note: Abbreviations on electrical/electronic
being rotated or reversed may be so oriented for diagrams which are circulated in foreign countries
simplification of circuit layout. should be avoided because of possible
misunderstanding and misinterpretation derived
4.1.2 Applications shown in this standard, are from language differences.
examples of preferred drafting practice for
electrical/electronic diagrams. No attempt has been 4.1.7.1 Except for the slash (/) and hyphen (-),
made to show all possible applications. Additional punctuation marks are not indicated for any
applications may be devised provided they are a abbreviation. A period shall be added to an
reasonable use of good drafting practice. For abbreviation if it may be mistaken for a word.
applications not covered, , use ANSI Standards
Y14.15 (includes supplements ANSI Y14.15a) and 4.1.8 Device Identification. Device identifications
Y14.15b). are intended for use on diagrams in connection with the
corresponding graphical symbols to identify and refer
4.1.3 A combined form of diagrams may be used to the particular device. Device identification falls into
when the net result is helpful to the user. When this three classifications:
principle is applied, the diagram title shall be selected
on the basis of the major purpose of the diagram. 1. Functional description
2. Functional designation
4.1.4 A multiple diagram is used when two or more 3. Reference designation
electrical diagram types are shown on a single form,
this form shall be identified as an electrical/electronic These classifications provide a device identification
diagram. method which will satisfy the requirements of a wide

2
ARI STANDARD 120-97

range of diagrams with varying degrees of two or more assemblies or one or more levels
electrical/electronic complexities, and serve to identify the of subassemblies, to completely identify an
same devices on related documents. item within the set, the basic reference
designation shall be prefixed with the
Devices not separately replaceable may be identified as designations assigned to the subassemblies
required. Mounting devices for lamps, fuses, etc., are and the unit incorporating the device as shown
not usually shown or identified on schematic diagrams. in Figure 3 .

4.1.8.1 Functional Description. In this 4.1.8.3.3 When items are eliminated as a


classification, a brief functional description is result of a drawing revision, remaining items
written near the component device or graphic shall not be renumbered. For circuits showing
symbol of the device on the connection or many devices, a figure may be used to show
schematic diagram. This is generally limited to which numbers are not used and the highest
diagrams containing a small number of component numbered reference designations, as shown in
devices. Figure 4.

4.1.8.2 Functional Designation. A functional 4.1.8.3.4 Terminals. To identify terminals


designation is used on diagrams in connection with of devices (such as relays, terminal boards,
the graphic symbols to indicate the function of the and transformers), the device reference
particular device. The designation is based on the designation and terminals shall be one of the
assignment of a letter or letters to each of the two methods shown in Figure 5. These
fundamental functions performed by the device or methods are:
part. Suitable prefix and/or suffix letters or
numbers, or both, shall be permitted to be added to 1. The device reference
the basic functional designation to discriminate designation is suffixed with a
between devices performing similar functions. For dash followed by the terminal
examples of functional designations, see Figure 2. identification, separated by
If no appropriate functional designation exists, a commas. For example, a relay
suitable functional designation may be used and contact connected to terminals 5
shall be defined in the legend. and 6 of relay K7 would be
assigned the reference K7-5, 6.
4.1.8.3 Reference Designation. Reference
designations are distinct combinations of letters 2. The device reference
and numbers which identify and locate discrete designation is located near the
devices shown on the diagram. symbol with the terminal
identification beside the
appropriate terminal.
All graphic symbols of separately replaceable
items shall be identified by an appropriate
This principle shall also be
reference designation located as near as practical
permitted to be applied, by
to the graphic symbol.
extension, to key switches, and
similar devices, provided the
For the selection of reference designation letters
terminals of the devices have
and numbers, refer to ANSI/IEEE Standard 315A.
been or may be assigned
numerical identifications.
4.1.8.3.1 Basic Reference Designation. A
reference designation that consists only of a
4.1.9 Legend. A legend shall be provided which is
class letter portion and a number.
an explanatory list of symbols, notes and designations
used on the diagram.
4.1.8.3.2 Complete Reference Designation.
A reference designation that consists of a
basic reference designation and, as prefixes,
all the reference designations that apply to the
subassemblies or assemblies within which one
device is located, including those of the
highest level needed to designate the device
uniquely. For more complex sets, involving

3
ARI STANDARD 120-97

DEVICE OR FUNCTION DESIGNATIONS


Ammeter AM
Capacitor C
Circuit breaker CB
Control relay CR
Current transformer CT

Demand Meter DM
Diode (Rectifier) D
Disconnect switch DS or DISC

Frequency meter FM
Fuse FU

Ground protective GP

Limit switch LS

Main contactor M

Overcurrent OC
Overload OL
Overvoltage OV

Potentiometer P
Pressure switch PS
Pushbutton PB

Resistor R

Select switch SS
Solenoid valve SV
Starting contactor S
Suppressor SU

Terminal block or board TB


Time-delay relay TR
Transformer T
Transistor Q

Undervoltage UV

Voltmeter VM

Watthour meter WHM


Wattmeter WM

Figure 2. Functional Or Device Designations

4
ARI STANDARD 120-97

Figure 3. Complete Reference Designation

Numbers Used & Omitted

Reference Highest Number Number(s)


Designation Used Omitted

C 32 24

CR 3

DS 28

E 50 4-6, 27, 28

J 7 1, 4

LS 1

P 4 2, 3

Q 1

R 45 1

U 17

W 9

Y 1

Figure 4. Used and Omitted Reference Designations

5
ARI STANDARD 120-97

Figure 5. Terminal Identification

4.1.9.1 When either the functional designation or


Legend
reference designation classification is used, a
Functional Description Line legend box shall be shown on the diagram. The
Designation Number legend shall list all the devices and abbreviations
appearing on the diagram with descriptions or
CC1 Compressor Contactor 45 functions of the devices. This list shall be in
CKT1 alphabetical order. The line number on which the
device (or the coil of the device) appears on the
CC2 Compressor Contactor 46 schematic may be included. See Figure 6.
CKT2
4.1.9.2 Notes which give additional information
CCH1 Crankcase Heater 13
such as timing settings, exceptions, changes in
CKT1
wiring for different voltages, motor protection
CCH2 Crankcase Heater 18 devices being used, wires that must be altered
CKT2 when changing motor speeds, plus other necessary
information that is valuable for trouble-shooting or
CF1 Outdoor Motor 21 installing the equipment, shall be included. Notes
Capacitor shall be referenced at the point on the diagram
where applicable.
CFM Combustion Fan Motor 27
4.1.9.3 When multiple line weights or styles are
CPR1 Compressor CKT1 11
used to indicate wiring identification, they shall be
CPR2 Compressor CKT2 16 defined in the legend.

ECA Economizer Actuator 50 4.1.10 Diagram Identification. All diagrams shall


be marked with a number or code that identifies the
F Indoor Fan Contactor 42 diagram. This number or code shall be clearly labeled
as the identifying code.
FTB Fan Terminal Block 7, 5, 9
4.1.10.1 Revisions. Revisions to diagrams shall
Figure 6. Typical Legend Information be indicated by a number or code, and that number
or code shall appear on the diagram.

4.1.11 Wire Color Code Abbreviation. When colors


are used to identify wiring they shall conform to the
color code abbreviations shown in Figure 7.

6
ARI STANDARD 120-97

A control circuit shall be drawn between vertical lines


Wire Color Color Code Abbreviation
which represent the source of control power. All
Black BK control devices shall be shown between these lines.
Brown BR Activating coils of control devices shall be shown on
Red R the right side. All contacts shall be shown between the
Orange O coils and left vertical line except when the right vertical
Yellow Y line is not at neutral or ground potential.
Green G
Blue BL 5.1.1.1 Control devices shall be shown in the
Violet (Purple) V (PR) order in which the controls are energized and
Gray (Slate) GY (S) positioned on the diagram for clarity.
White W
5.1.1.2 The purpose or function of all switches
shall be shown either adjacent to the symbols, or in
Figure 7. Abbreviations For Colors
a switch description chart. The chart shall be on
the same sheet as the symbol(s).
4.1.11.1 When color combinations are used, the
5.1.1.3 The purpose or function of controls such
colors shall be separated by a slash (/) for example:
as relays, starters, contactors, solenoids, sub-
green/yellow (G/Y). The primary color code of the
assemblies and timers may be shown on the
wire shall be shown first, tracer or stripe shown
diagram adjacent to their respective symbols.
last.
5.1.1.4 A cross-referencing system shall be used
4.1.11.2 When other colors or color abbreviations
in conjunction with each relay coil so that
not listed in Figure 7 are used, they shall be
associated contacts may be readily located on the
defined in the legend.
diagram. Each horizontal control line shall be
numbered on the left side of the diagram. To the
right of each coil, the line numbers on which the
Section 5. Diagrams
associated contacts appear shall be listed. Those
contacts which are normally closed, shall be
5.1 Schematic Diagrams. The following contains general
indicated by underlining the line number.
information for use in preparation of schematic diagrams.
There are three commonly used methods of device
5.1.1.5 Optional devices that require additional
identification in schematic diagrams. These methods are:
wiring shall be shown either separated from the
main wiring or integral with the main wiring with
1. Reference designation, see Figure 8.
a phantom line around the component(s) and
labeled as an optional device. All connection
2. Functional designation, see Figure 9.
points to the main wiring shall be clearly indicated.
3. Functional description, see Figure 10.
5.1.1.6 Each electrical node shall be assigned
one unique number or color. All wires associated
5.1.1 Layout. The schematic diagram shall use a
with the node shall be identified by the same color
layout which follows the circuit or signal, either from
or number.
input to output, source to load, or, in the order of
functional sequence. Diagrams shall have the main
5.1.2 Connecting Lines. Connecting lines
power or signal input in the upper left area of the
representing the electrical path shall be drawn with as
diagram. The wiring shall then be drawn as logically
few bends and crossovers as possible. Connecting lines
and simply as possible toward the output or load at the
and the symbols joined by them shall be drawn
lower right.
horizontally and vertically. Connections (junctions)
shall be represented by using the "dot" method as
Where the internal diagrams of subassemblies are
shown in Figure 11.
furnished on separate sheets, they shall be shown as a
rectangle in the schematic diagram with all external
points identified and cross-referenced to the separate
sheet(s) of the control circuits.

7
ARI STANDARD 120-97

Figure 8. Schematic Diagram With Reference Designations

8
ARI STANDARD 120-97

Figure 8. (Continued)

9
ARI STANDARD 120-97

Figure 9. Schematic Diagram With Functional Designations

10
ARI STANDARD 120-97

Figure 9. (Continued)

11
ARI STANDARD 120-97

Figure 10. Schematic Diagram With Functional Description

12
ARI STANDARD 120-97

Figure 11. Electrical Path Connections


(Junctions)

Figure 12. Interrupted Electrical Path

5.1.3 Interrupted Electrical Paths. Connecting 5.1.5.1 Identification of Terminals (General).


lines, whether single or in groups, may be interrupted Terminal identifications shall be added to graphic
at convenient points and identified, with the destination symbols to indicate actual physical markings
indicated. Letters, numbers, abbreviations, or other which appear on or near the device terminations.
identifiers for interrupted lines shall be located as close When the terminals of devices (such as relays,
as possible to the point of interruption. See Figure 12. switches, or transformers) are not shown or
marked on the device, number or letter
5.1.4 Mechanical Linkages. When mechanical identifications shall be arbitrarily assigned. This
functions are closely related to certain electrical practice will facilitate use of the circuit
functions, it may be desirable to link the mechanical information for connection diagram preparation
components with graphic symbols on the schematic and circuit testing. When terminal identifications
diagram. See the typical room thermostat included in are arbitrarily assigned, the schematic diagram
Figure 9. shall include an explanatory note and a simplified
terminal orientation diagram which relates the
5.1.5 Terminals. Terminal circles shall be omitted assigned symbol terminal nomenclature to the
unless required for clarification. When terminal functional markings on the equipment and physical
symbols are omitted from the terminations of a device, features of the device.
or an enclosed or shielded group of devices, terminal
markings shall be placed immediately outside the
enclosure. See Figure 13.

13
ARI STANDARD 120-97

Figure 13. Terminal Markings On Terminal Boards, Strips Or Relays

14
ARI STANDARD 120-97

5.1.6 Adjustable Resistor Terminal Identification. 1. Continuous-line, see paragraph 5.2.2


When rotary type adjustable resistors are shown on 2. Interrupted-line, see paragraph 5.2.3
schematic diagrams, it is often desirable to indicate 3. Tabular, see paragraph 5.2.4
direction of rotation. For indicating direction of
rotation, it is customary to refer to the rotary motion as These methods will satisfy the requirements of a wide range
clockwise (CW), or counterclockwise (CCW) when of equipment design.
rotation is viewed from the knob or actuator end of the
control. The preferred method of terminal 5.2.1 General Requirements. The connection
identification is to designate the terminal adjacent to the diagram is used to show pictorially the location of
movable contact when it is in the extreme clockwise devices in an installation. The connection diagram
position with the capital letters "CW". shows electrical connections to devices and may show
wire routing. No care is taken to aid in the circuit
5.1.7 Graphical Separation of Devices. To clarify function, but to merely show the point to point wiring of
the circuit layout, portions of multi-element devices devices.
may be separated, with portions of the graphic symbol
shown at different locations on the schematic diagram. 5.2.1.1 Equipment Views. The view or views of
Subdivisions of a device shall be identified by adding equipment required for a connection diagram are
a suffix letter to the reference designation. For those which will most clearly show the terminals or
example, S1A and S1B may be used to identify wiring sides of the devices as they are mounted in
electrically separate sections of a dual switch the equipment.
designated S1.
Symbols for connections diagrams are intended to
5.1.8 Test Points. Test points shall be identified on pictorially represent each device or terminal of the
a diagram with the capital letters "TP" followed by a equipment that is to be wired. The symbols shall
number suffix. The number suffix shall be assigned on be of the pictorial, simple geometric (rectangle or
the diagram in sequence for trouble-shooting circle) or schematic type. When the geometric
convenience. shape is used, only terminal circles are shown
within these shapes. When schematic symbols are
5.1.9 Additional Circuit Information. Additional used, refer to paragraph 4.1.1.
circuit information, as listed below (but not limited to
this list), may be included on schematic diagrams: 5.2.1.2 Arrangement of Devices. The
arrangement of device symbols in the diagram shall
a. DC resistance of windings and coils closely approximate the relative location of the
b. Critical input or output impedance values devices as shown on the assembly drawing or as
c. Waves shapes (voltage or current) at located on the actual equipment. Within
significant points reasonable limits, symbol placement may differ
d. Wiring requirements for critical ground points, from the actual arrangement in order to avoid
shielding, etc. unnecessary crowding of connecting lines and
e. Indication of operational controls or circuit designations, or to simplify the layout.
functions
f. Power or voltage ratings of parts 5.2.1.3 Designation. Designations for
g. Caution notations for electrical hazards at equipment, assemblies, sub-assemblies and
maintenance points devices, shown on connection diagrams shall
h. Circuit voltage values at significant points, correspond to those shown on any associated
pins, test points, terminal boards, etc. diagram.
i. Significant circuit resistance values at
designated reference points 5.2.1.4 Wire Identification. Wire identification
j. The amount of time on a timed device shall be placed at both ends of a connecting line or
as near as possible to each terminal end. A single
5.2 Connection (Wiring) Diagrams. The following appearance of the identification may be sufficient
section contains general information for use in preparation when the ends of continuous connecting lines are
of a connection diagram. Connection diagrams covered in obvious. The identification may be shown within
this standard fall into three classifications. These or parallel to the connecting or feed line.
classifications are: However, whichever identification method is used,
that method shall be used consistently throughout
the diagram.

15
ARI STANDARD 120-97

5.2.1.5 Phasing Indication. Phasing of 5.2.2.1 Point-to-Point. In point-to-point


alternating current equipment shall be indicated so connection diagrams, separate connecting lines
that there is general agreement with the actual represent the actual terminal-to-terminal
physical arrangement and suitable notes shall be connections which are to be provided on the
used when necessary. When physical arrangement equipment; see Figure 14. On this type of
is not the governing factor, the phasing shall be connection diagram, connecting line layout or
indicated in sequence 1, 2, 3, N or A, B, C, N from arrangement is not intended to convey actual or
left to right or top to bottom. preferred conductor path location. Connection
sequence shall be determined on the basis of the
5.2.1.6 Polarity Indication. Polarity of direct most suitable path from terminal to terminal on the
current devices shall be indicated with a "P" or "+" diagram.
for positive, "N" or "-" for negative, and "PN" or
"±" for neutral. Direct current busses shall be The point-to-point method is useful mainly for the
shown in sequence: positive, neutral, negative from representation of wiring information for the less
left to right or top to bottom when physical complex equipment that may consist of relatively
arrangement is not the governing factor. When it few connection lines. If use of the point-to-point
is necessary to indicate the polarity or orientation method results in a diagram difficult to read
of terminals, the feature whereby the polarity or because of the number of adjacent and crossing
orientation is indicated on the equipment, connecting lines, another of the methods described
assembly, sub-assembly or device shall be noted on in this standard shall be considered.
the diagram.
5.2.2.2 Highway (Cable) Diagrams. The
5.2.1.7 Twisted Wire Designations. When two highway connection diagram is similar to the point-
or more wires are twisted, they shall be as shown in to-point diagram with the exception that groups of
ARI Standard 130. connecting lines are merged into lines called
highways instead of being shown in their entire run
5.2.2 Continuous-Line Connection Diagram. In this as individual lines; see Figure 15.
type of diagram, continuous lines, generally
representative of the actual connection between
terminal conductors or cable paths, are shown from
symbol to symbol.

16
ARI STANDARD 120-97

Figure 14. Point To Point Connection Diagram

17
Figure 15. Highway Connection Diagram
18
Figure 15. (Continued)
19
ARI STANDARD 120-97

5.2.2.2.1 Feed Lines. Short lines from the sacrificed. When this is done, it is recommended
device terminals are referred to as feed lines. that the feed line represent wires of the same
Feed lines are drawn perpendicular to gauge and type.
highway lines. At the point where the feed
line enters the highway line, direction of wire Wire colors, when shown, shall be indicated on
run in the highway may be indicated when each feed line. On a feed line that represents two
necessary with an inclined or curved line; see or more wires, each of a different color, the colors
Figure 16. Crossovers of inclined or curved shall be indicated in the same order in which the
portions of feed lines shall be avoided. destination location numbers appear on the feed
line.
When wire data is shown on feed lines, it
shall include wire destination (item reference The Interrupted Line method shall only be used
designation, wiring path number, or lead with complex diagrams when the Continuous Line
designation) and if required, also, wire color, type becomes difficult to produce or understand.
code or type. This information may be shown A section of a typical interrupted line connection
adjacent to, or within the feed line. If wire diagram is shown in Figure 17.
data is not specified on feed lines or in
drawing notes, this information shall be 5.2.3.2 Letter Suffixes for Wire Identification.
shown in a separate wire data list. When two or more terminals of one device are to
be connected to terminals of another device with
5.2.2.2.2 Highway Lines. In highway wire of the same color (surface or direct wiring), a
layout, unidentified branching points shall be suffix letter shall be added to the feed line
avoided. More than one highway line may be destination number as a means of differentiating
used to facilitate indication of wire runs or to similarly colored wires.
indicate grouping of particular wires into
cable assemblies. Another use of a separate 5.2.4 Tabular connection Diagram. In the tabular
highway line is to indicate which wires have arrangement of information, connections between
to be segregated for electrical reasons. A devices shall be listed in a FROM-TO type of
drawing note with the aid of a symbol, if tabulation which includes all the information necessary
necessary, shall identify the highways as to identify the connections. A symbolic or pictorial
being part of the same or different cable representation showing the relative location of the
assemblies. devices with or without connecting lines, shall be
referenced on or accompany the tabulation.
5.2.2.2.3 Critical and Segregated Wiring.
Critical wiring shall not be included in a A tabular connection diagram lends itself to factory
highway line, but shall be run separately. production line applications where identical wiring is
When circuit functions are so sensitive as to required for multiple component devices; See Figure
be affected by wire path, direction, or 18.
position, the wiring involved is regarded as
"critical." Critical wiring requirements can 5.3 Interconnection Diagrams. The following section
frequently be covered by drawing notes. contains general information for use in preparation of
Wires which must be segregated for electrical interconnection diagrams. Interconnection diagrams
reasons from other wires, but which are not covered in this standard fall into two classifications. These
otherwise critical, may also be shown classifications are:
separately or run directly from terminal to
terminal. 1. Wiring type, see paragraph 5.3.2
2. Cabling type, see paragraph 5.3.3
5.2.3 Interrupted Line Connection Diagram. Instead
of continuous lines as used in the preceding method, 5.3.1 General Requirements. An interconnection
connecting lines in this type of diagram start at a diagram lends itself to installation of equipment,
symbol and are interrupted a short distance away. assemblies, subassemblies and devices when physically
separated. It may be used as a planning guide for
5.2.3.1 Feed Line Representation. Connections establishing interconnecting cable requirements.
are shown by means of short feed lines from Internal wiring of the equipment, assemblies,
device terminals. A single feed line may represent
more than one wire to a terminal if clarity is not

20
ARI STANDARD 120-97

Figure 16. Highway Feed Line Connection Diagram

21
Figure 17. Interrupted Line Connection Diagram
22
Figure 17. (Continued)
23
ARI STANDARD 120-97

Figure 18. Tabular Connection Diagram

24
ARI STANDARD 120-97

Figure 18. Tabular Connection Diagram (continued)

25
ARI STANDARD 120-97

subassemblies, or devices shall not be shown on 1. The connectors are part of a prefabricated
interconnection diagrams. cable assembly where reference
identification is shown in the
5.3.1.1 Layout. Equipment, assemblies, interconnection information and this
subassemblies and devices shall be represented by supplementary information is available to
rectangles or circles. Their arrangement on the fully identify the connectors at each end
diagram shall provide clarity for the detailed of the cable.
interconnection information. Views shall be 2. The connectors are of only one type
shown as though all connections are in one plane. covered by an explanatory note in the
If the relative location of equipment, assemblies, interconnection information. If cable
subassemblies or devices is not clear, a physical assembly numbers are not referenced nor
location diagram shall accompany or be referenced made available with the interconnection
on the diagram. information, the information provided for
each connector shall include
5.3.1.2 Identification. The equipment, assembly, identification of its accessories together
subassembly or device shall be identified by one or with any special assembly instructions
more of the following: which may be required.

1. Functional title 5.3.1.6.1 Connector Contact Identification.


2. Functional designation or reference Connector contacts shall be identified by one
designation, if assigned or more of the following:
3. Nomenclature or identification number, if
used 1. According to the markings on the
connector, if assigned.
Additional information, such as schematic or 2. According to the markings assigned on
connection diagram identifications may also be the schematic or connection diagram, if
shown. Reference designations shall be in designations have been arbitrarily
accordance with 4.1.8.3. assigned.
3. If no prior assignment exists, according
5.3.1.3 Graphic Symbols. Graphic symbols to an arbitrary system explained in the
shall be in accordance with 4.1.1. On interconnection information.
interconnection diagrams, the symbol for multi-
conductor, shielded cable or coaxial cable, shall be 5.3.1.6.2 Wire Identification. Wire shall be
shown at least once on each path and at additional identified as described in 5.2.1.4. Equivalent
points as needed for clarity. designations printed on the wire may also be
used. On highway and point-to-point
5.3.1.4 Connecting Lines. Connecting lines diagrams, this data shall be shown inserted in
(whether representing wires individually, grouped, a break in the connecting lines, or keyed to a
or cabled) shall be drawn as straight lines running tabular list shown and referenced on the
vertically or horizontally. diagram.

5.3.1.5 Terminals. Terminals may be shown in 5.3.2 Wiring Type Diagrams. The wiring type
symbol form or the symbols may be omitted when interconnection diagram shall show individually, each
the individual connecting lines are terminated at connection to be made between equipment, assemblies,
the device outline. In either case, the terminal subassemblies or devices represented on the diagram.
shall be identified in accordance with 5.1.5. There are three commonly used methods of wiring type
Reference designations, if assigned, shall be interconnection diagrams. These three methods
shown for individual terminals, terminal boards, covered in this section are:
connectors, etc.
1. Point-to-point
5.3.1.6 Connector Identification. Each 2. Highway
connector shall be identified by its reference 3. Interrupted line
designation, if assigned, or by its part number or
an equivalent identification adjacent to its symbol
unless:

26
ARI STANDARD 120-97

5.3 Point-to-Point. Point-to-point 5.3.3.1 Diagrammatic. Each cable shall be


interconnection diagrams shall be prepared in represented by a single line running between the
accordance with 5.2.2.1. Each connecting line equipment assemblies, subassemblies, or devices
shall be identified and may include an explanatory connected by the cable. Connectors, terminal
note describing the destination of the wire and the boards, etc., shall be represented by the single-line
circuit function of the connection, if applicable. form of graphic symbols. Identification of
These identifications shall be placed in breaks in individual terminals of a connector, terminal board
the connecting line. See Figure 19. or other devices are usually omitted. See Figure
22.
5.3.2.2 Highway. Highway interconnection
diagrams shall be prepared in accordance with 5.3.3.2 Tabular. Each cable shall be represented by
5.2.2.2. See Figure 20. one or more lines of data in a list. The connection data
for the individual wires of the cable are normally not
5.3.2.3 Interrupted Line. Interrupted included as this tabular list is primarily a summary of
interconnection line diagrams shall be prepared in interconnection cables. See Figure 23.
accordance with 5.2.3. See Figure 21.

5.3.3 Cabling Type Diagrams. The cabling type Section 6. Voluntary Conformance
interconnection diagram shall show that the cable is to
be run between the equipment, assemblies, 6.1 Conformance. While conformance with this Standard
subassemblies or devices. There are two commonly is voluntary, conformance shall not be claimed or implied
used methods of cabling type interconnection diagrams. for electrical/electronic diagrams within its Purpose (Section
These methods covered in this section are: 1) and Scope (Section 2) unless such claims meet all of the
requirements of the Standard.
1. Diagrammatic
2. Tabular

27
ARI STANDARD 120-97

Figure 19. Point To Point Interconnection Diagram

28
ARI STANDARD 120-97

Figure 20. Highway Interconnection Diagram

29
ARI STANDARD 120-97

Figure 21. Interrupted Line Interconnection Diagram

30
ARI STANDARD 120-97

Figure 22. Diagrammatic Cabling Interconnection Diagram

REF CABLE ORIGIN DESTINATION


DSGN PART NO CONN FROM CONN TO REMARKS

W1 123456 1J1 2J1


W2 123457 1J2 W3P1
W3 123458 W2P2 3J1

Figure 23. Tabular Cabling Interconnection Diagram

31
ARI STANDARD 120-97

APPENDIX A. REFERENCES - NORMATIVE


A1 Listed here are all standards, handbooks and other A1.5 ANSI/IEEE Standard 315-1975 (R1994),
publications essential to the formation and implementation Graphic Symbols for Electrical and Electronics
of the standards. All references in this appendix are Diagrams, 1994, 11 West 42nd Street, New York, NY
considered as part of the standard. 10036, U.S.A/345 East 47th Street, New York, NY
10017, U.S.A
A1.1 ANSI Standard Y14.15-1966 (R1988),
Electrical and Electronics Diagrams, 1988, American A1.6 ANSI/IEEE Standard 315A-1986 (R1994),
National Standards Institute, 11 West 42nd Street, New Graphical Symbols for Electrical and Electronics
York, NY 10036, U.S.A. Diagrams, 1994, Institute of Electrical and Electronics
Engineers, 11 West 42nd Street, New York, NY 10036,
A1.2 ANSI Standard Y14.15a-1971 (R1988), U.S.A/345 East 47th Street, New York, NY 10017,
Electrical and Electronics Diagrams (supplement to U.S.A
ANSI Y-14.15-1966, 1988, American National
Standards Institute, 11 West 42nd Street, New York, A1.7 ARI Standard 130-88, Graphic
NY 10036, U.S.A. Electrical/Electronic Symbols for Air-Conditioning and
Refrigerating Equipment, 1988, Air-Conditioning and
A1.3 ANSI Standard Y14.15b-1973 (R1988), Refrigeration Institute, 4301 North Fairfax Drive, Suite
Electrical and Electronics Diagrams (supplement to 425, Arlington, VA 22203, U.S.A.
ANSI Y14.15-1966 and ANSI Y14.15a-1971), 1988,
American National Standards Institute, 11 West 42nd A1.8 ASHRAE Terminology of Heating,
Street, New York, NY 10036, U.S.A. Ventilation, Air Conditioning and Refrigeration,
American Society of Heating, Refrigerating and Air-
A1.4 ANSI/ASME Standard Y1.1-1989, Conditioning Engineers, Inc., 1791 Tullie Circle N.E.,
Abbreviations for Use on Drawings and in Text, 1989, Atlanta, GA 30329, U.S.A.
American National Standards Institute/American
Society of Mechanical Engineers, 11 West 42nd Street,
New York, NY 10036, U.S.A/345 East 47th Street,
New York, NY 10017, U.S.A

APPENDIX B. REFERENCES - INFORMATIVE


None.

32

You might also like