Design of a Double Pipe Heat Exchanger

http://excelcalculations.blogspot.com
Instructions
1) Define your Parameters (blue cells). Provide initial guesses for the parameter you will change in step 2 (i.e. mass flowrates)
2) Use Goal Seek to set value in Heat Balance to 0 by varying a parameter (e.g. flowrates)
Notes
Hot fluid is on the shell side, cold fluid is on the tube side
The log mean temperature difference is set up for cocurrent flow (but can be eaily modified for countercurrent flow)

PARAMETERS
Inside Pipe Thermal Conductivity kp 40 W m-1K-1
Hot Fluid Cold Fluid
Inlet Temperature Tin 120 9C
Outlet Temperature Tout 85 35 C
Thermal Conductivity k 0.7 0.78 W m-1K-1
Specific Heat Capacity Cp 4100 4070 J kg-1 K-1
Viscosity m 0.0003 0.0008 Pa s
Density rho 970 1000 kg m-3
Mass Flow Rate m 1.0323902 1.4 kg s-1
Inside Diameter di 0.07 0.0508 m
Outside Diameter do 0.08 0.054 m
Pressure Loss Coefficient Kp 1.23 1.23

CALCULATIONS Hot Fluid Cold Fluid


Heat Transfer Q 148148 148148 W
Prandtl Number Pr 1.7571429 4.174359
Flow Area A 0.0015582 0.0020268 m2
Hydraulic Diameter Dh 0.016 0.0508 m
Heat Transfer Surface Area As 1.024752 0.964026 m2
Fluid Velocity V0.6830313 0.6907338 m s-1
Reynolds Number Re35335.486 43861.598
Friction Factor f0.0056816 0.0054
Nusselt Number Nu124.30647 227.75927
Heat Transfer Coefficient h 5438.4082 3497.0912 W m-2K-1
Pressure Drop DP 2776.2941 1492.9846 Pa

HEAT EXCHANGER DESIGN CALCULATIONS


Length L 6.0405315 m
Log Mean Temp Diff (cocurrent) DTLMTD 76.488338 C
Overall Heat Transfer Coefficient UA 1936.8704 W K-1
Heat Transfer Qoverall 148148 W