Professional Documents
Culture Documents
CSS 1250kva & 800kva
CSS 1250kva & 800kva
3.0 Interconnection
3.1
Interconnection between HT section &Transformer through Al. Ar. XLPE 95 Having 0.8A
1
Sq.mm Cable, Transformer & LT Section through Al. Busbar of 2000 Amp Current density
Capacity
4.0 CSS ENCLOSURE
RITTAL /TATA
CSS Enclosure Made out of GI sheet complete with standard fittings and suitable for
outdoor installation with our innovative ' COMPLETE WITH EXHAUST FAN,
1
THERMOSTAT, INTERNAL , 2mm CRCA for Doors Min 1.6 mm for Canopy 3.2
mm with necessary rain water slope
A
PSS Incoming (Transformer Incomer) Make RATING Qty.
1 BSSCPL Approved
EDO type air circuit breaker complete with microprocessor based with O/C, S/C & 2000A, FP,50KA 1
E/F Protection With TNC
2 BSSCPL Approved
Auxiliary Contact for Breaker Status – Dry Type – ON/OFF/Trip 24V DC 1
8 BSSCPL Approved
Red, Yellow, and blue phase indication LED -230VAC 230 VAC 1
9 BSSCPL Approved
Control MCB 6A, SP,10KA C CURVE 8
10 BSSCPL Approved
Red and green indication LED - 230V AC 230 VAC 1
Note – We need Aluminum Busbar arrangement (2500 Amp, with 0.8 Current density) in LT side for terminating 18 runs of 4C X 400 sqmm cables.So
LT panels to be constructed accordingly with proper bending radius and ecessary clearances for termination(as per standard)
1000 KVA COMPACT SUBSTATION - BILL OF MATERIAL
3.0 Interconnection
3.1
Interconnection between HT section &Transformer through Al. Ar. XLPE 95 Having 0.8Sq mm Current
1
Sq.mm Cable, Transformer & LT Section through Al. Busbar of 1600 Amp density
Capacity
A
PSS Incoming (Transformer Incomer) Make RATING Qty.
1 BSSCPL Approved
EDO type air circuit breaker complete with microprocessor based with O/C, S/C & 1600A, FP,50KA 1
E/F Protection With TNC
2 BSSCPL Approved
Auxiliary Contact for Breaker Status – Dry Type – ON/OFF/Trip 24V DC 1
8 BSSCPL Approved
Red, Yellow, and blue phase indication LED -230VAC 230 VAC 1
9 BSSCPL Approved
Control MCB 6A, SP,10KA C CURVE 8
10 BSSCPL Approved
Red and green indication LED - 230V AC 230 VAC 1
Note – We need Aluminum Busbar arrangement (2500 Amp, with 0.8 Current density) in LT side for terminating 16 runs of 4C X 400 sqmm cables. So
LT panels to be constructed accordingly with proper bending radius and ecessary clearances for termination(as per standard)
800 KVA COMPACT SUBSTATION - BILL OF MATERIAL
3.0 Interconnection
3.1
Interconnection between HT section &Transformer through Al. Ar. XLPE 95 Sq.mm Having 0.8Sq mm Current
1
Cable, Transformer & LT Section through Al. Busbar of 1600 Amp Capacity density
A
PSS Incoming (Transformer Incomer) Make RATING Qty.
1 BSSCPL Approved
EDO type air circuit breaker complete with microprocessor based with O/C, S/C & 1250A, FP,50KA 1
E/F Protection With TNC
2 BSSCPL Approved
Auxiliary Contact for Breaker Status – Dry Type – ON/OFF/Trip 24V DC 1
9 BSSCPL Approved
Red, Yellow, and blue phase indication LED -230VAC 230 VAC 1
10 BSSCPL Approved
Control MCB 6A, SP,10KA C CURVE 8
11 BSSCPL Approved
Red and green indication LED - 230V AC 230 VAC 1
Note – We need Aluminum Busbar arrangement (2500 Amp, with 0.8 Current density) in LT side for terminating 16 runs of 4C X 400 sqmm cables. So
LT panels to be constructed accordingly with proper bending radius and ecessary clearances for termination(as per standard)