1250 KVA COMPACT SUBSTATION - BILL OF MATERIAL

Sl. Item Name Rating Make Qty


1250 KVA Compact Substation
1.0 HT Section – IP54
Sl No. Description Make
A MOVING PORTION :
11KV, 800A draw out 26.3 KA STC for 3 Sec, IAC 0.1 Sec VCB Panel BSSCPL Approved
Horizontal Draw out type. Circuit Breaker complete with motor & electrically
1 operated 230V AC spring charged, trip free type VCB with electrical as well as 1
mechanical ON/OFF indication in service position, 110V DC Shunt trip &
110V DC Closing coil with inbuilt antipumping protection
2 TP Copper Busbar Links suitable for Bottom Cable Entry of 1/C Cables BSSCPL Approved 1
B CT DETAILS
Single phase cast resin, Dual core 11KV CT
1 BSSCPL 3
CORE I : Class-0.5s, CORE II : Class 5P10, 15VA 80/5-5A Approved
PT DETAILS
PT Cast resin 11KV / √3 : 110 / √3 Volt, class 0.5, 50 VA, Fixed Type 3 BSSCPL Approved
2 1
Phase
3 11KV HV Fuses 3.15A BSSCPL Approved 3
C BREAKER PANEL INDICATION LAMPS
1 Breaker ON 110V DC RED BSSCPL Approved 1
2 Breaker OFF 110V DC GREEN BSSCPL Approved 1
3 Breaker TRIP 110V DC AMBER BSSCPL Approved 1
4 Three phase Indication 110V AC RED/YELLOW/BLUE BSSCPL Approved 3
5 Trip Circuit Healthy 110V DC WHITE BSSCPL Approved 1
6 Spring Charge 110V DC BLUE BSSCPL Approved 1
7 DC Supply ON 110V DC RED BSSCPL Approved 1
D SWITCHES AND OTHER ACCESSORIES :
1 10A DP MCB (DC Application) BSSCPL Approved 2
2 6A DP MCB (C-Curve) BSSCPL Approved 1
3 16A DP MCB (C-Curve) BSSCPL Approved 1
4 10A DP MCB (C-Curve) BSSCPL Approved 2
5 230V AC CFL with Holder BSSCPL Approved 1
6 15A, 230V, 3 Pin Plug & Socket BSSCPL Approved 1
7 16A TNC Switch BSSCPL Approved 1
8 6A Local/Remote Selector Switch BSSCPL Approved 1
9 7AH DC Power Pack for Battery Bank Selector Switch (110VAC – 24VDC) BSSCPL Approved 1
10 Emergency Stop Push Button BSSCPL Approved 1
11 Space Heater with Thermostat BSSCPL Approved 1
12 110V DC Aux Contactors 2NO+2NC BSSCPL Approved 2
13 110V DC hooter BSSCPL Approved 1
14 110V DC Power Pack 7Ah BSSCPL Approved 1
15 16 Window Annunciator BSSCPL Approved 1
16 Fuses & Control MCBs BSSCPL Approved As per design
E METERS :
1 Digital Ammeter ASS CL-0.5 BSSCPL Approved 1
2 Digital Voltmeter VSS CL-0.5 BSSCPL Approved 1
3 Digital Multifunction Meter CL-0.5s with RS485 BSSCPL Approved 1
4 Digital WTI , OTI Indicator with Rs485
F RELAYS :
1 110V DC 3 O/C & 1E/F IDMT Relay (50,50N,51,51N) with RS485 BSSCPL Approved 1
2 Master Trip Relay BSSCPL Approved 1
3 Trip Circuit Supervision Relay BSSCPL Approved 1
4 Auxiliary Relay – (Bucholtz , OSR , PRV – Alarm & Trip) BSSCPL Approved 1
4 Wiring & LV Box BSSCPL Approved 1
5 Trip Supervision Relay BSSCPL Approved
6 Back Side Box TTB and Short link arrangement BSSCPL Approved 1
2.0 Transformer Section - IP34
2.1 BIS Approved and
1250KVA 11kV/.433 KV Copper Wound ONAN Oil Type Transformer with On Design to be Type
Load Tap Changer +5% to -15% insteps 1.25% Complete with all accessories as Tested 1
per BIS 1180 Level -2 with NCT of 0.2S class of 2000 Amp

3.0 Interconnection
3.1
Interconnection between HT section &Transformer through Al. Ar. XLPE 95 Having 0.8A
1
Sq.mm Cable, Transformer & LT Section through Al. Busbar of 2000 Amp Current density
Capacity
4.0 CSS ENCLOSURE
RITTAL /TATA
CSS Enclosure Made out of GI sheet complete with standard fittings and suitable for
outdoor installation with our innovative ' COMPLETE WITH EXHAUST FAN,
1
THERMOSTAT, INTERNAL , 2mm CRCA for Doors Min 1.6 mm for Canopy 3.2
mm with necessary rain water slope

ILLUMINATION, DOOR LIMIT SWITCHES ETC"

(Internal ARC Test approved)


5.0 LT SECTION -IP 54

A
PSS Incoming (Transformer Incomer) Make RATING Qty.
1 BSSCPL Approved
EDO type air circuit breaker complete with microprocessor based with O/C, S/C & 2000A, FP,50KA 1
E/F Protection With TNC
2 BSSCPL Approved
Auxiliary Contact for Breaker Status – Dry Type – ON/OFF/Trip 24V DC 1

3 BSSCPL Approved CTR-/5A 2


Digital multimeter CTR-2000/5A CL-0.5S, Nominal Voltage -415V AC
4 BSSCPL Approved
Current transformer resin cast 2000/5A, CL-1,15VA 3
5 BSSCPL Approved 2000/5A, CL-5P10,15VA
Current transformer resin cast for 64R 1
6 BSSCPL Approved 230 VAC 1
Red, Yellow, and blue phase indication LED -230VAC
7 BSSCPL Approved 230 VAC 1
Red and green indication LED - 230V AC
8 BSSCPL Approved MRP11,230VAC 1
Reverse power relay Auxiliary supply -230V AC, CTR-2000/5A
9 BSSCPL Approved 4NO+1NC 1
Emergency stop push button
10 BSSCPL Approved
Surge protection device (SPD) Type 1+2, 40 KA TYPE1+2 1
11 BSSCPL Approved VSPD2,2C/O 1
Voltage monitoring relay (27/59) 415V AC
12 BSSCPL Approved S2VMR2,2C/O 1
Negative phase sequence relay (46)
13 BSSCPL Approved 2NO+2NC,24VDC 3
Auxiliary contactor
14 BSSCPL Approved 230 VAC/24V DC 1
Power Loss relay with Timer for Automatic on Feature
15 BSSCPL Approved 230 VAC/24V DC 1
Redistricted Earth Fault Relay (64R)
16 BSSCPL Approved 230 VAC/24V DC 1
Mini PLC for Maximum Demand control
17 BSSCPL Approved 230 VAC/24V DC 1
Digital Multifunction Meter 0.5s Class accuracy with RS485 for PLC
18 BSSCPL Approved 230 VAC/24V DC 1
Digital Multifunction Meter 0.5s Class accuracy with RS485 for Incomer
19 BSSCPL Approved 230 VAC/24V DC 1
Hooter
20 BSSCPL Approved 230 VAC/24V DC 1
Reset and accept push button
21 BSSCPL Approved 230 VAC/24V DC 1
UPS 1 KVA With 30 Minute backup
22 BSSCPL Approved
Control MCB 6A, SP,10KA C CURVE 8
23 BSSCPL Approved
PT 100 Bus bar temperature Monitoring device with 3 meter temperature witre Temp sensor 4
24 BSSCPL Approved
Digital Temperature Scanner with Temperature to Rs485 converter & hooter linked Temp Scanner 1

PSS Outgoing Make RATING Qty.


1 BSSCPL Approved
EDO type air circuit breaker complete with microprocessor based with O/C, S/C & 1000A, FP,50KA 3
E/F Protection With TNC
2 BSSCPL Approved
Auxiliary Contact for Breaker Status – Dry Type – ON/OFF/Trip 24V DC 1
3 BSSCPL Approved
Control MCB 6A, SP,10KA C CURVE 8
4 BSSCPL Approved
Red, Yellow, and blue phase indication LED -230VAC 230 VAC 1
5 BSSCPL Approved
Red and green indication LED - 230V AC 230 VAC 1
6 BSSCPL Approved
LSING MCCB complete with microprocessor based with Rotary handle and 800A, FP,50KA 2
Spreader links with extended Bus bar support
7 BSSCPL Approved
Auxiliary Contact for Breaker Status – Dry Type – ON/OFF/Trip 24V DC 1

8 BSSCPL Approved
Red, Yellow, and blue phase indication LED -230VAC 230 VAC 1
9 BSSCPL Approved
Control MCB 6A, SP,10KA C CURVE 8
10 BSSCPL Approved
Red and green indication LED - 230V AC 230 VAC 1
Note – We need Aluminum Busbar arrangement (2500 Amp, with 0.8 Current density) in LT side for terminating 18 runs of 4C X 400 sqmm cables.So
LT panels to be constructed accordingly with proper bending radius and ecessary clearances for termination(as per standard)
1000 KVA COMPACT SUBSTATION - BILL OF MATERIAL

Sl. Item Name Rating Make Qty


1000 KVA Compact Substation
1.0 HT Section – IP54
Sl No. Description Make
A MOVING PORTION :
11KV, 800A draw out 26.3 KA STC for 3 Sec, IAC 0.1 Sec VCB Panel BSSCPL Approved
Horizontal Draw out type. Circuit Breaker complete with motor & electrically
1 operated 230V AC spring charged, trip free type VCB with electrical as well as 1
mechanical ON/OFF indication in service position, 110V DC Shunt trip &
110V DC Closing coil with inbuilt antipumping protection
2 TP Copper Busbar Links suitable for Bottom Cable Entry of 1/C Cables BSSCPL Approved 1
B CT DETAILS
Single phase cast resin, Dual core 11KV CT
1 BSSCPL 3
CORE I : Class-0.5s, CORE II : Class 5P10, 15VA 60/5-5A Approved
PT DETAILS
PT Cast resin 11KV / √3 : 110 / √3 Volt, class 0.5, 50 VA, Fixed Type 3 BSSCPL Approved
2 1
Phase
3 11KV HV Fuses 3.15A BSSCPL Approved 3
C BREAKER PANEL INDICATION LAMPS
1 Breaker ON 110V DC RED BSSCPL Approved 1
2 Breaker OFF 110V DC GREEN BSSCPL Approved 1
3 Breaker TRIP 110V DC AMBER BSSCPL Approved 1
4 Three phase Indication 110V AC RED/YELLOW/BLUE BSSCPL Approved 3
5 Trip Circuit Healthy 110V DC WHITE BSSCPL Approved 1
6 Spring Charge 110V DC BLUE BSSCPL Approved 1
7 DC Supply ON 110V DC RED BSSCPL Approved 1
D SWITCHES AND OTHER ACCESSORIES :
1 10A DP MCB (DC Application) BSSCPL Approved 2
2 6A DP MCB (C-Curve) BSSCPL Approved 1
3 16A DP MCB (C-Curve) BSSCPL Approved 1
4 10A DP MCB (C-Curve) BSSCPL Approved 2
5 230V AC CFL with Holder BSSCPL Approved 1
6 15A, 230V, 3 Pin Plug & Socket BSSCPL Approved 1
7 16A TNC Switch BSSCPL Approved 1
8 6A Local/Remote Selector Switch BSSCPL Approved 1
9 7AH DC Power Pack for Battery Bank Selector Switch (110VAC – 24VDC) BSSCPL Approved 1
10 Emergency Stop Push Button BSSCPL Approved 1
11 Space Heater with Thermostat BSSCPL Approved 1
12 110V DC Aux Contactors 2NO+2NC BSSCPL Approved 2
13 110V DC hooter BSSCPL Approved 1
14 110V DC Power Pack 7Ah BSSCPL Approved 1
15 16 Window Annunciator BSSCPL Approved 1
16 Fuses & Control MCBs BSSCPL Approved As per design
E METERS :
1 Digital Ammeter ASS CL-0.5 BSSCPL Approved 1
2 Digital Voltmeter VSS CL-0.5 BSSCPL Approved 1
3 Digital Multifunction Meter CL-0.5s with RS485 BSSCPL Approved 1
4 Digital WTI , OTI Indicator with Rs485
F RELAYS :
1 110V DC 3 O/C & 1E/F IDMT Relay (50,50N,51,51N) with RS485 BSSCPL Approved 1
2 Master Trip Relay BSSCPL Approved 1
3 Trip Circuit Supervision Relay BSSCPL Approved 1
4 Auxiliary Relay – (Bucholtz , OSR , PRV – Alarm & Trip) BSSCPL Approved 1
4 Wiring & LV Box BSSCPL Approved 1
5 Trip Supervision Relay BSSCPL Approved
6 Back Side Box TTB and Short link arrangement BSSCPL Approved 1
2.0 Transformer Section - IP34
2.1 BIS Approved and Design to
1000KVA 11kV/.433 KV Copper Wound ONAN Oil Type Transformer with On be Type Tested
Load Tap Changer +5% to -15% insteps 1.25% Complete with all accessories as 1
per BIS 1180 Level -2 with NCT of 0.2S class of 2000 Amp

3.0 Interconnection
3.1
Interconnection between HT section &Transformer through Al. Ar. XLPE 95 Having 0.8Sq mm Current
1
Sq.mm Cable, Transformer & LT Section through Al. Busbar of 1600 Amp density
Capacity

4.0 CSS ENCLOSURE


RITTAL /TATA
CSS Enclosure Made out of GI sheet complete with standard fittings and suitable for
outdoor installation with our innovative ' COMPLETE WITH EXHAUST FAN,
1
THERMOSTAT, INTERNAL , 2mm CRCA for Doors Min 1.6 mm for Canopy 3.2
mm with necessary rain water slope

ILLUMINATION, DOOR LIMIT SWITCHES ETC"

(Internal ARC Test approved)


5.0 LT SECTION -IP 54

A
PSS Incoming (Transformer Incomer) Make RATING Qty.
1 BSSCPL Approved
EDO type air circuit breaker complete with microprocessor based with O/C, S/C & 1600A, FP,50KA 1
E/F Protection With TNC
2 BSSCPL Approved
Auxiliary Contact for Breaker Status – Dry Type – ON/OFF/Trip 24V DC 1

3 BSSCPL Approved CTR-/5A 2


Digital multimeter CTR-2000/5A CL-0.5S, Nominal Voltage -415V AC
4 BSSCPL Approved
Current transformer resin cast 1600/5A, CL-1,15VA 3
5 BSSCPL Approved 1600/5A, CL-5P10,15VA
Current transformer resin cast for 64R 1
6 BSSCPL Approved 230 VAC 1
Red, Yellow, and blue phase indication LED -230VAC
7 BSSCPL Approved 230 VAC 1
Red and green indication LED - 230V AC
8 BSSCPL Approved MRP11,230VAC 1
Reverse power relay Auxiliary supply -230V AC, CTR-2000/5A
9 BSSCPL Approved 4NO+1NC 1
Emergency stop push button
10 BSSCPL Approved
Surge protection device (SPD) Type 1+2, 40 KA TYPE1+2 1
11 BSSCPL Approved VSPD2,2C/O 1
Voltage monitoring relay (27/59) 415V AC
12 BSSCPL Approved S2VMR2,2C/O 1
Negative phase sequence relay (46)
13 BSSCPL Approved 2NO+2NC,24VDC 3
Auxiliary contactor
14 BSSCPL Approved 230 VAC/24V DC 1
Power Loss relay with Timer for Automatic on Feature
15 BSSCPL Approved 230 VAC/24V DC 1
Redistricted Earth Fault Relay (64R)
16 BSSCPL Approved 230 VAC/24V DC 1
Mini PLC for Maximum Demand control
17 BSSCPL Approved 230 VAC/24V DC 1
Digital Multifunction Meter 0.5s Class accuracy with RS485 for PLC
18 BSSCPL Approved 230 VAC/24V DC 1
Digital Multifunction Meter 0.5s Class accuracy with RS485 for Incomer
19 BSSCPL Approved 230 VAC/24V DC 1
Hooter
20 BSSCPL Approved 230 VAC/24V DC 1
Reset and accept push button
21 BSSCPL Approved 230 VAC/24V DC 1
UPS 1 KVA With 30 Minute backup
22 BSSCPL Approved
Control MCB 6A, SP,10KA C CURVE 8
23 BSSCPL Approved
PT 100 Bus bar temperature Monitoring device with 3 meter temperature witre Temp sensor 4
24 BSSCPL Approved
Digital Temperature Scanner with Temperature to Rs485 converter & hooter linked Temp Scanner 1

PSS Outgoing Make RATING Qty.


1 BSSCPL Approved
EDO type air circuit breaker complete with microprocessor based with O/C, S/C & 1000A, FP,50KA 2
E/F Protection With TNC
2 BSSCPL Approved
Auxiliary Contact for Breaker Status – Dry Type – ON/OFF/Trip 24V DC 1
3 BSSCPL Approved
Control MCB 6A, SP,10KA C CURVE 8
4 BSSCPL Approved
Red, Yellow, and blue phase indication LED -230VAC 230 VAC 1
5 BSSCPL Approved
Red and green indication LED - 230V AC 230 VAC 1
6 BSSCPL Approved
LSING MCCB complete with microprocessor based with Rotary handle and 800A, FP,50KA 3
Spreader links with extended Bus bar support
7 BSSCPL Approved
Auxiliary Contact for Breaker Status – Dry Type – ON/OFF/Trip 24V DC 1

8 BSSCPL Approved
Red, Yellow, and blue phase indication LED -230VAC 230 VAC 1
9 BSSCPL Approved
Control MCB 6A, SP,10KA C CURVE 8
10 BSSCPL Approved
Red and green indication LED - 230V AC 230 VAC 1

Note – We need Aluminum Busbar arrangement (2500 Amp, with 0.8 Current density) in LT side for terminating 16 runs of 4C X 400 sqmm cables. So
LT panels to be constructed accordingly with proper bending radius and ecessary clearances for termination(as per standard)
800 KVA COMPACT SUBSTATION - BILL OF MATERIAL

Sl. Item Name Rating Make Qty


800 KVA Compact Substation
1.0 HT Section – IP54
Sl No. Description Make
A MOVING PORTION :
11KV, 800A draw out 26.3 KA STC for 3 Sec, IAC 0.1 Sec VCB Panel BSSCPL Approved
Horizontal Draw out type. Circuit Breaker complete with motor & electrically
1 operated 230V AC spring charged, trip free type VCB with electrical as well as 1
mechanical ON/OFF indication in service position, 110V DC Shunt trip &
110V DC Closing coil with inbuilt antipumping protection
2 TP Copper Busbar Links suitable for Bottom Cable Entry of 1/C Cables BSSCPL Approved 1
B CT DETAILS
Single phase cast resin, Dual core 11KV CT
1 BSSCPL 3
CORE I : Class-0.5s, CORE II : Class 5P10, 15VA 40/5-5A Approved
PT DETAILS
PT Cast resin 11KV / √3 : 110 / √3 Volt, class 0.5, 50 VA, Fixed Type 3 BSSCPL Approved
2 1
Phase
3 11KV HV Fuses 3.15A BSSCPL Approved 3
C BREAKER PANEL INDICATION LAMPS
1 Breaker ON 110V DC RED BSSCPL Approved 1
2 Breaker OFF 110V DC GREEN BSSCPL Approved 1
3 Breaker TRIP 110V DC AMBER BSSCPL Approved 1
4 Three phase Indication 110V AC RED/YELLOW/BLUE BSSCPL Approved 3
5 Trip Circuit Healthy 110V DC WHITE BSSCPL Approved 1
6 Spring Charge 110V DC BLUE BSSCPL Approved 1
7 DC Supply ON 110V DC RED BSSCPL Approved 1
D SWITCHES AND OTHER ACCESSORIES :
1 10A DP MCB (DC Application) BSSCPL Approved 2
2 6A DP MCB (C-Curve) BSSCPL Approved 1
3 16A DP MCB (C-Curve) BSSCPL Approved 1
4 10A DP MCB (C-Curve) BSSCPL Approved 2
5 230V AC CFL with Holder BSSCPL Approved 1
6 15A, 230V, 3 Pin Plug & Socket BSSCPL Approved 1
7 16A TNC Switch BSSCPL Approved 1
8 6A Local/Remote Selector Switch BSSCPL Approved 1
9 7AH DC Power Pack for Battery Bank Selector Switch (110VAC – 24VDC) BSSCPL Approved 1
10 Emergency Stop Push Button BSSCPL Approved 1
11 Space Heater with Thermostat BSSCPL Approved 1
12 110V DC Aux Contactors 2NO+2NC BSSCPL Approved 2
13 110V DC hooter BSSCPL Approved 1
14 110V DC Power Pack 7Ah BSSCPL Approved 1
15 16 Window Annunciator BSSCPL Approved 1
16 Fuses & Control MCBs BSSCPL Approved As per design
E METERS :
1 Digital Ammeter ASS CL-0.5 BSSCPL Approved 1
2 Digital Voltmeter VSS CL-0.5 BSSCPL Approved 1
3 Digital Multifunction Meter CL-0.5s with RS485 BSSCPL Approved 1
4 Digital WTI , OTI Indicator with Rs485
F RELAYS :
1 110V DC 3 O/C & 1E/F IDMT Relay (50,50N,51,51N) with RS485 BSSCPL Approved 1
2 Master Trip Relay BSSCPL Approved 1
3 Trip Circuit Supervision Relay BSSCPL Approved 1
4 Auxiliary Relay – (Bucholtz , OSR , PRV – Alarm & Trip) BSSCPL Approved 1
4 Wiring & LV Box BSSCPL Approved 1
5 Trip Supervision Relay BSSCPL Approved
6 Back Side Box TTB and Short link arrangement BSSCPL Approved 1
TOTAL A 1
2.0 Transformer Section - IP34
2.1 BIS Approved and Design to
800KVA 11kV/.433 KV Copper Wound ONAN Oil Type Transformer with On be Type Tested
Load Tap Changer +5% to -15% insteps 1.25% Complete with all accessories as 1
per BIS 1180 Level -2 with NCT of 0.2S class of 2000 Amp

3.0 Interconnection
3.1
Interconnection between HT section &Transformer through Al. Ar. XLPE 95 Sq.mm Having 0.8Sq mm Current
1
Cable, Transformer & LT Section through Al. Busbar of 1600 Amp Capacity density

4.0 CSS ENCLOSURE


RITTAL /TATA
CSS Enclosure Made out of GI sheet complete with standard fittings and suitable for
outdoor installation with our innovative ' COMPLETE WITH EXHAUST FAN,
1
THERMOSTAT, INTERNAL , 2mm CRCA for Doors Min 1.6 mm for Canopy 3.2
mm with necessary rain water slope

ILLUMINATION, DOOR LIMIT SWITCHES ETC"

(Internal ARC Test approved)


5.0 LT SECTION -IP 54

A
PSS Incoming (Transformer Incomer) Make RATING Qty.
1 BSSCPL Approved
EDO type air circuit breaker complete with microprocessor based with O/C, S/C & 1250A, FP,50KA 1
E/F Protection With TNC
2 BSSCPL Approved
Auxiliary Contact for Breaker Status – Dry Type – ON/OFF/Trip 24V DC 1

3 BSSCPL Approved CTR-/5A 2


Digital multimeter CTR-2000/5A CL-0.5S, Nominal Voltage -415V AC
4 BSSCPL Approved
Current transformer resin cast 1200/5A, CL-1,15VA 3
5 BSSCPL Approved 1200/5A, CL-5P10,15VA
Current transformer resin cast for 64R 1
6 BSSCPL Approved 230 VAC 1
Red, Yellow, and blue phase indication LED -230VAC
7 BSSCPL Approved 230 VAC 1
Red and green indication LED - 230V AC
8 BSSCPL Approved MRP11,230VAC 1
Reverse power relay Auxiliary supply -230V AC, CTR-2000/5A
9 BSSCPL Approved 4NO+1NC 1
Emergency stop push button
10 BSSCPL Approved
Surge protection device (SPD) Type 1+2, 40 KA TYPE1+2 1
11 BSSCPL Approved VSPD2,2C/O 1
Voltage monitoring relay (27/59) 415V AC
12 BSSCPL Approved S2VMR2,2C/O 1
Negative phase sequence relay (46)
13 BSSCPL Approved 2NO+2NC,24VDC 3
Auxiliary contactor
14 BSSCPL Approved 230 VAC/24V DC 1
Power Loss relay with Timer for Automatic on Feature
15 BSSCPL Approved 230 VAC/24V DC 1
Redistricted Earth Fault Relay (64R)
16 BSSCPL Approved 230 VAC/24V DC 1
Mini PLC for Maximum Demand control
17 BSSCPL Approved 230 VAC/24V DC 1
Digital Multifunction Meter 0.5s Class accuracy with RS485 for PLC
18 BSSCPL Approved 230 VAC/24V DC 1
Digital Multifunction Meter 0.5s Class accuracy with RS485 for Incomer
19 BSSCPL Approved 230 VAC/24V DC 1
Hooter
20 BSSCPL Approved 230 VAC/24V DC 1
Reset and accept push button
21 BSSCPL Approved 230 VAC/24V DC 1
UPS 1 KVA With 30 Minute backup
22 BSSCPL Approved
Control MCB 6A, SP,10KA C CURVE 8
23 BSSCPL Approved
PT 100 Bus bar temperature Monitoring device with 3 meter temperature write Temp sensor 4
24 BSSCPL Approved
Digital Temperature Scanner with Temperature to Rs485 converter & hooter linked Temp Scanner 1

PSS Outgoing Make RATING Qty.


1 BSSCPL Approved
EDO type air circuit breaker complete with microprocessor based with O/C, S/C & 1000A, FP,50KA 1
E/F Protection With TNC
2 BSSCPL Approved
Auxiliary Contact for Breaker Status – Dry Type – ON/OFF/Trip 24V DC 1
3 BSSCPL Approved
Control MCB 6A, SP,10KA C CURVE 8
4 BSSCPL Approved
Red, Yellow, and blue phase indication LED -230VAC 230 VAC 1
5 BSSCPL Approved
Red and green indication LED - 230V AC 230 VAC 1
6 BSSCPL Approved
LSING MCCB complete with microprocessor based with Rotary handle and Spreader 800A, FP,50KA 4
links with extended Bus bar support
7 BSSCPL Approved
LSING MCCB complete with microprocessor based with Rotary handle and Spreader 800A, FP,50KA 4
links with extended Bus bar support
8 BSSCPL Approved
Auxiliary Contact for Breaker Status – Dry Type – ON/OFF/Trip 24V DC 1

9 BSSCPL Approved
Red, Yellow, and blue phase indication LED -230VAC 230 VAC 1
10 BSSCPL Approved
Control MCB 6A, SP,10KA C CURVE 8
11 BSSCPL Approved
Red and green indication LED - 230V AC 230 VAC 1

Note – We need Aluminum Busbar arrangement (2500 Amp, with 0.8 Current density) in LT side for terminating 16 runs of 4C X 400 sqmm cables. So
LT panels to be constructed accordingly with proper bending radius and ecessary clearances for termination(as per standard)