Compliance 14.7.2020-EJC - Holy Haram - Service Building BID-807
Compliance 14.7.2020-EJC - Holy Haram - Service Building BID-807
Project: King Abdullah Bin Abdulaziz Project- Holy Haram - Date: 14th July 2020
Service Building BID-807
C. Movement Capability: Value obtained from the difference Movement Capability: Value obtained from the Comply
between widest and narrowest widths of a joint opening difference between maximum opening of the
typically expressed in numerical values (mm or inches) or a profile and minimum opening of the profile. The
percentage (plus or minus) of nominal value of joint width. joint opening typically expressed in numerical
values (mm & inches) of nominal value of joint
width.
D. Nominal Joint Width: The width of the linear opening specified Nominal Joint Width: The width of the linear Comply
in practice and in which the joint system is installed. opening specified in practice and in which the
joint system is installed.
1 Include manufacturer's color charts showing the full range of Noted, CS will provide color charts showing the Comply
colors and finishes available for each exposed metal and full range of colors and finishes available for
elastomeric seal material. each exposed metal and elastomeric seal
material.
E Samples for Verification: For each type of architectural joint Noted Comply
system indicated.
1 Full width by 150 mm long, for each system required. CS will provide sample 150mm long for each Comply
system proposed.
F Warranty: Sample copy of manufacturer's proposed warranty Noted, CS draft warranty enclosed in the Comply
complying with specified requirements, and stating obligations, submittal for reference.
remedies, limitations, and exclusions of warranty.
B Source Limitations: Obtain architectural joint systems through CS is supplying expansion joint covers and fire Comply
one source from a single manufacturer. barrier from single source.
C Product Options: Drawings indicate size, profiles, and CS will provide the section details of the Comply
dimensional requirements of architectural joint systems and proposed model which indicates size, profiles,
are based on the specific systems indicated. Refer to Division and dimensional requirements of architectural
1 Section "Product Requirements." joint systems and are based on the specific
systems indicated.
1. Floor- to-Floor Assemblies: All assemblies are fire rated. Noted Comply
2. Soffit-to-Soffit Assemblies: Where indicated on Drawings or
mandated by applicable fire code.
3. Floor-to-Wall Assemblies: All assemblies are fire rated.
4. Wall-to-Wall Assemblies: Assemblies in fire rated walls are
to be fire rated.
5. Fire resistance rating of joint assembly is to be identical to
fire rating of the construction to which joint assembly will be
installed.
F Fire Barriers: Any material or material combination, when fire Fire Barriers:CS proposed fire barrier when fire Comply
tested after cycling, designated to resist the passage of flame tested after cycling, designated to resist the
and hot gases through a movement joint and to meet passage of flame and hot gases through a
performance criteria for required rating period. movement joint and to meet performance criteria
for required rating period.
1 Provide blanket-type fire barriers. Fire barriers in the form of CS has proposed blanket type fire barrier OFX Comply
joint sealant or intumescent blocks are not acceptable. series.
H Accessories: Manufacturer's standard anchors, clips, CS standard anchors, clips, fasteners, set Comply
fasteners, set screws, spacers, and other accessories screws, spacers, and other accessories
compatible with material in contact, as indicated or required for compatible with material in contact, as indicated
complete installations. or required for complete installations.
2. Include factory-fabricated closure materials and transition CS will provide factory-fabricated closure Comply
pieces, tee-joints, corners, curbs, cross-connections, and other materials and transition pieces, tee-joints,
accessories as required to provide continuous joint systems. corners, curbs, cross-connections, and other
accessories as required to provide continuous
joint systems.
C Floor-to-Wall Joint and Wall to Wall Systems: Shall be from Floor-to-Wall Joint and Wall to Wall Systems: Comply
same manufacturer of Floor-to-Floor assemblies, same series, CS will proposed Floor-to-Floor assemblies,
configuration, movement capability and finish material but same series, configuration, movement capability
fabricated for floor-to-wall joint system. and finish material but fabricated for floor-to-wall
joint system.
5. Fire resistance rating is to be not less than that of adjacent 5. CS proposed fire barrier are 2 Hours fire rated Comply..
construction. 6. Fire Barrier: CS proposed fire barrier are RFX
6. Fire Barrier: As specified before. series or OFX series based on the joint sizes
7. Moisture Barrier: As specified before. 7. Moisture Barrier: As specified before.
8. Movement Capability: ± 50 %. 8. Movement Capability: ± 50 %.
9. Type of Movement: Thermal and seismic. 9. Type of Movement: Thermal and seismic.
10. Opening width: As indicated on Structural Drawings. 10. Opening width: As indicated on Structural
Drawings.
6. The fire-retardant foam ends are coated with a full layer of 6. The fire-retardant foam ends are coated with CS proposal is
intumescent sealant. a full layer of intumescent sealant. based on the
7. Cover plate is (10mm) shot-blasted aluminum. 7. Cover plate is (10mm) shot-blasted aluminum. provided BOQ.
8. Total 100% movement capability: +50% and -50%. 8. Total 100% movement capability: +50% and - Mentioned profiles
9. Fire resistance rating is to be not less than that of adjacent 50%. will be proposed
construction. 9. Fire resistance rating to be 2 Hours. upon request
10. Reference Product: SJS-FR1 as manufactured by Emseal 10. Reference Product: CS proposed model PC-
or other equal and approved product. MOD+VFR series
H Wall-to-Wall Joint Systems: 1. Use: Joints at piazza basement. Wall-to-Wall Joint Systems: Comply
2. Type: Vertical cover plate. 2. Type: Vertical cover plate.
a. Exposed Metal: Aluminum. a. Exposed Metal: Aluminum.
1) Finish: Class II, clear anodic. 1) Finish: Class II, clear anodic.
3. Attachment Method: Mechanical anchors. 3. Attachment Method: Mechanical anchors.
4. Frame Material: Mill finish aluminum. 4. Frame Material: Mill finish aluminum.
L Ceiling-to-Walls Joint Systems: 1. Use: Joints 75 mm wide at Ceiling-to-Ceiling Joint Systems: Comply
suspended acoustical ceiling in expansion building. 2. Type: Accordion.
2. Type: Accordion. a. Seal Material: Dual durometer PVC.
a. Seal Material: Dual durometer PVC. 1) Color: White
1) Color: As selected by Engineer from manufacturer's full 3. Reference Product: CS proposed model HCW
range. series
3. Reference Product: HCW from C/S group or other equal and
approved product
5. Panels held in place with hook and loop attachment system 5. Panels held in place with hook and loop Comply
and incorporate a secondary system comprised of a pre- attachment system and incorporate a secondary
tensioned shock cord. system comprised of a pre-tensioned shock
6. Covers that utilize turnbars or other similar centering devices cord.
limit lateral shear movement and are not acceptable. 6. Covers that utilize turnbars or other similar
7. Reference Product: LAF from C/S group or other equal and centering devices limit lateral shear movement
approved product. and are not acceptable.
7. Reference Product: CS proposed model LAF
series based on the drawing and specification
PART 3 - EXECUTION
3.1 EXAMINATION
C Coordinate and furnish anchorages, setting drawings, and Noted/Included in installation Package
instructions for installing joint systems. Provide fasteners of
metal, type, and size to suit type of construction indicated and
to provide for secure attachment of joint systems.
3.3 INSTALLATION
A Comply with manufacturer's written instructions for storing, Noted CS is the manufacturer
handling, and installing architectural joint assemblies and
materials unless more stringent requirements are indicated.
B Water Barriers: Install water stops so as the installed Noted to be coordinated with slab isolation.
architectural joint assembly is perfectly watertight and shall not
allow leak of water between floors through joint opening:
1. Confirm that no surface water can leak through opening
under sides of water stop fixed to opening sides.
2. Prior to installing remaining parts of each architectural joint
assembly inclusive of a water stop, fluid test the water stop to
insure its water tightness. Submit test procedure to approval of
Engineer.
3.4 PROTECTION
A Do not remove protective covering until finish work in adjacent Noted
areas is complete. When protective covering is removed, clean
exposed metal surfaces to comply with manufacturer's written
instructions.
B Protect the installation from damage by work of other Sections. Noted
Where necessary due to heavy construction traffic, remove
and properly store cover plates or seals and install temporary
protection over joints. Reinstall cover plates or seals prior to
Substantial Completion of the Work.