2.1 Seismic Load
2.1 Seismic Load
Parameters
h = 11.50 m Average roof height of structure
z = 0.000 m Height in structure of point of attachment of component with respect to base (0 if on ground)
site = C Site classification (Table 11)
Spectral Acceleration
As per Civil Design Criteria the following are the acceleration parameters.
SS = 0.400 Spectral response acceleration parameter at short period
S1 = 0.100 Spectral response acceleration parameter at 1 sec period
FP = 0.3SDSIP
= 0.1440 Wp Seismic force lower limit
0.3SDSIP FP 1.6SDSIP
> < Horizontal seismic force factor = 0.144
0.1440 0.1152 0.7680