Professional Documents
Culture Documents
Section 5 RD Handbook Apr2013
Section 5 RD Handbook Apr2013
Section 5 RD Handbook Apr2013
Performance Monitoring
To ensure the scheme continues to provide the expected high levels of performance,
RDL conduct random visual inspections and tests on a proportion of sites registered.
So please remember that your site may be visited by us as well as the Verifier.
This involves submitting details of the construction; and a number of sound tests conducted within
dwellings on real developments. To meet the robust details performance criteria, the mean of the
test results must be at least 5dB better than the Building (Scotland) Regulations minimum.
Contents
Introduction
List of robust details™
• Table 1 – Separating walls
• Table 2 – Separating floors
• Tables 3a, 3b and 3c
– Robust detail™ separating walls and floors which can be
used together in flats/apartments
Robust details™
Separating walls
• Masonry
• Timber
• Steel
Separating floors
• Timber
• Steel-concrete composite
Contents
Appendices
Appendix A1 Additional guidance
Appendix A2 Proprietary flanking constructions
Appendix A3 Specific proprietary products
Appendix B Glossary
Appendix C Determination of the acoustic performance requirements
for floating floor treatments used with RD timber frame
separating floors
Appendix D Determination of the acoustic performance requirements
for floating floor treatments used with RD concrete and
steel-concrete composite separating floors
Appendix E Determination of the acoustic performance requirements
for resilient bars used on ceilings
Appendix F Determination of the acoustic performance of
downlighters and recessed lighting in lightweight
separating floors
Introduction
This handbook produced by Robust Details Ltd Each robust detail™ includes materials and
contains the separating wall and separating floor construction details for the separating wall/floor and
constructions that have achieved the status of its key interfaces with other elements and should be
robust details™ for Section 5. The prescribed read in conjunction with Appendix A.
robust details™ contained herein are applicable to
The final page of each robust detail™ is a checklist,
limiting the transmission of noise only within new
which should be photocopied and used by the site
build domestic buildings within the scope of the
manager/supervisor to confirm that the separating
Building (Scotland) Regulations 2004.
wall/floor has been built correctly. The verifier may
The robust details™ have undergone an extensive ask to see the checklist.
sound insulation testing regime, robust design
It is important that separating walls/floors and their
analysis and independent audit and have satisfied
associated junctions and flanking conditions are
the robust details™ Management Board that they
constructed entirely in accordance with the relevant
should provide a level of sound insulation compliant
robust detail™; otherwise the verifier may require
with Section 5. Only then can they be incorporated
pre-completion testing to be carried out.
within this Robust Details Handbook.
The tables on pages 4, 5 and 6 show which robust
Importantly, the designer and the verifier can be
detail™ separating floors and walls can be used in
confident that when considering approval of a
flats/apartments.
building warrant for new build housing
incorporating robust details™, compliance with
Introduction
Mandatory Standard 5.1 will be achieved.
Note:
It can be safely assumed that the pre-emptive
approval of the building warrant is based on sound The guidance contained in this handbook
evidence and design competence. relates only to Section 5. The building work will
also have to comply with the requirements of
As noted previously, the Building (Scotland) all other relevant parts of the Building (Scotland)
Regulations 2004 recognise that compliance on site Regulations and other relevant legislation.
can only be achieved by having sufficient checks in
place to provide comfort to the designer and verifier Where testing is required on a wall or floor the
that the design proposals have been followed to the user should seek expert acoustic advice prior
letter during the construction and installation phase to construction commencing.
prior to completion and handover. In essence,
buildings containing designed elements of
construction to combat unacceptable levels of Further information on the robust details™ scheme
noise transmission, should be subjected to a post- (including how to apply for new robust details™) is
completion assessment (and test) to confirm their available on the robust details™ web site at:
performance test levels. www.robustdetails.com
The use of robust details™ provides an alternative or from:
to pre-completion testing for demonstrating
compliance with the performance standards of Robust Details Ltd
Section 5 for new build dwellings. Every dwelling Davy Avenue
built using robust details™ needs to be registered Knowlhill
with Robust Details Ltd and a plot registration Milton Keynes
fee paid. MK5 8NB
Telephone: 0870 240 8209 - Technical
0870 240 8210 - General
Fax: 0870 240 8203
™: trade mark
© Robust Details Limited 2011. All rights reserved. No part of this Handbook (other than the checklists) may be reproduced in any material
form or issued or communicated to the public (including photocopying or storing it in any medium by electronic means, and whether or not
transiently or incidentally to some other use of this Handbook) without the prior written permission of Robust Details Limited except in
accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Warning: the doing of an unauthorised act in relation to a copyright work may result in both a civil claim for damages and criminal prosecution.
Introduction
List of Robust Details™
V-WM-11™ masonry – lightweight aggregate blockwork (render and gypsum-based board) with 100mm minimum
cavity
V-WM-14™ masonry – lightweight aggregate blockwork Saint Gobain - Isover RD35 (gypsum-based board) with
100mm minimum cavity
V-WM-19™ masonry – dense or lightweight aggregate blockwork (render and gypsum-based board) with 100mm
minimum cavity and MONARFLOOR® BRIDGESTOP® system
V-WM-20™ masonry – lightweight aggregate blockwork Saint Gobain - Isover RD Party Wall Roll (gypsum-based
board) with 100mm minimum cavity
V-WM-21™ masonry – lightweight aggregate blockwork (wet plaster) with minimum 100mm cavity
V-WT-1™ timber frame – without sheathing board
V-WT-2™ timber frame – with sheathing board
V-WT-3™ timber frame – Elecoframe prefabricated panels
V-WT-4™ timber frame – Excel Industries Warmcell 500 insulation - with sheathing board
Introduction
List of Robust Details™
Introduction
Introduction
Separating floors
Separating walls Separating floors
Separating walls V-FT-1™
V-FT-2™ V-FS-1™
No separating walls are currently approved for use
V-WT-1™ ✔ W see note 1 for flats/apartments in reinforced concrete and
steel frame constructions
V-WT-2™ ✔ W see note 1
See also notes relating to Combining loadbearing masonry and lightweight framed separating walls included on page 6.
Introduction
Introduction
Introduction
V-WM-11™
Lightweight aggregate, or nominated hollow or cellular blocks ■
Render and gypsum-based board on dabs ■
Minimum 100mm cavity ■
Internal floor
Continuous horizontal ribbon of adhesive
Section
4. Internal floor junction: timber floor joists built in, beam and block or
precast concrete
Internal floor
Internal floors should not be continuous
between dwellings
Floor construction:
• timber joists built in with:
– all voids around the joists filled with mortar
– the joint interface between the joist and the
mortar sealed with flexible sealant (see
Appendix A for full specification), or
• beam and block floor with all voids filled with
mortar, or
• concrete planks with all voids between planks
and blockwork filled with mortar or flexible
sealant
6. Ground floor junction: timber floor, beam and block, precast concrete plank, cast
in-situ suspended concrete slab or ground bearing concrete slab
Complete wall face rendered (except in the floor
joist/beam zone where it may be omitted)
Ground floor not continuous between dwellings
Ground floor construction:
• timber joists built in with:
– all voids around the joists filled with mortar
– the joint interface between the joist and the
mortar sealed with flexible sealant (see
Appendix A for full specification), or
• beam and block floor with all voids filled with
mortar, or
• concrete planks with all voids between planks
and blockwork filled with mortar or flexible
sealant, or
• ground bearing slab
Cavity separating wall continuous to foundation,
cavity fill may be provided below minimum clear
cavity indicated. Continuous raft foundations
between dwellings are not acceptable. Solid walls
which support separating walls are only acceptable
where each ground floor (not timber joists) is
Section
built into one side of the separating wall and
breaks the vertical continuity of the wall and the
minimum clear cavity indicated is maintained.
Section
blank page
See overleaf for checklist
11. Are all junctions of wall and ceiling boards sealed with tape
or caulked with sealant?
™: trade mark
© Robust Details Limited 2011. All rights reserved. No part of this Handbook (other than the checklists) may be reproduced in any material
form or issued or communicated to the public (including photocopying or storing it in any medium by electronic means, and whether or not
transiently or incidentally to some other use of this Handbook) without the prior written permission of Robust Details Limited except in
accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Warning: the doing of an unauthorised act in relation to a copyright work may result in both a civil claim for damages and criminal prosecution.
V-WM-14™
Lightweight aggregate blocks ■
35mm (minimum) Saint Gobain-Isover RD35 Acoustic Batt ■
Gypsum-based board (nominal 9.8 kg/m2) on dabs ■
DO
■ Keep cavity, insulation batts and wall ties ■ Ensure that Isover RD35 acoustic batts
free from mortar droppings and debris are installed against the same face of the
cavity wall construction throughout
■ Fully fill all blockwork joints with mortar
■ Ensure Isover RD35 acoustic batts are
■ Make sure there is no connection
installed in accordance with
between the two leaves except for wall
manufacturer’s recommendations
ties and foundation
■ Ensure Isover RD35 acoustic batts do not
■ Ensure that only solid blocks (i.e. not
bridge the cavity
hollow or cellular) are used in the
construction of separating and flanking ■ Keep any chases for services to a
walls minimum and fill well with mortar.
Stagger chases on each side of the wall
■ Ensure all Isover RD35 acoustic batts are
to avoid them being back to back
tightly butted together and half cuts are
made with a clean sharp knife ■ Refer to Appendix A
Internal floor
Section
100mm (min)
4. Internal floor junction: timber floor joists built in, beam and block or
precast concrete
6. Ground floor junction: timber floor, beam and block, precast concrete plank, cast
in-situ suspended concrete slab or ground bearing concrete slab
100mm (min)
100mm (min)
100mm (min) overlap of Isover batts Flue block (stagger flues in accordance with the
manufacturer’s instructions)
100mm (min)
Plan Gypsum-based board (nominal 9.8 kg/m2) mounted
on dabs
blank page
See overleaf for checklist
10. Are voids around floor joists, chases, etc. fully filled/sealed?
12. Are all junctions of wall and ceiling boards sealed with tape
or caulked with sealant?
Contact details for technical assistance from Saint Gobain-Isover, manufacturer of Isover RD35 acoustic Batt:
Telephone: 01159 451143 Fax: 01159 451915 E-mail: isover.enquiries@saint-gobain.com
™: trade mark
© Robust Details Limited 2011. All rights reserved. No part of this Handbook (other than the checklists) may be reproduced in any material
form or issued or communicated to the public (including photocopying or storing it in any medium by electronic means, and whether or not
transiently or incidentally to some other use of this Handbook) without the prior written permission of Robust Details Limited except in
accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Warning: the doing of an unauthorised act in relation to a copyright work may result in both a civil claim for damages and criminal prosecution.
V-WM-19™
Minimum 100mm cavity wall with the MONARFLOOR® BRIDGESTOP® system ■
Dense or lightweight aggregate blocks or nominated hollow or cellular blocks ■
Render and gypsum-based board on dabs ■
Attached houses only ■
applied in accordance with the manufacturer's ■ Ensure cavity is minimum 100mm wide
instructions. and that correct wall ties are used
■ Ensure that only solid blocks or the
nominated hollow or cellular blocks are
Hollow or Cellular Blocks used in the construction of separating and
The Besblock Star Performer is the only block flanking walls. Place blocks with cellular
of this type currently accepted for use as an holes open to lower mortar bed
alternative to solid blocks in V-WM-19™. ■ Keep any chases for services to a
The separating wall must not be minimum and fill well with mortar.
constructed using a mix of the block types. Stagger chases on each side of the wall
to avoid them being back to back
■ Ensure that render is applied to the
Separating wall cavity insulation complete face of each leaf with a scratch
(optional) finish (it may be omitted within the floor
joist/beam zone)
The cavity may be insulated with mineral
wool with a maximum density of 40 kg/m3. ■ Refer to Appendix A
Plan
Separating Separating
wall wall
Toothed Tied
Plan
Internal floor
Continuous horizontal ribbon of adhesive
Section
4. Internal floor junction: timber floor joists built in, beam and block or
precast concrete
Internal floor
Internal floors should not be continuous
between dwellings
Floor construction:
• timber joists built in with:
– all voids around the joists filled with mortar
– the joint interface between the joist and the
mortar sealed with flexible sealant (see
Appendix A for full specification), or
• beam and block floor with all voids filled with
mortar, or
• concrete planks with all voids between planks
and blockwork filled with mortar or flexible
sealant
Section
6. Ground floor junction: timber floor, beam and block, precast concrete plank, cast
in-situ suspended concrete slab or ground bearing concrete slab
Complete wall face rendered (except in the floor
joist/beam zone where it may be omitted)
MONARFLOOR® BRIDGESTOP® Tie to penetrate at
max 450mm centres. Ties are reversible. May
also be used as render depth marker.
Section
10. Are voids around floor joists, chases, etc. fully filled/sealed?
11. Is render coat applied to the whole wall face (except where it
may be omitted between floor joists/beams)?
12. Are all junctions of wall and ceiling boards sealed with tape
or caulked with sealant?
Contact details for technical assistance from Icopal-MONARFLOOR®, manufacturer of the MONARFLOOR® BRIDGESTOP® system:
Telephone: 0161 866 6540 Fax: 0161 865 8433 E-mail: acoustics.uk@icopal.com
™: trade mark
© Robust Details Limited 2011. All rights reserved. No part of this Handbook (other than the checklists) may be reproduced in any material
form or issued or communicated to the public (including photocopying or storing it in any medium by electronic means, and whether or not
transiently or incidentally to some other use of this Handbook) without the prior written permission of Robust Details Limited except in
accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Warning: the doing of an unauthorised act in relation to a copyright work may result in both a civil claim for damages and criminal prosecution.
V-WM-20™
Lightweight aggregate blocks ■
Isover RD Party Wall Roll or Isover Round The House Roll ■
Gypsum-based board (nominal 9.8 kg/m2) on dabs ■
DO
■ Keep cavity, insulation rolls and wall ties ■ Keep any chases for services to a
free from mortar droppings and debris minimum and fill well with mortar.
Stagger chases on each side of the wall
■ Fully fill all blockwork joints with mortar
to avoid them being back to back
■ Make sure there is no connection
■ Refer to Appendix A
between the two leaves except for wall
ties, insulation and foundation ■ Ensure that either ‘Isover RD Party Wall
Roll’ or ‘Isover Round The House Roll’ is
■ Ensure that only solid blocks (i.e. not
printed on the insulation material.
hollow or cellular) are used in the
construction of separating and flanking
walls
Internal floor
Section
100mm (min)
4. Internal floor junction: timber floor joists built in, beam and block or
precast concrete
100mm (min)
Sketch shows timber joists built in
6. Ground floor junction: timber floor, beam and block, precast concrete plank, cast
in-situ suspended concrete slab or ground bearing concrete slab
100mm (min)
100mm (min)
10. Are voids around floor joists, chases, etc. fully filled/sealed?
12. Are all junctions of wall and ceiling boards sealed with tape
or caulked with sealant?
Contact details for technical assistance from Saint Gobain-Isover, manufacturer of RD Party Wall Roll
and Round The House Roll:
Telephone: 01159 451143 Fax: 0844 5618816 E-mail: isover.enquiries@saint-gobain.com
™: trade mark
© Robust Details Limited 2011. All rights reserved. No part of this Handbook (other than the checklists) may be reproduced in any material
form or issued or communicated to the public (including photocopying or storing it in any medium by electronic means, and whether or not
transiently or incidentally to some other use of this Handbook) without the prior written permission of Robust Details Limited except in
accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Warning: the doing of an unauthorised act in relation to a copyright work may result in both a civil claim for damages and criminal prosecution.
V-WM-21™
Lightweight aggregate blocks ■
Wet plaster ■
Minimum 100mm cavity ■
■ Refer to Appendix A
Toothed Tied
Internal floor
Section
4. Internal floor junction: timber floor joists built in, beam and block or
precast concrete
Internal floor
Separating floor:
• if using robust detail™ for floor, refer to Table
3a in introduction and see separating floor
robust detail™ for floating floor and ceiling
Section options
• if using floor requiring pre-completion testing,
seek specialist advice
Sketch shows E-FC-1™ type separating floor,
FFT1™ type floating floor treatment and CT3™
type ceiling
6. Ground floor junction: timber floor, beam and block, precast concrete plank,
cast in-situ concrete slab or ground bearing slab
Plaster complete wall surface down to finished
floor level
Ground floor not continuous between dwellings
Ground floor construction:
• timber joists built in with:
– all voids around the joists filled with mortar
– the joint interface between the joist and the
mortar sealed with flexible sealant (see
Appendix A for full specification), or
• beam and block floor with all voids filled with
mortar, or
• concrete planks with all voids between planks
and blockwork filled with mortar or flexible
sealant, or
• ground bearing slab
Cavity separating wall continuous to foundation,
cavity fill may be provided below minimum clear
cavity indicated. Continuous raft foundations
between dwellings are not acceptable. Solid walls
which support separating walls are only acceptable
where each ground floor (not timber joists) is
Section built into one side of the separating wall and
breaks the vertical continuity of the wall and the
minimum clear cavity indicated is maintained.
Section
™: trade mark
© Robust Details Limited 2011. All rights reserved. No part of this Handbook (other than the checklists) may be reproduced in any material
form or issued or communicated to the public (including photocopying or storing it in any medium by electronic means, and whether or not
transiently or incidentally to some other use of this Handbook) without the prior written permission of Robust Details Limited except in
accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Warning: the doing of an unauthorised act in relation to a copyright work may result in both a civil claim for damages and criminal prosecution.
V-WT-1™
Without sheathing board ■
Twin timber frames ■
Plan
Section
Alternative detail
Rip liner
Diagram 5.1
Plan
6. Ground floor junction: timber floor, beam and block, precast concrete plank, cast
in-situ concrete suspended slab or ground bearing slab
7. Raft foundation
Section
Alternative detail Mastic sealant, ensure skirting and wall lining are
with screed finish isolated from screed
Perimeter insulation, isolating screed from timber
frame
Below screed insulation, isolating screed from raft
Polyethylene
Plan
Plan
Plan
blank page
See overleaf for checklist
™: trade mark
© Robust Details Limited 2011. All rights reserved. No part of this Handbook (other than the checklists) may be reproduced in any material
form or issued or communicated to the public (including photocopying or storing it in any medium by electronic means, and whether or not
transiently or incidentally to some other use of this Handbook) without the prior written permission of Robust Details Limited except in
accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Warning: the doing of an unauthorised act in relation to a copyright work may result in both a civil claim for damages and criminal prosecution.
V-WT-2™
With sheathing board ■
Twin timber frames ■
Section
Alternative detail
Rip liner
Diagram 5.1
Plan
6. Ground floor junction: timber floor, beam and block, precast concrete plank, cast
in-situ concrete suspended slab or ground bearing slab
7. Raft foundation
Section
Alternative detail Mastic sealant, ensure skirting and wall lining are
with screed finish isolated from screed
Perimeter insulation, isolating screed from timber
frame
Below screed insulation, isolating screed from raft
Polyethylene
Plan
Plan
Plan
™: trade mark
© Robust Details Limited 2011. All rights reserved. No part of this Handbook (other than the checklists) may be reproduced in any material
form or issued or communicated to the public (including photocopying or storing it in any medium by electronic means, and whether or not
transiently or incidentally to some other use of this Handbook) without the prior written permission of Robust Details Limited except in
accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Warning: the doing of an unauthorised act in relation to a copyright work may result in both a civil claim for damages and criminal prosecution.
V-WT-3™
ElecoFrame prefabricated panels ■
Twin timber frames ■
For use in timber frame houses and flats/apartments ■
FRAME CONSTRUCTION DO
ElecoFrame
■ Keep wall linings at least 240mm apart
identification plate
■ Ensure quilt or batts cover whole lining
area, fitting tight between studs without
sagging
■ Ensure that all cavity stops/closers are
flexible or are fixed to one frame only
■ Make sure there is no connection
between the two leaves except where
ties are necessary for structural reasons
(see above).
■ Stagger joints in wall linings to avoid
air paths
Nail plate ■ Seal all joints in outer layer with tape or
caulk with sealant
■ Refer to Appendix A
Plan
Section
Diagram 5.1
Plan
5. Ground floor junction: timber floor, beam and block, precast concrete plank, cast
in-situ concrete suspended slab or ground bearing slab
6. Raft foundation
Section
Alternative detail Mastic sealant, ensure skirting and wall lining are
with screed finish isolated from screed
Perimeter insulation, isolating screed from timber
frame
Below screed insulation, isolating screed from raft
Polyethylene
Plan
Plan
Plan
blank page
See overleaf for checklist
9. Is inner leaf lined with 45mm (min) foil faced PIR insulation,
minimum density 32 kg/m3?
Contact details for technical assistance from Eleco Timber Frame Ltd, manufacturer of ElecoFrame prefabricated panels:
Telephone: 0151 448 0055 Fax: 0151 448 0066 E-mail: elecoframe@eleco.com
™: trade mark
© Robust Details Limited 2011. All rights reserved. No part of this Handbook (other than the checklists) may be reproduced in any material
form or issued or communicated to the public (including photocopying or storing it in any medium by electronic means, and whether or not
transiently or incidentally to some other use of this Handbook) without the prior written permission of Robust Details Limited except in
accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Warning: the doing of an unauthorised act in relation to a copyright work may result in both a civil claim for damages and criminal prosecution.
V-WT-4™
With sheathing board ■
Twin timber frames ■
Excel Industries Warmcel 500 insulation ■
Section
Alternative detail
Rip liner
Diagram 5.1
Plan
6. Ground floor junction: timber floor, beam and block, precast concrete plank, cast
in-situ concrete suspended slab or ground bearing slab
7. Raft foundation
Section
Alternative detail Mastic sealant, ensure skirting and wall lining are
with screed finish isolated from screed
Perimeter insulation, isolating screed from timber
frame
Below screed insulation, isolating screed from raft
Polyethylene
Section
Plan
Plan
Plan
blank page
See overleaf for checklist
4. Are stud voids fully filled with Warmcel 500 except above
ceiling line in roof void zone?
Contact details for technical assistance from Excel Industries, providers of Warmcel 500:
Telephone: 01685 845 200 Fax: 01685 844 106 E-mail: sales@excelfibre.com
™: trade mark
© Robust Details Limited 2011. All rights reserved. No part of this Handbook (other than the checklists) may be reproduced in any material
form or issued or communicated to the public (including photocopying or storing it in any medium by electronic means, and whether or not
transiently or incidentally to some other use of this Handbook) without the prior written permission of Robust Details Limited except in
accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Warning: the doing of an unauthorised act in relation to a copyright work may result in both a civil claim for damages and criminal prosecution.
V-FT-1™
Timber I-Joists ■
Use with timber frame walls only ■
* FFT80™ resilient batten must comply with ■ Stagger joints in ceiling layers
laboratory performance requirements
detailed on page 5 ■ Refer to Appendix A
Section
Rip liner
Alternative detail
Section
Rip liner
Alternative detail
Rip liner
Alternative detail
Timber floor ceiling treatment must be CT1™, (see Downlighters and recessed lighting
below). All joints to outer layers of ceiling must be Downlighters or recessed lighting may be installed
sealed with tape or caulked with sealant. in the ceiling:
The maximum load on resilient bars should not • in accordance with the manufacturer’s
exceed that specified in the manufacturer’s instructions
instructions. • at no more than one light per 2m2 of ceiling area
in each room unless the use of a greater density
Ensure ceiling layers have staggered joints.
of light fittings is supported by testing undertaken
Services must not puncture ceiling linings (except in accordance with Appendix F
cables, which should be sealed around with flexible • at centres not less than 0.75m
sealant) • into openings not exceeding 100mm diameter or
100 x100mm
Particular attention should also be paid to Building
Standards Section 2: Fire
Section
Alternative detail
3. Has quilt (min 100mm thick) been fitted between the joists?
™: trade mark
© Robust Details Limited 2011. All rights reserved. No part of this Handbook (other than the checklists) may be reproduced in any material
form or issued or communicated to the public (including photocopying or storing it in any medium by electronic means, and whether or not
transiently or incidentally to some other use of this Handbook) without the prior written permission of Robust Details Limited except in
accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Warning: the doing of an unauthorised act in relation to a copyright work may result in both a civil claim for damages and criminal prosecution.
V-FT-2™
Timber Solid Joists ■
Use with timber frame walls only ■
Section
Rip liner
Alternative detail
Rip liner
Section
Alternative detail
Rip liner
Alternative detail
Timber floor ceiling treatment must be CT1™ (see Downlighters and recessed lighting
below). All joints to outer layers of ceiling must be Downlighters or recessed lighting may be installed
sealed with tape or caulked with sealant. in the ceiling:
The maximum load on resilient bars should not • in accordance with the manufacturer’s
exceed that specified in the manufacturer’s instructions
instructions. • at no more than one light per 2m2 of ceiling area
in each room unless the use of a greater density
Ensure ceiling layers have staggered joints.
of light fittings is supported by testing undertaken
Services must not puncture ceiling linings (except in accordance with Appendix F
cables, which should be sealed around with flexible • at centres not less than 0.75m
sealant) • into openings not exceeding 100mm diameter or
100 x100mm
Particular attention should also be paid to Building
Standards Section 2: Fire
Section
Alternative detail
2. Has quilt (min 100mm thick) been fitted between the joists?
7. Has 50mm (min) quilt been fitted between the floor battens?
10. Are vertical service pipes wrapped in quilt and boxed in with
two layers of gypsum-based board combined nominal mass
per unit area of 16 kg/m2?
™: trade mark
© Robust Details Limited 2011. All rights reserved. No part of this Handbook (other than the checklists) may be reproduced in any material
form or issued or communicated to the public (including photocopying or storing it in any medium by electronic means, and whether or not
transiently or incidentally to some other use of this Handbook) without the prior written permission of Robust Details Limited except in
accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Warning: the doing of an unauthorised act in relation to a copyright work may result in both a civil claim for damages and criminal prosecution.
All floating floor treatments : d) For further guidance on floating floor treatments
a) Must achieve a minimum laboratory performance and flanking strips please refer to Appendix A.
of rd ∆Lw = 17dB - see Appendix D. * Note - void dimensions indicated are when floor
is loaded to 25 kg/m2.
b) Must be installed in accordance with the
manufacturer’s instructions.
c) Require 5mm (min) resilient flanking strips
around the perimeter of the flooring board to
isolate floor from walls and skirting.
Section
9. Are vertical service pipes wrapped in quilt and boxed in with two
layers of gypsum-based board, nominal 8 kg/m2 each layer?
™: trade mark
© Robust Details Limited 2011. All rights reserved. No part of this Handbook (other than the checklists) may be reproduced in any material
form or issued or communicated to the public (including photocopying or storing it in any medium by electronic means, and whether or not
transiently or incidentally to some other use of this Handbook) without the prior written permission of Robust Details Limited except in
accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Warning: the doing of an unauthorised act in relation to a copyright work may result in both a civil claim for damages and criminal prosecution.
Minimum 1.0m
Diagram c
Solid timber joists • the joint between the masonry and the timber
and any other air paths are carefully pointed
Solid timber joists may be built into the separating
with silicone sealant.
wall, provided that:
Alternatively, proprietary joist caps/ends designed
• the mortar joints around each joist perimeter are
to satisfy air leakage requirements may be used.
recessed or struck, and
• the joint between the masonry and the timber is
carefully pointed with silicone sealant.
Frame (timber or
metal) Gypsum-based board
Flexible or Gypsum-based boards may be either plaster
acoustic sealant gypsum-based or cement gypsum-based.
Cavity stop The mass per unit area or surface density specified
is a nominal minimum value in kilograms per
square metre (kg/m2): the use of a higher density
board will increase the sound insulation
performance.
Boards should be abutted and all joints sealed with
tape or caulked with sealant. Where two or more
Two panels may be adopted provided they are
layers of gypsum-based board are required on
constructed with a minimum 50mm cavity maintained
separating walls or ceilings all joints should be
between wall panels, or stud should board be
staggered, and only the outer layer boards need
omitted from the inner faces of the spandrel panels.
to be sealed with tape or caulked with sealant.
Wall cavities must be maintained within roof voids. The order in which boards are fitted and lapped is
Linking of wall leaves by spandrel panels is not not critical provided the overall mass per unit area
permitted. is maintained. The same applies to combined
render/plaster finishes.
Services and chases in separating walls Boards fitted to steel and timber frame separating
Where possible, services should not be built into walls should be mounted in accordance with the
the separating wall. manufacturer’s instructions – some boards may
need to be mounted horizontally.
However, where chasing is permitted in the Detail,
they should be kept to a minimum. Chases must Thermal laminate boards may be used as the wall
not be located back to back. Care must be taken finish to masonry walls, provided the nominal mass
to ensure all voids are fully filled with mortar. Where per unit area indicated in the robust detail™ is
conduits or cappings are used they should not be maintained - seek advice from the manufacturer.
in contact with the gypsum-based board.
An acceptable alternative to caulking or sealing
The robust details™ for timber and steel framed the joint between the wall and the ceiling is to
walls show how services should be built in. use gypsum coving.
3. Construct the internal wall directly off core floor Precast concrete plank separating floors
with the floating floor treatment (FFT) or screed with steel beams
installed around the internal walls, provided:
In some situations precast concrete planks may
• the 5mm (min) resilient flanking strip or require intermediate support by steel beams
isolating edge strip, as appropriate for the supported on masonry.
robust detail™ adopted, is correctly installed
to all perimeters of the FFT or screed to isolate • cavity masonry separating walls must not be
the floor from all the walls and skirtings built off steel beams – where necessary, external
cavity walls may be built off steel beams
4. Construct the internal wall off the floating floor
treatment flooring board or screed, provided: • all voids between the steel beam and the slabs
should be fully filled with grout or concrete, and
• the floating floor treatment is installed in
accordance with the manufacturer’s • the supports for the ceiling treatment and the
instructions, including the provision of ceiling lining should not come into contact with
additional battens to support the internal walls the steel beam, and
if necessary
• the depth of the ceiling void from the underside
of the plank should be as shown in the following
Subfloor ventilation diagrams and in accordance with the
Where possible it would be preferable to avoid corresponding separating floor robust detail™
providing ventilation for the sub floor void through
• mineral wool quilt should be provided if shown
the separating walls.
in the following diagrams
However, where necessary, the ventilation of the
sub floor void of Section 5 Robust Detail™
separating walls may be achieved through the
installation of ducts through the separating wall,
provided:
• the top of the duct is at least 300mm below the
finished floor surface of the ground floor
structure
• the number of ducts passing through the
separating wall is kept to the minimum
necessary.
Screed thickness
The screed thickness stated is the minimum
thickness at any point and a greater thickness
should be specified to take account of deviations
in the finished levels of the surfaces of bases and
any reinforcement provided.
Cement:sand screed should be at least 50mm to
comply with BS 8204. Concrete screed is acceptable.
are used which have surface indents for the heating • any specific guidelines, regarding the installation
conduits to be situated within, this is acceptable. For of such finishes, stipulated by the manufacturer
floors that incorporate an insulation layer, such of the FFT system are strictly followed;
indented boards may be used as part of the resilient
• the laminate timber floor finish does not bypass
layers, provided they are of an appropriate type of
the isolation provided by the flanking strips at
material, and that the minimum thickness of the
the perimeters of the FFT by being in direct
resilient layer is maintained.
contact with the wall or skirting;
Resilient bars In the case of the Section 5 Robust Details™ with
floating screed, it would also be acceptable in
When using resilient bars the specifier should
principle to provide a laminate timber floor finish,
ensure that the resilient bar manufacturer has a
provided:
laboratory sound test report (as outlined in
Appendix E) that demonstrates compliance with • the laminate timber floor finish does not bypass
the robust details™ performance criteria. the isolation provided by the isolating edge strips
at the perimeters of the screed by being in direct
Timber floating floor treatments contact with the wall or skirting;
When using timber floating floor treatments (e.g.
battens, cradles, platforms) the specifier should
Screed floating floor treatments
ensure that the floating floor treatment manufacturer Where screeds are separated from the core floor
has a laboratory sound test report (as outlined in by resilient layers the screed must be fully isolated
Appendix C or D) that demonstrates compliance from the floor slabs, perimeter walls and skirtings
with robust details™ performance criteria. and must not come into direct contact with these
areas. The resilient layer(s) should completely cover
It may be necessary for battens to be installed
the core floor surface and be wrapped round the
at closer centres or for additional support to be
edge of the screed to isolate the screed from the
provided under heavy loads from internal walls,
perimeter walls and skirtings.
sanitary ware and kitchen units, etc. in accordance
with the manufacturer's instructions.
Masonry angle supports
Rigid insulation boards (e.g. expanded, extruded
The masonry outer leaf of external walls used with
or bead polystyrene) are not acceptable for use
robust details™ concrete or steel-concrete
as the resilient layer or as a flanking strip with a
composite separating floors, may be supported on
floating floor treatment where the walking surface
suitable proprietary masonry angle supports that
is board based.
are fixed to the edge of the separating floors.
Mineral wool may not be used as a resilient
flanking strip. See Appendix B, Glossary, for Full height glazing units junction with
definition of a resilient flanking strip. robust details separating floor
Floating Floor Treatments in kitchens and If referred to in the detail, full height glazing units
may be used. Where there is no inner leaf and a full
bathrooms height glazing unit, the core floor slab must break
It is permissible to install kitchen units and the vertical continuity of the glazing facade,
appliances along with bathroom sanitary fittings as shown below.
directly onto the sub floor construction. In all cases
it is recommended that you contact the
manufacturer directly to seek their advice relating
to the specific FFT.
Specification requirements
Where details have “minimum” in their specification,
it indicates that the value should not be lower
than that stated. It does not preclude the use
of higher values.
For example, where a 75mm (min) cavity size
is specified, it does not preclude the use of wider
cavities. Similarly, a reference to a wall finish
with 8 kg/m2 gypsum-based board does not
preclude the use of boards with a greater mass
per unit area.
Icopal-MONARFLOOR® BRIDGESTOP®
System for robust details™ cavity
masonry walls 2
Smartroof complete Interlocking
“room-in-roof” panel system using robust
details™ timber or masonry cavity walls 3
Kingspan TEK inner leaf flanking condition
for robust details™ timber separating walls 4
Prestoplan PresPeak 60 interlocking single
spandrel panel system for robust details™
timber separating walls 5
Appendix A
A2 – Proprietary Flanking Conditions
Icopal-MONARFLOOR® BRIDGESTOP® System for robust details™ cavity masonry
walls. Refer to Table 6 in Introduction.
1. Separating wall – direct support on raft 2. Separating wall – suspended floor with gas
membrane
a a
3 3
b b
2 c 2 c
1 4 d 5 1 4 d 5
1 1 250mm
250mm
e
150mm (min)
Appendix A
A2 – Proprietary Flanking Conditions
Smartroof complete interlocking “room-in-roof” panel system using robust details™
timber or masonry cavity walls. Refer to Table 6 in Introduction.
i b
i
1 1
a e
2
f f
h
c c
Min 75mm
3. Gable flanking junction – timber frame 4. Room-in-roof junction with timber frame
cavity walls
1 1
a e
g k
d d
Min 50mm
a a
b b
1 1
2 2
3 3
4 4 c
e d c
d 4 e
Key
1 Kingspan TEK – 142 Panel. a Masonry outer leaf (min 100mm thick).
2 Service void (if required). b External wall cavity (min 50mm).
3 One layer of gypsum-based board nominal c Robust Details™ timber frame separating wall.
8 kg/m2 on inner leaf where there is no (Refer to Table 6 in Introduction and relevant
separating floor, e.g. for houses. timber frame robust details™ in Handbook).
Two layers of gypsum-based board nominal d Close cavity with flexible cavity stop
8 kg/m2 each on inner leaf where there is a (see Appendix A).
separating floor (non Robust Detail™ floor), e.g. e Seal all joints with tape or caulk with sealant.
for flats and apartments.
4 Approved fixings to TEK BBA Cert No. 02/S029.
1. Spandrel panel located parallel to trussed rafters 2. Spandrel panel located across trussed rafters
d
1
a
b e
c
Section
1 g
Top chord detail Bottom chord detail
d f
Plan g 1 Elevation
Elevation
Key
1 PresPeak 60 spandrel panels. Plan
a Firestop wired mineral wool closer.
b Flexible cavity stop. Refer also to manufacturer’s guidance
c Timber frame separating wall.
d Site-fixed rafter extension.
e Continuous blocking between bottom chords of Contact details for Prestoplan Limited:
trusses. Telephone: 01772 627373
f Bottom chord extended for support. Fax: 01772 627575
Web: www.prestoplan.co.uk
g Intumescent tape.
blank page
Key
1 British Gypsum 70 SB 65 steel batten. a Robust Detail™ concrete separating floor.
2 British Gypsum 50 SB 65 steel batten. b 18mm (min) t&g flooring board.
Option 1 Option 2
Insumate trays may be inverted
a a
b b
c
c
d
d
e e
1 1
Key Note
1 Insumate insulation support tray. Ensure absorbent material ‘c’ is fitted between all
joists, and also between the final joist and the
perimeter blocking.
a Floating floor treatment.
Insumate must be installed in accordance with the
b Floor sub-deck. manufacturer’s instructions.
c Absorbent material.
d Floor joist – Refer also to Table 7 in Introduction.
Contact details for Insumate Limited:
e Ceiling treatment.
Telephone: 01768 398 991
(For specification of items a to e, refer to the Fax: 01768 398 991
relevant robust detail™) E-mail: info@insumateltd.com
Web: www.insumateltd.com
blank page
Appendix B
Glossary
The definitions given below are for the purposes Direct transmission
of this document only and are not intended to Sound which is transmitted only through the
be rigorous. main separating element and involves no other
flanking element.
Absorption
Conversion of sound energy into heat, often DnT
by the use of a porous material. Standardised level difference. The difference in
sound level between a pair of rooms (source and
Absorbent material receiving rooms), for a stated frequency, which is
Material that absorbs sound energy. corrected (normalised) for the reverberation time (in
the receiving room). See BS EN ISO 140-4.
Airborne sound
Sound propagating through the air, often linked DnT,w
to noise sources such as speech and television. Weighted standardised level difference. A single-
number quantity (weighted) which characterises
Airborne sound insulation the airborne sound insulation between two rooms.
Sound insulation that reduces the transmission See BS EN ISO 717-1.
of airborne sound between adjoining dwellings
or parts of adjoining dwellings. Flanking element (e.g. flanking wall)
Any building element that contributes to the
Block thickness airborne sound or impact transmission between
The block thickness quoted is the work size. rooms in a building which is not the direct
Permissible manufacturing tolerances are given separating element (i.e. not the separating
in BS 6073. wall or separating floor).
Built in insulation Flanking strip or edge strip
Insulation batts built in during construction (not A 5mm (min) resilient strip which is located at the
pumped or blown material). perimeter of a floor to isolate the floor surface layer
from the perimeter walls and skirtings. A typical
Cavity stop example of a flanking strip is 5mm (min) foamed
A proprietary product or material such as mineral polyethylene. Rigid boards, (such as extruded,
wool (fibre) used to close the gap in a cavity wall. expanded or bead polystyrene) or mineral wool
based products may not be used as a flanking strip
Composite resilient batten where the walking surface is board based.
A timber batten which is composed of a timber
batten with a prebonded resilient material to For screed floating floors the permitted flanking
provide isolation between the flooring surface strip or edge strip detail will be dependant on the
layers and floor base. resilient layer system adopted and the relevant
robust detail™ must be strictly followed.
Cradle / Saddle
An intermediate support system (with a resilient Flanking transmission
layer base) which uses levelling packer pieces Airborne sound or impact transmission between
to support a timber batten, isolating it from the rooms which is transmitted via flanking elements
floor base. and/or flanking elements in conjunction with the
main separating elements.
Ctr (see also rd ∆Rw+Ctr)
Spectrum adaptation term (No.2) from BS EN ISO Flexible closer
717-1 to take account of a specific sound spectra A flexible cavity stop or cavity barrier which seals
(which are predominantly low frequency based). the air path in cavities linking adjoining dwellings.
Appendix B
rd ∆Lw
This is specific to Robust Details™ performance
requirements and is the difference in weighting
between two floor impact tests undertaken in
an acoustic test laboratory. This should not be
confused with ∆Lw using ISO 140-8.
rd ∆Rw+Ctr
This is specific to Robust Details™ performance
requirements and is the difference in weighting
Appendix C
Determination of the acoustic performance requirements for floating
floor treatments used with RD timber separating floors
To determine the acoustic performance of floating The timber joists should be mounted on joist
floor treatments on robust detail™ timber separating hangers at 450mm centres and the 100mm (deep)
floors airborne and impact measurements should be glass based mineral wool insulation should be
undertaken in an acoustic test laboratory. The placed in the cavities between the joists and also
following test procedure may be used for Robust between cavities formed between the joists and
Detail™ timber separating floors with floating floor the test aperture border. The floor decking should
treatments. The following sections C.1 to C.4 outline be mounted on the timber joists with screws at
the measurement and performance rating criteria. 300mm centres. All junctions between the floor
surface perimeter and test aperture should be
C.1 Test Laboratory Requirements sealed with a flexible or acoustic sealant.
The test facility must have UKAS Accreditation The ceiling layers should be mounted with joints
(or EC equivalent) for the measurement of sound staggered and the first layer (inner layer) should be
insulation in the laboratory, for both airborne sound fixed to the underside of the joists with screws, at
insulation and impact sound transmission. The test 300mm centres within the field of the boards and
measurement should be undertaken in accordance at 150mm centres at the board ends. The second
with BS EN IS0 140-3, BS EN ISO 140-6 and the layer (outer layer) should be fixed with screws, at
performance of each measurement rated in 230mm centres within the field of the boards and
accordance with BS EN ISO 717 (Parts 1 & 2). The at 150mm centres at the board ends. The perimeter
measurements should be undertaken in a laboratory of the ceiling should be sealed with flexible or
with suppressed flanking transmission and in acoustic mastic sealant and all joints and
accordance with BS EN IS0 140-1 and screwheads taped with self-adhesive tape.
BS EN IS0 140-2.
Floating Floor Treatment
The R’max value of the laboratory test facility shall The floating floor treatment should cover the entire
be at least 10 dB greater than the sound insulation test area of the core floor surface and should be
value of the structure under test. constructed in accordance with the manufacturer's
instructions. All robust detail™ floating floor
C.2 Core (or base) Timber Floor and treatments require a flanking strip to isolate the
Floating Floor Treatment edge of the floorboard from the perimeter walls. As
Testing should be undertaken on a core (or base) such the manufacturer should also use the flanking
floor which consists of the following construction strip, which they would normally use on site, in the
specification: laboratory measurements.
Floor Decking 15mm OSB timber decking board C.3 Testing Required
(or equivalent timber based board)
with mass per unit area of For the purposes of evaluating the performance of
10-11 kg/m2 a floating floor treatment for robust details™
involving timber separating floors four different
Joists 235mm x 50mm solid timber joists measurements are required (2 airborne and 2
C16 grade timber impact measurements). The following
Insulation 100mm glass based mineral measurements are required:
wool insulation with a density Airborne
of 10-11 kg/m3
Test 1 Determination of Rw +Ctr* for the core (or
Ceiling Two layers of 12.5mm gypsum- base) timber floor.
based board with a mass per unit
area for each layer of 8-8.5 kg/m2. Test 2 Determination of Rw +Ctr* for the core (or
base) timber floor with the floating floor
treatment applied to the core floor surface.
Impact
Test 3 Determination of L n,w for the core (or base)
timber floor.
Test 4 Determination of L n,w for the core (or base)
timber floor with the floating floor treatment
applied to the core floor surface.
Laboratory Test Core Floor Construction
Appendix C
Appendix D
Determination of the acoustic performance requirements for floating
floor treatments used with Robust Detail™ concrete and
steel-concrete composite separating floors
To determine the acoustic performance of floating The precast concrete hollow-core planks should be
floor treatments on robust detail™ concrete mounted in the test aperture to cover the entire test
separating floors airborne and impact measurements aperture area. The planks should be tightly abutted
should be undertaken in an acoustic test laboratory. and all joints should be filled with grout including
The following test procedure may be used for Robust top and bottom joints. No voids should remain at
Detail™ concrete and steel-concrete composite the floor perimeter junction with the test aperture
separating floors with floating floor treatments. The border. The levelling screed should be applied such
following sections D.1 to D.4 outline the that it is directly bonded to the entire floor surface
measurement and performance rating criteria. of the planks. No ceiling treatments are permitted
and no additional ceiling layers should be applied.
D.1 Test Laboratory Requirements
Floating Floor Treatment
The test facility must have UKAS Accreditation (or The floating floor treatment should cover the entire
EC equivalent) for the measurement of sound test area of the core floor surface and should be
insulation in the laboratory for impact sound constructed in accordance with the manufacturer's
transmission. The test measurement should be instructions. All robust detail™ floating floor
undertaken in accordance with BS EN IS0 140-6 treatments require a flanking strip to isolate the
and the performance of each measurement rated edge of the flooring board from the perimeter walls.
in accordance with BS EN ISO 717-2. The As such the manufacturer should also use the
measurements should be undertaken in a laboratory flanking strip, which they would normally use on
with suppressed flanking transmission and in site, in the laboratory measurements.
accordance with BS EN ISO 140-1 and
BS EN IS0 140-2. D.3 Testing Required
The R’max value of the laboratory test facility shall For the purposes of evaluating the performance of
be at least 10 dB greater than the sound insulation a floating floor treatment for Robust Detail™
value of the structure under test. concrete and steel-concrete composite separating
floors, two different impact measurements are
D.2 Core (or base) Concrete Floor and required. The following measurements are required:
Floating Floor Treatments
Impact
Testing should be undertaken on a core (or base)
floor which consists of the following construction Test 1 Determination of L n,w for the core (or base)
specification: concrete floor.
Levelling 10mm (min) - 25mm (max) Test 2 Determination of L n,w for the core (or base)
Screed levelling screed using proprietary concrete floor with the floating floor
cement based screed with bonding treatment applied to the core floor surface.
agent. ‘Rapidry Formula’ screeds
may be used. D.4 Expression of Performance
Precast plank 150mm deep hollow-core precast The impact sound transmission performance of the
concrete plank of mass per unit floating floor treatment should be expressed as the
area 295-305 kg/m2. The hollow reduction in impact sound transmission (rd ∆L w) as
segments of the precast plank a result of the application of the floating floor
should be located at regular treatment to the core floor (rd ∆L w = Test 1 - Test 2).
centres and should be distributed
over a minimum of 80% of the D.5 Replacement Products
plank width. A new replacement product may be benchmark
tested using an ISO 140-8 laboratory test core floor
as an alternative to the laboratory test core floor
indicated above, provided:
• the ISO 140-8 floor structure is 140mm thick
±5mm tolerances
• the original product has been successfully tested
Laboratory Test Core Floor Construction
in accordance with Appendix D of the Robust
Details™ Part E Handbook using the laboratory
test core floor specified in Appendix D
Appendix D
Appendix E
Determination of the acoustic performance requirements for
resilient bars used on ceilings
To determine the acoustic performance of resilient The timber joists should be mounted on joist
bars for use within robust detail™ separating floors hangers at 450mm centres and the 100mm (deep)
airborne and impact measurements should be glass based mineral wool insulation should be
undertaken in an acoustic test laboratory. The placed in the cavities between the joists and also
performance of the resilient bars is calculated between cavities formed between the joists and the
from the improvement in airborne and impact test aperture border. The floor decking should be
performance by a ceiling connected via resilient mounted on the timber joists with screws at
bars as opposed to a direct fix ceiling. The ceiling 300mm centres. All junctions between the floor
linings should be identical in both tests. The surface perimeter and test aperture should be
following sections E.1 to E.4 outline the sealed with a flexible or acoustic sealant.
measurement and performance rating criteria.
The direct fix ceiling is composed of two layers of
gypsum-based board which have an overall mass
E.1 Test Laboratory Requirements per unit area of 23-25 kg/m2 and have a minimum
The test facility must have UKAS Accreditation (or overall thickness of 30mm. The ceiling layers
EC equivalent) for the measurement of sound should be mounted with joints staggered and the
insulation in the laboratory, for both airborne sound first layer (inner layer) should be fixed to the
insulation and impact sound transmission. The test underside of the joists with screws, at 300mm
measurement should be undertaken in accordance centres within the fields of the boards and 150mm
with BS EN IS0 140-3, BS EN IS0 140-6 and the centres at the board ends, and the second layer
performance of each measurement rated in (outer layer) should be fixed with screws, at 230mm
accordance with BS EN ISO 717 (Parts 1 & 2). The centres within the fields of the boards and at
measurements should be undertaken in a laboratory 150mm centres at the board ends. The perimeter of
with suppressed flanking transmission and in the ceiling should be sealed with flexible or
accordance with BS EN ISO 140-1 and acoustic sealant and all joints and screwheads
BS EN ISO 140-2. taped with self-adhesive tape.
The R’max value of the laboratory test facility shall
be at least 10 dB greater than the sound insulation
value of the structure under test.
Appendix E
Airborne
Test 1 Determination of Rw +Ctr* for the floor with a
direct fix ceiling.
Test 2 Determination of Rw +Ctr* for the floor with a
ceiling connected with resilient bars.
Impact
Test 3 Determination of L n,w for the floor with a
direct fix ceiling.
Test 4 Determination of L n,w for the floor with a
ceiling connected with resilient bars.
Appendix F
Determination of the Influence on the Acoustic Performance of RD
Timber Separating Floors due to the presence of Downlighters
(Recessed Lighting)
To determine the influence on the acoustic Insulation 100mm glass based mineral
performance due to the presence of downlighters wool insulation with a density
for use within Robust Detail™ timber separating of 10-11 kg/m3
floors airborne and impact measurements should
Ceiling Two layers of gypsum-based board
be undertaken in an acoustic test laboratory. For
with an overall mass per unit area
the purposes of Robust Detail™ separating floors
of 23-25 kg/m2.
the following test procedure may be used.
Note: This test method may also be used by
manufacturers to demonstrate whether they
can exceed the spacing/area criteria which
are specified in the robust detail specification
sheets for the timber, concrete and steel-
concrete composite floors.
The influence on the acoustic performance of the
timber floor is calculated from airborne and impact
measurements on a timber floor structure with and Construction of Initial Timber Floor (no
without downlighters present. The timber floor downlighters)
structure must be identical in both sets of tests The timber joists should be mounted on joist
(for airborne and impact) except for the presence hangers at 450mm centres and the 100mm (deep)
of the downlighters. glass based mineral wool insulation should be
placed in the cavities between the joists and also
For downlighters to qualify for inclusion in Robust between cavities formed between the joists and
Detail™ timber separating floors, the difference in the test aperture border. The floor decking should
performance with the downlighters present should be mounted on the timber joists with screws at
be no worse than 1dB for both airborne and impact 300mm centres. All junctions between the floor
measurements, when tested under the following surface perimeter and test aperture should be
conditions. The following sections F.1 to F.4 outline sealed with a flexible or acoustic mastic sealant.
the measurement and performance rating criteria.
The direct fix ceiling is composed of two layers of
F.1 Test Laboratory Requirements gypsum-based board which have an overall mass
per unit area of 23-25 kg/m2 and have a minimum
The test facility must have UKAS Accreditation overall thickness of 30mm. The ceiling layers
(or EC equivalent) for the measurement of sound should be mounted with joints staggered and the
insulation in the laboratory, for both airborne sound first layer (inner layer) should be fixed to the
insulation and impact sound transmission. The test underside of the joists with screws, at 300mm
measurement should be undertaken in accordance centres within the fields of the boards and 150mm
with BS EN ISO 140-3, BS EN ISO 140-6 and the centres at the board ends, and the second layer
performance of each measurement rated in (outer layer) should be fixed with screws, at 230mm
accordance with BS EN ISO 717 (Parts 1 & 2). The centres within the fields of the boards and at
measurements should be undertaken in a laboratory 150mm centres at the board ends. The perimeter
with suppressed flanking transmission and in of the ceiling should be sealed with flexible or
accordance with BS EN ISO 140-1 and acoustic mastic sealant and all joints and
BS EN ISO 140-2. screwheads taped with self adhesive tape.
The R’max value of the laboratory test facility shall
Construction of Timber Floor with Downlighters
be at least 10dB greater than the sound insulation
value of the structure under test. The floor construction and materials used should
be identical to the initial timber floor test structure
F.2 Core Timber Floor (no downlighters) except that downlighters have been installed into
the ceiling. The downlighters should be spaced at
Testing should be undertaken on a floor with the a minimum of 1 downlighter per 2m2 of ceiling area
following construction specification: and at not less than 0.75m spacings. (e.g. 10m2
Floor Decking 15mm OSB timber decking board of ceiling area equates to at least 5 downlighters).
(or equivalent timber based board) The test results must indicate the number per unit
with mass per unit area of area and the spacings used in the tests and, if
10-11 kg/m2 successful manufacturers are expected to include
this information in their test reports and fitting
Joists 235mm x 50mm solid timber joists instructions.
C16 grade timber
Appendix F
Airborne
Test 1 Determination of Rw +Ctr* for the initial
timber floor
Test 2 Determination of Rw +Ctr* for the initial
timber floor plus downlighters
Impact
Test 3 Determination of L n,w for the initial timber
floor.
Test 4 Determination of L n,w for the initial timber
floor plus downlighters