Professional Documents
Culture Documents
thong-so khải111
thong-so khải111
Generator Specification
Service Power PRP(1) ESP(2) Performance Data
-
Fuel
100% prime power -
Consumption
75% prime power -
(L/H)
50% prime power
Electrical system
Cranking motor (Heavy duty, 24V
positive engagement
Battery charging system, TBD
negative ground
Maximum allowable resistance 0.002 ohm
of cranking circuit
Minimum recommended battery 1800 CCA
capacity- cold soak
Fuel system
Injection system Cummins PT
Governor type Electronic
Maximum restriction at lift pump /
Maximum fuel inlet temperature /
Total drain flow /
(constant for all loads)
Alternator Specification
Emergency voltage curve
Sudden increase warp
Sudden voltage warp
Sudden decrease warp
520
464
+1%
380
352
296
0 1 2 3 4 5 6 7 8 9 10 1 1 1 2
70
62
54 +1%
50
-1%
46
38
30
0 1 2 3 4 5 6 7 8 9 10 1 1 1 2
δf%: -10.64 Benchmark phase: A Min. frequency: 44.68Hz Recovery time: 1.95s
Max. frequency: 53.87Hz Recovery time:
Alternator
Number of phase 3
Power factor (Cos Phi) 0.8
Poles 4
Winding Connections (standard) Star-serie
Terminals 12
Insulation type H class
Winding Pitch 2/3
IP rating IP23
Excitation system Self-excited
Bearing Single bearing
Coating Vacuum impregnation
Voltage regulator A.V.R
Couping Flexible disc
Options
Engine Alternator Generator Fuel System
Sets
-Water Jacket - Winding Temp - Tools with -Low fuel level
Pre-heater measuring the machine alarm
Instrument - Extended -Automatic fuel
-Fuel heater
- Alternator Pre- range fuel feeding system
heater tank
-Fuel T-valves
- PMG - Bunded fuel
- Anti-damp and tank
anti-corrosion
Treatment
- Anti-condensation
heater
- Winding and
bearing RTD
Canopy Lub oil system Cooling Control Panel
System
-Rental type - Oil Pre-heater - Front heat - Remote control
Canopy panel
Oil temp sensor protection - ATS
-Trailer - Synchronizing
controller
- Adjustable
earth leakage
relay
Control Panel
Configuration Benefits
· Less wiring and components
· Emergency stop button · Integrated solution
· Less engineering and programming
· Protection MCB · User friendly set-up and button layout
· Module can be configured to suit
· Battery charger individual applications
· PC software for simplified configuration
· Integrated aviation plug · Wide range of communication capabilities
· ATS connection
- · Digital control module
Operation conditions
· Operation temp: -20 ˚C to + 70 ˚C
· Storage temp: -30 ˚C to + 80 ˚C
· Operating humidity: 95% w/o condensation
· Vibration:5-25Hz, ±1.6 mm
5-100Hz, a= 4g
· Shocks: a= 500m/s²7
Options
- Ethernet interface (Remote monitoring and control)
- GSM modem/wireless internet (Remote monitoring and control)
- RS232-RS485 Dual port interface
- Synchronizing control panel
- Distribution board with sockets kit and power busbar
- Battery trickle charge ammeter
- Earth leakage protection
- Earth fault protection
- Low fuel level alarm
- Low fuel level shutdown
- High fuel level alarm
- Fuel transfer system control
- Low coolant level shutdown
- High lube oil temp shutdown
- Overload via alarm switch on breaker
- Engine coolant heater controls
- Control panel heater
- Speed adjust switch
- Oil temp displayed on LCD screen
- Additional 8 inputs and outputs
Features