Professional Documents
Culture Documents
Coordination of LV CB
Coordination of LV CB
Protection Devices
Internal
Co-ordination protection
Internal
The availability of electrical energy
and the LV protection plan
Co-ordination of
protection devices:
discrimination, cascading
Protection Plan & constraint limitation
Internal
LV co-ordination techniques
Optimising LV electrical distribution
through 3 actions at the Protection Plan Level
> 1 - discrimination to guarantee continuity of supply
Internal
Co-ordination of protection devices 1/3
1 - Discrimination
Internal
LV discrimination techniques
> Discrimination limit Is
> Is represents the fault current
- From which the 2 breakers trip IcuD1
- Before which only the downstream breaker trips
> Quality of discrimination IcuD2
> Comparison of the discrimination limit Is
to the presumed short-circuit current Isc
determines the quality of discrimination
> Total discrimination: Is > Isc
> Partial discrimination: Is < Isc
> Manufacturers catalog data: only D2 trips D1 and D2 trip
> Total discrimination: Is = IcuD2
> Partial discrimination: limited to Is < IcuD2
> Is is the intersection of D1 and D2 tripping curves
Internal
Current discrimination
> Linked to the natural staging of Long Delay curves of the association
> discrimination limit Is = Isd1
Internal
Time discrimination
> discrimination technique generally used on the incoming end of the installation
8
Internal
Logic discrimination (ZSI)
> Circuit-breakers fitted out with electronic trip units
> a pilot wire between upstream / downstream
circuit-breakers
> no threshold rules
> Implementation:
> The trip unit of the breaker located directly
upstream(D3)
- gives the order to trip the breaker
- send a signal to its upstream breaker (D2) to
prevent its tripping
> The upstream breaker (D2)
- delay its tripping due to the signal sent by D3
- send a signal to its upstream breaker (D1) to prevent its tripping
- will trip only if the fault has not been eliminated after the delay
> This technique
> is easily implemented
> reduces to a minimum constraints from delayed tripping of time discrimination
9
Internal
Energy discrimination
10
Internal
Energy discrimination
11
Internal
Discrimination
12
Internal
Discrimination
◼ Abstracted example of discrimination tables :
13
Internal
Co-ordination of protection devices 2/3
2 - limitation
14
Internal
Co-ordination of protection devices 2/3
2 - limitation
Current-limiting circuit breakers greatly reduce the negative effects of short-circuits on installations.
2. Thermal effects
Less temperature rise in conductors, therefore longer service life for cables.
3. Mechanical effects
Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars being deformed or
broken.
4. Electromagnetic effects
15
Internal
Co-ordination of protection devices 2/3
2 - limitation
Example
What is the real value of a 150 kA rms
prospective short-circuit (i.e. 330 kA peak)
limited by an NSX250L upstream ?
16
Internal
Co-ordination of protection devices 2/3
2 - limitation
Example
17
Internal
Co-ordination of protection devices 2/3
2 - limitation
➢ Energy limiting curves
Maximum permissible cable stresses
The table below indicates the maximum permissible thermal stresses for cables depending on their
insulation, conductor (Cu or Al) and their cross-sectional area (CSA). CSA values are given in mm² and
thermal stresses in A2s.
• The table above indicates that the permissible stress is 1.32x106 A2s.
• All short-circuit currents at the point where an NSX160F (Icu = 35 kA) is installed are limited with a
thermal stress less than 6x105 A2s. (look at the CB energy limiting curve)
• Cable protection is therefore ensured up to the limit of the breaking capacity of the circuit
breaker.
18
Internal
La coordination des protections 3/3
3 - Cascading
19
Internal
Cascading
➢ Example abstracts from cascading tables for a network 380/415 V :
20
Internal
Cascading in practice
21
Internal
Cascading ….in practice !!
source ❑ Primary substation: 2 x 1600kVA = 3.2 MVA
2880A ❑ 400V
250A
30m Selection of the devices required:
of cable
❑ Manual approach:
1) Standard selection of circuit breakers and ratings
panelboard
Isc 27kA … 2) Implementation of cascading
… 3) Checking selectivity
22
Internal
Standard choice of the main LV switchboard
circuit breaker
source
MLVS
Isc 81kA
Manufacturer
catalogue
250A
…
…
23
Internal
Standard choice of feeder circuit breakers
number rating type curve magnetic breaking capacity at 415V
of poles threshold (kA)
In
16 25 36 50
10..32..80
NG 125 H
Panelboard
Isc27kA
Isc 27kA …
…
catalogue
30A
10 office feeders
24
Internal
Now, with implementation of cascading
The NG 125 H is replaced by a smaller device: the iC60 N Manufacturer technical data
sheets
25
Internal
Checking for
selectivity
MLVS
NS250L
Isc
Isc27kA
27kA
iC60N
10 office feeders
Total Up graded
selectivity
30/30 Cascading
Up to (kA) Breaking
… capacity (kA)
26
selectivity 100% guaranteed
Internal
©2014 Schneider Electric. All Rights Reserved.
All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies or their respective owners. 27
Internal