(MFT tire alarm system
Addressable Module Input Type; Normally-Closed|Contact- Model Number FRROIUA-DB:
LZ
+ UL listed to standard 864, sth edition
+ NFPA Styles 4, 6, and 7 applicable for signal line circuit
+ Status LEDs for active and normal condition monitoring
+ Electronic address setting
+ Down-sized unit
+ Easy installation
PEE
The addressable module for normally-closed contact input devices provides the system with an ability to interface with
contact type devices. The module supervises its initiating Device Circuit (IDC) that can be connected to any normally
closed contact which opens to signal a status change. The status change can be supervisory or trouble condition that
needs to be monitored by the system. The module equips with a central microprocessor with memory that controls the
basic activities of the module, The CPU activity is supported by the internal power supply, transmission circuit, address
setting control, and IDC wiring monitor circuit.
‘The module is connected to addressable Signal Line Circuit (SLC) loop of Main Control Unit (MCU) and/or Sub Control
Unit (SCU). The module supports NFPA Style 4, 6, and 7 wiring methods for the SLC, The module also sources its
‘operating power from the SLC and provides the IDC supervision and activation detection functions associated with
contact type devices. The module uses an electronic address setting method that eliminates any mechanical switches.
‘The module supervises the voltage of its IDC. When an open circuit is detected the module informs the active condition
to MCU or SCU. If the module has been programmed for detecting alarm condition, the module activation condition
remains active at FACP until the system is reset. If the module has been programmed for detecting supervisory or
trouble condition, the module activation condition is cleared when the contact type device on IDC is reset to normal
condition.
‘The module contains two status indicators (LEDs): one red and one green. The green LED indicates normal monitoring
operation of the module when flashing. When a status change condition is detected on the IDC the green LED
extinguishes and the red LED begins flashing, When the status change is cleared (reset to normal) the red LED turns off,
and the green LED resumes flashing. The module informs MCU or SCU of the status change when itis cleared to
normal
POPES
+ Model no, FRROTUA-DB.
[ Specifications:
me rm Speciation
1 Rated voage range of SLC put poner Tate s07 VOC
7 [Maximus S10 74 VOC stand curert 201A
[Maximus S40 24 VDC alarm caret 290A
4 [Anplcabe Sc wing se NEPA Sivee 4 6 and
5 [Mass wig resstance a DS creat son
6 | Operating temperature range wim F Oa o)
7 [operat hui ange ie 58 (Nenzoncensing)
| Ween. of module ero 255 unis
3 | Dinensons san @ FDA TT xo SATO)
70 | ApieabnsioeiaT oxo ntaaton Tort Ararican 2-12 (nn) doo sale garaboe
Integlex fire alarm system
Catalog Number 08021000-F-12002¥01 NoHMTBOSAILTD.Normalhsed cote
ice Nee
cam Se
veer
soodlsd
ut tens
Installation in an electrical box
Installation on a plane plane
Ca
+ These instructions do not purport to cover all the details or variations in the equipment described, nor provide for every
possible contingency to be met in connection with installation, operation and maintenance.
+ Specifications are subject to change without notice, Contact Nohmi before relying on above specifications,
+ Actual performance is based on proper application of the product by a qualified professional
+ Should further information be desired or should particular problems arise, which are not covered sufficiently for the
purchasers purposes, the matter should be referred to Nohmi or a distributor in your region,