SCHEDULE LOADS

PROTECTION SWITCHES CONDUIT


CIRCUIT NO. DESCRIPTION NO. OF OULETS VOLTS WATTS AMPERES WIRE SIZES
PER CIRCUIT
S1 S2 S3
SIZE SCHEMATIC DIAGRAM
1 LIGHTING OUTLET 6 220 600 2.73 15 6 2-3.5mm² THIN COPPER WIRE 20 mm Ø
2 LIGHTING OUTLET 10 220 1000 4.55 15 4 1 2-3.5mm² THIN COPPER WIRE 20 mm Ø
3 CONVENIENCE OUTLET 6 220 1080 4.91 20 2-3.5mm² THIN COPPER WIRE 20 mm Ø
4 CONVENIENCE OUTLET 5 220 900 4.09 20 2-3.5mm² THIN COPPER WIRE 20 mm Ø
5 CONVENIENCE OUTLET 6 220 1080 4.91 20 2-3.5mm² THIN COPPER WIRE 20 mm Ø
6 CONVENIENCE OUTLET 4 220 720 3.27 20 2-3.5mm² THIN COPPER WIRE 20 mm Ø
7 REFRIGERATOR 1 220 750 3.41 30 2-3.5mm² THIN COPPER WIRE 20 mm Ø
TOTAL 6130 27.87

COMPUTATION:
FOR MAIN FEEDER:
LIGHTING LOAD= 1600 WATTS 60 AMP

CONVENIENCE OUTLET LOAD= 3780 WATTS


TOTAL= 5380 WATTS
SECONDARY RACK 1 15 AT 15 AT
2
SINGLE
FIRST 3000WATTS @ 100% DF= 3000 WATTS 1"Ø x 3.0 MTS. UPVC
ELECTRICAL PIPE
REMAINDERS AT 35% DF= 833 WATTS ( PROVISION FOR CABLING ) 3 20 AT 20 AT
4
TOTAL= 3833 WATTS
32 mmØ SERVICE
5 20 AT 20 AT
6
ACU @ 80% DF= 0 WATTS ENTRANCE CAP

RANGE @ 80% DF= 0 WATTS


REF @ 80% DF= 600 WATTS 7 30 AT

600 WATTS
2-22 MM² THW CU. WIRE
3833 WATTS IN 32 MMØ RSC
S
TOTAL= 4433 WATTS
0.25 M. x 0.25 M.
IT= 4433 WATTS CONC. CASING (TAPERED)

5.65 m
5.50 m
W/ 12 MMØ MAIN REBARS
220VOLTS & 9 MMØ TIESW @

5.20 m
1-0.05,1-0.10 REST @ 0.25 M.O.C.
CURRENT TOTAL= 20.15 AMPS

USE 2 - 8 MM^2 THHN COPPER WIRE ON 20 MM DIA. #6 TW


RSC. METER SOCKET
USE 60 AMP CIRCUIT BREAKER

SYMBOLS:
SPECIFICATIONS

2.25 m
ELECTRICAL NOTES
1. ALL INSTALLIONS SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION
1. ALL ELECTRICAL WORKS SPECIFIED HEREIN SHALL BE DONE IN OF THE PHILIPPINE ELECTRICAL CODE AND PERTINENT REQUIREMENT OF THE LIGHTING OUTLET
ACCORDANCE WITH THE PROVISIONS OF THE LATEST EDITION OF THE LOCAL POWER AUTHORITY.
PHILIPPINE ELECTRICAL CODE, LAWS AND REGULATIONS OF THE 2. ALL WIRE INSTALLIONS SHALL BE DONE IN RIGID PVC CONDUIT.
LOCAL UTILITY POWER COMPANY. 3. ALL NONE-CURRENT CARRYING PARTS OF ELECTRICAL APPLIANCES DEVICES CONVENIENCE OUTLET
2. INCOMING POWERS SHALL BE 230V, SINGLE PHASE, 3-WIRES; 60 SHALL BE PROVIDED WITH PERMANENT PLUGS.
HERTZ 4. ALL ELECTRICAL MATERIALS AND FIXTURES SHALL BE FREE FROM DEFECTS. CIRCUIT HOME RUN
3. ALL WIRING SHALL BE IN RIGID STEEL CONDUIT UNLESS 5. NECESSARY BOXES,FITTINGS,ETC. SHALL BE PROVIDED AS REQUIRED ,EVEN
OTHERWISE SPECIFIED. IF NOT SHOWN IN THE DRAWINGS. PANEL BOARD
4. BRANCH CIRCUIT AND FEEDER WIRES SHALL BE CODED. 6. ALL ELECTRICAL INSTALLATIONS SHALL BE DONE BY EXPERIENCE ELECTRICIAN
5. ALL FLUORESCENT LAMPS SHALL BE PROVIDED WITH RAPID START/ WITH THE DIRECT SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER.
0.25 m CIRCUIT BREAKER

VERIFY
PRE-HEAT BALLAST.
6. ALL MATERIALS SHALL BE NEW AND OF THE APPROVED TYPE FOR

0.25 m
THE LOCATIONS AND PURPOSES INTENDED TO. M KILO WATT HOUR METER

0.50 m

0.20 m
7. ALL WORKS SHALL BE EXECUTED UNDER THE DIRECT
SUPERVISIONS OF A DULY REGISTERED PROFESSIONAL ELECTRICAL
ENGINEER.
SERVICE ENTRANCE
8. CONFORM THE ARCHITECT, THE TYPE AND COLOR RENDERING
CATALOGS/INDEX OF LIGHTING FIXTURES BEFORE FINAL GROUND LINE
INSTALLATION.
9. VERIFY ARCHITECTURAL DRAWINGS FOR LIGHTING FIXTURES AND
WIRING DEVICES INCLUDING EXACT LOCATIONS AND MOUNTING 0.50 m S2 DOUBLE GANG SWITCH
HEIGHTS. PLAN 0.50M. x 0.50M. COLUMN
10. REFER TO ELECTRICAL TECHNICAL SPECIFICATIONS FOR FOOTING WITH 4 - 12mmØ
S1 SINGLE GANG SWITCH
FURTHER INSTRUCTIONS.
REBARS BOTHWAYS
0.50 m
11. NO REVISIONS IN THE DESIGN NOR ADDITIONAL LOADS SHALL BE
DONE WITHOUT THE PRIOR KNOWLEDGE OR APPROVAL OF THE ACU
BUILDING ENGINEER AND THE DESIGNER, ANY SUCH REVISION
WITHOUT APPROVAL SHALL CAUSE RESPONSUBILITY OF THE DESIGNER TO CEASE AS A WHOLE. ENTRANCE POST DETAIL
SCALE 1:50 m R RANGE

DESIGNER: SEAL: REPUBLIC ACT SECTION 25(4) PROJECT TITLE: PROJECT OWNER: SHEET
SIGNATURE: 545.
Drawing and Specification duty signed and
NO.
stamped or sealed as instrument of service
are properties of the Author whether the

BEAVER object for which they are models executed


or not. It is unlawful for any person, PROPOSED 2- STOREY RESIDENTIAL HOUSE ABIGNIGO BARCOMA E 2
without the writer consent of the author of
INC PRC NO:

IAPOA NO:
VALIDITY:
O.R. NO:
the said document to duplicate or copy for
use in other projects, whether executed
partly or in whole.
PTR NO: DATE:
ADDRESS: CUGMAN ,CAGAYAN DE ORO CITY PLACE: TIN: LOCATION: ZONE 2, KAWILIHAN, CUGMAN, CDOC ADDRESS: ZONE-2 CUGMAN, MISAMIS ORIENTAL

You might also like