PROJECT ADDRESS BELOW TO GET SDS VALUE

USE z/h ratio of 2/35 for Fp calcs


SEE WALL MOUNT NEXT PAGE
Wall Mounting Instructions

1) Punch out the two small knock-outs located on each


side, at the top and towards the back of the enclosure.

2) Mount one angle bracket (A) over each of the two holes A
as shown using one of each of the 3/8” bolts, washers,
lock washers and nuts. (With the head of the bolt on the
outside of the enclosure.)

3) Mount the other two angle brackets (B) on the outside


face of each of the enclosure mounting channels (C) as
shown, using two of the 1/2 bolts, washers, lock washers
and nuts for each.
B
4) Carefully, using a properly rated fork lift, raise the
transformer into your pre-measured, marked and drilled
position and attach the unit to the wall using a minimum of
Grade 8 hardware.

5) Position the bottom drip plate (D) underneath the unit C


D
onthe bottom of the enclosure channels as shown. Attach
the drip plate using four of the 1/2” bolts, washers, lock
washers and nuts. Wall Mount Configuration
IMPORTANT
Please ensure your wall mounting location and
position meets all local building and fire codes and
regulations.

DW3 WALL MOUNT - MOUNTING DIMENSIONS


STRUCTURAL NOTES
GENERAL

1. THE GOVERNING CODE IS THE 2015


2021 INTERNATIONAL BUILDING CODE (IBC) AS
AMENDED BY THE 2022 OREGON
ACI 318-14, STRUCTURAL SPECIALTY CODE (OSSC), ACI
ASCE 7-16.
318-19, ASCE 7-16.
2. ALL FEATURES OF CONSTRUCTION NOT FULLY SHOWN SHALL BE OF THE SAME
TYPE AND CHARACTER AS SHOWN FOR SIMILAR CONDITIONS, SUBJECT TO
REVIEW BY THE ENGINEER.

3. ALL PRODUCTS AND MATERIALS USED BY THE CONTRACTOR SHALL BE INSTALLED


IN STRICT ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.

4. CONTRACTOR SHALL COMPARE ALL CONDITIONS AND DIMENSIONS WITH


STRUCTURAL PLANS AND DETAILS AS SHOWN IN THIS SET, AND NOTIFY THE
ENGINEER OF ANY DISCREPANCIES RIGHT AWAY.

5. ADEQUACY OF EXISTING STRUCTURE IS RESPONSIBILITY OF OTHERS.

DESIGN CRITERIA

1. DESIGN WAS BASED ON THE STRENGTH AND DEFLECTION CRITERIA OF THE IBC.
IN ADDITION TO THE DEAD LOADS AND EQUIPMENT LOADS THE FOLLOWING
LOADS WERE USED FOR DESIGN:

1.1. EARTHQUAKE DESIGN WAS BASED UPON THE FOLLOWING:


SDS = 0.709, Ip =1.5

POST INSTALLED CONCRETE ANCHORS 4266

1. ANCHORS IN CONCRETE SHALL CONFORM TO ESR-1917 PERIODIC SPECIAL


INSPECTION IS REQUIRED.

MINIMUM CONCRETE COMPRESSIVE STRENGTH, f'c = 2500 PSI.

you will get that value


via ATC hazard tool
online 3000

TARGET GALLERIA
AKH 20-1059
TRANSFORMER T-1
PORTLAND, OR 12/30/2020
THIS IS JUST FOR REFRENCE,TO
SHOW YOU OUR DRAFTING STYLE,
OUR EQUIPMNET ARE SIMILAR
CONCEPT BUT WALL MOUNTED
UNIT OUTLINE

8 1/4" TYP.
A

2'-9 11/16" MAX.


WT=1624 LBS
1 "
Ø SS 304
2
HILTI KB-TZ
W/2" EMBED,
4 7/16" TYP.

3'-2" TYP.

TRANSFORMER ANCHORAGE PLAN VIEW


1 Scale: 3/4"=1'-0"

UNIT OUTLINE

UNIT BASE (BY OTHERS)


(E) MIN. 2500PSI
CONCRETE PLANCK (BY 1 " Ø SS 304 HILTI
4"

2
OTHERS) KB-TZ W/2" EMBED.,TYP
4 PER SIDE.
3 1/2"
MIN

6"
MIN

EQUIPMENT CONNECTION DETAIL


A Scale: NTS

TARGET GALLERIA
AKH 20-1059
TRANSFORMER T-1
PORTLAND, OR 12/30/2020
THIS IS ANOTHER EXAMPLE OF A
WALLMMOUNTED EQUIPMENT BUT TO WOOD
STUD WALL, OURS HERE ARE TO CONCRETE
WALL WITH HILTI ANCHORS