Design company: Amelicor Engineering AG

Kantonstrasse 57,
3930 Eyholz, Switzerland

Client: Lonza AG
Hochbergerstrasse 60A
CH-4057 Basel

Project Name: KUJIRA


Location: Rottenstrasse 6
CH-3930, Visp, Switzerland

Project Number: SAP IM 422197 / P.4222.51

Document Title: Technical Description – Cooling water MKWH, HLK, MKWP, MKWE
Document Code: LVK_OV_DD_MC_TD_01_01

Document Approval
Author Company Date Signature
Function Department
Nemanja Kojić
Amelicor Engineering AG 06-DEC-2023
Lead engineer BU
Review Company Date Signature

Amelicor Engineering AG

Approval Company Date Signature

Revision History
Version Date Author Remarks
1 06-DEC-2023 Nemanja Kojić First Issue
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

TABLE OF CONTENTS

1 Introduction & Purpose .............................................................................................................. 3


Project information ................................................................................................................ 3
Applicable rules and standards........................................................................................... 3
2 cooling water system Technical Description .......................................................................... 5
Media and material specifications ...................................................................................... 5
Required capacities .............................................................................................................. 7
Technical Description ......................................................................................................... 12
2.3.1 Functions of the Cooling system ............................................................................... 12
2.3.2 Cooling water HVAC system design – AHU coils................................................... 12
2.3.3 Cooling water HVAC - Run – around systems for AHU ........................................ 13
2.3.4 Cooling water HVAC - PIFF Units ............................................................................. 13
2.3.5 Cooling water HVAC - Coolers for technical area .................................................. 14
2.3.6 MKWE- Ice water ......................................................................................................... 14
2.3.7 MKWP - Process cooling water ................................................................................. 14
3 Design parameters ................................................................................................................... 15
4 Abbreviation .............................................................................................................................. 17

Date: 06.12.2023.
Page 2 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

1 INTRODUCTION & PURPOSE


The present Technical Report elaborates design of the Cooling water systems that shall
be installed in the facility of LONZA AG in Visp – KUJIRA Project.
The design of Cooling water system is developed in accordance with:
• Building architectural and structural design;
• Room types, subject to the process requirements for these rooms;
• Concept Design for KUJIRA Project
• Applicable standards and regulations
• GMP zone
• As built documentation

Project information

Project details
Client Lonza AG
Project name Kujira
Project location Rottenstrasse 6, CH-3930 Visp, Switzerland
MC01 Wing-2:
Level 0 (+0) DMA tank, OWWT Iruka extension = Existing areas
Level 5 (+24.000) Cleanroom area (Grade C, D and CNC) = 1721 m2
Building Level 5 (+24.000) Gowning area = 189 m2
Level 6 (+28.500) Technical area = 1244 m2
I-12:
Level 0 (+0) Technical area= 118 m2
Basis of design review
Detail design
Project phases
Execution
As built

Applicable rules and standards


For all activities, from design to construction, start-up, and validation the general
pharmaceutical laws/norms and Compliance Regulations are obligatory and have to be
followed:
 European norms: (EN 10216-2, EN 1092-1, EN 14304, EN ISO 15494/C),
 National guidelines,
 American Society of Heating, Refrigerating and Air Conditioning Engineers
(ASHRAE) Publications

Lonza Standards
 Technical Standard_191011
 CHVI-193925 PID HLK Musteranlage
 CHVI-320245 HVAC design concept table
 0060_200 Rohrklassenübersicht

Date: 06.12.2023.
Page 3 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

 0063_001 Rohrklasse LH001; bis 8 bar max. 100°C,CrNi(Mo)


 0063_130 Rohrklasse LH130; Versorgungsmedien für HLK
 CHVI-108513 Richtlinien für Rohrleitungsisometrien; TR 0022-400
 LST-GEN-GEN-PRO-010_Fluid list
 3500_051 Thermische Dämmungen, Rohrleitungen
 3500_054 Thermische Dämmungen Apparate
 Festlegung der Isolationsarten an Rohrleitungen
 TR BCI 158_2017_06_22

Besides these regulations, there have to be followed all other relevant national
regulations for the particular systems.
In the case of different requirements, the most stringent regulation applies.
The system should operate safely.

Date: 06.12.2023.
Page 4 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

2 COOLING WATER SYSTEM TECHNICAL DESCRIPTION


The present Technical Description elaborates design of the Heating systems that shall
be installed in the LONZA AG in Visp – KUJIRA Project, and utilities are extended from the
existing systems in Visp, Switzerland.
The design of Heating system is developed in accordance with:
 Building architectural and structural design;
 Required capacities data from HVAC

Media and material specifications

Cooling water generation, for all three type of cooling water: Cooling water HVAC, AHU
run-around recuperators, Cooling water process and Ice water, equipment is not included in
the scope of the project. Generation and main distribution loop is in Lonza scope.

Media specification:

MKWH - HVAC cooling water:


Supply temperature: ........................................... 12 °C
Return temperature: ........................................... 18 °C
Working fluid: ……………………………………… pure water
Design pressure: ................................................ max. 8 barg

Media specification:

HLK – AHU run-around recuperators:


Supply temperature: ........................................... according to system
Return temperature: ........................................... according to system
Working fluid: ……………………………………… 40% ethylene glycol
Working pressure: .............................................. max. 8 barg

Media specification:

MKWP - Process cooling water:


Supply temperature: ........................................... 18 °C
Return temperature: ........................................... 26 °C, (38 °C WFI Distribution Loop)
Working fluid: ……………………………………… pure water
Design pressure: ................................................ max. 8 barg

Media specification:

MKWE- Ice water:


Supply temperature: ........................................... 2 °C
Return temperature: ........................................... 10 °C
Working fluid: ……………………………………… pure water
Design pressure: ................................................ max. 6 barg

Date: 06.12.2023.
Page 5 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

Pipe work and fittings will be executed according Lonza standards.


Primary piping will be executed according Lonza pipe standard LH001, while secondary
(connections to cooling water consumers) will be executed according Lonza pipe standard
LH130.
Fittings are selected according to those pipe type standards, and overview per each
application, is given in separate document “Specification of equipment per application”.

Date: 06.12.2023.
Page 6 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

Required capacities
MKWH - HVAC cooling capacities are shown below:

EQUIPMENT ROOM SUPPLY TEMP DIVERSITY CONNECTED LOADS


NAME NUMBER TEMP DIFF. FACTOR HEAT FLOW
TRANSFER RATE
(°C) (°C) (kW) (M3/HR)

E6402-Technical
740-VH001 - AHU 12 6 1,0 137,9 19,70
Area HVAC
E6402-Technical
740-VH002 - AHU 12 6 1,0 110,8 15,83
Area HVAC
E6402-Technical
740-VH003 - AHU 12 6 1,0 20,7 2,96
Area HVAC
E6402-Technical
740-VH004 - AHU 12 6 1,0 10,7 1,53
Area HVAC
E6402-Technical
740-VH005 - AHU 12 6 1,0 16,8 2,40
Area HVAC
740-VH005V21 - E6402-Technical
12 6 1,0 12,1 1,73
Unit Cooler Area HVAC
740-VH005V22 - E6402-Technical
12 6 1,0 12,1 1,73
Unit Cooler Area HVAC
740-VH005V23 - E6402-Technical
12 6 1,0 12,1 1,73
Unit Cooler Area HVAC
740-VH005V24 - E6402-Technical
12 6 1,0 12,1 1,73
Unit Cooler Area HVAC
740-VH005V25 - E6402-Technical
12 6 1,0 12,1 1,73
Unit Cooler Area HVAC
740-VH005V26 - E6402-Technical
12 6 1,0 12,1 1,73
Unit Cooler Area HVAC
740-VH005V31 - E6401-Technical
12 6 1,0 18,0 2,57
Unit Cooler Area Utilities
740-VH005V32 - E6401-Technical
12 6 1,0 18,0 2,57
Unit Cooler Area Utilities
740-VH005V33 - E6401-Technical
12 6 1,0 18,0 2,57
Unit Cooler Area Utilities
740-VH005V34 - E6401-Technical
12 6 1,0 18,0 2,57
Unit Cooler Area Utilities

740-VP010 - E5453-Buffer
12 6 1,0 2,6 0,37
Downflow Booth preparation

740-VH005V01 - E5426-Buffer
12 6 1,0 2,6 0,37
PIFF Hold
740-VH005V02 - E5426-Buffer
12 6 1,0 2,6 0,37
PIFF Hold
740-VH005V03 - E5426-Buffer
12 6 1,0 2,6 0,37
PIFF Hold
740-VH005V04 - E5426-Buffer
12 6 1,0 2,6 0,37
PIFF Hold
740-VH005V05 - E5426-Buffer
12 6 1,0 2,6 0,37
PIFF Hold

Date: 06.12.2023.
Page 7 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

740-VH005V06 - E5426-Buffer
12 6 1,0 2,6 0,37
PIFF Hold
740-VH005V07 - E5426-Buffer
12 6 1,0 2,6 0,37
PIFF Hold
740-VH005V08 - E5426-Buffer
12 6 1,0 2,6 0,37
PIFF Hold
740-VH005V11 - E5421-Buffer
12 6 1,0 2,6 0,37
PIFF Hold
740-VH005V12 - E5421-Buffer
12 6 1,0 2,6 0,37
PIFF Hold
740-VH005V13 - E5421-Buffer
12 6 1,0 2,6 0,37
PIFF Hold
740-VH005V41 - E5429-Freezer
12 6 1,0 2,1 0,30
Hygienic Cooler Room
740-VH005V42 - E5429-Freezer
12 6 1,0 2,1 0,30
Hygienic Cooler Room
740-VS731A1 - E6402-Technical
12 6 1,0 9,0 1,29
Cooling Generator Area HVAC
740-VS731A2 - E6402-Technical
12 6 1,0 9,0 1,29
Cooling Generator Area HVAC
740-VS732A1 - E6402-Technical
12 6 1,0 9,0 1,29
Cooling Generator Area HVAC
740-VS732A2 - E6402-Technical
12 6 1,0 9,0 1,29
Cooling Generator Area HVAC
E6402-Technical
Future Connection 12 6 1,0 50,0 7,14
Area HVAC
E6402-Technical
Future Connection 12 6 1,0 50,0 7,14
Area HVAC
E6402-Technical
Future Connection 12 6 1,0 50,0 7,14
Area HVAC
E6402-Technical
Future Connection 12 6 1,0 50,0 7,14
Area HVAC
E6402-Technical
Future Connection 12 6 1,0 50,0 7,14
Area HVAC

TOTAL DEMAND 763 kW 109 m3/h

Capacities and connections to existing coolin system are agreed and confirmed by Lonza.

Date: 06.12.2023.
Page 8 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

MKWP - Process cooling capacities are shown below:

EQUIPMENT ROOM SUPPLY TEMP DIVERSITY DESIGN LOADS


NAME NUMBER TEMP DIFF. FACTOR HEAT FLOW
TRANSFER RATE
(°C) (°C) (kW) (M3/HR)

SYSTEM DIVERSITY: 57%

Autoclave E5471 20 40 1,0 607 13,00

Product Bag Freezing E5425 18 8 1,0 15 1,65

Product Bag Freezing E5429 18 8 1,0 15 1,65

Product Bag Freezing E5429 18 8 1,0 15 1,65

Product Bag Freezing E5429 18 8 0,0 0 0,00

Product Bag Freezing E5429 18 8 0,0 0 0,00

Product Bag Freezing E5429 18 8 0,0 0 0,00

Product Bag Freezing E5429 18 8 0,0 0 0,00

Product Bag Freezing E5429 18 8 0,0 0 0,00

Plate Freeze and Thaw


E5445 18 8 0,1 2 0,17
Unit
Plate Freeze and Thaw
E5445 18 8 0,1 2 0,17
Unit
Cryo TCU E5428 18 8 0,0 0 0,00
Cryo TCU E5428 18 8 0,0 0 0,00
WFI Distribution Loop 1
Cold - Cooling E6401 18 20 0,0 0 0,00
Exchanger #1
WFI Distribution Loop 1
Cold - Cooling E6401 18 20 1,0 809 34,67
Exchanger #2
WFI Distribution Loop 2
Cold - Cooling E6401 18 20 1,0 1011 43,33
Exchanger #1
WFI Distribution Loop 2
Cold - Cooling E6401 18 20 0,0 0 0,00
Exchanger #2
TCU for Buffer Prep
E6502 18 8 0,0 0,0 0,0
Tank 3 550L (VP003)
TCU for Buffer Prep
E6502 18 8 0,0 0,0 0,0
Tank 4 550L (VP004)
TCU for Buffer Prep
E6502 18 8 1,0 28,7 3,1
Tank 1 3000L (VP001)
TCU for Buffer Prep
E6502 18 8 0,0 0,0 0,0
Tank 2 3000L (VP002)

Date: 06.12.2023.
Page 9 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

TCU for Buffer Hold


E6502 18 8 0,0 0,0 0,0
Tank 1 3000L (VP031)
TCU for Buffer Hold
E6502 18 8 1,0 43,5 4,7
Tank 2 9000L (VP032)
TCU for Buffer Hold
E6502 18 8 0,0 0,0 0,0
Tank 3 9000L (VP033)
TCU for Buffer Hold
E6502 18 8 0,0 0,0 0,0
Tank 1 3000L (VP041)
TCU for Buffer Hold
E6502 18 8 0,0 0,0 0,0
Tank 2 9000L (VP042)
TCU for Buffer Hold
E6502 18 8 0,0 0,0 0,0
Tank 3 9000L (VP043)
TCU for Process Tank
E6502 18 8 1,0 23,7 2,5
PT1 1200L (VP131)
TCU for Process Tank
E6502 18 8 0,0 0,0 0,0
PT2 1200L (VP132)
TCU for Process Tank
E6502 18 8 1,0 23,7 2,5
PT1 1200L (VP141)
TCU for Process Tank
E6502 18 8 0,0 0,0 0,0
PT2 1200L (VP142)
TCU for Process Tank
E6502 18 8 0,0 0,0 0,0
PT3 700L (VP133)
TCU for Process Tank
E6502 18 8 0,0 0,0 0,0
PT3 700L (VP143)

DR Sample Cooler E6502 18 8 0,0 0,0 0,0

DR Sample Cooler E6502 18 8 0,0 0,0 0,0

DR Sample Cooler E6502 18 8 0,0 0,0 0,0

DR Sample Cooler E6502 18 8 0,0 0,0 0,0

DR Sample Cooler E6502 18 8 0,0 0,0 0,0

DR Sample Cooler E6502 18 8 0,0 0,0 0,0

DR Sample Cooler E6502 18 8 0,0 0,0 0,0

TOTAL DEMAND 2.596 kW 109 m3/h

Date: 06.12.2023.
Page 10 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

MKWE- Ice water capacities are shown below:


EQUIPMENT ROOM SUPPLY TEMP DIVERSITY DESIGN LOADS
NAME NUMBER TEMP DIFF. FACTOR HEAT FLOW
TRANSFER RATE
(°C) (°C) (kW) (M3/HR)
SYSTEM DIVERSITY: 21%
TCU for Buffer Prep Tank 3
E6502 2 8 0,0 0,0 0,0
550L (VP003)
TCU for Buffer Prep Tank 4
E6502 2 8 0,0 0,0 0,0
550L (VP004)
TCU for Buffer Prep Tank 1
E6502 2 8 1,0 41,8 4,5
3000L (VP001)
TCU for Buffer Prep Tank 2
E6502 2 8 0,0 0,0 0,0
3000L (VP002)
TCU for Buffer Hold Tank 1
E6502 2 8 0,0 0,0 0,0
3000L (VP031)
TCU for Buffer Hold Tank 2
E6502 2 8 1,0 68,1 7,3
9000L (VP032)
TCU for Buffer Hold Tank 3
E6502 2 8 0,0 0,0 0,0
9000L (VP033)
TCU for Buffer Hold Tank 1
E6502 2 8 0,0 0,0 0,0
3000L (VP041)
TCU for Buffer Hold Tank 2
E6502 2 8 0,0 0,0 0,0
9000L (VP042)
TCU for Buffer Hold Tank 3
E6502 2 8 0,0 0,0 0,0
9000L (VP043)
TCU for Process Tank PT1
E6502 2 8 1,0 20,3 2,2
1200L (VP131)
TCU for Process Tank PT2
E6502 2 8 0,0 0,0 0,0
1200L (VP132)
TCU for Process Tank PT3
E6502 2 8 0,0 0,0 0,0
700L (VP133)
TCU for Process Tank PT1
E6502 2 8 0,0 0,0 0,0
1200L (VP141)
TCU for Process Tank PT2
E6502 2 8 0,0 0,0 0,0
1200L (VP142)
TCU for Process Tank PT3
E6502 2 8 0,0 0,0 0,0
700L (VP143)

TOTAL DEMAND 130 kW 14 m3/h

Date: 06.12.2023.
Page 11 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

Technical Description

2.3.1 Functions of the Cooling system

Cooling water HVAC is used as cooling medium for following users:

- AHU, 5 users, room E6402-Technical Area HVAC,


- Unit Cooler, 6 users, room E6402-Technical Area HVAC
- Unit Cooler, 4 users, room E6401-Technical Area Utilities,
- Downflow Booth, 1 user, room E5453-Buffer preparation,
- PIFF, 8 users, room E5426-Buffer Hold,
- PIFF, 3 users, room E5421-CNC Corridor,
- Hygienic Cooler, 2 users, room E5429-Freezer Room
- Cooling Generator, 2 users, room E6402-Technical Area HVAC

Cooling water for AHU run-around recuperators is used as cooling medium for following users

- AHU, 5 users, room E6402-Technical Area HVAC,

Cooling water process is used as cooling medium for following users:

- Autoclave, 1 user, room E5471,


- Plate Freeze and Thaw Unit, 1 user, room E5425,
- Plate Freeze and Thaw Unit, 7 users, room E5445,
- Cryo TCU, 2 users, room E5428,
- WFI Distribution Loop Cold, 4 users, room E6401,
- TCU, 16 users, room E6402,
- DR Sample Cooler, 3 users,

Ice water is used as cooling medium for following users:

- TCU, 16 users, room E6402,

2.3.2 Cooling water HVAC system design – AHU coils

Cooling water for systems noted above will be generated in separate cooling plant
which is not in scope of this project. Therefore, we will not design any safety equipment for
this system (safety valves, expansion vessels).
Connection to existing pipes DN150 is in technical shaft.
AHU coils are with variable flow. All coolers have regulation with constant supply
temperature and variable flow. This is achieved with 2-way control valve (modulating
Date: 06.12.2023.
Page 12 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

regulation). Valve is controlled by air desired temperature. Temperature indicators are


installed on supply and return pipe.
All consumers have balancing valves for proper hydraulic balancing of cooling system.
Air vents are predicted on system high points so that is possible to remove all air from
hydraulic system.

2.3.3 Cooling water HVAC - Run – around systems for AHU

Recuperation of heat in AHUs is realized by run – around systems between supply


and exhaust AHU units.
Temperature regime is individual for each circuit and we will get it from the selection of
AHUs. Exact temperature regime will be indicated on schematic drawing.
Run-around loop is consisting from pump, pipes and pipe accessories.
Frost protection of run-around heat exchanger is achieved with use of three-way valve.
Run-around loop is secured with use of expansion vessel and safety valve.

2.3.4 Cooling water HVAC - PIFF Units

The Plenum Integrated Filter Fan (PIFF) is a fan filter unit with integrated return air,
cooling coil and HEPA filter. It is used to supply turbulent mixed airflow while reducing the
concentration of particles and the temperature inside of clean environments.
PIFF has a function to:
• control temperature of the rooms via cooling coils
• provides the proper amount of clean air to rooms (particle reduction)
The PIFF unit fulfils the following functions:
• Filtration – Return air ISO Coarse (G4)
• Filtration – Supply air H13
• Cooling

Temperature of supply air depends on of temperature inside the room. The unit is working
in 100% recirculation.
To prevent condensation on cold surfaces and avoid water dripping in the clean room
cooling coil is connected to 14/20 °C water cooling system.
PIFF coils are with variable flow. All coolers have regulation with constant supply
temperature and variable flow. This is achieved with 2-way control valve (modulating
regulation). Valve is controlled by air desired temperature.

Date: 06.12.2023.
Page 13 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

2.3.5 Cooling water HVAC - Coolers for technical area

The industrial air coolers for technical area are air coolers with integrated cooling coil
and fan. It is used to supply cold air into room from front side, and collect hot air from rear
side.

Temperature of supply air depends on of temperature inside the room. The unit is working
in 100% recirculation

2.3.6 MKWE- Ice water

Existing DN150 flanged MC1 connections for Ice water is located on Level 1 technical
shaft. That connection should be continued until Level 6, also with two DN100 main branches
with valves for Kujira purpose.
Ice water consumers are located in E6402 Technical Area, on grating area between
AHU. Consumers are TCU (Temperature Control Units) with purpose to obtain hot/cold water
distribution to process tanks on Level 5.

2.3.7 MKWP - Process cooling water

Connection to existing pipes DN150 is in technical shaft.


At 6th floor there are WFI loop skids consumers in technical area utilities and in
interstitial space are located TCU units and clean steam sample coolers.
At 5th floor there are PFT users in bag thawing room and in storage CNC, autoclave
in technical room. In Cryovessel thaw room are two TCU comsumers.
Number of Users:
- Autoclave, 1 user, room E5471,
- Plate Freeze and Thaw Unit, 1 user, room E5425,
- Plate Freeze and Thaw Unit, 7 users, room E5445,
- Cryo TCU, 2 users, room E5428,
- WFI Distribution Loop Cold, 4 users, room E6401,
- TCU, 16 users, room E6402,
- DR Sample Cooler, 3 users,

Date: 06.12.2023.
Page 14 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

3 DESIGN PARAMETERS
Cooling system pipes are designed according to following parameters:

Cooling system Distribution Net


Operating temperature According to loop
Operating pressure 3-8 bar (g)
Design pressure PN 16
Up to DN100 - 1,5 m/s
Maximum design velocity
Up to DN250 – 2 m/s
Maximum design pressure 150 Pa/m
drops

Piping installation will be designed to be drainable. Design will include low point
drains, installed in accordance with the LONZA Design principles

Cooling lines are sized according to optimal velocity and specific pressure drop.
Pipes are sized according adopted utilization factor for all consumers.

Piping and other fittings shall be supported, anchored, or guided to prevent undue
line deflection or excessive vibration. For calculation and construction stainless steel pipes
are used according to ISO 1127:

Seamless steel pipes according to ISO


1127
DN Ds, mm δ, mm D, mm
10 17 1.8 13.6
15 21.3 2 17.3
20 26.9 2.3 22.3
25 33.7 2.6 28.5
32 42.4 2.6 37.2
40 48.3 2.6 43.1
50 60.3 2.9 54.5
65 76.1 2.9 70.3
80 88.9 3.2 82.5
100 114.3 3.6 107.1
125 139.7 4 131.7
150 168.3 4.5 159.3
200 219.1 6.3 206.5
250 273 6.3 260.4

All pipes must be insulated according to functional requirements - operating


temperature, permissible heat losses or temperature changes of the medium, frost
protection, ambient conditions, and LONZA documents:
 3500_051 Thermische Dämmungen, Rohrleitungen
 3500_054 Thermische Dämmungen Apparate
 Festlegung der Isolationsarten an Rohrleitungen

Date: 06.12.2023.
Page 15 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

Cooling water (MKWH, MKWP) pipes insulation is LONZA type T60, elastomer type, with
following thicknesses:

 pipe sizes up to DN100 δ=13mm


 pipe sizes DN125 and larger δ=19mm

For ice water - MKWE pipes insulation is LONZA type K51, PUR with AL coating type, with
following thicknesses:

 pipe sizes up to DN150 δ=50mm

Date: 06.12.2023.
Page 16 of 17
Document title: Technical Description
Client: Lonza AG
Project Name: Kujira
Project Number: SAP IM 422197

4 ABBREVIATION

AHU Air Handling Unit


HEX Heat exchanger
CE Conformité Européenne
DIN Deutsches Institut für Normung
FDA Food and Drugs Administration
GMP Good Manufacturing Practice
HEPA High-Efficiency Particulate Air
HSE Health Safety Environment
HVAC Heating Ventilation Air Conditioning
ISO International Standardization Organization
ISPE International Society for Pharmaceutical Engineering
QC Quality Control
QM Quality Management
SOP Standard Operating Procedures
URS User Requirements Specification
BOM Bill of Materials

Date: 06.12.2023.
Page 17 of 17