Professional Documents
Culture Documents
AQT 10 Edit
AQT 10 Edit
com
Diesel Power Generation
Control System & Power Solutions
Output Rating:
Standard Specifications: PRIME: STANDBY:
50 Hz—1500 Rpm 400 V, 3ph
9 kVA 7 kW 10 kVA 8 kW
1 Prime Rating:
Unlimited hours usage, with an average 60 Hz—1800 Rpm 480 V, 3ph
load factor of 80% over each 24 hour peri- 9 kVA 7 kW 10 kVA 8 kW
od. 10% overload is available for 1 hour in ENGINE SPECIFICATIONS
every 12 hours operation. Engine Make PERKINS
o overload is permitted on standby power. Engine Model 403A-11G1
No. of Cylinders 4 vertical in-line
2 Standby Rating: Cycle 4 Strokes
Limited to 500 hours annual usage, with an Aspiration Naturally Aspirated
average load factor of 80% of the pub- Cooling Method Water cooled
lished standby power rating over each 24 Governing Type Mechanical
hour period. Up to 300 hours of annual Governing Class G2 - ISO 8528 Part 1
usage may be run continuously. Compression Ratio 23.3:1
No overload is permitted on standby pow- Displacement 2.216 L
er. Bore/Stroke 84 x 100 mm
Dynamic Charging Alternator 15AMP, 12V
3 Engine: ALTERNATOR SPECIFICATIONS
Perkins, including air filters, fuel filters, Alternator Make Leroy Somer | STAMFORD | AQT
oil filter, starting motor and charging alter- Alternator Model TAL-040-F
nator etc. Number of Poles 4
Number of Winding Leads 6
4 AlternatorType: Type of Bearing Single Bearing
brushless AC alternator Insulation Class - Temp Rise Cont. H - 125/40 ̊C
Ingress Protection Rating IP 23
5 Radiator: Excitation System Self Excited
50°C, fan protective shroud AVR Model R120
Comply with Standards
ISO 3046, BS 5514, DIN 6271, NEMA-MGI, DIN EN, BS 5000, IEC 60034,IEC 60947-2
www.aqtgenerators.com | info@aqtgenerators.Com | Dubai, Alnahda2 AL Murjan Tower, 409 | (04) 547 1703
Standard Specifications:
Control System:
6– Fuel Tank:
Large back-lit text display protection
Capacity of fuel tank is for 8 hours Multiple display languages Generator overload protection (kW)
DSENet® expansion Breaker control via fascia buttons
running compatible Fuel and start outputs, configurable when
Built in fuel tank up to 800 kVA Data logging facility using CAN
Fully configurable via PC using USB com- 4 configurable DC outputs
munication 4 configurable analogue/digital inputs
7- Circuit Breaker: Front panel configuration Automatically transfers between mains
Efficient power save mode (utility) and generator
3 phase generator sensing Increased input and output expansion
3 pole LS MCCB capability via DSENet ®
Accumulated power
monitoring IP65 rating (with optional gasket) offers
8– Control system alarms: (kW h, kVA h, kVAr h) increased resistance to water ingress
Generator/load current monitoring and
DIGITAL INPUTS
•Over and Under Speed ANALOGUE INPUT
•Low and High Battery Volt.
•Start and Stop Failure
•Over Current
•Under / Over Generator Voltage DSE4520 MKII
•Low Oil Pressure AUTO START & AUTO MAINS
•Emergency stop FAILURE CONTROL
•High engine temperature
9– Warranty policy:
www.aqtgenerators.com | info@aqtgenerators.Com | Dubai, Alnahda2 AL Murjan Tower, 409 | (04) 547 1703
Engine:
Optional configurations:
Engine accessories:
🗆 Heavy-duty air filter
🗆 Coolant heater
🗆 Lubricant oil heater
🗆 Fuel and Water Separator
🗆 Lube oil rotary pump
Cooling System:
🗆 55 degree Radiator
🗆 Remote Radiator
Control System:
🗆 AMF
Perkins heavy duty high performance industrial type diesel engine.
🗆 Parallel
🗆 Practical type in low temperature environment
COOLING SYSTEM 🗆 Control Screen Heater
Total Coolant Capacity (L) 7.0 L 🗆 Remote Annunciators
Cooling Fan Air Flow 40.2 m3/ min 🗆 Other(ComP, DEIF)
Radiator Fan Load 0.3 kW
Heat Radiation to Room (PRP) 3.3kW Circuit Breaker:
🗆 3/4 poles
Heat Radiation to Room (ESP) 4.4 kW
🗆 Fixed/handcart type
LUBRICATION SYSTEM 🗆 Electric mechanism
Oil Filter Type Spin-On Full Flow
Automatic Transfer Switch (ATS):
Total Oil Capacity 10.6L
🗆 ATS cabinet
Oil Type API-CH-4 or ACEA E5
🗆 Contractor type ATS
EXHAUST SYSTEM 🗆 Motorized changeover type ATS
Mufler Type Industrial Grade
Start Battery:
Max. Back Pressure 10.2 kPa
🗆 Nickel-cadmium battery
🗆
3
Exhaust Gas Flow (PRP/ESP) 3.64/3.94 m / min Maintenance-free battery
Exhaust Gas Temperature < 4050C 🗆 Battery charger and selector switch
FUEL SYSTEM 🗆 Charging current meter
www.aqtgenerators.com | info@aqtgenerators.Com | Dubai, Alnahda2 AL Murjan Tower, 409 | (04) 547 1703