www.aqtgenerators.

com
Diesel Power Generation
Control System & Power Solutions

AQT-2000 Generating Set


TECHNICAL DATA SHEET

Output Rating:
Standard Specifications: PRIME: STANDBY:

50 Hz—1500 Rpm 400 V, 3ph


1850 kVA 1480 kW 2000 kVA 1600 kW
1 PrimeRating:
60 Hz—1800 Rpm 480 V, 3ph
Unlimited hours usage, with an average
load factor of 80% over each 24 hour peri-
od. 10% overload is available for 1 hour in ENGINE SPECIFICATIONS
every 12 hours operation. Engine Make PERKINS
o overload is permitted on standby power. Engine Model 4016-61TRG1
No. of Cylinders 16 60º Vee form
2 Standby Rating:
Cycle 4 Stroke
Limited to 500 hours annual usage, with an
Aspiration Turbocharged & air to air charged cooled
average load factor of 80% of the pub-
lished standby power rating over each 24 Cooling Method Water cooled
hour period. Up to 300 hours of annual Governing Type Electronic
usage may be run continuously. Governing Class G2 - ISO 8528 Part 1
No overload is permitted on standby pow- Compression Ratio 13.6:1
er. Displacement 61.123 litres
Bore/Stroke 160 x 190 mm
3 Engine: Dynamic Charging Alternator 55 AMP, 24V
Perkins, including air filters, fuel filters,
oil filter, starting motor and charging alter-
ALTERNATOR SPECIFICATIONS
Alternator Make Leroy Somer | STAMFORD | AQT
nator etc.
Alternator Model LSA52.3 S5
Number of Poles 4
4Alternator Type: Number of Winding Leads 12
brushless AC alternator Type of Bearing Single Bearing
Insulation Class - Temp Rise Cont. H - 125/40 C̊
5 Radiator: Ingress Protection Rating IP 23
50°C, fan protective shroud Excitation System AREP + PMI
AVR Model D 510C

Comply with Standards


ISO 3046, BS 5514, DIN 6271, NEMA-MGI, DIN EN, BS 5000, IEC 60034,IEC 60947-2
Powered By: Alternator Operating data
Over speed 2250 rpm
Voltage Regulation + 0.5%
Harmonic Coefficient THF < 2%
Tel. influence TIF < 50
Cooling air flow 2.5 m3/ Sec

www.aqtgenerators.com | info@aqtgenerators.Com | Dubai, Alnahda2 AL Murjan Tower, 409 | (04) 547 1703
Standard Specifications:
Control System:
6– Fuel Tank:
Large back-lit text display Fuel and start outputs, configurable when
(4-Line back-lit LCD text display) using CAN
Capacity of fuel tank is for 8 hours Multiple display languages 8 configurable DC outputs
running DSENet® expansion compatible 9configurable analogue/digital inputs
Built in fuel tank up to 800 kVA Data logging facility Automatically transfers between mains
Fully configurable via PC using USB com- (utility) and generator
munication (DSE7320 MKII only)
7- Circuit Breaker: Front panel configuration Increased input and output expansion
Efficient power save mode capability via DSENet®
3 phase generator sensing IP65 rating (with optional gasket) offers
3 pole LS MCCB increased resistance to water ingress
Accumulated power monitoring
DIGITAL INPUTS
(kW h, kVA h, kVAr h)
ANALOGUE INPUT
8– Control system alarms: Generator/load current monitoring and
protection
Generator overload protection (kW)
•Over and Under Speed Breaker control via fascia buttons
•Low and High Battery Volt.
•Start and Stop Failure
•Over Current
•Under / Over Generator Voltage DSE7320 MKII
•Low Oil Pressure AUTO START & AUTO MAINS
•Emergency stop FAILURE CONTROL
•High engine temperature

9– Warranty policy:

• AQT GENERATOR products has a Dimensions:


warranty for 12 Months or 1000
Length Width Height Fuel Tank Weight
hours whichever occurs first Type
(mm) (mm) (mm) (L) (KG)
against any manufacturing defects
OPEN
• Wearing parts (filters), incorrect
man made operation, mainte- 12192 2438 2896 NA* 26500
nance failures are excluded from
the warranty policy

Acoustic Enclosure Specifications:


Acoustic & Weather
EnclosureType
Proof
Drainage Fuel and Water Drainage

Tested Single Point Lifting


Transportation
Facility & Forklift Pockets

Ingress Protection Rating IP 23

Lifting ISO Standard Lifting


Canopy RAL Color TAL 9010
Base frame RAL Color RAL 9011

Noise Pressure level @ 7m TBD

www.aqtgenerators.com | info@aqtgenerators.Com | Dubai, Alnahda2 AL Murjan Tower, 409 | (04) 547 1703
Engine: Optional configurations:
Engine accessories:
⦁ Heavy-duty air filter
⦁ Coolant heater
⦁ Lubricant oil heater
⦁ Fuel and Water Separator
⦁ Lube oil rotary pump

Alternator And Accessories:


⦁ Leroy somer/stamford
⦁ Anti condensation heater
⦁ PMG + AVR ◇Double bearing alternator
⦁ High voltage kV
⦁ RTDs for Bearing and winding

Cooling System:
⦁ 55 degree Radiator
⦁ Remote Radiator

Control System:
⦁ AMF
Perkins heavy duty high performance industrial type diesel engine. ⦁ Parallel
⦁ Practical type in low temperature environment
COOLING SYSTEM ⦁ Control Screen Heater
Total Coolant Capacity (L) 210 L ⦁ Remote Annunciators
Cooling Fan Air Flow 2394 m3/ min ⦁ Other(ComP, DEIF)
Radiator Fan Load 51 kW
Circuit Breaker:
Heat Radiation to Room (PRP) 103 Kw ⦁ 3/4 poles
Heat Radiation to Room (ESP) 107 kW ⦁ Fixed/handcart type
LUBRICATION SYSTEM ⦁ Electric mechanism
Oil Filter Type Spin-On Full Flow
Automatic Transfer Switch (ATS):
Total Oil Capacity 214 L ⦁ ATS cabinet
Oil Type API-CH-4 or ACEA E5 ⦁ Contractor type ATS
EXHAUST SYSTEM ⦁ Motorized changeover type ATS

Muffler Type Industrial Grade


Start Battery:
Max. Back Pressure 3.0 kPa ⦁ Nickel-cadmium battery
Exhaust Gas Flow (PRP/ESP) 343 m3/ min ⦁ Maintenance-free battery
Exhaust Gas Temperature < 439 0C ⦁ Battery charger and selector switch
⦁ Charging current meter
FUEL SYSTEM
Recommended Fuel Class A2 Diesel External Fuel Tank:
⦁ Single /double wall fuel tank (500-5000 L)
Fuel Consumption Standby 424 L/hr
⦁ Fuel Transfer pump
Fuel Consumption 100% PRP 383 L/hr
Fuel Consumption 75% PRP 277 L/hr Exhaust Muffler:
Fuel Consumption 50% PRP 155 L/hr ⦁ Residential grade
⦁ Critical grade
AIR SYSTEM
⦁ Hospital grade
Air Filter Type Cylindrical paper pleat
Available for voltages :
Combustion Air Flow (PRP) 132 m3/min
⦁ 400/230V, 480/277V, 380/220V, 440/254V,
Combustion Air Flow (ESP) 140 m3/min 416/240V,220/127V, 208/120V
Max Air Filter Intake Restriction 3.7 kPA