ED-2002-204 Power Supply Module (2113) User Manual

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Messung Systems NEXGEN-2000 PLC PSU Modules

NEXGEN-2000 Series of PLCs


Universal

100-240 VAC Power Supply Module (2113)

Document No. ED-2002-204

Version: 1.0

Published Apr 2005

MESSUNG SYSTEMS
EL-2, J- Block MIDC Bhosari,
Pune – 411026.(INDIA)

Tel: (+91)-020-27102000
Fax: (+91)-020-27102100
Email : marketing@ms.messung.com
WEB: http://www.messungautomation.com/

Power Supply Module (2113) User Manual Published Apr 2005


Document No.: ED-2002-204 /V1.0 Page 1 of 12
NEXGEN-2000 PLC PSU Modules Messung Systems

Revision:

Version Date Description

1.0 Apr 2005 Power Supply Module (2113) NEXGEN Series of PLCs.

Published Apr 2005 Power Supply Module (2113) User Manual


Page 2 of 12 Document No.: ED-2002-204/V1.0
Messung Systems NEXGEN-2000 PLC PSU Modules

INDEX
1. Power Supply Module (2113) ...................................................................................... 5
2. Module Specifications ................................................................................................. 6
3. Module Wiring............................................................................................................... 7
3.1 LINE, NEUTRAL and EARTH connections ................................................................ 8
3.2 Red LED 'ON' ............................................................................................................. 8
3.3 Fuse Protection........................................................................................................... 8
4. Auxiliary Power Supply Requirement ........................................................................ 9
5. Module Insertion and Removal from Rack .............................................................. 10
6. Troubleshooting ......................................................................................................... 11

INDEX OF FIGURES
Figure 1: Front View of Power Supply Module (2113) .............................................................. 6
Figure 2: Connection Diagram of Power Supply Module (2113) .............................................. 7
Figure 3: PSU Module Mounting and Removal from Base Rack............................................ 10

Power Supply Module (2113) User Manual Published Apr 2005


Document No.: ED-2002-204 /V1.0 Page 3 of 12
NEXGEN-2000 PLC PSU Modules Messung Systems

Guidelines for the Safety of the user and protection of Power Supply Module

a) DESIGN ENGINEER Any engineer who is responsible for the planning, design,
and construction of automatic equipment using the product associated with this
manual should be of a competent nature, trained and qualified to the local and
national standards required to fulfill the role. These engineers should be fully
aware of all the aspects of safety with regards to automated equipment.
b) COMMISSIONING/SERVICE ENGINEER. Any engineer who is responsible for
the commissioning, use and maintenance of automatic equipment using the
product associated with this manual should be of a competent nature, trained
and qualified to the local and national standards required to fulfill the role. This
includes being completely familiar with all the associated documentation for the
said system. Maintenance to be carried out in accordance to the established
safety practices.
c) OPERATORS. The personnel using the completed equipment should be trained
to use the product in a safe and coordinated manner in compliance to
established safety practices. They should be also familiar with documentation,
which is relevant to the actual operation of the equipment.
Note: The term-completed equipment refers to a third party constructed device,
which contains or uses the product associated with this manual.

Notes on Symbols used in this Manual


The following symbols will be used throughout this manual to highlight points of information
regarding the users personal SAFETY and protection of the unit's integrity. The meaning of the
symbols must be clearly understood and due cognizance be taken of the associated note
where these symbols appear. The symbols and their descriptions are given ahead for ready
reference

HARDWARE RELATED
1
Indicates that the identified danger WILL cause physical and property damage.

2
Indicates that the identified danger could POSSIBLY cause physical and property
damage.

3
Indicates a point of further interest or explanation.

Published Apr 2005 Power Supply Module (2113) User Manual


Page 4 of 12 Document No.: ED-2002-204/V1.0
Messung Systems NEXGEN-2000 PLC PSU Modules

1. Power Supply Module (2113)


This is a switched mode type of power supply module with 100-240 VAC
input. The power supply serves following purposes.

Output Use External Access


5 VDC For Processor and I/O modules, even No
relays on output modules are driven by
same PSU
PFNMI signal Aid for CPU house-keeping function No

This module is not recommened to use for any other application other than
powering up a Nexgen-2000 series PLC.

The power supply module is generally fixed at the left most position in the
base rack, though additional power supply module can be placed in any
other slot, depending on load current requirement.

The subsequent sections explain technical specifications and recommended


wiring of the module

Power Supply Module (2113) User Manual Published Apr 2005


Document No.: ED-2002-204 /V1.0 Page 5 of 12
NEXGEN-2000 PLC PSU Modules Messung Systems

2. Module Specifications
The technical specifications of the Power Supply Module are as given below.

Input supply 100-240 VAC ± 15%, (85-265 V)


50 /60 Hz, ± 6%
20 VA nominal
Inrush current 8(?) Amp for 10 ms typical at 220V
Output voltages 5.00 VDC@ 2.5 Amp (For single PSU in
operation)
5.00 VDC@ 2.25A (For multiple PSU in parallel
operation)
Hold ON time > 5 ms at 85 V AC input supply
Fuse protection for 2 Amp Miniature fuse (On board).
incoming mains
Protections provided MOV protection for input over voltage.
Output short circuit protection for 5VDC
Noise Immunity Conforms to EMC requirements of EN 61131-2
(2003)
Connector 5 pin (polarized, removable) connector with 3.81
mm (0.15”) pitch

Figure 1: Front View of Power Supply Module (2113)

Published Apr 2005 Power Supply Module (2113) User Manual


Page 6 of 12 Document No.: ED-2002-204/V1.0
Messung Systems NEXGEN-2000 PLC PSU Modules

3. Module Wiring
The figure shows the connection diagram of the power supply module.

1.5 mm2 (22-16 AWG) stranded


copper wire is recommend.

Isolation transformer
with shield

100/220
440/220 VAC
VAC
20 VA
0

Earth

Earth

Figure 2: Connection Diagram of Power Supply Module (2113)

Power Supply Module (2113) User Manual Published Apr 2005


Document No.: ED-2002-204 /V1.0 Page 7 of 12
NEXGEN-2000 PLC PSU Modules Messung Systems

3.1 LINE, NEUTRAL and EARTH connections

A clean, noise free AC supply with proper earth should be connected to


power up the PLC. The Line and Neutral to the Power Supply Module should
be preferably isolated from those of load supply by shielded isolation
transformer of minimum 20 VA rating. Earth should be connected to a good
quality factory ground. For this matter the complete PLC installation should
have a single electrical grounding point, which can be called a reference
ground. This can be either grounding point of an electrical cabinet or the
main earth bus-bar. The Earth line on module should be connected to this
ground by copper wire with a size of 1.0 mm2. This connection should be
direct, continuous and permanent.

It is recommended to use such an isolated supply exclusively for PLC power


supply only. It is suggested that isolation transformers with inter-winding
shield shall be used.

3.2 Red LED 'ON'

The red LED ‘ON’ provided on fascia of the module glows after applying AC
supply; if the power supply module is healthy i.e. 5VDC is properly
generated by the module.

3.3 Fuse Protection

This is a miniature fuse with 2 A rating provided for incoming mains


protection. It is recommended to connect a Miniature Circuit Breaker (MCB)
of proper rating in series with mains as additional protection and to serve as
a manual isolator.

Published Apr 2005 Power Supply Module (2113) User Manual


Page 8 of 12 Document No.: ED-2002-204/V1.0
Messung Systems NEXGEN-2000 PLC PSU Modules

4. Auxiliary Power Supply Requirement


The power supply module in base rack provides 5 VDC to the Processor and
I/O modules fixed in base rack. The current rating of 5 VDC supply
generated by 2113 module is 2.5 Amp maximum, if only single power supply
module is used in the system. Each I/O module along with CPU module
draws current as per the 5 VDC consumption mentioned in the technical
specifications of each module. Around 5-10% capacity should be kept as
spare.

If total current consumption of all the modules for 5 VDC supply exceeds 2.5
Amp, auxiliary supply is required in the base rack. The same Power Supply
Module (2113) can be used for this purpose. More than one power supply
modules (2113) can be inserted in the same rack for parallel operation and
more load current can be supplied to the system. Even though 5 VDC
current rating of single power supply module is 2.5 A, when additional power
supply module (2113) is connected in parallel, the effective capacity is
reduced by 10%. For e.g. If two power supply modules (2113) are connected
in parallel, then total current drawn by the system should be less than 4.5
Amps and not (2.5 + 2.5 = 5) Amps.

One has to calculate the total current consumption of 5 VDC supply and
accordingly additional power supply module shall be selected and ordered.

Power Supply Module (2113) User Manual Published Apr 2005


Document No.: ED-2002-204 /V1.0 Page 9 of 12
NEXGEN-2000 PLC PSU Modules Messung Systems

5. Module Insertion and Removal from Rack


In order to ensure that user is consciously removing the module from the
rack, there is additional HV-Clip provided at top surface of the rack. This HV-
Clip is in addition to regular locking clips provided towards fascia of the
module. The HV-Clip shall be lifted using proper blade size of screw driver,
before pulling out the module from the slot.

Figure 3: PSU Module Mounting and Removal from Base Rack

Published Apr 2005 Power Supply Module (2113) User Manual


Page 10 of 12 Document No.: ED-2002-204/V1.0
Messung Systems NEXGEN-2000 PLC PSU Modules

6. Troubleshooting
The Power supply module (2113) has a red LED indication named as ‘ON’. If
this LEDs is on, then module is healthy. If this LED is off, the probable
causes are explained in table below and proper corrective action should be
taken.

LED Indication Probable Cause Remedial Action


‘ON’ LED 1. Input supply is absent Check for external problem if any. Input supply
indication is OFF should be as per specifications.
MCB may be tripped/Switch off.
2. Input supply not within Check for proper input supply as per
specified range specifications.
3. Module fuse blown. Replace the miniature fuse 2 Amp by same
type*
4. Overloading of 5 VDC supply due to –
a. Faulty Processor module Remove the Processor module from rack and
check if ‘ON’ LED is glowing. If it is glowing,
problem is due to the Processor module.
Replace it.
b. Faulty I/O module Remove all I/O modules from the rack and
then insert one by one to find out which
module is creating problem. If faulty module is
located, replace it.
c. 5 VDC current capacity is Ensure that total load on 5 VDC supply does
exceeded. not exceed the specified limit of 2.5 Amp. If the
current demand from all modules in the system
is exceeding the capacity of single PSU
module, then use auxiliary power supply
module.
5. Module defective Replace the module.

• The PSU supply module has high value capacitors which store
significant energy after power is switched off. Hence it is necessary
to wait for at least one minute before removing the module from
base rack. This is safety precaution to avoid electrical shock.

• Ensure that power is removed while replacing the 2 A miniature


fuse. To remove the fuse, remove the module from the slot and then
replace the fuse. Always replace the fuse with another fuse of same
type and same rating to maintain user and equipment safety. If the
fuse repeatedly blows, then module could be faulty.

Troubleshooting points explained in the above table are also applicable for
the auxilliary power supply module. In case, if auxilliary power supply
module has failed, then Processor module is put in STOP mode.

Power Supply Module (2113) User Manual Published Apr 2005


Document No.: ED-2002-204 /V1.0 Page 11 of 12
NEXGEN-2000 PLC PSU Modules Messung Systems

Warning!
Specifications of the product and contents of this manual are subject to change
without notice. This manual has been prepared taking utmost care; the performance
of the final equipment depends on many other parameters beyond any control of
Messung Systems. Messung systems do not assume any responsibility/ liability of
any damage to life or property that might result due to any malfunction due to design,
use of the equipment, using this component.

MESSUNG SYSTEMS
EL – 2, J - Block, MIDC, Bhosari,
PUNE – 411 026. INDIA
Tel. – (+91)–020–27102000
Fax. – (+91)–020–27102100

NEXGEN-2000 PLC PSU Modules


100-240 VAC Power Supply Module (2113)

Document No.: ED-2002-204 Version 1.0

Published Apr 2005 Power Supply Module (2113) User Manual


Page 12 of 12 Document No.: ED-2002-204/V1.0