CONCRETE COMPRESSIVE STRENGTH TEST RESULT (ASTM-39)

IDENTIFICATION DATA
Project: 21-188 Rehabilitation of Public Market - Jaro Public Market Lab. Report No.:
Location Jaro, Iloilo City Report Date:
Contractor: AMO-IBC JV Submitted By: Jezreel S. Flotilde
Inspector: BRYAN PAUL CENTENO Tested By:
MATERIAL MIX DATA FIELD TEST DATA
Concrete Supplier AMO-IBC JV Max. Agg. Size (inches): 3/4 Cast by: B.P. Centeno/J. Flotilde Slump(mm) 100-200
Cement Type Portland Cement Type I Admixtures: PXP-X Date Received: January 6, 2024 Concrete Temp © N/A
Compressive Strength Required 3000psi @ 28 days Mts. Rep. (cu.m.) Date Tested: January 6, 2024 Air Content(%) N/A

Condition
Date Age in Weight Length Diameter X-Area Max. Load Strength Strength Type of
Sample No. Client's Reference of
Sampled Days (kg) (mm) (mm) (mm2) (KN) (MPA) (Psi) Fractured
Cylinder

1 Structural Concrete (Slab, Beam, Column 12/9/2023 28

2 Structural Concrete (Slab, Beam, Column 12/9/2023 28

3 Structural Concrete (Slab, Beam, Column 12/9/2023 28

Witnessed by:
JEZREEL S. FLOTILDE, QC In-charge - AMO-IBC
BRYAN PAUL CENTENO, Iloilo City Engineers Office Inspector
CONCRETE COMPRESSIVE STRENGTH TEST RESULT (ASTM-39)
IDENTIFICATION DATA
Project: 21-188 Rehabilitation of Public Market - Jaro Public Market Lab. Report No.:
Location Jaro, Iloilo City Report Date:
Contractor: AMO-IBC JV Submitted By: Jezreel S. Flotilde
Inspector: BRYAN PAUL CENTENO Tested By:
MATERIAL MIX DATA FIELD TEST DATA
Concrete Supplier AMO-IBC JV Max. Agg. Size (inches): 3/4 Cast by: B.P. Centeno/J. Flotilde Slump(mm) 100-200
Cement Type Portland Cement Type I Admixtures: PXP-X Date Received: January 18, 2024 Concrete Temp © N/A
Compressive Strength Required 3000psi @ 28 days Mts. Rep. (cu.m.) Date Tested: January 18, 2024 Air Content(%) N/A

Condition
Date Age in Weight Length Diameter X-Area Max. Load Strength Strength Type of
Sample No. Client's Reference of
Sampled Days (kg) (mm) (mm) (mm2) (KN) (MPA) (Psi) Fractured
Cylinder

1 Structural Concrete (Flooring) 12/21/2023 28

2 Structural Concrete (Flooring) 12/21/2023 28

Witnessed by:
JEZREEL S. FLOTILDE, QC In-charge - AMO-IBC
BRYAN PAUL CENTENO, Iloilo City Engineers Office Inspector
CONCRETE COMPRESSIVE STRENGTH TEST RESULT (ASTM-39)
IDENTIFICATION DATA
Project: 21-188 Rehabilitation of Public Market - Jaro Public Market Lab. Report No.:
Location Jaro, Iloilo City Report Date:
Contractor: AMO-IBC JV Submitted By: Jezreel S. Flotilde
Inspector: BRYAN PAUL CENTENO Tested By:
MATERIAL MIX DATA FIELD TEST DATA
Concrete Supplier AMO-IBC JV Max. Agg. Size (inches): 3/4 Cast by: B.P. Centeno/J. Flotilde Slump(mm) 100-200
Cement Type Portland Cement Type I Admixtures: PXP-X Date Received: January 24, 2024 Concrete Temp © N/A
Compressive Strength Required 3000psi @ 28 days Mts. Rep. (cu.m.) Date Tested: January 24, 2024 Air Content(%) N/A

Condition
Date Age in Weight Length Diameter X-Area Max. Load Strength Strength Type of
Sample No. Client's Reference of
Sampled Days (kg) (mm) (mm) (mm2) (KN) (MPA) (Psi) Fractured
Cylinder

1 Structural Concrete (Beam, Slab, Stair) 12/27/2023 28

2 Structural Concrete (Beam, Slab, Stair) 12/27/2023 28

Witnessed by:
JEZREEL S. FLOTILDE, QC In-charge - AMO-IBC
BRYAN PAUL CENTENO, Iloilo City Engineers Office Inspector
CONCRETE COMPRESSIVE STRENGTH TEST RESULT (ASTM-39)
IDENTIFICATION DATA
Project: 21-188 Rehabilitation of Public Market - Jaro Public Market Lab. Report No.:
Location Jaro, Iloilo City Report Date:
Contractor: AMO-IBC JV Submitted By: Jezreel S. Flotilde
Inspector: BRYAN PAUL CENTENO Tested By:
MATERIAL MIX DATA FIELD TEST DATA
Concrete Supplier AMO-IBC JV Max. Agg. Size (inches): 3/4 Cast by: B.P. Centeno/J. Flotilde Slump(mm) 100-200
Cement Type Portland Cement Type I Admixtures: PXP-X Date Received: February 6, 2024 Concrete Temp © N/A
Compressive Strength Required 3000psi @ 28 days Mts. Rep. (cu.m.) Date Tested: February 6, 2024 Air Content(%) N/A

Condition
Date Age in Weight Length Diameter X-Area Max. Load Strength Strength Type of
Sample No. Client's Reference of
Sampled Days (kg) (mm) (mm) (mm2) (KN) (MPA) (Psi) Fractured
Cylinder

1 Structural Concrete (Flooring, Column) 1/9/2024 28

2 Structural Concrete (Flooring, Column) 1/9/2024 28

Witnessed by:
JEZREEL S. FLOTILDE, QC In-charge - AMO-IBC
BRYAN PAUL CENTENO, Iloilo City Engineers Office Inspector
CONCRETE COMPRESSIVE STRENGTH TEST RESULT (ASTM-39)
IDENTIFICATION DATA
Project: 21-188 Rehabilitation of Public Market - Jaro Public Market Lab. Report No.:
Location Jaro, Iloilo City Report Date:
Contractor: AMO-IBC JV Submitted By: Jezreel S. Flotilde
Inspector: BRYAN PAUL CENTENO Tested By:
MATERIAL MIX DATA FIELD TEST DATA
Concrete Supplier AMO-IBC JV Max. Agg. Size (inches): 3/4 Cast by: B.P. Centeno/J. Flotilde Slump(mm) 100-200
Cement Type Portland Cement Type I Admixtures: PXP-X Date Received: February 8, 2024 Concrete Temp © N/A
Compressive Strength Required 3000psi @ 28 days Mts. Rep. (cu.m.) Date Tested: February 8, 2024 Air Content(%) N/A

Condition
Date Age in Weight Length Diameter X-Area Max. Load Strength Strength Type of
Sample No. Client's Reference of
Sampled Days (kg) (mm) (mm) (mm2) (KN) (MPA) (Psi) Fractured
Cylinder

1 Structural Concrete (Stairs, Elevator) 1/11/2024 28

2 Structural Concrete (Stairs, Elevator) 1/11/2024 28

Witnessed by:
JEZREEL S. FLOTILDE, QC In-charge - AMO-IBC
BRYAN PAUL CENTENO, Iloilo City Engineers Office Inspector
CONCRETE COMPRESSIVE STRENGTH TEST RESULT (ASTM-39)
IDENTIFICATION DATA
Project: 21-188 Rehabilitation of Public Market - Jaro Public Market Lab. Report No.:
Location Jaro, Iloilo City Report Date:
Contractor: AMO-IBC JV Submitted By: Jezreel S. Flotilde
Inspector: BRYAN PAUL CENTENO Tested By:
MATERIAL MIX DATA FIELD TEST DATA
Concrete Supplier AMO-IBC JV Max. Agg. Size (inches): 3/4 Cast by: B.P. Centeno/J. Flotilde Slump(mm) 100-200
Cement Type Portland Cement Type I Admixtures: PXP-X Date Received: February 13, 2024 Concrete Temp © N/A
Compressive Strength Required 3000psi @ 28 days Mts. Rep. (cu.m.) Date Tested: February 13, 2024 Air Content(%) N/A

Condition
Date Age in Weight Length Diameter X-Area Max. Load Strength Strength Type of
Sample No. Client's Reference of
Sampled Days (kg) (mm) (mm) (mm2) (KN) (MPA) (Psi) Fractured
Cylinder

1 Structural Concrete (Ramp Flooring) 1/16/2024 28

2 Structural Concrete (Ramp Flooring) 1/16/2024 28

Witnessed by:
JEZREEL S. FLOTILDE, QC In-charge - AMO-IBC
BRYAN PAUL CENTENO, Iloilo City Engineers Office Inspector

CONCRETE COMPRESSIVE STRENGTH TEST RESULT (ASTM-39)


IDENTIFICATION DATA
Project: 21-188 Rehabilitation of Public Market - Jaro Public Market Lab. Report No.:
Location Jaro, Iloilo City Report Date:
Contractor: AMO-IBC JV Submitted By: Jezreel S. Flotilde
Inspector: BRYAN PAUL CENTENO Tested By:
MATERIAL MIX DATA FIELD TEST DATA
Concrete Supplier AMO-IBC JV Max. Agg. Size (inches): 3/4 Cast by: B.P. Centeno/J. Flotilde Slump(mm) 100-200
Cement Type Portland Cement Type I Admixtures: PXP-X Date Received: February 17, 2024 Concrete Temp © N/A
Compressive Strength Required 3000psi @ 28 days Mts. Rep. (cu.m.) Date Tested: February 17, 2024 Air Content(%) N/A

Condition
Date Age in Weight Length Diameter X-Area Max. Load Strength Strength Type of
Sample No. Client's Reference of
Sampled Days (kg) (mm) (mm) (mm2) (KN) (MPA) (Psi) Fractured
Cylinder

1 Structural Concrete (Deckslab) 1/20/2024 28

2 Structural Concrete (Deckslab) 1/20/2024 28

Witnessed by:
JEZREEL S. FLOTILDE, QC In-charge - AMO-IBC
BRYAN PAUL CENTENO, Iloilo City Engineers Office Inspector

CONCRETE COMPRESSIVE STRENGTH TEST RESULT (ASTM-39)


IDENTIFICATION DATA
Project: 21-188 Rehabilitation of Public Market - Jaro Public Market Lab. Report No.:
Location Jaro, Iloilo City Report Date:
Contractor: AMO-IBC JV Submitted By: Jezreel S. Flotilde
Inspector: BRYAN PAUL CENTENO Tested By:
MATERIAL MIX DATA FIELD TEST DATA
Concrete Supplier AMO-IBC JV Max. Agg. Size (inches): 3/4 Cast by: B.P. Centeno/J. Flotilde Slump(mm) 100-200
Cement Type Portland Cement Type I Admixtures: PXP-X Date Received: February 22, 2024 Concrete Temp © N/A
Compressive Strength Required 3000psi @ 28 days Mts. Rep. (cu.m.) Date Tested: February 22, 2024 Air Content(%) N/A

Condition
Date Age in Weight Length Diameter X-Area Max. Load Strength Strength Type of
Sample No. Client's Reference of
Sampled Days (kg) (mm) (mm) (mm2) (KN) (MPA) (Psi) Fractured
Cylinder
Structural Concrete (Column, Stair,
1 1/25/2024 28
Flooring)
Structural Concrete (Column, Stair,
2 1/25/2024 28
Flooring)

Witnessed by:
JEZREEL S. FLOTILDE, QC In-charge - AMO-IBC
BRYAN PAUL CENTENO, Iloilo City Engineers Office Inspector

CONCRETE COMPRESSIVE STRENGTH TEST RESULT (ASTM-39)


IDENTIFICATION DATA
Project: 21-188 Rehabilitation of Public Market - Jaro Public Market Lab. Report No.:
Location Jaro, Iloilo City Report Date:
Contractor: AMO-IBC JV Submitted By: Jezreel S. Flotilde
Inspector: BRYAN PAUL CENTENO Tested By:
MATERIAL MIX DATA FIELD TEST DATA
Concrete Supplier AMO-IBC JV Max. Agg. Size (inches): 3/4 Cast by: B.P. Centeno/J. Flotilde Slump(mm) 100-200
Cement Type Portland Cement Type I Admixtures: PXP-X Date Received: March 2, 2024 Concrete Temp © N/A
Compressive Strength Required 3000psi @ 28 days Mts. Rep. (cu.m.) Date Tested: March 2, 2024 Air Content(%) N/A

Condition
Date Age in Weight Length Diameter X-Area Max. Load Strength Strength Type of
Sample No. Client's Reference of
Sampled Days (kg) (mm) (mm) (mm2) (KN) (MPA) (Psi) Fractured
Cylinder

1 Structural Concrete (Beam, Flooring) 2/3/2024 28

2 Structural Concrete (Beam, Flooring) 2/3/2024 28

Witnessed by:
JEZREEL S. FLOTILDE, QC In-charge - AMO-IBC
BRYAN PAUL CENTENO, Iloilo City Engineers Office Inspector

CONCRETE COMPRESSIVE STRENGTH TEST RESULT (ASTM-39)


IDENTIFICATION DATA
Project: 21-188 Rehabilitation of Public Market - Jaro Public Market Lab. Report No.:
Location Jaro, Iloilo City Report Date:
Contractor: AMO-IBC JV Submitted By: Jezreel S. Flotilde
Inspector: BRYAN PAUL CENTENO Tested By:
MATERIAL MIX DATA FIELD TEST DATA
Concrete Supplier AMO-IBC JV Max. Agg. Size (inches): 3/4 Cast by: B.P. Centeno/J. Flotilde Slump(mm) 100-200
Cement Type Portland Cement Type I Admixtures: PXP-X Date Received: December 29, 2023 Concrete Temp © N/A
Compressive Strength Required 3000psi @ 28 days Mts. Rep. (cu.m.) Date Tested: December 29, 2023 Air Content(%) N/A

Condition
Date Age in Weight Length Diameter X-Area Max. Load Strength Strength Type of
Sample No. Client's Reference of
Sampled Days (kg) (mm) (mm) (mm2) (KN) (MPA) (Psi) Fractured
Cylinder

1 Structural Concrete (Deckslab) 12/1/2023 28

2 Structural Concrete (Deckslab) 12/1/2023 28

Witnessed by:
JEZREEL S. FLOTILDE, QC In-charge - AMO-IBC
BRYAN PAUL CENTENO, Iloilo City Engineers Office Inspector

CONCRETE COMPRESSIVE STRENGTH TEST RESULT (ASTM-39)


IDENTIFICATION DATA
Project: 21-188 Rehabilitation of Public Market - Jaro Public Market Lab. Report No.:
Location Jaro, Iloilo City Report Date:
Contractor: AMO-IBC JV Submitted By: Jezreel S. Flotilde
Inspector: BRYAN PAUL CENTENO Tested By:
MATERIAL MIX DATA FIELD TEST DATA
Concrete Supplier AMO-IBC JV Max. Agg. Size (inches): 3/4 Cast by: B.P. Centeno/J. Flotilde Slump(mm) 100-200
Cement Type Portland Cement Type I Admixtures: PXP-X Date Received: December 19, 2023 Concrete Temp © N/A
Compressive Strength Required 3000psi @ 28 days Mts. Rep. (cu.m.) Date Tested: December 19, 2023 Air Content(%) N/A

Condition
Date Age in Weight Length Diameter X-Area Max. Load Strength Strength Type of
Sample No. Client's Reference of
Sampled Days (kg) (mm) (mm) (mm2) (KN) (MPA) (Psi) Fractured
Cylinder
Structural Concrete (Beam, Column,
1 11/21/2023 28
Slab)
Structural Concrete (Beam, Column,
2 11/21/2023 28
Slab)

Witnessed by:
JEZREEL S. FLOTILDE, QC In-charge - AMO-IBC
BRYAN PAUL CENTENO, Iloilo City Engineers Office Inspector