Professional Documents
Culture Documents
Ipact 2017 8244958
Ipact 2017 8244958
Ipact 2017 8244958
Abstract— The two aspects of power transmission that goes oscillates between source and load is reactive power. Hence,
hand in hand, is the voltage control and the reactive power flow. reactive power compensation is also important for efficient
Voltage control is very important in a transmission line to ensure transfer of real power and also to overcome power quality
system security, stability and reliability. The under consumption issues [3-4]. The methods of reactive power compensation
or over consumption of reactive power at load side, effects the include static shunt compensation, static series compensation,
voltage profile, which may lead to Ferranti effect, heating of static Var compensation, synchronous condenser. The
lines, insulation failure. Since it is not always possible to change drawback of static shunt and series compensation is that it can
the nature of load, power compensation circuits are established. provide only a fixed amount of reactive power compensation.
These circuits employ inductors (consumes reactive power),
To overcome this issue fast acting reactive power
capacitors (generates reactive power) and power electronic
compensation devices namely Flexible Alternating Current
switches (controls). Here; comes the advent of Flexible
Alternating Current Transmission Systems (FACTS) devices for Transmission Systems (FACTS) are used. FACTS devices use
reactive power compensation. The commonly used FACTS thyristor based switches to provide dynamic compensation of
devices for reactive power compensation are Thyristor reactive power. FACTS devices include TCR, TCS, SSSC,
Controlled Reactor (TCR), Thyristor Controlled Series UPFC, TCSC, STATCOM [5-7]. Disadvantages of FACTS
Compensator (TCSC), Static Var Compensator (SVC), and Static devices includes expensive cost, size of device, reliability of
Synchronous Compensator (STATCOM). In this paper, semiconducting switches, transient overload capacity, smooth
characteristics of a new FACTS device named magnetically adjustment of reactance, harmonics [8-9]. Hence, to overcome
controlled reactor (MCR) design is drawn out and its harmonic these issues a new FACTS device named Magnetically
and voltage profile is compared with TCR using Controlled Reactor (MCR) is used for reactive power
MATLAB/Simulink. compensation. Unlike other FACTS controller, MCR adjusts
the reactive power by means of adjusting core saturation.
Keywords— Reactive power compensation; Flexible Alternating Therefore, smooth control of reactance is ensured. MCR’s
Current Transmission Systems (FACTS); Magnetically Controlled construction resembles a transformer; hence efficiency of it is
Reactor (MCR); Thyristor Controlled Reactor (TCR). guaranteed [10-15]. As the thyristor switches used in MCR are
of low ratings (required to excite control windings) the
I. INTRODUCTION harmonic profile is much improved when compared to TCR
Electricity is a useful form of energy. In present scenario, [16-18].
the need for electric power transmission by maintaining This paper deals with the study of characteristics of a
system security and reliability has been considerably MCR and its harmonic profile and performance comparison
increased. The system security and reliability is attained by with TCR. For the analysis; MCR and TCR module [19]
maintaining voltage in a transmission line within limits, operating on a single phase supply of 230V drawing current of
maximizing utilization of transmission lines and by reducing 1.5A is considered. The characterization of MCR is necessary
the line losses [1-2]. Voltage limits can be maintained by to compensate the reactive power based on surge impedance
means of compensating reactive power. 90% of the load loading of the line [20] and capability of its action than other
connected to the transmission line are non-linear and FACTS devices for improving the stability of the system [21-
consumes reactive power. If a load is suddenly disconnected 22]. In the following way the sections details about the work.
from a line, the reactive power at the receiving end will Section I focuses towards introduction; section II explains
remain unconsumed which causes the receiving end voltage to construction and working of MCR; Section III derives the
be greater than the sending end voltage. This is an undesirable design equations of MCR and TCR; Section IV presents the
effect and leads to heating of transmission lines, insulation results and discussions in terms of harmonic profile and
failure. The reactive power is also related to real power and performance comparison with TCR. And voltage profile
apparent power by means of a power triangle. The power comparison with and without MCR, in a long transmission
dissipated across load is the real power and the power that
1
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]
line under loaded condition is followed. Section V concludes The working of MCR is categorized in two regions based
the work. on the polarity of the supply. Fig. 2 and Fig. 3, represents the
working of MCR during positive half cycle and negative half
II. CONSTRUCTION AND WORKING PRINCIPLE OF cycle respectively. Since the saturation of core depends on the
MAGNETICALLY CONTROLLED REACTOR amount of excitation, the control windings can be replaced by
means of dc voltage sources.
A magnetically controlled reactor is a type of FACTS
device used for compensation of reactive power flow in a
transmission line. It is a kind used for shunt compensation
technique in order to compensate the reactive power in a
transmission line. The construction of MCR resembles a
transformer but it works on the principle of magnetic
amplifier. MCR consist of a four legged iron core. Iron core is
used instead of ferrite core because of its higher degree of
saturation. It consists of two sets of windings. One used for
controlling the saturation level of core, named as control
winding and other used for reactive power compensation,
named as working winding. The working windings are
connected to the supply.
The control winding is provided with dc excitation by Fig. 2. control winding current during positive half cycle of supply voltage
means of semiconductor switches. The degree of saturation of During positive half cycle, T1 becomes active due to
the core varies by means of varying the firing angle to positive voltage on anode. As the voltage across T1 is zero,
thyristor. The number of turns of control winding is less than the control windings K11, K12 are indicated by shorted lines
the working winding, therefore; the rating of the and K21, K22 contributes the control winding current during
semiconductor switches used for control is comparatively low positive half cycle.
than those in other FACTS devices. The Fig. 1 represents the
winding connections of a MCR.
Fig. 3. control winding current during negative half cycle of supply voltage
2
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]
where; ‘N’ is the number of turns, ‘ Φ ’ is the flux and ‘E’ is Where ‘B’ is the flux density, ‘lm’ is the mean magnetic
the supply voltage. The flux density is given by Equation (2), length and ‘ȝ’ is the permeability. The thyristor is connected
across the control winding, hence, the voltage rating depends
Φ
B max = (2) on the turns ‘Nk’ and the current rating depends on the main
Ac winding turns. The reverse voltage of thyristor is given by
Hence; integrate Equation (1) w.r.t angular frequency ‘Ȧ equation (11),
(2ʌf)’ and substitute Equation (2) in Equation (1) to calculate Vt = 2E.δ (11)
induced emf ‘E’ whose equation is highlighted in Equation The current rating is determined by Equation (12);
(3);
E = ω.N.Ac.B.Ks (3) B.lm
I=2 (12)
where ‘Ac’ is the core area and ‘Ks’ is the stacking factor. (1 − δ)Nμ
With the known values of E, N, B, Ks, Ȧ the core area is IV. RESULTS AND DISCUSSIONS
calculated using Equation 3. The window area ‘Aw’ is needed
to find the area product (Ap) of the core which is calculated A. Magnetically Controlled Reactorc characteristics
using Equation (4);
Ap = Ac.Aw (4) For the analysis, a model MCR is developed using
Hence; the window area is calculated using Equation (5); MATLAB/ Simulink by referring to Fig.1 and using the
Aw.Kw = a.J (5) single line diagram connecting a generator feeding to a long
transmission line via MCR to load is shown in Fig. 3.
where ‘a’ is the cross sectional area of wire, ‘J’ is the current
density and ‘Kw’ is the winding factor.
B. Inductance and reactive power rating
The rating of a MCR is determined by the value of
inductance or the reactive power consumed by the reactor. The
value of inductor is given by Equation (6);
d2 N 2
L(μH) = (6)
18d + 401
where; ‘d’ is the diameter of the wire in inches and ‘l’ is the Fig.3 Single line diagram of a system with MCR module.
length of the wire in inches. The reactive power rating of
MCR is determined using Equation (7); As, a MCR module, saturation transformer is taken into
account which replicates the action of MCR. For the two sets
Q(Var) = ω.B.Ap.Ks.Kw.J.B (7)
of winding, which operates for positive and negative half
By using Equation (4) and Equation (5) and substituting in cycle respectively, two saturation transformers are used. The
Equation (7) gives the reactive power rating of MCR. primary of the transformers is considered as the working
C. Tap ratio and turns winding and the secondary is considered as the control
winding. The secondary of the two transformers are cross
The taping ratio ‘į’ is the factor which is determined by coupled and a diode is connected across it and further excited
varying range of reactance in a reactor and is usually in by means of thyristor switches. Saturation transformer of
between 0.01 to 0.05. Hence, considering ‘į’ as a known value 0.5kVA rating is considered which is fed with a single phase
the number of turns of control winding is given by Equation supply of 230V, supply current of 1.5A. The designed values
(8); of MCR obtained using Equation (3), Equation (6) and
Nk Equation (7) is incorporated in modeling. The Table I depicts
δ= (8)
N the range of inductance value chosen for the MCR based on
where; ‘Nk’ is the control winding turns and N is the total the firing angle.
number of turns. TABLE I. CHARACTERISTICS OF SINGLE PHASE MCR
Firing Current Reactive Reactance Inductance
D. Selection of diode and thyristor
Angle (A) Power (Q) (Xl in ) (L in H)
The voltage and current rating of diode and thyristor is
determined by the reverse voltage and the current influenced (º) Var
by the taping ratio ‘į’. The peak reverse voltage of the diode is 0 1.48 247.8 213.47 0.68
given by Equation (9); 30 1.41 242.6 218.05 0.69
δ
Vr = 2E (9) 60 1.24 217.6 243.10 0.77
1− δ 90 0.95 160.2 330.21 1.05
The current rating of the diode is determined by using
120 0.60 89.5 591.06 1.88
Equation (10);
B.lm 150 0.25 24.22 2184.4 6.9
I= (10) 180 0.00 0.00 inf Inf
Nμ
3
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]
From the Table I, it is clear that with increase in firing From the Fig.6, it shows that with increase in firing angle the
angle the current and reactive power consumed by the reactor magnitude of flux in the saturation transformer decreases
decreases and on the other hand the reactance and inductance thereby the saturation of the core increases.
increases. The inductance and reactance for each value of Once the core gets saturated no current flows through the
current and reactive power is calculated by the following reactor hence the reactive power absorbed by the reactor
Equations (13) and (14). becomes zero.
I = 2Vrms /(2Π fL) (13) B. Harmonic profile comparison of MCR and TCR
X L = (( 2Vrms) ^ 2)) /Q (14) Thyristor controlled reactor (TCR) is a type of FACTS
device used in reactive power compensation. It consist of two
‘Vrms’ considered for the analysis is ‘230V’ and frequency
antiparallel thyristor connected in series with inductor. The
is 50Hz; Q’ is the reactive power, ‘XL’ is the inductive reactive power consumed by the reactor is based on the firing
reactance of MCR. The characteristics of MCR with respect angle of thyristor. The range of firing angle of thyristor is
to TABLE I is shown in Fig. 4 and Fig. 5.
from 90º to 180º. Maximum current is obtained at 90º and
minimum current is at 180º. In order to compare
characteristics of MCR with TCR, the specifications of TCR
should be same as that of MCR.
Hence, the inductor value chosen for TCR is with respect
to the maximum reactive power consumed by MCR. TCR is
connected to the single phase system operating at 230V
drawing a supply current of 1.5A with respect to Fig. 2. Table
II shows the behavior of TCR for the firing angle variation.
4
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]
of 90º to 180º.The harmonic analysis is carried out under the Hence, from the above results highlighted in TABLE IV
same snubber conditions. This show, the filter circuits and indicates that the MCR module regulates the receiving end
harmonic compensation techniques required will be of low voltage such that the line is free from Ferranti effect and also
rating. from the increased line losses.
Hence, the overall cost and size of the device reduces to
a greater extent than that conventional FACTS device V. CONCLUSIONS
namely TCR.
The application of power electronic devices in power
C.Voltage profile improvement using MCR system not only has advantages like fast response and
Under no load or lightly loaded condition the receiving controlled action. But also introduces disadvantages like
end voltage will be greater than the sending end voltage and cost, increased size and harmonic injection. Therefore a
results in Ferranti effect, which is undesirable in a single phase MCR which is a new type of FACTS device is
transmission line. Hence, as effect of reactive power control suggested in this work to overcome all the disadvantages of
using MCR, the improvement in the voltage profile of a the conventional FACTS devices. The characteristics of
MCR supports a wide operating range by varying the firing
system with load is discussed in this section. A system of long
angle, smooth control of reactance and comparatively lower
transmission line with a 2HP motor and a MCR module is
harmonic profile than TCR could be achieved. The MCR
simulated using MATLAB/Simulink. Voltage profile under
would prove its relevance in reactive power control on
loaded condition is shown in Table III. transmission line which proves being economical due to low
harmonic behavior and efficient operation of device in terms
TABLE III. VOLTAGE PROFILE OF THE SYSTEM DURING of improved voltage profile w.r.t wide range.
UNDER- LOADED CONDITION WITHOUT MCR
5
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]
[14] Ebrahimi, Monazzah, Rahim Zeinali, and Hassan Siahkali. "A multi-
objective model for allocation of Magnetically Controlled Shunt
Reactors." In GCC Conference and Exhibition (GCCCE), 2015 IEEE
8th, pp. 1-6. IEEE, 2015.
[15] Tumey, Mehmet, Selva Bal, Rahmi Ilker Kayaalp, “Review of the
control strategies applied to magnetically controlled shunt reactor”,
National conference on Electrical, Electronics and biomedical
Engineering, pp.96-100, December 2016.
[16] Karymov, R.R. and Ebadian, M, “Comparison of magnetically
controlled reactor (MCR) and thyristor controlled reactor (TCR) from
harmonics point of view”. International Journal of Electrical Power &
Energy Systems, 29 No.3, pp.191-198,2007.
[17] Yuan, Jiaxin, Junwei Zhou, Changting Yu, Yixiong Wang, Baichao
Chen, Meng Song, Nannan Hu, Jun Wang, and Hao Zheng. "Study on
Harmonics Characteristics of Magnetic-Valve Controllable Reactor
Based on the Finite Element Method." IEEE Transactions on Magnetics
51, no. 3, pp.1-4,2015.
[18] Chen, Xuxuan, Baichao Chen, Cuihua Tian, Jiaxin Yuan, and Yaozhong
Liu. "Modeling and harmonic optimization of a two-stage saturable
magnetically controlled reactor for an arc suppression coil." IEEE
Transactions on Industrial Electronics 59, no. 7,pp. 2824-2831,2012.
[19] Khonde, Rohan S., and M. V. Palandurkar. "Simulation Model of
Thyristor Controlled Reactor." International Journal of Engineering
Research and Technology. Vol. 3. No. 4, ESRSA Publications, 2014.
[20] S. Balamurugan S.,N. Janarthanan and K.R.M. Vijaya Chandrakala,
“Laboratory model to teach surge impedance loading.” 2016 - Biennial
International Conference on Power and Energy Systems: Towards
Sustainable Energy, PESTSE 2016, Institute of Electrical and
Electronics Engineers Inc. (2016).
[21] K.R.M. Vijaya Chandrakala, S. Balamurugan and K.Sankaranarayanan,
“Damping of tie-line power oscillation in interconnected power system
using variable structure system and unified power flow controller.”
Journal of Electrical Systems, Vol.8, No.1, pp.85-94, 2012.
[22] S Balamurugan, S Selvakumar, K.R.M. Vijaya Chandrakala,
“Improvement of transient stability of the power system using small
magnetic energy storage.”, International Conference on Advances in
Engineering, Science and Management (ICAESM), 2012.
[23] Ned Mohan, Tore M.Undeland, “Power Electronics: Converters,
Application and Design”, Willey edition, 2015.
[24] L. ummanand, “Design of magnetic components for switched mode
power supply”, New age international publishers, 1992.
[25] Chen Feng, Wang Jun, Zheng Hao, “Fast Response research of
Magnetically controlled reactor”, International journal of smart home,
Vol.9, No.10, pp.97-106,2015.