Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

WTP C32

DESCRIPTION

WTP C32 is used as an industrial biocide for the preservation of water and other liquids in
open cooling systems (i.e. evaporative cooling towers) and processing systems (both open
and closed recirculating type systems) by the control of harmful organisms.

WTP C32 contains the Active substance: Reaction mass of 5-Chloro-2-methyl-2H-Isothiazol-


3-one and 2-methyl-2H-Isothiazol-3-one – C(M)IT/MIT (3:1).

ADVANTAGES

• WTP C32 is approved under the Biocidal Products Regulations No 528/2012 (BPR)
for Product Type 11 application.

Authorisation Number: UK-2019-1196

• WTP C32 controls a wide range of harmful bacteria:

Legionella pneumophila
Desulfovibrio desulfuricans
Shewanella oneidensis
Desulfovibrio vulgaris
Shewanella putrefaciens
Enterobacter cloacae
Pseudomonas aeruginosa
Klebsiella pneumoniae
Pseudomonas fluorescens
Serratia marcescens
Enterobacter aerogenes
Escherichia coli
Serratia plymuthica
Pseudomonas stutzeri

PRODUCT DATA

Physical State Colourless liquid


Density 1.025 g ml-1 +/- 0.02
pH 3 – 4 (concentrate)
APPLICATION METHODS

WTP C32 is intended to be fed intermittently into the system either by:

1. Manual dosing

Product to be decanted from the drum or IBC using a drum tap into a measuring jug
or cylinder and poured into the system.

2. Automatic dosing

Product is to be dosed directly from the drum or IBC, and decanted into either on-site
day tanks or chemical dosing pots and pumped into the system.

APPLICATION RATE AND FREQUENCY

Open cooling systems (i.e. evaporative cooling towers)


For use in systems with a volume of ≤ 300 m3 and where emissions are directed via an STP
(Sewage Treatment Plant).

• Initial dose: 500mL of product per m3 of water


• Typical dosing for a clean system (preventative use): 200mL of product per m3 of
water at 3 hour contact time.
• Contaminated system (curative use): 500-2000mL of product per m3 of water at 24
hour contact time.
• Dose weekly as a minimum (adjust dose based on dip slide results)

Processing systems (both open and closed recirculating type systems)

• Initial dose: 500mL of product per m3 of water


• Typical dosing for a clean system (preventative use): 200mL of product m3 of water
at 1 hour contact time.
• Contaminated system (curative use): 500-2000mL of product per m3 of water at 24
hour contact time.
• Dose quarterly (adjust dose based on dip slide results)

ADDITIONAL INFORMATION

In order to minimise the potential for resistance arising in PT11 systems treated with WTP
C32, the product may be used in rotation with biocides containing a different active
substance, either oxidising or non-oxidising.

For Industrial use only.

TESTING

• Test with dipslides to ensure TVC’s are in an acceptable range (<104)


• A drop test kit is available (WTP TK123) to determine correct Biocide levels in the
system.
HANDLING

Please refer to safety data sheet for detailed handling/storage instructions.

SERVICE

Field representatives will work closely with customer personnel to assure the effective
application of the water treatment programme. Regular service calls can be provided by
qualified personnel.

PACKAGING

WTP C32 treatments are shipped in 25 litre and 200 litre non-returnable drums.

The above information is believed to be correct but does not purport to be all inclusive and shall be
used only as a guide. The company shall not be held liable for any damage resulting from handling,
contact, mis-use or mis-application of the above product. In all instances the user should satisfy
themselves that this product is suitable for the anticipated application and should carry out suitable and
sufficient risk/COSHH assessments and a method of use statement.

Use biocides safely. Always read the label and product information before use.