C218-SM-ME007-CA-00001, Rev.

A, Implement comments and resubmit, 05-Jan-2024

Intended for
EQUINOR

Document type
CA

Date
2023-12-27

Doc no.:
C218-SM-ME007-CA-00001

Rev.:
A

EMPIRE WIND 1 OFFSHORE SUBSTATION


EW1 - STRUCTURAL CALCULATIONS
EMPIRE WIND 1 OFFSHORE SUBSTATION
EW1 - STRUCTURAL CALCULATIONS

Project name Empire Wind 1 Offshore Substation


Project no. 0910J310012

Rev Date Prepared Checked Approved Approved Reason for Issue


by by by PE by PM

A 2023-12-27 Arina Roslinah Issued for IDC

Change Log
Rev Section Description of Changes

C218-SM-ME007-CA-00001_A_IDC_20231227.docx
EW1 - STRUCTURAL CALCULATIONS

CONTENTS

1. Introduction 2
1.1 Purpose 3
2. Strength Calculation Sheet For Demin Water Tanks 6

APPENDICES

Appendix 1

EW1 - Structual Calculation

C218-SM-ME007-CA-00001_A_IDC_20231227.docx 1/4
EW1 - STRUCTURAL CALCULATIONS

1. INTRODUCTION
The Empire Wind 1 project comprises the following main elements:

 54 off 15 MW wind turbine generators (WTG) mounted on foundations fixed to the seabed.
Monopiles (MP) have been selected as WTG foundations.
 66 kV infield cabling (Inter Array Cables (IAC)) connecting the WTGs to the Offshore Substation.
 One Power Export System per phase, consisting of:
 One Offshore Substation (OSS), which includes a topside structure and a piled jacket as
substructure.
 Two (2x50%) submarine export cable circuits, voltage level 230 kV.
 One Onshore Substation (ONS) at Gowanus, adapting the power quality according to the
grid code compliance requirements.
 Two HV cable circuits (Onshore Interconnection cables) connecting the Onshore Substation
to the transmission existing grid substation, Point of Interconnection (POI) at Gowanus.
 Operation and Maintenance Base and infrastructure at South Brooklyn Marine Terminal (SBMT)
close to Gowanus POI.
 O&M personnel transfer and service vessel(s).

Figure 1-1: EW1 characteristics

C218-SM-ME007-CA-00001_A_IDC_20231227.docx 2/4
EW1 - STRUCTURAL CALCULATIONS

1.1 Document scope


This document is prepared as part of the EPC contract for the Empire Wind 1 (EW1) Offshore
Substation (OSS).
The purpose of this document is to present the STRUCTURAL CALCULATIONS.

C218-SM-ME007-CA-00001_A_IDC_20231227.docx 3/4
EW1 - STRUCTURAL CALCULATIONS

APPENDIX 1
EW1 - STRUCTUAL CALCULATIONS

C218-SM-ME007-CA-00001_A_IDC_20231227.docx 4/4
MECHANICAL

STRENGTH CALCULATION SHEET FOR

DEMIN WATER FRP TANK

A 21-Nov-23 Issued For Review ITA IFF YAN


Rev. Date Description By Chk App

Status Code: A = Issued For Review, B = Issued For Approval, 0 = Issued For Construction
INFO = For Information
Doc. No : TK-23055-CAL-01
Revision : A
STRENGTH CALCULATION SHEET Date : November 21, 2023
Page : 1 of 14

STRENGTH CALCULATION SHEET


FOR DEMIN WATER TANK
(Design code : BS 4994-1987 & ASME RTP-1 2015)

II. TANK
II.1.Design Data:
Length of tank, L = 2000 mm (refer to MDS)
= 2 m
Width of tank, W = 2000 mm (refer to MDS)
= 2 m
Hight of tank, H = 1125 mm (refer to MDS)
= 1.125 m
Capacity of tank = 4.5 m3
Liquid contents = Water
Specific gravity of liquid = 1
Density of liquid, ρLiquid = 0.001 kg/cm³
Density of liquid, ρWater = 0.001 kg/cm³
Design pressure, P = Atmospheric
P = Total pressure = 0.1125 kg/cm2
Pi = Internal pressure (+) = 0.0 kg/cm2 = 0.0 Barg
Pe = External pressure (-) = 0.0 kg/cm2 = 0.0 Barg
2
L = Stored Liquid, SG x ρliquid x H = 0.1125 kg/cm
Design temperature = 50 Deg C
Operating pressure = Atmospheric
Operating temperature = Ambient
Type of tank installation = Square Tank
Shape of roof tank = Open Top
Wind velocity, Vb = 25.00 m/s = 90 km/h
Design wind speed, V = 1.2 x Vb
= 108 km/h
Doc. No : TK-23055-CAL-01
Revision : A
STRENGTH CALCULATION SHEET Date : November 21, 2023
Page : 2 of 14

Tanks sketch drawing :

II.2. Summary Laminate Properties


To obtained the competitive design analysis of shell height is divided by = 1 Graduate length = 1125 cm each
Summary hand lay up & type-II laminate properties from Physical and Mechanical properties using lamination
Analysis Method

Unit Shell Bottom Top


Type Laminate of Roof : Laminate type II
Type Laminate of Shell : Laminate type II
Type Laminate of Bottom : Laminate type II
Trial Thickness cm 1.0 0.6 1.0
2
Glass content kg/cm 0.0005 0.0004 0.0005
Laminate density kg/cm3 0.0013 0.0014 0.0013
Laminate weight kg/cm2 0.0013 0.0009 0.0013
Glass content by weight % 39.76 40.98 39.76

Hoop Tensile Modulus kg/cm2 152986.29 143880.90 152986.29


Hoop Flexural Modulus kg/cm2 131756.23 145923.75 131756.23
Axial Tensile Modulus kg/cm2 152986.29 143880.90 152986.29
2
Axial Flexural Modulus kg/cm 155095.15 166590.76 155095.15
Shear Modulus kg/cm2 42685.25 42682.47 42685.25

Axial Poisson's Ratio - 0.297 0.305 0.297


Hoop Poisson's Ratio - 0.297 0.305 0.297
Axial zmean cm 0.106 0.021 0.106
Hoop zmean cm 0.067 0.006 0.067
Doc. No : TK-23055-CAL-01
Revision : A
STRENGTH CALCULATION SHEET Date : November 21, 2023
Page : 3 of 14

II.3. Wall 1 thickness (flat with fixed joint at each side)

3.2 Calculation wall 1 design using rib for stiffener


3.2.1 Minimum thickness for uniform load and local load

α1p b4 α2W1 b2 0.25

tmin = + (base on BS-4994-1987 edition, para 17.5.4, equation (29), page 32)
E lam E lam

where;
a = panel dimension for length = 468 mm
b = panel dimension for breadth/ height = 332 mm
a/b = = 1.41
α1 = Constant approproate to combination of edge condition and type of loading = 0.0760
(interpolate from fixing built in edge, table 8, page 34)
α2 = Constant approproate to combination of edge condition and type of loading = 0.162
(interpolate from fixing built in edge, table 9, page 35)
W1 = Local Load = 0 N
p = Design Pressure = 0.011 N/mm2
2
E lam = Tensile modulus of laminate = 15003.075 N/mm

4 2 0.25
0.076 x 0.011 x 332 0.162 x 0.00 x 332
tmin = + = 5.1 mm
15003.075 15003.075

tmin = 5.1 mm < 10 mm OK, thickness is satisfactory

3.3 Rib Stiffener wall 1 design;


Data;
Panel height dimension, Rectangular panel, b = 332 mm
Young modulus steel L bar under consideration, E lam = 205000 N/mm2
FRP Solid panel thickness,t = 10 mm
Design unit pressure, p = 0.011 N/mm2
Applied local load, W1 = 0 N
Length of stiffener, L = 1125 mm
Uniform of self load per linear length, q = 0.97 N/mm
Doc. No : TK-23055-CAL-01
Revision : A
STRENGTH CALCULATION SHEET Date : November 21, 2023
Page : 4 of 14

P
q = 0.97 N

L = 1125 mm

Assume stiffener size: b = 6 mm


(L 50 x50 x 6 mm Thk) h = 50 mm

50 mm 332 mm

6 mm
332 mm

468 mm

Stiffener quantity, N = 3 nos


N b h (0.5 h + t) + L t (0.5 t)
Z = (ref. Static Moment analysis)
N (b h) + L t

3 x 6 x 50 x ( 0.5 x 50 + 6 )+ 468 x 6 x ( 0.5 x 6 )


Z =
3 x( 6x 50 )+ 468 x 6

Z = 9.7961 mm

Calculate I
3
I1 = N b h /12
3
= 3 x 6 x 50 / 12
4
= 187500 mm

I2 = N b h x (0.5h + t - Z)2
2
= 3x 6x 50 x ( 0.5 x 50 + 6 - 9.7961 )
= 404644 mm4

I3 = 1/12 L t3
3
= 1/ 12 x 468 x 6
= 8424 mm4

I4 = L t (Z - 0.5t)2
= 468 x 6 x ( 9.7961 - 0.5 x 6 )2
4
= 129693.6563 mm

4
I = 730261.8641 mm
Doc. No : TK-23055-CAL-01
Revision : A
STRENGTH CALCULATION SHEET Date : November 21, 2023
Page : 5 of 14

Deflection;
q L4 P L3
δ = + < f (smaller value of 0.5% L or 12.7 mm)
384 EI 48 EI

4 3
0.97 x 468 0.00 x 468
= + < 2.34 mm
384 x 205000 x 730262 48 x 205000 x 730262

= 0.0008112 mm < 2.34 mm OK

Stress;
M.y 1/8 q L2 Z 1/4 P L Z
σ = = + < Sa ( E lam ε)
I I I

0.125 x 0.97 x 468 x 9.7961 0.25 x 0.00 x 468 x 9.7961


= + < Sa
730261.8641 730261.8641

2
= 0.357 N/mm < 205 N/mm2 OK

Conclusion: Thickness of wall 1 more effective used rib reinforced as stiffener with type and condition shown as a bove.
The thickness of flat wall 1 is = 10 mm, with added 1 stiffener crossing the length.
Stiffener has the dimension = 50 mm height, and thickness = 6 mm

II.4. Roof thickness (flat with fixed joint at each side)


4.1 Minimum thickness under distributed load and local load, t min ;

468
468
Doc. No : TK-23055-CAL-01
Revision : A
STRENGTH CALCULATION SHEET Date : November 21, 2023
Page : 6 of 14

α1p b α2W1 b
4 2 0.25

tmin = + (base on BS-4994-1987 edition, para 17.5.4, equation (29), page 32)
E lam E lam

a = panel dimension for length = 468 mm


b = panel dimension for breadth/ height = 468 mm
a/b = = 1.0
α1 = Constant approproate to combination of edge condition and type of loading = 0.0440
(interpolate from fixing built in edge, table 8, page 34)
α2 = Constant approproate to combination of edge condition and type of loading = 0.1267
(interpolate from fixing built in edge, table 9, page 35)
W1 = Local Load (Manpower Load) = 890 N
p = Design Pressure = 0.000 N/mm2
E lam = Hoop Tensile modulus of laminate = 0.000 N/mm2

4 2 0.25
0.044 x 0.000 x 468 0.1267 x 890.00 x 468
tmin = + = 6.4 mm
15003.075 15003.075

tmin = 6.4 mm < 10 mm OK, thickness is satisfactory

II.5. Bottom Flat (Fully Supported)


5.1 Analysis the thickness of bottom flat and slope
Doc. No : TK-23055-CAL-01
Revision : A
STRENGTH CALCULATION SHEET Date : November 21, 2023
Page : 7 of 14

α p b2 0.25

t min = (ref. BS-4994-1987 edition, equation 35, page 35, page 36)
E lam
where:
t = Assumed thickness of bottom flat = 6 mm
P = Total effective pressure (in N/mm2), i.e design pressure (negative if vaccum) plus hydrostatic head
at point under consideration;
Design pressure = 0.1125 kg/cm2 = 0.011033 N/mm2
α = Constant factor for type 1 edge condition = 0.1267
2
E lam = Hoop Tensile modulus of laminate = 14110.127 N/mm

2 0.25
0.1267 x 0.0110 x 332
t min = = 0.3247 mm < 6 mm OK thickness is satisfactory
14110.13

II. 6. Decided Lamination Thickness

Calculated
Nominal Decided Thickness
Shell
Thickness
cm mm cm mm
Wall 0.51 5.1 1.0 10
Roof 0.64 6.4 1.0 10
Bottom 0.03 0.3 0.6 6
Doc. No : TK-23055-CAL-01
Revision : A

STRENGTH CALCULATION SHEET Date : November 21, 2023


Page : 8 of 14

III. LOADING DATA


III.1. Design data :
Length of tank , L = 200 cm ROOF

Width of tank, W = 200 cm


WALL
Hight of tank, H = 112.5 cm
Type of roof = Flat BOTTOM

Thickness of FRP wall-1, t1 = 1.0 cm


Thickness of FRP wall-1, t2 = 1.0 cm
Thickness of FRP roof, t3 = 1.0 cm
Thickness of FRP bottom flat, t4 = 0.6 cm
Thickness of FRP bottom slope, t5 = 0.6 cm
Density of liquid, r1 = 0.001 kg/cm³
Density of water, r2 = 0.001 kg/cm³
Density of FRP, r3 = 0.00138 kg/cm³

III.2. FRP weight ;


FRP wall-1 weight, w1 = (L.H.t1.r3) x 2
= ( 200 x 112.50 x 1.00 x 0.00138 ) x 2
= 62.07 kg

FRP wall-2 weight, w2 = (L.H.t2.r3) x 2


= ( 200 x 112.50 x 1.00 x 0.00138 ) x 2
= 62.07 kg

Total shell weight = 124.13 kg

FRP top flat weight, w3 = (L.W.t3.r3)


= ( 200 x 200 x 1.02 x 0.00138 )
= 56.05 kg

FRP bottom flat weight, w4 = (L.W.t4.r3)


= ( 200 x 200 x 0.60 x 0.00138 )
= 33.10 kg

FRP bottom slope weight, w5 = (L.W.t5.r3)


= ( 200 x 200 x 0.60 x 0.00138 )
= 33.10 kg

Total FRP shell, roof, bottom weight = 246.39 kg


Total of FRP joint + girth flange = 70.0 kg
Total of FRP laminasi reinforce weight = 121.5 kg
Total of FRP HDL, etc weight = 53 kg
Total of FRP nozzles weight = 83 kg
Grand total FRP Weight, w6 = 573.89 kg

III.3. Steel Accesoriess weight


3.1. Steel lifting lugs on shell;
- Steel pad = L W t n 0.00784 ,where :
= 17.5 x 20 x 0.60 x 4x 0.00784 L = Length of pad or lug
= 6.6 kg W = Width of pad or lug
- Steel lug = L W t n 0.00784 t = Thickness pad or lug
= 15 x 20 x 1.20 x 4x 0.0078 n = Number of pad or lug
= 11.3 kg
Doc. No : TK-23055-CAL-01
Revision : A

STRENGTH CALCULATION SHEET Date : November 21, 2023


Page : 9 of 14

Steel lifting lug weight on shell = 17.9 kg

Grand total steel Lifting weight, W 6 = 17.88 kg

3.2. Reinforce Rib:


- Reinforce Rib Weight = 227.5 kg
L Bar 50 x 50 x 6 mm Thk

3.3. Other:
- Other Accessories Weight = 53 kg
Total accessories weight = 298.38 kg

III.4. Full liquid weight


Shell volume weight = L.W.H.r1
= 200 x 200 x 112.5 x 0.00100
= 4500 kg

Grand total full liquid weight, w 7 = 4500 kg

III.5. Full water weight (at hydrotest condition)


Shell volume weight = L.W.H.r2
= 200 x 200 x 113 x 0.00100
= 4500 kg

Grand total full water weight, w 8 = 4500 kg

III.6. Summary loading data


Empty Weight, We = 872.27 kg

Operation Weight Condition, Wo = w9 + w7


= 872.27 kg + 4500.0 kg
= 5372.3 kg

Hydrotest Weight Condition, Wh = w9 + w8


= 872.27 kg + 4500.0 kg
= 5372.3 kg
Doc. No : TK-23055-CAL-01
Revision : A

STRENGTH CALCULATION SHEET Date : November 21, 2023


Page : 10 of 14

IV.1 Design Lifting Lugs for lift of Tank

1.1 Material of Lifting Lugs


Pad & Lugs Material = SS 400 with FRP lamination
Yield Stress of Lugs Material, Sy = 250 Mpa = 25 kg/mm2
2
Allowable Shear Stress, Ssa (0.4xSy) = 10.20 kg/mm
Allowable Bending Stress, Sba (0.66xSy) = 16.83 kg/mm2
Allowable Tensile Stress, Sta (0.6xSy) = 15.30 kg/mm2
Number of Lifting, N = 4 ea
Erection Weight (suppoted by Lug only), We = 872.27 kg (from loading data)
Dynamic Load factor, F = 1.25
Loading per lug W = (We / N) x 1.25 = 272.58 kg
Angle of lift, α = 12 deg
W1 = W cos (α) = 272.6 x cos(12) = 267 kg
W2 = W tan (α) = 272.6 x tan(12) = 57.9 kg
W3 = 0.5 W = 136 kg

Dimension of Lifting Lug:


t = 12 mm d = 40 mm
b = 150 mm a = 150 mm
R = 50 mm
c = 7 mm

Dimension of Pad Lifting Lug:


a
Lp = 175 mm Wp = 200 mm
tp = 6 mm

1.2 Strength Calculation of lifting lugs


1.2.1 Tension Stress due to 'W'
ST = W/(2R-d)xt
= 272.6 /( 2x 50 - 40 )x 12
2
= 0.3786 kg/mm < 15.30 kg/mm2 OK

1.2.2 Bending Stress due to 'W1'


M1 = W1 x b
= 266.6 x 150 = 39993.964 kg.mm
Z1 = a x t2/6 = 150 x 12 2
/ 6= 3600 mm3
2 2
Sb1 = M1/Z1 = 11.109 kg/mm < 16.83 kg/mm OK

1.2.3 Bending Stress due to 'W3'


M2 = W3 x b
= 136.3 x 150 = 20443.726 kg.mm
Z2 = a x t2/6 = 150 x 12 2
/ 6= 3600 mm3
2
Sb2 = M2/Z2 = 5.6788 kg/mm < 16.83 kg/mm2 OK

1.2.5 Shear Stress due to weldment


SWS = W/(2*a*c)
= 272.6 /( 2x 150 x 7)
2
= 0.1298 kg/mm < 10.20 kg/mm2 OK
Doc. No : TK-23055-CAL-01
Revision : A

STRENGTH CALCULATION SHEET Date : November 21, 2023


Page : 11 of 14

1.3 Strength Calculation of pad lifting lug

1.3.1 Tensile Stress of pad due to 'W'


S1 = W / (Lpx tp)
= 272.6 /(( 175 x 6)
= 0.26 kg/mm2 < 15.30 kg/mm
2
OK

1.3.2 Tensile Stress of pad due to 'W1'


S2 = W1/ (Lpx tp)
= 266.6 /(( 175 x 6)
= 0.25 kg/mm2 < 15.30 kg/mm
2
OK

1.3.2 Tensile Stress of pad due to 'W2'


S3 = W2/ (LpxWp)
= 57.9 /(( 175 x 200 )
= 0.0017 kg/mm2 < 15.30 kg/mm
2
OK

1.3.4 Tensile Stress of pad due to 'W3'


S4 = W3/ (Wpx tp)
= 136 /(( 200 x 6)
= 0.11 kg/mm2 < 15.30 kg/mm
2
OK

1.3.5 Bending Stress due to 'W'


M1 = W x tp = 272.58 x 6 = 1635.4981 kg.mm
Z1 = Wp x tp2/6 = 200 x 6 2
/ 6 = 1200 mm2
Sb1 = M1/Z1
= 1635.4981 / 1200
2
= 1.3629 kg/mm < 16.83 kg/mm2 OK

1.3.6 Bending Stress due to 'W1'


M2 = W1 x tp = 266.63 x 6 = 1599.7585 kg.mm
Z2 = Wp x tp2/6 = 200 x 6 2
/ 6 = 1200 mm2
Sb2 = M2/Z2
= 1599.7585 / 1200
2
= 1.3331 kg/mm < 16.83 kg/mm2 OK

1.3.7 Bending Stress due to 'W2'


M3 = W2 x tp = 57.94 x 6 = 347.6359 kg.mm
Z3 = Wp x tp2/6 = 200 x 6 2
/ 6 = 1200 mm2
Sb3 = M3/Z3
= 347.6359 / 1200
2
= 0.2897 kg/mm < 16.83 kg/mm2 OK

1.3.8 Bending Stress due to 'W3'


M4 = W3 x tp = 136.29 x 6 = 817.74905 kg.mm
Z4 = Wp x tp2/6 = 200 x 6 2
/ 6 = 1200 mm2
Sb4 = M4/Z4
= 817.74905 / 1200
2
= 0.6815 kg/mm < 16.83 kg/mm2 OK
Doc. No : TK-23055-CAL-01
Revision : A

STRENGTH CALCULATION SHEET Date : November 21, 2023


Page : 12 of 14

1.3.9 Shear Stress due to 'W''


SSH = W /(WpxLp) = 272.6 / ( 200 x 175 )
2
= 0.0078 kg/mm < 10.20 kg/mm2 OK

1.3.10 Shear Stress due to 'W3''


SSH = W3 /(WpxLp) = 136.3 / ( 200 x 175 )
2
= 0.0039 kg/mm < 10.20 kg/mm2 OK

Laminate overlay properties:


Sts = Ultimate tensile strength = 15000 psi = 1055 kg/cm² (refer to ASME RTP-1, Table 2A-3)
Sfs = Ultimate flexural strength = 22000 psi = 1547 kg/cm² (refer to ASME RTP-1, Table 2A-3)
Ssh = Ultimate secondary bond shear stress = 2000 psi = 141 kg/cm² (refer to ASME RTP-1, 3A-800)
Sax = Axial tensile modulus = 1500000 psi = 105457 kg/cm²
Shp = Flexural modulus = 1000000 psi = 70305 kg/cm²
F = Safety factor = 5
σts = Allowable tensile stress = 211 kg/cm²
σsa = Allowable Shear accross thickness = 105 kg/cm²
σsh = Allowable Secondary Bond Shear Stress = 14 kg/cm²

σax = Allowable axial tensile stress = 422 kg/cm²


σhp = Allowable hoop tensile stress = 281 kg/cm²

1.4 Laminate overlay of pad calculation:


Minimum required overlay area of secondary bond each pad
ASL = W / Sh
= 273 / 14.0
= 19.47 cm2

The minimum required area of secondary RTP bond


ASV = ASL
2
= 19.47 cm

Designed overlay area of secondary bond overlay on the vessel wall


Lp = 17.5 cm
Wp = 20.0 cm
HLAM = 50.0 cm
WLAM = 45.0 cm

ASV ≥ ASL
A overlay - A Lug ≥ ASL
hLAM x WLAM - Lp x Wp ≥ ASL
1900 cm2 ≥ 19.47 cm2 OK
Doc. No : TK-23055-CAL-01
Revision : A

STRENGTH CALCULATION SHEET Date : November 21, 2023


Page : 13 of 13

Calculate unit radial load on overlay each pad (F = W)

Wmax = 3F/Lp2
2
= 3 x 272.6 / 17.5
2
= 2.670 kg/cm

Calculate total radial load due to moment all pad

= ( 2.67 x 17.5 )/2


= 23.36 kg

Calculate tensile perimeter,


=
= 2 x 17.5 + 20.0
= 55 cm2

Maximum tensile perimeter load = 50 lb/in (as per ASME RTP-1, NM4-520)
= 8.929 kg/cm

Check for perimeter


= Total radial load / Tensile parameter
= 0.42 kg/cm < 8.929 kg/cm OK

Calculate mean radius of overlay


Rm = (length) / 2
= 10 cm = 3.9 in

Calculate overlay hoop load

= 5.1921 kg

The overlay hoop tensile stress


σ = Ttot/ht
= 5.1921 /( 50 x 1.5 )
= 0.07 kg/cm² < 211 kg/cm² OK
Calculate shear across roof wall
Tw = P/tL
= 23.36 /( 1.5 x 20.0 )
= 0.78 kg/cm² < 105 kg/cm² OK

Calculate local bending in roof tank wall


β
1/2
= 1.25/(Rmt)
= 0.32275 in-1 = 0.8198 cm-1

Calculate unit radial loading

= 1.17 kg/cm
Doc. No : TK-23055-CAL-01
Revision : A

STRENGTH CALCULATION SHEET Date : November 21, 2023


Page : 14 of 14

Bending Load, axial

= 1.17 / 4 x 0.81978
= 0.4 kg/cm

Bending Load, hoop

= 0.30 x 0.4
= 0.1 kg/cm

Load due to bending stresses

= 1 kg/cm2 < 421.83 OK

= 0.285 kg/cm2 < 281.22 OK

Overlay thickness due to uplift load as stress limit

= 0.1424 cm

= 0.078 cm

Lifting Lug Overlay thickness used = 0.1 cm = 1.5 cm (used)

IV.2. Summary of Lifting Lug

LIFTTING LUG Decided Unit


Quantity of Lifting Lug 4 pcs
Lifting Lug Witdh 15 cm
Lifting Lug Height 20 cm
Lifting Thickness 1.2 cm
Lifting Lug pad Witdh 20 cm
Lifting Lug pad length 17.5 cm
Lifting Lug Pad Thickness 0.6 cm
Lifting Lug Overlay Thickness 1.5 cm
MECHANICAL

STRENGTH CALCULATION SHEET FOR LIFTING LUGS

DEMIN WATER FRP TANK

A 13-Nov-23 Issued For Review ITA IFF YAN


Rev. Date Description By Chk App

Status Code: A = Issued For Review, B = Issued For Approval, 0 = Issued For Construction
INFO = For Information
Doc. No : TK-21030-CAL-01
Revision : A

STRENGTH CALCULATION SHEET Date : November 13, 2023


Page : 3 of 7

IV.1 Design Lifting Lugs for lift of Tank

1.1 Material of Lifting Lugs


Pad & Lugs Material = SS 400 with FRP lamination
Yield Stress of Lugs Material, Sy = 250 Mpa = 25 kg/mm2
2
Allowable Shear Stress, Ssa (0.4xSy) = 10.20 kg/mm
Allowable Bending Stress, Sba (0.66xSy) = 16.83 kg/mm2
Allowable Tensile Stress, Sta (0.6xSy) = 15.30 kg/mm2
Number of Lifting, N = 4 ea
Erection Weight (suppoted by Lug only), We = 797.41 kg (from loading data)
Dynamic Load factor, F = 1.25
Loading per lug W = (We / N) x 1.25 = 249.19 kg
Angle of lift, α = 12 deg
W1 = W cos (α) = 249.2 x cos(12) = 244 kg
W2 = W tan (α) = 249.2 x tan(12) = 53.0 kg
W3 = 0.5 W = 125 kg

Dimension of Lifting Lug:


t = 12 mm d = 40 mm
b = 150 mm a = 150 mm
R = 50 mm
c = 7 mm

Dimension of Pad Lifting Lug:


a
Lp = 175 mm Wp = 200 mm
tp = 6 mm

1.2 Strength Calculation of lifting lugs


1.2.1 Tension Stress due to 'W'
ST = W/(2R-d)xt
= 249.2 /( 2x 50 - 40 )x 12
2
= 0.3461 kg/mm < 15.30 kg/mm2 OK

1.2.2 Bending Stress due to 'W1'


M1 = W1 x b
= 243.7 x 150 = 36561.855 kg.mm
Z1 = a x t2/6 = 150 x 12 2
/ 6= 3600 mm3
2 2
Sb1 = M1/Z1 = 10.156 kg/mm < 16.83 kg/mm OK

1.2.3 Bending Stress due to 'W3'


M2 = W3 x b
= 124.6 x 150 = 18689.335 kg.mm
Z2 = a x t2/6 = 150 x 12 2
/ 6= 3600 mm3
2
Sb2 = M2/Z2 = 5.1915 kg/mm < 16.83 kg/mm2 OK

1.2.5 Shear Stress due to weldment


SWS = W/(2*a*c)
= 249.2 /( 2x 150 x 7)
2
= 0.1187 kg/mm < 10.20 kg/mm2 OK
Doc. No : TK-21030-CAL-01
Revision : A

STRENGTH CALCULATION SHEET Date : November 13, 2023


Page : 4 of 7

1.3 Strength Calculation of pad lifting lug

1.3.1 Tensile Stress of pad due to 'W'


S1 = W / (Lpx tp)
= 249.2 /(( 175 x 6)
= 0.24 kg/mm2 < 15.30 kg/mm
2
OK

1.3.2 Tensile Stress of pad due to 'W1'


S2 = W1/ (Lpx tp)
= 243.7 /(( 175 x 6)
= 0.23 kg/mm2 < 15.30 kg/mm
2
OK

1.3.2 Tensile Stress of pad due to 'W2'


S3 = W2/ (LpxWp)
= 53.0 /(( 175 x 200 )
= 0.0015 kg/mm2 < 15.30 kg/mm
2
OK

1.3.4 Tensile Stress of pad due to 'W3'


S4 = W3/ (Wpx tp)
= 125 /(( 200 x 6)
= 0.10 kg/mm2 < 15.30 kg/mm
2
OK

1.3.5 Bending Stress due to 'W'


M1 = W x tp = 249.19 x 6 = 1495.1468 kg.mm
Z1 = Wp x tp2/6 = 200 x 6 2
/ 6 = 1200 mm2
Sb1 = M1/Z1
= 1495.1468 / 1200
2
= 1.246 kg/mm < 16.83 kg/mm2 OK

1.3.6 Bending Stress due to 'W1'


M2 = W1 x tp = 243.75 x 6 = 1462.4742 kg.mm
Z2 = Wp x tp2/6 = 200 x 6 2
/ 6 = 1200 mm2
Sb2 = M2/Z2
= 1462.4742 / 1200
2
= 1.2187 kg/mm < 16.83 kg/mm2 OK

1.3.7 Bending Stress due to 'W2'


M3 = W2 x tp = 52.97 x 6 = 317.8033 kg.mm
Z3 = Wp x tp2/6 = 200 x 6 2
/ 6 = 1200 mm2
Sb3 = M3/Z3
= 317.8033 / 1200
2
= 0.2648 kg/mm < 16.83 kg/mm2 OK

1.3.8 Bending Stress due to 'W3'


M4 = W3 x tp = 124.60 x 6 = 747.57338 kg.mm
Z4 = Wp x tp2/6 = 200 x 6 2
/ 6 = 1200 mm2
Sb4 = M4/Z4
= 747.57338 / 1200
2
= 0.623 kg/mm < 16.83 kg/mm2 OK
Doc. No : TK-21030-CAL-01
Revision : A

STRENGTH CALCULATION SHEET Date : November 13, 2023


Page : 5 of 7

1.3.9 Shear Stress due to 'W''


SSH = W /(WpxLp) = 249.2 / ( 200 x 175 )
2
= 0.0071 kg/mm < 10.20 kg/mm2 OK

1.3.10 Shear Stress due to 'W3''


SSH = W3 /(WpxLp) = 124.6 / ( 200 x 175 )
2
= 0.0036 kg/mm < 10.20 kg/mm2 OK

Laminate overlay properties:


Sts = Ultimate tensile strength = 15000 psi = 1055 kg/cm² (refer to ASME RTP-1, Table 2A-3)
Sfs = Ultimate flexural strength = 22000 psi = 1547 kg/cm² (refer to ASME RTP-1, Table 2A-3)
Ssh = Ultimate secondary bond shear stress = 2000 psi = 141 kg/cm² (refer to ASME RTP-1, 3A-800)
Sax = Axial tensile modulus = 1500000 psi = 105457 kg/cm²
Shp = Flexural modulus = 1000000 psi = 70305 kg/cm²
F = Safety factor = 5
σts = Allowable tensile stress = 211 kg/cm²
σsa = Allowable Shear accross thickness = 105 kg/cm²
σsh = Allowable Secondary Bond Shear Stress = 14 kg/cm²

σax = Allowable axial tensile stress = 422 kg/cm²


σhp = Allowable hoop tensile stress = 281 kg/cm²

1.4 Laminate overlay of pad calculation:


Minimum required overlay area of secondary bond each pad
ASL = W / Sh
= 249 / 14.0
2
= 17.799 cm

The minimum required area of secondary RTP bond


ASV = ASL
2
= 17.799 cm

Designed overlay area of secondary bond overlay on the vessel wall


Lp = 17.5 cm
Wp = 20.0 cm
HLAM = 50.0 cm
WLAM = 45.0 cm

ASV ≥ ASL
A overlay - A Lug ≥ ASL
hLAM x WLAM - Lp x Wp ≥ ASL
1900 cm2 ≥ 17.80 cm2 OK
Doc. No : TK-21030-CAL-01
Revision : A

STRENGTH CALCULATION SHEET Date : November 13, 2023


Page : 6 of 6

Calculate unit radial load on overlay each pad (F = W)

Wmax = 3F/Lp2
2
= 3 x 249.2 / 17.5
2
= 2.441 kg/cm

Calculate total radial load due to moment all pad

= ( 2.44 x 17.5 )/2


= 21.36 kg

Calculate tensile perimeter,


=
= 2 x 17.5 + 20.0
= 55 cm2

Maximum tensile perimeter load = 50 lb/in (as per ASME RTP-1, NM4-520)
= 8.929 kg/cm

Check for perimeter


= Total radial load / Tensile parameter
= 0.39 kg/cm < 8.929 kg/cm OK

Calculate mean radius of overlay


Rm = (length) / 2
= 10 cm = 3.9 in

Calculate overlay hoop load

= 4.7465 kg

The overlay hoop tensile stress


σ = Ttot/ht
= 4.7465 /( 50 x 1.5 )
= 0.06 kg/cm² < 211 kg/cm² OK
Calculate shear across roof wall
Tw = P/tL
= 21.36 /( 1.5 x 20.0 )
= 0.71 kg/cm² < 105 kg/cm² OK

Calculate local bending in roof tank wall


β
1/2
= 1.25/(Rmt)
= 0.32275 in-1 = 0.8198 cm-1

Calculate unit radial loading

= 1.07 kg/cm
Doc. No : TK-21030-CAL-01
Revision : A

STRENGTH CALCULATION SHEET Date : November 13, 2023


Page : 7 of 7

Bending Load, axial

= 1.07 / 4 x 0.81978
= 0.3 kg/cm

Bending Load, hoop

= 0.30 x 0.3
= 0.1 kg/cm

Load due to bending stresses

= 1 kg/cm2 < 421.83 OK

2
= 0.2605 kg/cm < 281.22 OK

Overlay thickness due to uplift load as stress limit

= 0.1361 cm

= 0.0746 cm

Lifting Lug Overlay thickness used = 0.1 cm = 1.5 cm (used)

IV.2. Summary of Lifting Lug

LIFTTING LUG Decided Unit


Quantity of Lifting Lug 4 pcs
Lifting Lug Witdh 15 cm
Lifting Lug Height 20 cm
Lifting Thickness 1.2 cm
Lifting Lug pad Witdh 20 cm
Lifting Lug pad length 17.5 cm
Lifting Lug Pad Thickness 0.6 cm
Lifting Lug Overlay Thickness 1.5 cm