QCEPT Make Facia Alarm Annunciator - Q 1100N & Q 1100D series is designed with
Microcontroller based advance technology and field proven model for all types of fields and environmental
conditions. This model is Type tested for all EMI, EMC tests(as per IEC), Temperature rise and Cold test at a
NABL accredited Govt. Lab.
FEATURES
Ø Advanced high speed Single Chip Microcontroller with reliability and accuracy
Ø Available from 2windows to 64 windows
Ø Available in small, Big windows and combination of both
Ø Low power consumption
Ø Long life super bright SMD LED used
Ø with multi-colour selection
Ø Wide range AC/ DC Aux. supply
Ø Standby power supply
Ø DC supervision & fail Indication with Alarm contacts
Ø AC fail Indication with Alarm contacts
Ø Contacts for external Alarms
Ø Inbuilt Alarm
Ø RS 485 communications& TCP-IP.
Ø Opto isolated inputs
Ø Field selectable Window colour
Ø Field selectable Trip & Non trip
Ø Field selectable NO/NC inputs
Ø Field selectable operating Mode
Ø Field selectable window flash rate
Ø Field selectable Alarm during Test
Ø Provision for External Push buttons for Test, Mute, Accept & Reset
Ø Built in Push buttons – Test, Mute, Accept& Reset
Ø Potential free input contacts
Ø Two sets of potential free normally open contacts for Audible Alarms(T & NT)
Ø Watch dog LED with Flashing
Ø Shock proof shrouded terminal's
Ø Low depth
TECHNICAL SPECIFICATION
Ø Windows available :-2, 4, 6, 8, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30, 32, 34, 36 38, 40, 42, 44, 46, 48,
52,56,60 & 64 windows
Ø Aux. supply:1) 10 to 18 V DC, 2)20 to 150V DC,3)75 to 275V AC/DC
Ø Window illumination: Ultra high bright SMD LED
Ø Window Colour: All Red, Red/ Yellow, Red/ White – site selectable (other colors optional)
Ø Window size:
For Q 1100N = 34 (H) x 37(W) mm and 34 (H) x 74 (W) mm – combination of both sizes
For Q 1100D = 34.5(H) x 69(W) mm and 34.5(H) x 34.5(W) mm – combination of both series
Ø Window Flash rate: 100 / 60 flashes per minute –site selectable
Ø Window Legend(Inscription): Tracing sheet print or Photo negative
Ø Power consumption : 0.8W per window
Ø Field input: potential free protective relay Normally open contact (with potential is optional)
Ø Input interrogation Voltage: -24V DC(from the unit) – No external voltage required
Ø Input Field contacts: Normally open contact(site selectable NO/NC selection is optional)
Ø Input Isolation: Opto isolated (2 kv) (from internal circuits)
Ø Response Time: 20 m Sec (other response time upon request)
Ø Sequence of operation:
Site selectable –Manual Reset (ISA sequence code M), Ring Back (ISA sequence code R)
Auto Reset (ISA sequence code A) , First out Manual Reset (ISA sequence code A), First out Auto
Reset (ISA sequence code F2A, First in First Accept (Custom sequence)
Ø Output Contact: 1 NO contact for Trip Alarm,1 NO contact for Non Trip Alarm,
1 NO contact for DC fail alarm& 1 NO contact for AC Fail (Optional feature)
Ø Output contact Rating: 10A@30V DC/ 230V AC resistive load (make & carry)
Ø Push buttons: Inbuilt push buttons for Test, Mute, Accept & Rest, and also terminals provided
for external PB's
Ø Built in Alarm: Built in Alarm will be of 1 Tone, 2 Tone, 3 Tone (optional)
Ø Sound Output: 90 dB
Ø Enclosure: FR Grade ABS plastic
Ø Protection: Front: IP54 , Back: IP20
Ø Standby power supply: 230V AC - 45 to 55 Hz (it can withstand and work up to 75 to 350V AC )
Ø DC Fail Indication: Last window flashing with1NO potential free contact for Alarm (Any specific
window no. is upon request)
Ø AC Fail Indication: Last but one window Flashing with Non trip contact for Alarm (separate contact
for Alarm upon request)
Ø Built in Event Logger contact: 1 NO Potential free contact per window will be given for SCADA
application
Built in serial Communication: RS 485 Modbus RTU, MODBUS TCP-IP (Over Ethernet, IEC 61850 over
Ethernet & IEC 61850 over fibered
PANEL CUTOUT:- Q 1100N SERIES
8 2N 147(H) X 148 (W) X 120 154(H) X 156 44 11N 147(H) X 850 (W) X 154(H) X 858 (W)
(D) (W) 120 (D)
12 3N 147(H) X 226 (W) X 120 154(H) X 234 48 12N 147(H) X 928(W) X 154(H) X 936 (W)
(D) (W) 120 (D)
16 4N 147(H) X 305 (W) X 120 154(H) X 312 52 13N 147(H) X 1006 (W) X 154(H) X 1014 (W)
(D) (W) 120 (D)
20 5N 147(H) X 383 (W) X 120 154(H) X 390 56 14N 147(H) X 1084 (W) X 154(H) X 1092 (W)
(D) (W) 120 (D)
24 6N 147(H) X 461 (W) X 120 154(H) X 468 60 15N 147(H) X 1162 (W) X 154(H) X 1170 (W)
(D) (W) 120 (D)
28 7N 147(H) X 538 (W) X 120 154(H) X 546 64 16N 147(H) X 1240 (W) X 154(H) X 1248 (W)
(D) (W) 120 (D)
SMALL WINDOWS – 34 X 37 mm
NO. OF
WINDOWS CASE PANEL CUTOUT – mm FRONT BEZZEL SIZE
8 2N 138(H) X 138 (W) X 94 (D) 159.2(H) X 144(W) 16 2N 138(H) X 138 (W) X 159(H) X 144 (W)
94 (D)
12 3N 138(H) X 210 (W) X 94 (D) 159(H) X 216 (W) 24 3N 138(H) X 210 (W) X 159(H) X 216(W)
94 (D)
16 4N 138(H) X 282 (W) X 94 (D) 144(H) X 288 (W) 32 4N 138(H) X 282 (W) X 144(H) X 288 (W)
94 (D)
20 5N 138(H) X 354(W) X 94 (D) 144(H) X 360 (W) 40 5N 138(H) X 354 (W) X 144(H) X 360 (W)
94 (D)
24 6N 138H) X 426 (W) X 94 (D) 144(H) X 432 (W) 48 6N 138(H) X 426 (W) X 144(H) X 432 (W)
94 (D)
28 7N 138(H) X 538 (W) X 94 (D) 144(H) X 546 (W) 56 7N 138(H) X 538 (W) X 144(H) X 546 (W)
94 (D)
32 8N 138(H) X 570 (W) X 94 (D) 144(H) X 576 (W) 64 8N 138(H) X 570 (W) X 144(H) X 576(W)
94 (D)
Note: We have 2R, 3R 4R, 5R, 6R & 7 Row type also – Dimensions are available on request