Notification Appliances

Voltage Drop Analysis


APS-6R to FCM-1 (Resistive Load: 3.0 amps) Source Voltage: 24 VDC Nominal

Protected Premises: NCC- PROJECT - UNITED STATES CONSULATE Date: 1/15/2009


Address: SURABAYA - INDONESIA City: SURABAYA
State: INDONESIA Zip: Note: NOB - Building NAC 8 - 14 No's Strobe

Prepared By: First Kuwaiti Trading & Contracting W.L.L. Phone: +965-800500
Address: P.O.Box : 480 Al - Souk Al - Dakhi 15255 Kuwait City: Kuwait
State: Kuwait Zip: 00965

Current Distance (Feet) Circuit Voltage @ Each Device


(amps)
Device # PartNumber Between Total 10 AWG 12 AWG 14 AWG 16 AWG 18 AWG
1 S122415MC 0.0590 39 39 23.94 23.90 23.85 23.76 23.62
2 S122415MC 0.0590 20 59 23.91 23.85 23.78 23.65 23.45
3 HS4-2415MCW-FW 0.0410 49 108 23.85 23.74 23.62 23.40 23.05
4 HS4-2415MCW-FW 0.0410 42 150 23.80 23.65 23.49 23.20 22.73
5 HS4-2430MCW-FW 0.0650 13 163 23.79 23.62 23.46 23.14 22.64
6 HS4-2415MCW-FW 0.0410 13 176 23.78 23.60 23.42 23.09 22.56
7 HS4-2415MCW-FW 0.0410 32 208 23.75 23.55 23.35 22.98 22.38
8 HS4-2415MCW-FW 0.0410 36 244 23.72 23.50 23.28 22.86 22.19
9 HS4-2415MCW-FW 0.0410 36 280 23.70 23.45 23.21 22.76 22.03
10 S122415MC 0.0590 29 309 23.68 23.42 23.16 22.68 21.91
11 S122415MC 0.0590 7 316 23.67 23.41 23.15 22.67 21.89
12 HS4-2430MCW-FW 0.0650 170 486 23.61 23.30 22.98 22.39 21.45
13 HS4-2430MCW-FW 0.0650 46 532 23.60 23.27 22.95 22.35 21.38
14 HS4-2430MCW-FW 0.0650 30 562 23.59 23.27 22.94 22.33 21.35
Total Current: 0.7420 % Voltage Drop: 1.70 3.06 4.41 6.96 11.04

Go Go Go Go Go

Strikethrough indicates a value below the device's minimum voltage at indicated location and wire gauge