Ventilation system S ta n d a r d a n d o v e r r a te d ty p e

e q u ip m e n t

T h e v entilation ru les g iv en in th is manu al N o r m a l o p e r a tin g c o n d itio n s to IE C 60 4 39 -1


are v alid u nd er normal op erating c ond itions. b m a x im u m te m p e ra tu re in th e e le c tric a l ro o m : 4 0 ° C
T h ey ensu re th at th e temp eratu res w ith in b a v e ra g e te m p e ra tu re o v e r 24 h o u rs in th e e le c tric a l ro o m : 35 ° C
th e c u b ic les d o not ex c eed th e max imu m b a v e ra g e a n n u a l te m p e ra tu re in th e e le c tric a l ro o m : 25 ° C
temp eratu res to w h ic h th e c omp onents c an b m in im u m te m p e ra tu re : -5 ° C
b e su b jec ted . b m a x im u m a ltitu d e : 20 0 0 m .
T h e ru les p rov id e for an av erag e d elta T of
1 0 to 1 5 ° C b etw een th e ou tsid e and insid e
of th e c u b ic le. T h e fo llo w in g r u le s a p p ly to :
bL 60 0 s ta n d a rd a n d o v e r r a te d p o w e r fa c to r c o r r e c tio n
m o d u le s
bP 4 0 0 s ta n d a rd a n d o v e r r a te d p o w e r fa c to r c o r r e c tio n
m o d u le s
bV a r p lu s s ta n d a rd a n d o v e r r a te d c a p a c ito rs .

V e n tila tio n r u le s
C a p a c ito rs , c o n ta c to rs , fu s e s a n d e le c tric a l c o n n e c tio n s d is s ip a te h e a t:
D B 1 0 226 4

2.5 W /k v a r.
T h e fo llo w in g v e n tila tio n ru le s m u s t th e re fo re b e c o m p lie d w ith :
b th e a ir w ith in th e c u b ic le m u s t flo w u p w a rd s .
It is re c o m m e n d e d th a t e x tra c to r fa n s b e fitte d o n to p o f th e c u b ic le .
b th e c ro s s -s e c tio n o f th e to p a ir o u tle t m u s t b e a t le a s t 1 .1 tim e s th e c ro s s -
s e c tio n o f th e b o tto m a ir o u tle t
b th e o p e n in g s m u s t b e c o m p a tib le w ith th e s a fe ty ra tin g (IP )
b th e re s h o u ld b e a t le a s t 1 0 0 m m b e tw e e n th e fa n a n d th e m o d u le s o r
c o m p o n e n ts
b th e a ir in le t a t th e b o tto m a ir in ta k e g rille m u s t n o t b e o b s tru c te d o r
re s tric te d b y a c o m p o n e n t o r m o d u le .

A p p lic a tio n s
T h e v e n tila tio n ru le s a p p ly to c u b ic le s w ith th e fo llo w in g d im e n s io n s :
b h e ig h t H = 20 0 0 m m
b w id th W = 6 0 0 m m m in im u m
b d e p th D = 4 0 0 m m m in im u m
b a n d p o w e r le s s th a n o r e q u a l to 4 0 5 k v a r 4 0 0 V - 5 0 H z p e r c o lu m n .

R e a c tiv e p o w e r Type of A ir in le t M in . a ir flo w


6
(k v a r a t 4 0 0 V - 5 0 H z ) v e n tila tio n (m 3/h o u r )
C u b ic le s a fe ty r a tin g (IP ) y 3X
P o w e r y1 0 0 kva r N a tu ra l 20 0 c m 2 -
P o w e r 1 0 0 to 20 0 k v a r N a tu ra l 40 0 cm 2 -
P o w e r > 20 0 k v a r F o rc e d - u 0 .7 5 tim e s th e
p o w e r in k v a r
C u b ic le s a fe ty r a tin g (IP ) > 3X
A ll p o w e r v a lu e s F o rc e d - u 0 .7 5 tim e s th e
p o w e r in k v a r

33