Professional Documents
Culture Documents
SP 2416
SP 2416
Revision: 01
Effective: May 2022
Document ID SP-2416
Security Restricted
Revision 1.0
Keywords: This document is the property of Petroleum Development Oman, LLC. Neither the
whole nor any part of this document may be disclosed to others or reproduced, stored in a
retrieval system, or transmitted in any form by any means (electronic, mechanical,
reprographic recording or otherwise) without prior written consent of the owner.
i Document Authorization
Document Authorization
Document Owner Document Custodian Document Author
(CFDH)
Alex van der Veen, MSE4 Johannes Intven, MSE8 Johannes Intven, MSE8
ii Revision History
The following is a brief summary of the 4 most recent revisions to this document. Details of all
revisions prior to these are held on file by the issuing department.
Table of Content
Table of Content ...........................................................................................................................................3
1. Introduction ..............................................................................................................................................5
2. Scope .........................................................................................................................................................5
3. Basic Process Safety Systems ...............................................................................................................5
4. Definitions .................................................................................................................................................6
4.1 Remote and Unmanned Site Definition ............................................................................................................. 6
4.2 Safety Device Symbols and Identification .......................................................................................................... 7
5. General ......................................................................................................................................................9
5.1 Background .......................................................................................................................................................... 9
5.2 Safety Analysis .................................................................................................................................................. 10
5.3 Application of the Safety Analysis Checklist ....................................................................................................... 10
6. Wellheads and Flowlines ...................................................................................................................... 11
6.1 General .............................................................................................................................................................. 11
6.2 Figures ............................................................................................................................................................... 11
6.3 Safety Analysis Table......................................................................................................................................... 12
6.4 Safety Device Location and Initiation ................................................................................................................. 13
6.4.1 Pressure safety devices (PZH, and RV) .................................................................................................................13
6.4.2 Flow safety device (FZV) ..........................................................................................................................................13
6.4.3 Shutdown valve (ESD) ..............................................................................................................................................13
6.4.4 Sand probe (YCP)......................................................................................................................................................13
6.4.5 Temperature safety devices (TZH) ..........................................................................................................................13
6.5 Safety Analysis Checklist (SAC) ........................................................................................................................ 13
7a. Headers ................................................................................................................................................ 14
7a.1 General ............................................................................................................................................................ 14
7a.2 Figures ............................................................................................................................................................. 14
7a.3 Safety Analysis Table....................................................................................................................................... 14
7a.4 Safety Device location and Initiation ................................................................................................................ 15
7a.4.1 Pressure safety devices (PZH, and RV) ...............................................................................................................15
7a.4.2 Flow safety device (FZV) ........................................................................................................................................15
7a.4.3 Shutdown devices (ESD) ........................................................................................................................................15
7a.5 Safety Analysis Checklist (SAC) ...................................................................................................................... 15
8. Pressure Vessels................................................................................................................................... 17
8.1 General .............................................................................................................................................................. 17
8.2 Figure ................................................................................................................................................................. 18
8.3 Safety Analysis Table......................................................................................................................................... 18
8.4 Safety Device Location and Initiation ................................................................................................................. 19
8.4.1 Safety devices (PZH, PZL and RV) .........................................................................................................................19
8.4.2 Level safety devices (LZH and LZL)........................................................................................................................19
8.4.3 Flow safety device (FZV) ..........................................................................................................................................20
8.5 Safety Analysis Checklist ................................................................................................................................... 20
9. Atmospheric Tanks ............................................................................................................................... 20
9.1 General .............................................................................................................................................................. 20
9.2 Figure ................................................................................................................................................................. 21
9.3 Safety Analysis Table......................................................................................................................................... 21
9.4 Safety device location and initiation ................................................................................................................... 22
9.4.1 Pressure safety devices (PVV and BOH) ...............................................................................................................22
9.4.2 Level safety devices (LZH and LZL)........................................................................................................................22
TZHTZHTZH9.5 Safety Analysis Checklist .............................................................................................................. 22
10. Fired Components............................................................................................................................... 22
10.1 General ............................................................................................................................................................ 22
10.2 Figures ............................................................................................................................................................. 23
10.3 Safety Analysis Table....................................................................................................................................... 23
10.4 Safety Device Location and Initiation ............................................................................................................... 24
10.4.1 Temperature safety devices (TZH)........................................................................................................................24
1. Introduction
This document specifies the requirements and gives recommendations for the Basic Process Safety
Systems. This SP contains requirements to mitigate process safety risks in accordance with the
Design Engineering Manual (DEM)-1 requirements as included in SP-2388.
This document should be used in an early phase of the design to develop the PFS and PEFS before
the Design Review (DR) and HAZOP. The assurance of the design will be done by the DR and the
HAZOP.
This PDO standalone specification is a First Issue of the SP-2416 dated April 2022.
2. Scope
Define the process inclusive of its mapping to the latest version of the PDO Business Model. This
Specification provides guidance on Basic Process Safety Systems during the early design phase.
This will be assured by the DR and HAZOP
Responsibility for this document is with the Technical Safety CFDH, the Owner. Changes to this
document are only be authorized and approved by the Owner. Users of the Document who identify
inaccuracy or ambiguity can notify the Custodian and request changes be initiated.
Feedback from users of this Specification will be considered as indicators of performance levels of
this SP by the Owner to ascertain the timeline for updating the document and actions to be taken if
measurements indicate corrective action is required.
Performance monitoring for this SP is to be undertaken every 3 years under Technical Safety CFDH,
and actions to be taken if measurements indicate corrective action is required based on performance
feedback.
The Document Owner and the Custodian have to ensure review and reverification of this specification
every 3 years and/or whenever there is significant update of specifications referred in this document.
Periodic, systematic review for the process specification will be decided by Technical Safety CFDH,
the Owner and there is review of specifications referred in this specification.
• Equipment containing light liquid hydrocarbons (i.e., butane or lighter); Water injection
systems
• Sour gas production or processing; Power plants; LNG facilities.
This Specification is modelled after API RP 14C, applicable to off-shore production installations,
however, is focusing on the on-shore requirements. It uses the same approach of identifying the
common controls that could be necessary while clearly defining the reasons some controls would not
be necessary. The Safety Analysis Checklists (SACs) are provided in the appendices of this
specification for each component type.
4. Definitions
General definitions and abbreviations have been provided in Appendix A.
4.1 Remote and Unmanned Site Definition
1. A site is defined as REMOTE when all of the following conditions are met:
Rationale: To establish the criteria to determine what can be considered to be a REMOTE site.
a. Within a 450-meter radius of the site, none of the following are present:
i 10 or more occupied buildings (per SP-1127) or permanent campsites of any type,
(e.g., residences, recreational vehicle parking spots);
ii any hospitals,
iii any residential areas,
iv any places of worship,
v any schools,
vi any sports parks,
vii any places of business,
viii any multi-lane roads, meaning two lanes or more in each direction.
b. There are no habitable buildings or public roads located such that, in the event of a release,
public receptors would be exposed to hydrocarbons >50 % Lower Flammability Limit (LFL)
or very toxic >Immediately Dangerous To Life or Health (IDLH). For H2S toxic limits see
SP-1190-1.
2. A site is defined as UNMANNED when the site does not have employees regularly assigned to
work at the location on a daily shift basis.
Rationale: If the site is operated, maintained, or serviced by employees who visit the site only
periodically to check its operation and to perform necessary operating or
maintenance tasks, then this is not considered a regularly assigned shift basis.
Note: A site operated on a dayshift basis is not considered UNMANNED.
3. A site is defined as REMOTE AND UNMANNED when the conditions in both (4.1, Item 1 and
Item 2) are met.
Rationale: To establish that a site that is both a REMOTE site and an UNMANNED site can be
considered to be a REMOTE AND UNMANNED site without having to satisfy any
additional criteria.
International
Variable Society of Combination
Common Single Device
Automation Device
(ISA)
Flow Safety
Backflow Check Valve
Valve
Level
Pressure
International
Variable Society of Combination
Common Single Device
Automation Device
(ISA)
Emergency
Pressure Relief Pressure
Vent Safety Valve
Pressure Pressure
Vacuum Relief
or Safety Valve Safety Valve
Pressure or
Vacuum
Vent None
High
Temperature Temperature
Safety High
Sensor
Temperature
Low
Temperature Temperature
Safety Low
Sensor
Flame or Stack
Flame spark arrestor None
Flame Detector
(Ultraviolet/
Infrared)
Fire
Heat Detector Temperature
(Thermal) Safety High
International
Variable Society of Combination
Common Single Device
Automation Device
(ISA)
Temperature
Fusible Material Safety Element
Sand Probe
Sand
(Erosion Probe)
Actuated valves
5. General
5.1 Background
The purpose of a safety system is to protect personnel, the environment, and the facility from
threats to safety caused by the production process. Potential threats to safety are identified
through proven systems analysis techniques that have been adapted to the production process.
Recommended protective measures are common industry practices proven through experience.
The systems analysis and protective measures have been combined into a “safety analysis” for
production installations.
4. The safety devices should be incorporated into the design at the locations provided in this
Specification.
Notes:
1. Long radius Elbows or cushion tees are recommended for bends on the flowlines for flowing wells per Materials.
2. FZV recommended to prevent cross circulation.
3. For gas wells a local RV needs to be added to cater for HIPPS leakage.
Notes:
1. FZV recommended to prevent cross circulation.
2. The Stuffing box level switch is a secondary containment device that catches liquid from a seal leak and shuts
down the pump jack when a level is detected.
The safety system remains the same whether gas is routed within a dedicated line or is mixed with liquid.
Detectable abnormal
Undesirable event Cause condition at component
7a. Headers
7a.1 General
Safety devices for typical manifolds are shown in Figure 7.1.
7a.2 Figures
Figure 7a.1 Safety devices –Headers
Detectable abnormal
Undesirable event Cause condition at component
7b. Manifolds
7b.1 General
Safety devices for typical manifolds are shown in Figure 7b.1.
7b.2 Figures
Figure 7b.1 Safety devices –Manifolds
Detectable abnormal
Undesirable event Cause
condition at component
8. Pressure Vessels
8.1 General
This discussion covers only the effects of heat input to the process section of a heated vessel.
Heating equipment is covered in (8).
Pressure vessels associated with compressors, other than compressor cylinders, are covered in
this section.
Safety devices for typical pressure vessels are shown in Figure 8.1.
8.2 Figure
Figure 8.1 Safety devices –Pressure vessel
2. The LZHs and LZLs should be installed in external columns that can be isolated from the vessel,
allowing device testing without interrupting the process:
a. However, if solid deposits or foam cause fouling or false indication of devices in external
columns, the level sensors may be installed directly in the vessel.
In this case, a pump could be required to manipulate vessel liquid level for testing.
8.4.3 Flow safety device (FZV)
1. Check valves (FZVs) should be located in the outlet piping.
Note: If a FZV is installed, the downstream system requires its own overpressure protection.
8.5 Safety Analysis Checklist
1. Refer to (Appendix E) for the SAC associated with pressure vessels.
9. Atmospheric Tanks
9.1 General
This discussion covers only the effects of heat input to the process section of an atmospheric
tank. Heating equipment is covered in (10).
Safety devices for typical atmospheric tanks used in a production process system are shown in
(Figure 9.1). Small portable tanks (< 2500 liters (660 gallons)) such as those used for methanol
or chemical storage that are ancillary to the production process system are not covered by this
document.
1. Tanks should be equipped for emergency venting based on exposure to an external fire case,
per section 7.3 of SP-2399.
2. For emergency venting of tanks located at remote onshore production sites, the exemption
permitted under API SPEC 12F should not be applied.
3. Use of non-metallic tanks for hydrocarbon or produced water storage should be subject to
approval by the Owner’s Mechanical Static TA.
9.2 Figure
Figure 9.1 Safety devices –Atmospheric tanks
Detectable abnormal
Undesirable event Cause condition at component
Overpressure • Blocked or restricted outlet High pressure
• Inflow exceeds outflow
• Gas blowby/vapor breakthrough
(upstream component)
• Pressure control system failure
• Thermal expansion
• Excess heat input
Ignition source within • Flashback from lightning strike on -
tank vent
• Static electricity due to splash
• filling
• Static electricity during gauging
or sampling
Detectable abnormal
Undesirable event Cause condition at component
Flammable mixture in • Tank in breathing -
vapor space
Under-pressure • Pump-out Low pressure
• Thermal contraction
• Pressure control system failure
9.4 Safety device location and initiation
9.4.1 Pressure safety devices (PVV and BOH)
1. The pressure vacuum relief or safety valve (PVV) or the emergency pressure relief vent (BOH)
should be located on the top (highest practical elevation in the vapor section) of atmospheric
tanks.
2. Provide low-low pressure safeguarding (PZL) on the fuel gas blanketing supply header. For
facilities which have no separate (independent) fuel-gas blanketing supply header, the PZLL-
pressure safeguarding is to be prioritized in the common supply header.”
9.4.2 Level safety devices (LZH and LZL)
1. The LZH and LZL should be located so that there is sufficient liquid hold-up time to provide
adequate time for operator intervention.
The LZH function can be accomplished by level transmitters or switches.
2. In firetube heated components, the LZL should be located above the fire tubes.
a. Where a firetube heater is operated in an aqueous layer and organic layer, the LZL should
measure the interface between the aqueous and organic phases.
3. The LZH and LZL functions may be provided by either transmitters or switches.
a. The LZH and LZL functions should be installed to allow for testing without interrupting the
process
b. The same level transmitter may have both a LZL and LZH setting.
TZHTZHTZH9.5 Safety Analysis Checklist
1. Refer to (Appendix F) for the SAC associated with atmospheric tanks.
10.2 Figures
Figure 10.1 Safety devices –Fired Heater
Note: TZE designations are symbolic and are not intended to reflect actual location of quantity.
2. The PZL in the fuel supply line should be located between the last fuel control valve and the
burner.
10.4.3 Level safety devices (LZH and LZL)
1. In fire-tube heated components, the LZL should be located above the fire tubes.
10.4.3 Ignition safety devices
1. The intake flame arrestor and stack spark arrestor on fired components should be located to
prevent flame emission from the air intake and spark emission from the exhaust stack.
2. The BZL should be located in the firing chamber.
10.5 Safety Analysis Checklist
1. Refer to the following for the SACs associated with fired components:
a. Fired Heaters – Heater Treater (Pressure Vessel), refer to (Appendix G);
b. Fired Heaters – Glycol Reboiler (Pressure Vessel), refer to (Appendix H);
c. Fired Heaters – Indirect Heater (Atmospheric Tank), refer to (Appendix I);
d. Fired Heaters – Direct Fired Heated Tanks (Atmospheric Tank), refer to (Appendix J).
11. Pumps
11.1 General
Safety devices for typical pump installations are shown in Figure 11.1 and Figure 11.2. “Pipeline
pumps” are referred to as pumps transferring fluid to a regulated pipeline or to a facility operated
by another entity.
11.2 Figures
Figure 11.1 Safety devices –Pumps
Detectable abnormal
Undesirable event Cause condition at component
12. Compressors
12.1 General
The safeguards not specified by ISO 13631 Table 7 are shown in Figure 12.1.
1. Safeguards should address Figure 12.1 and those specified by ISO 13631 Table 7.
2. All RV outlets and vents should be routed outside of the building.
3. The outlet piping design should both keep the discharge side of the relief piping drained and
minimize the precipitation that could come inside the building through a drain or weephole.
12.2 Figure
Figure 12.1 Safety devices –Compressor unit
Note:
1. Compressor design with all shutdowns per ISO 13631 Table 7.
2. Suction Scrubber are not shown; they should be analyzed according to the heat exchanger list.
3. All RV outlets and vents to be routed outside of the building.
4. UZH, AZH, OZH designated by the Fire Safety Assessment and may not be necessary for compressors installed
outside of buildings.
5. UZH, AZH, OZH designations are symbolic and are not intended to reflect actual location of quantity.
Detectable abnormal
Undesirable event Cause condition at component
13.2 Figure
Figure 13.1 Safety devices –Shell-and-tube heat exchangers
Detectable abnormal
Undesirable event Cause condition at component
14. Combustors
14.1 General
Safety devices for a typical combustor are shown in Figure 14.1.
1. Combustors with internal knock-out vessels should also comply with the requirements in (8).
14.2 Figure
Figure 14.1 Safety devices –Combustors
Detectable abnormal
Undesirable event Cause condition at component
Undesirable Event:
Accumulation and
delayed ignition of • Unburned fuel in firing chamber
during operation due to flame out
fuel/air mixture in firing • Flame failure
chamber • Unburned fuel in firing chamber
Consequence: during start-up
Fire/explosion
Undesirable Event:
Ignition outside of firing
chamber • Hot surfaces and/or flame/spark • High stack temperature
Consequence: emission
Fire/explosion
15. References
Standard SP DEP No Title
PR-1696 80.00.00.15 Hazard and operability (HAZOP) study
SP-2357 01.00.01.30 Definition of temperature, pressure, and toxicity levels
SP-1127 80.00.10.11 Layout of onshore facilities
SP-2361 80.45.10.10 Design of pressure relief, flare and vent systems
SP-2399 80.45.10.11 Overpressure and under pressure – Prevention and protection
31.24.67.10 Firetube heaters
32.24.20.44 Instrumentation control and protection for fired equipment
SP-2283 Off-Plot Production Facilities Overpressure Safeguarding
SP-2388 Design Engineering Manual DEM 1
SP-2388 Design Engineering Manual DEM 2
API RP 14C Recommended Practice for Analysis, Design, Installation, and Testing
of Basic Surface Safety Systems for Offshore Production Platforms
API SPEC 12F Specification for Shop Welded Tanks for Storage of Production
Liquids - Twelfth Edition
ISO 13631 Petroleum and natural gas industries -- Packaged reciprocating gas
compressors
Note: Unless specifically designated by date, the latest edition of each publication should be used, together with any
amendments/supplements/revisions thereto.
Appendix A. Definitions
A.1 General definitions
The Contractor is the party that carries out all or part of the design, engineering, procurement,
construction, commissioning or management of a project or operation of a facility. The Owner may
undertake all or part of the duties of the Contractor. The Manufacturer/Supplier is the party that
manufactures or supplies equipment and services to perform the duties specified by the Contractor.
The Owner is the party that initiates the project and ultimately pays for it. The Owner may also
include an agent or consultant authorized to act for, and on behalf of, the Owner.
The word shall indicates a requirement.
The capitalized term SHALL [PS] indicates a process safety requirement.
The word should indicates a recommendation.
The word may indicates a permitted option.
A.2 Specific definitions
The following definitions are specific to this SP.
Term Definition
Toxic Refer to SP-1190 series for additional details concerning the
(substances) Definitions.
Manifold Piping that combines or has the potential to combine feeds from multiple
sources and directs them to processing equipment.
Maximum Maximum pressure allowed in a piece of equipment, e.g., vessel or pipe,
Allowable within its design temperature range.
Working
Pressure
(MAWP)
Natural Gas Natural gas processing plant (gas plant) means any processing site engaged
Processing in the extraction of natural gas liquids from field gas, fractionation of mixed
Plant natural gas liquids to natural gas products, or both, classified as North
American Industrial Classification System (NAICS) code 211112 (previously
Standard Industrial Classification (SIC) code 1321).
Overpressure Pressure increase over the set pressure of a pressure relief device during
discharge and is usually expressed as a percentage of the set pressure.
Pipeline Pumps transferring fluid to a regulated pipeline or to a facility operated by
Pumps another entity.
Process Pictorial representation of a process or utility unit which shows all the
Engineering equipment, including installed spares and the associated piping and piping
Flow Scheme components, instrumentation, heat tracing and insulation.
(PEFS) NOTE: These are also known as Piping and Instrumentation Diagrams
(P&ID).
Relief Pressure Set pressure plus the overpressure. Also known as the relieving pressure.
Term Definition
Closed-In Equilibrated pressure in the tubing/casing measured when the entire gas or
Tubing/Casing oil outflow has been shut off.
Pressure
(CITHP/SICP)
Sour gas ≥ 100ppm H2S as per SP-1190-1
A.3 Abbreviations
The following abbreviations are specific to this SP.
Term Definition
ASH Analyzer Safety High
BDV Blow Down Valve
BZL Burner Safety Low
BOH Emergency Pressure Relief or Safety Valve
ESD Emergency Shutdown
FZV Flow Safety Valve
LNG Liquefied Natural Gas
LZH Level Safety High
LZL Level Safety Low
YCP Sand Probe (Erosion Probe)
OZH Toxic Gas Detector
PRV Pressure Relief Valve
PSBR Process Safety Basic Requirements
PZH Pressure Safety High
PZL Pressure Safety Low
RV Pressure Safety Valve
PVV Pressure-Vacuum Relief or Safety Valve
SAC Safety Analysis Checklist
SAT Safety Analysis Table
ESD Shut Down Valve
SSV Surface Safety Valve
TA Technical Authority
TZE Temperature Safety Element
TZH Temperature Safety High
TZL Temperature Safety Low
UZH Flame Detector (Ultraviolet/Infrared)
ESDs installed on each producing line with an ESD button in a safe location.
FZV installed.
The well is not producing from different formations, so crossflow is not a concern.
PZH installed.
NOTES: PZH to be located upstream of the spec break to detect credible high pressure scenarios
caused by hydrates.
Flow line segment has a maximum allowable working pressure greater than the maximum shut in
pressure and is protected by a PZH on a downstream flow line segment.
Flowline segment is protected by a RV on downstream component that cannot be isolated from the
flowline segment.
A high reliability high pressure shutdown system is installed where there is adequate flowline volume
upstream of any block valves to allow sufficient time for the ESDs or wellhead pump tripto close before
exceeding the flowline MAWP.
Flow line segment has maximum allowable working pressure greater than maximum shut in pressure.
REMARKS
APPROVAL
Discipline Engineer
Approval Date
FZV installed.
In a pumped well, the flowline does not comingle liquid and casing gas.
No hazardous consequences have been identified associated with crossflow between casing and
tubing.
REMARKS
APPROVAL
Discipline Engineer
Approval Date
FZV installed.
PZH installed.
Inlet Header MAWP is greater than the maximum pressure of any input source. (Preferred)
All input sources to inlet header are protected by PZHs set no higher than the header MAWP.
RV installed. If the flowline contains liquid hydrocarbon, the vent system is designed per the SP-2361.
to prevent liquid hydrocarbon release to atmosphere.
Header MAWP is greater than the maximum pressure of any input source. (Preferred)
All input sources having a pressure rating greater than the inlet Header
MAWP are protected by a RV set no higher than the inlet Header MAWP.
All input sources having a pressure greater than the inlet manifold MAWP are protected by an IPF set
no higher than the inlet header MAWP.
REMARKS
APPROVAL
Discipline Engineer
Approval Date
PZH installed.
Inlet manifold MAWP is greater than the maximum pressure of any input source. (Preferred)
All input sources to inlet manifold are protected by PZHs set no higher than the manifold MAWP.
RV installed. If the flowline contains liquid hydrocarbon, the vent system is designed per the SP-2361.
to prevent liquid hydrocarbon release to atmosphere.
Manifold MAWP is greater than the maximum pressure of any input source. (Preferred)
All input sources having a pressure rating greater than the inlet manifold
MAWP are protected by a RV set no higher than the inlet manifold MAWP.
All input sources having a pressure greater than the inlet manifold MAWP are protected by an IPF set
no higher than the inlet manifold MAWP.
REMARKS
APPROVAL
Discipline Engineer
Approval Date
PZH installed.
Input is from a pump or compressor that cannot develop pressure greater than vessel MAWP.
Each input source is protected by a PZH that also protects the vessel.
Adequately sized piping without block or regulating valves connects gas outlet to downstream
equipment protected by a PZH that also protects the upstream vessel.
Vessel is final scrubber in a flare, relief, or vent system and is designed to withstand maximum built up
back pressure.
RV installed.
Each input source is protected by a RV set no higher than the vessel MAWP and a RV is installed on
the vessel for fire and thermal expansion.
Each input source is protected by a RV set no higher than the vessel MAWP and at least one of these
RVs cannot be isolated from the vessel.
RVs on downstream equipment can satisfy relief requirement of the vessel and a system is in place to
ensure that there is always an open flow path to the RV.
Vessel is the final scrubber in a flare, relief, or vent system, is designed to withstand maximum built up
back pressure, and has no obstructions, such as mist extractors or back pressure valves.
Vessel’s design pressure exceeds the maximum expected pressure and no credible fire or thermal
expansion scenario.
LZH installed.
Vessel function does not require handling separated fluid phases (e.g., volume bottles, pulsation
dampeners, mixing drum).
The equipment downstream of gas outlet is not a flare or vent system and can safely handle maximum
liquid carry-over.
Vessel is a small trap which is manually drained and is located in a normally dry system.
Liquid level is not automatically maintained in the vessel and the vessel does not have an immersed
heating element subject to excess temperature.
Equipment downstream of liquid outlet(s) can safely handle maximum gas rates that can be discharged
through the liquid outlet(s) without relieving to atmosphere, and the vessel does not have an immersed
heating element subject to excess temperature.
The maximum volume of hydrocarbons that could backflow from downstream equipment is
insignificant.
Relief on downstream equipment has been designed for maximum blowby (vapor breakthrough)
flowrate from the vessel.
Blowby (vapor breakthrough) scenarios can be safely dispersed and are acceptable from an
environmental perspective.
MAWP of downstream equipment is equal to or greater than the MAWP of the pressure vessel, and no
other hazardous conditions associated with liquid inflow or blowby (vapor breakthrough) have been
identified.
REMARKS
APPROVAL
Discipline Engineer
Approval Date
PVV installed.
(Note: PVV and BOH must be evaluated independently; PVV must be able to handle maximum relief
rates without taking credit from BOH).
Vent installed without flame arrestor, flammable or combustible liquid is not stored within the tank, and
vapors are not ignitable.
BOH installed.
(Note: PVV and BOH must be evaluated independently; BOH must be able to handle maximum relief
rates without taking credit from PVV).
Tank has second vent capable of handling maximum relief capacity (including external fire).
LZH installed.
LZL installed.
Liquid level is not automatically maintained in the tank, and the tank does not have an immersed
heating element subject to excess temperature.
Component is final tank in a containment system designed to collect and receive hydrocarbon liquids
from other tank overflows.
The heating element is an indirect heater (e.g. glycol heater) and the maximum temperature from the
indirect heater does not create a hazardous condition.
Blanket Gas
The tank does not contain ignitable or toxic vapors or flammable liquids.
The tank does contain ignitable vapors but does not contain flammable liquids and is properly
grounded, contains a submerged fill, and is not routinely sampled or strapped.
Downcomer
Downcomer installed.
REMARKS
APPROVAL
Discipline Engineer
Approval Date
TZH installed.
LZL installed.
LZH installed.
The equipment downstream of gas outlet is not a flare or vent system and can safely handle
maximum liquid carry-over.
Equipment downstream of liquid outlet(s) can safely handle maximum gas rates that can be
discharged through the liquid outlet(s) without relieving to atmosphere, and the vessel section does
not have an immersed heating element subject to excess temperature.
The maximum volume of hydrocarbons that could backflow from downstream equipment is
insignificant.
PZH installed.
Input is from a pump or compressor that cannot develop pressure greater than the vessel MAWP.
Each input source is protected by a PZH that also protects the vessel.
Adequately sized piping without block or regulating valves connects gas outlet to downstream
equipment protected by a PZH that also protects the upstream vessel.
PZL installed.
Piping without block or regulating valves connects gas outlet to downstream equipment protected by a
PZL.
RV installed.
Each input source is protected by a RV set no higher than the vessel MAWP and at least one of these
RVs cannot be isolated from the vessel.
RVs on downstream equipment can satisfy relief requirement of the vessel and a system is in place to
ensure there is always an open flow path to the RV.
REMARKS
APPROVAL
Discipline Engineer
Approval Date
PZH installed.
TZH installed.
The fluid being heated is not flammable and the heater fuel is natural gas.
PZL installed.
PZL installed.
LZL installed.
TZH installed.
PZH installed.
Input is from a pump or compressor that cannot develop pressure greater than the vessel MAWP.
Each input source is protected by a PZH that also protects the vessel.
Adequately sized piping without block or regulating valves connects gas outlet to downstream
equipment protected by a PZH that also protects the upstream vessel.
PZL installed.
Piping, without block or regulating valves connects gas outlet to downstream equipment protected by a
PZL.
RV installed.
Each input source is protected by a RV set no higher than the vessel MAWP and a RV is installed on
the vessel for fire and thermal expansion.
RVs on downstream equipment can satisfy relief requirement of the vessel and a system is in place to
ensure that there is always an open flow path to the RV.
LZH installed.
The equipment downstream of gas outlet is not a flare or vent system and can safely handle maximum
liquid carry-over.
Equipment downstream of liquid outlet(s) can safely handle maximum gas rates that can be
discharged through the liquid outlet(s) without relieving to atmosphere, and the vessel section does not
have an immersed heating element subject to excess temperature.
The maximum volume of hydrocarbons that could backflow from downstream equipment is
insignificant.
REMARKS
APPROVAL
Discipline Engineer
Approval Date
PZH installed.
TZH installed.
The fluid being heated is not flammable and the heater fuel is natural gas.
PZL installed.
PZL installed.
Atmospheric Tank Component (non-flammable heat medium with manual level control)
LZL installed.
TZH installed.
Atmospheric Vent
Adequately sized atmospheric vent installed capable of handling credible relief scenarios.
LZH installed.
REMARKS
APPROVAL
Discipline Engineer
Approval Date
PZH installed.
TZH installed.
The fluid being heated is not flammable and the heater fuel is natural gas.
PZL installed.
PZL installed.
LZL installed.
TZH installed.
PVV installed.
(Note: PVV and BOH must be evaluated independently; PVV must be able to handle maximum relief
rates without taking credit from BOH).
Vent installed without flame arrestor; flammable or combustible liquid is not stored in the tank, and
vapors are not ignitable.
BOH installed.
(Note: PVV and BOH must be evaluated independently; BOH must be able to handle maximum relief
rates without taking credit from PVV).
Tank has second vent capable of handling maximum relief capacity (including external fire).
LZH installed.
Blanket Gas
The tank does not contain ignitable or toxic vapors or flammable liquids.
The tank contains ignitable vapors, but does not contain flammable liquids and is properly grounded,
contains a submerged fill, and is not routinely sampled or strapped.
Downcomer
Downcomer installed.
REMARKS
APPROVAL
Discipline Engineer
Approval Date
PZH installed.
PZH installed.
Max pump discharge pressure does not exceed 70% of the max allowable working pressure of
discharge piping.
PZL installed.
PZL installed.
External release hazards have been reviewed and adequate mitigation measures are in place.
RV installed.
Pump is kinetic energy type and incapable of generating a head greater than the MAWP of the
discharge piping.
RV installed.
Max pump discharge pressure is less than MAWP of discharge piping MAWP.
Pump is a glycol powered glycol pump, and the wet glycol low pressure discharge piping is rated
higher than the maximum discharge pressure.
Pump is a glycol powered glycol pump, and the wet glycol low pressure discharge piping is protected
by a RV on a downstream component that cannot be isolated from the pump.
REMARKS
APPROVAL
Discipline Engineer
Approval Date
The compressor package is equipped with all shutdowns per ISO 13631 Table 7
PZH Installed
Each input source is protected by a PZH that will also protect the compressor
PZH Installed
Compressor is protected by a downstream PZH, located upstream of any cooler, that cannot be
isolated from the compressor
RV installed.
Each input source is protected by a RV set no higher than the 1st stage suction MAWP.
Vessel’s design pressure exceeds the maximum expected pressure and no credible fire or thermal
expansion scenario
RV installed.
Compressor is protected by a downstream RV, located upstream of any cooler, that cannot be
isolated from the compressor
BDV installed.
Compressor is not located in a building and risks associated with not automatically blowing down the
compressor during an upset are acceptable.
ESD installed.
ESDs located upstream within the facility limit that would isolate all flow to the compressor.
ESD installed.
Risks associated with backflow to the compressor during a release scenario have been reviewed and
adequate mitigation measures in place.
ASH installed.
Compressor package is not enclosed in a building and the ASH is not required by the facility Fire
Safety Assessment.
UZH installed.
Compressor package is not enclosed in a building and the UZH is not required by the facility Fire
Safety Assessment.
OZH installed.
FZV installed.
REMARKS
APPROVAL
Discipline Engineer
Approval Date
PZH installed.
Input source to heat exchanger section cannot develop pressure greater than the heat exchanger
section MAWP.
Each input source is protected by a PZH that also protects the heat exchanger section.
A PZH is installed on a downstream component and cannot be isolated from the heat exchanger
section by block or regulating valves.
PZL installed.
PZL installed on another component will provide necessary protection and the PZL cannot be isolated
from the heat exchanger section when the heat exchanger is in service.
External release hazards have been reviewed and adequate mitigation measures are in place.
RV installed.
Each input source is protected by a RV set no higher than the heat exchanger section MAWP and a
RV is installed on the heat exchanger section for fire exposure and thermal relief.
Each input source is protected by a RV that is set no higher than the heat exchanger section MAWP
and cannot be isolated from the heat exchanger section.
RVs on downstream equipment can satisfy relief requirement of the heat exchanger section and
cannot be isolated from the heat exchanger section.
Input sources to the heat exchanger section cannot develop pressure greater than the heat exchanger
section MAWP and the heat exchanger section cannot be over pressured due to temperature or
pressure in the other section.
Each input source is protected by a RV set no higher than the heat exchanger section MAWP and the
heat exchanger section cannot be over pressured due to temperature or pressure in the other section.
REMARKS
APPROVAL
Discipline Engineer
Approval Date
REMARKS
APPROVAL
Discipline Engineer
Approval Date