Ref. Certificate No.
CB TEST CERTIFICATE
NL-9997
IEC SYSTEM FOR MUTUAL RECOGNITION OF TEST CERTIFICATES FOR
ELECTRICAL EQUIPMENT (IECEE) CB SCHEME
Issued by: KEMA Quality BV.
Registration date: 2008-12-06
Product Moulded case circuit-breakers
Applicant LS INDUSTRIAL Yonse Jaedan Severance Building Korea, Republic Of
SYSTEMS CO.,LTD. 84-11, 5ga, Nemdaemun-ro
) Marking on equipment not needed to be visible fter mounting: ine
= manufacturer's name or trademark us
= type designation or serial number TS100 E, S100 N, TS100 S,
TS100 H, TS100 P, TS100 L,
T$160 E, TS160 N, T8160 ,
/TS160 H, TS160 P, TS160 L
T8250 E, TS250 N, T8250 ,
[75250 H, T8250 P, TS250 L
IEC 6047-2 ifthe manufacturer compliance with |IEC 60047-2 P
this standara,
- uilization category A
- rated operational voltage(s) Ue 500
= Gircult-breaker for use in IT systems. Compliance
Circuit-breaker for which all values of rated voltage
have not been tested according to annex H or are
not covered by such testing, shall be identified by
the symbol which shal be market onthe circuit
breaker immediately following these values of rated
voltage
- value (or range) of the rated frequency andlor | 50/60 Hz P
the indication DC (or symbol)
- rated service short-circuit breaking capacity. les |200 kA
= fated ultimate short-circuit breaking capacity. [cu |200 kA
|-rated short-time withstand current, (low) and | NA
associated short-time delay, for utilization
category B
line and load terminals, unless their connection is. |- NA
immaterial
- neutral pole terminals, if applicable, by the letter N | - NA
- protective earth terminal, where applicable, by the | - NA
symbol acc. 7.1.9.3 of part 1
‘TRF No.: IEC 60947_28 TRF originator: SEVnea ee
page 10 of 90
Report reference No: 208602900.51
IEC 60 947-2
Clause _| Requirement - Test Result Remark Verdict
- ref. temperature for non-compensated thermal 40°C P
releases, if diferent from 30°C
c) Marked on the circuit-breaker as specified in item b), or shall be made available in
the manufacturer's published information:
- rated short-circuit making capacity (lem) 440 kA P
(if higher than specified in 4.3.5.1
= rated insulation voltage. (Ui) ifhigher than the [750 V P
maximum rated operational voltage)
= rated impulse withstand voltage (Uimp), when |B KV P
deciared.
= pollution degree if other than 3 - NA
- conventional enclosed thermal current (the) if |- NA
different from the rated current
= IP Code, where applicable: 1P20 P
minimum enclosure size and ventilation data (if |- NA
any) to which marked ratings apply:
= details of minimum distance between circuit: | Compliance Pp
breaker and earthed metal parts for circuit-breaker
intended for use without enclosure:
~r:m.s sensing if applicable, according toF.4.1.1 | NA
= suitability for environment A or B A Pp
4) The following data conceming the opening and closing devices of the circult-breaker
shall be placed either on their own nameplates or on the nameplate of the circuit-
breaker:
rated control circuit voltage of the closing device, |- NA
and rated frequency for AC:
rated control circuit voltage of the shunt release |- NA
andlor of the under-voltage release, and rated
frequency:
-rated current of indirect over-current releases: _|- NA
- number and type of auxiliary contacts and kind of | - NA
current, rated frequency (if AC) and rated voltages.
of the auxiliary switches, i different from those of
the main circuit.
e) Terminal shall be clearly and permanently identified in acc. with IEC 60445 and Sees
Jannex L
line terminal = NA
= load terminal - NA
neutral pole terminal "N" - NA
~ protective earth terminal - NA
terminal of coils (A/B) - NA
‘TRF No.: IEC 60947_28
TRF originator: SEVKEMAX
page 11 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause [Requirement - Test Result ~ Remark Verdict
terminal of shunt release ( B ) - NA
terminals of under-vottage release (D) - NA
terminals of interlocking electromagnets (E) - NA
terminals of indicated light devices (X) - NA
- terminals of contact elements for switching - NA
devices (no)
74 [CONSTRUCTION
744 [Withdrawable circuit-breaker : NA
In the disconnected position (main- and auxiliary circuits)
Isolating distances for crcuit-breaker suitable for |- NA
isolating warranted
Mechanism fied with a reliable indicating device |- NA
]with indicates the position of the isolating contacts.
Mechanism fitted with interlocks witch only permit |- NA
the isolating contacts to be separate or re-closed
]when main contacts are open
Mechanism fitted with interlock witch only permit |- NA
the main contacts to be closed when the isolating
[contacts are fully closed.
Mechanism fitted with interlock witch only permit |- NA
the main contacts to be closed when in
disconnected position.
The isolating distances between the isolating - NA
contacts cannot be inadvertently reduced,
7.4.1.1 [Resistance to abnormal heat and fire 650T Pp
960 C
742 Current-carrying parts and their connection ‘Compliance P
743 Clearences and creepage distances:
For circuit-breakers for which the manufacturer has declared a value of rated =
impulse withstand voltage. (Uimp.)
‘Clearances distances: =
- Uimp is given as: l]akv Sea
- max. value of rated operational voltage to earth |289 V =
- nominal voltage of supply system: 500
- overvoltage category:
~ pollution degree: 3 cite
= field-in or homogeneous: Inhomogeneous 2
‘TRF No.: IEC 60947_28
TRF originator: SEVany 4
page 12 of 90
Report reference No: 208602900.51
IEC 60 947-2
[Clause
Requirement ~ Test
Result - Remark
Verdict
- minimum clearances (mm):
mm
- measured clearances (mm):
11,5mm
Creepage distances:
~ rated insulation vottage Ui (V)
750
- pollution degree
3
- comparative tracking index (V)
=600V
- material group
Ma
Minimum creepage distances (mm)
125mm
Measured creepage distances (mm)
125mm
7.1.4 part 4
[Actuator
7144
part 1
Insulation
The actuator of the equipment shall be insulated
from the live parts for the rated insulation voltage
and, if applicable, the rated impulse withstand
voltage
‘Compliance
Ifitis made of metal, it shall be capable of being
satisfactorily connected to a protective conductor
Unless itis provided with additional reliable
insulation
NA
Ifitis made of or covered by insulating material,
any internal metal part, which might become
accessible in the event of insulation failure, shall
also be insulated from live parts for the rated
insulation voltage
Compliance
TAZ
Direction of movernent
The direction of operation for actuators of devices
shall normally conform to IEC 60447,
(Compliance
Where devices cannot conform to these
requirements, e.g. due to special applications or
alternative mounting positions, they shall be clearly
‘marked such that there is no doubt as to the “I” and
"0" positions and the direction of operation
[Compliance
7.1.6 part 1
Indication of contact position
7.1.5.1
part 1
Indicating means.
‘When an equipment is provided with means for
indicating the closed and open positions, these
positions shall be unambiguous and clearly
indicated
Compliance
This is done by means of a position indicating
[device (see 2.3.18)
‘Compliance
‘TRF No.: IEC 60947_28
‘TRF originator:KEMAX
page 13 of 90
Report reference No: 208602900.51
IEC 60 947-2
Clause
Requirement - Test
Result ~ Remark
Verdict
I symbols are used, they shall indicate the closed and open position respectively, in
accordance with IEC 60417-2:
-60417-2EC-5007 1 On (power)
Compliance
=60417-2-IEC-5007 __O_Off (power)
|Compliance
For equipment operated by means of two push-
buttons, only the push-button designated for the
‘opening operation shall be red or marked with the
symbol"O"
NA
Red colour shall not be used for any other push-
button
NA
‘The colours of other push-buttons, illuminated
push-buttons and indicator lights shall be in
accordance with IEC 60073
NA
7AS2
part 1
Indication by the actuator
‘When the actuator is used to indicate the position
‘of the contacts, it shall automatically take up or
stay, when released, in the position corresponding
to that of the moving contacts; in this case, the
actuator shall have two distinct rest positions.
corresponding to those of the moving contacts, but
for automatic opening a third distinct position of the
actuator may be provided
[On position
JOFF postion
Trip position
716
‘Additional safety requirements for equipment suitable for isolation
74.61
‘Additional constructional requirements for equipment suitable for isolation
(Ue> 50 Vp
Equipment suitable for isolation shall provide in the open position an isolation
distance in acc. with the requirements necessary to satisfy the isolating function.
Indication of the main contacts shall be provide by one or more of the following
means:
-the position of the actuator
Compliance
a separate mechanical indicator
- visibility of the moving contacts
NA
[When means are provided or to lock the equipment
in the open position, locking only be possible when
[contacts are in the open position
NA
Actuator front-plate fitted to the equipment in a
‘manner witch ensures correct contact position
indication and locking
NA
The indicated open position is the only position in
witch the specified isolation distances between the
contacts is ensured.
Compliance
- minimum clearances across open contacts (see.
Table Xill, Part 1) (mm)
8mm
TRF No.: IEC 60947_2B
‘TRF originator: SEVa4
page 14 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause _ | Requirement — Test Result ~ Remark Verdict
- measured clearances (mm) 11,5 mm Pp
- test Uimp across gap (kV) 12,1 kV P
7.4.62 | Supplementary requirements for equipment with provision for electrical interlocking
with contactors or circuit-breakers:
‘auxiliary switch shall be rated according to = NA
IEC 60 947-5-1
equipment suitable for isolation is provided with
‘an auxiliary switch for the purpose of electrical
interlocking with contactor (s) or circuit-breaker(s)
and intended to be used in motor circuits, the
ollowing requirements shall apply unless the
lequipmentis rated for AC-23 utilization category
The time interval between the opening of the
Jcontacts of the auxiiary switch and the contacts of
the main poles shall be sufficient to ensure that the
associated contactor or circuit-breaker interrupts
the current before the main poles of the equipment
Jopen
Unless otherwise stated in the manufacturer's
{technical literature, the time interval shall be not
less than 20 ms when the equipment is operated
according to the manufacturer” instructions
NA
NA
NA
Compliance shall be verified by measuring the time
interval between the instant of opening of the
auxiliary switch and the instant of opening of the
main poles under no-load conditions when the
[equipment is operated according to the
manufacturers instructions
NA
During the closing operation the contacts of the
auxiliary switch shall close after or simultaneously
with the contacts of the main poles
NA
A suitable opening time interval may also be - NA
provided by an intermediate position (between the
‘ON and OFF position) at which the interlocking
Contact(s) is (are) open and the main poles remain
closed
7.163 [Supplementary requirements for equipment provided with means for padlocking the
‘open position:
the locking means shall be designed in such a way
that it cannot be removed with the appropriate
[padlock(s) installed
Alternatively, the design may provide padiockable
means to prevent access to the actuator
NA
NA
NA
test force F applied to the actuator in an attempt to
Joperate to the closed position (N)
rated impulse withstand voltage (kV) - NA
TRF No.: IEC 60947_28 ‘TRF originator: SEVKEMAX
page 15 of 90
Report reference No: 208602900.51
IEC 60 947-2
Clause
Requirement - Test
Result - Remark
Verdict
test Uimp on open main contacts at the test force
NA
TAT
Terminals
TATA
All parts of terminals which maintain contact and
[carry current shall be of metal having adequate
mechanical strength
‘Compliance
‘Terminal connections shall be such that necessary
contact pressure is maintained
‘Compliance
‘Terminals shall be so constructed that the
[conductor is clamped between suitable surfaces
without damage to the conductor and terminal
‘Compliance
Terminal shall not allow the conductor to be
displaced or to be displaced themselves in a
manner detrimental o the operator of equipment
[and the insulation voltage shall not be reduced
below the rated value
‘Compliance
TAIZ
[Connection capacity
type of conductors
Flexible and stranded type
minimum cross-sectional area of conductor (mm?)
40mm? or BAWG [40 A]
maximum cross-sectional area of conductor
(nm
120mm? or 250kcmil [250 A]
umber of conductors simultaneously connectable
to the terminal
7AT3
[Connection
terminals for connection to external conductors
shall be readily accessible during installation
‘Compliance
[clamping screws and nuts shall not serve to fix any
lother component
Compliance
TATA
Terminal identification and marking
{terminal intended exclusively for the neutral
[conductor
NA
protective earth terminal
NA.
other terminals.
NA
7.4.8 part 1
Additional requirements for equipment provided with
‘a neutral pole
When an equipment is provided with a pole
intended only for connecting the neutral, this pole
shall be clearly identified to that effect by the letter
N(see 7.1.74)
NA
‘A switched neutral pole shall break not before and
shall make not after the other poles
NA
‘TRF No.: IEC 60947_28
TRF originator: SEVKEMAX
page 16 of 90
Report reference No: 208602900.51
IEC 60 947-2
Clause
Requirement - Test
Result - Remark
Verdict
For equipment having a value of conventional
thermal current (free air or enclosed, see 4.3.2.1
and 4.3.2.2) not exceeding 63 A, this value shall be
identical for ail poles
NA
For higher conventional thermal current values, the
‘neutral pole may have a value of conventional
thermal current different from that of the other
poles, but not less than half that value or 63 A,
Whichever is the higher
NA
ia pole with a appropriate making and breaking
capacity is used as a neutral pole, then all poles,
incl. the neutral pole, shall operate substantially
together.
NA
7.1.9
Provisions for protective earthing
7.1.9.1
‘The exposed conductive parts (e.g, chassis,
framework and fixed parts of metal enclosures)
‘other than those which cannot constitute a danger
shall be electrically interconnected and connected
to a protective earth terminal for connection to an
earth electrode or to an external protective
jeonductor
NA.
part 1
This requirement can be met by the normal
structural parts providing adequate electrical
[continuity and applies whether the equipment is
Used on its own or incorporated in an assembly
NA
Exposed conductive parts are considered not to
‘constitute a danger i they cannot be touched on
large areas or grasped with the hand or if they are
of small size (approximately 50 mm x 50 mm) or
are so located as to exclude any contact with live
parts
NA
7AG2
part 1
Protective earth terminal
The protective earth terminal shall be readily
accessible and so placed that the connection of the
[equipment to the earth electrode or to the
protective conductor is maintained when the cover
Jor any other removable part is removed
NA
‘The protective earth terminal shall be suitably
protected against corrosion
NA
Inthe case of equipment with conductive
structures, enclosures, etc., means shall be
provided, if necessary, to ensure electrical
continuity between the exposed conductive parts,
the equipment and the metal sheathing of
‘connecting conductors
NA
‘TRF No. IEC 60947_28
‘TRF originator. SEVha 4
page 17 of 90
Report reference No: 208602900.51
IEC 60 947-2
(Clause
Requirement — Test
Result - Remark
Verdict
‘The protective earth terminal shall have no other
function, except when itis intended to be
[connected to a PEN conductor (see 2.1.1.5 —
Note). In this case, it shall also have the function of
‘a neutral terminal in addition to meeting the
requirements applicable to the protective earth
terminal
NA
7.1.9.3
Protective earth terminal marking and identification
‘The protective earth terminal shall be clearly and
permanently identified by its marking
NA
‘The identification shall be achieved by colour
(green-yellow mark) or by the notation PE, or PEN,
as applicable, in accordance with IEC 60445,
ssubclause 5.3, or, in the case of PEN, by a
graphical symbol for use on equipment
NIA
|Graphical symbol to be used:
60417-26C-5019 Protective earth (ground)
|in accordance with IEC 60417-2
NA
7.4.10
Enclosure for equipment
7.4.10.1
Design
‘The enclosure, when itis opened: all parts requiring
access for instalation and maintenance are readily
accessible
Sufficient space shall be provided inside the
enclosure
‘The fixed parts of a metal enclosure shall be
electrically connected to the other exposed
[conductive parts of the equipment and connected
0 a terminal which enables them to be earthed or
Jconnected to a protective conductor
NA
Under no circumstances shall a removable metal
part of the enclosure be insulated from the part
[caring the earth terminal when the removable part
isin piace
NA
The removable parts ofthe enclosure shall be
firmly secured to the fixed parts by a device such
that they cannot be accidentally loosened or
[detached owing to the effects of operation of the
equipment or vibrations.
NA
When an enclosure is so designed as to allow the
‘covers to be opened without the use of tools,
means shall be provided to prevent loss of the
fastening devices
NA
Ifthe enclosure is used for mounting push-buttons,
it shall not be possible to remove the buttons from
the outside of the enclosure
NA
TRF No.: IEC 60947_2B
TRF originator: SEVKEMAX
page 18 of 90
Report reference No: 208602900.51
IEC 60 947-2
Clause
Requirement - Test
Result - Remark
Verdict
7.4.102
Insulation
If, in order to prevent accidental contact between a
‘metallic enclosure and live parts, the enclosure is
partly or completely ined with insulating material,
then this lining shall be securely fixed to the
enclosure
NA
74.11
Degree of protection of enclosed equipment
Degree of protection
1P20
Test for first characteristic.
IPXX
Test for first numeral
SanOn=
NA
Test for second characteristic
IPXX.
Test for second numeral
SISGRGN=
NA
7AA2
part 4
‘Conduit pull-out, torque and bending with metallic co
duis
Polymeric enclosures of equipment, whether
integral or not, provided with threaded conduit
entries, intended for the connection of extra heavy
duty, rigid threaded metal conduits complying with
IEC 60981, shall withstand the stresses occurring
during its installation such as pull-out, torque,
bending
NA
72
Performance requirements
724
Operating condition
7.244
Closing
For a circuit-breaker to be closed safely on to the
‘making current corresponding to its rated short-
circuit making capacity, itis essential that it should
be operated with the same speed and the same
firmness as during the type test for proving the
short-circuit making capacity
‘Compliance
‘TRF No.: IEC 60947_2B
TRF originator:
SEVKEMAX
page 19 of 90
Report reference No: 208602900.51
IEC 60 947-2
Clause
Requirement — Test
Result ~ Remark
Verdict
72444
Dependent manual closing
For a circuit-breaker having a dependent manual
‘losing mechanism, its not possible fo assign a
short-circuit making capacity rating imespective of
the conditions of mechanical operation
NA
‘Such a circuit-breaker should not be used in
circuits having a prospective peak making current
exceeding 10 kA
NA
However, this does not apply in the case of a
circuit-breaker having a dependent manual closing
‘mechanism and incorporating an integral fast-
‘acting opening release which causes the circuit
breaker to break safely, respective of the speed
and firmness with which its closed on to
prospective peak currents exceeding 10 kA; in this
case, a rated short-circuit making capacity can be
assigned
NA
72142
Independent manual closing
A circuit-breaker having an independent manual
closing mechanism can be assigned a short-circuit,
‘making capacity rating irrespective ofthe conditions|
‘of mechanical operation
‘Compliance
7.2.4.1.3
Dependent power closing
[At 110% ofthe rated control supply voltage, the
closing operation performed on no-load shall not
‘cause any damage to the circuit-breaker.
NA.
‘At 85% of the rated control supply voltage, the
‘losing operation shall be performed when the
‘current established by the circuit-breaker is equal to|
its rated making capacity within the limits allowed
by the operation of its relays or releases and, if a
‘maximum time is stated for the closing operation, in
a time not exceeding this maximum time limit.
NA
724.44
Independent power closing
A citcuit-breaker having an independent power
‘closing operation can be assigned a rated short-
circuit making capacity irrespective of the
[conditions of power closing
Means for charging the operating mechanism, as
]well as the closing control components, shall be
[capable of operating in accordance with the
manufacturer's specification
NA
724.15
Stored energy closing
Capable ensuring closing of the circuit-breaker in
any condition between no-load and its rated making
[capacity
NA
‘TRF No.: IEC 60947_2B
‘TRF originator: SEVKEMAX
age 20 of 90
Report reference No: 208602900.51
IEC 60 947-2
Clause
Requirement ~ Test Result ~ Remark Verdict
/-when the stored energy is retained within the |
circuit-breaker, a device is provided witch indicates
]when the storing mechanism is fully charged,
NA
means for charging the operating mechanism and
[closing control components operates when auxiliary
supply voltage is between 85% and 110% of the
rated control supply voltage.
NA
- not possible for the moving contacts to move from
the open position, unless the charge is sufficient for
satisfactory completion of the closing operation,
NA
- by manually operated circut-breaker is the -
direction of operation indicated.
(00 for circuit breaker with an independent manual
closing operation)
NA
= For trip free circut-breaker it shall not be possible
to maintain the contacts in the touching or closed
position when the release isin the position to trip
the circuit-breaker
NA
724.2
Opening
72124
Circuit-breakers which open automatically shall be trip-free and, unless otherwise =
agreed between manufacturer and user, shall have their energy for the tripping
operation stored prior to the completion of the closing operation
7.2.1.2.2
Opening by undervoltage releases
7.24.34
part 1
Operating voltage
‘An under-voltage relay or release, when associated
with a switching device, shall operate to open the
equipment even on a slowiy falling voltage within
the range between 70% and 35% of its rated
voltage
NA
‘An under-voltage relay or release shall prevent the
closing of the equipment when the supply voltage is
[below 35% of the rated voltage of the relay or
release; it shall permit closing of the equipment at
supply voltages equal to or above 85% ofits rated
value
NA
Unless otherwise stated in the relevant product
standard, the upper limit of the supply voltage shall
be 110% of its rated value
NA
7.24.3.
Part 1
[Operating time
Fora time-delay under-voltage relay or release, the
time-tag shall be measured from the instant when
the voltage reaches the operating value until the
instant when the relay or release actuates the
tripping device of the equipment
NA
7.2.1.2.3
(Opening by shunt releases -
NA
‘TRF No. IEC 60947_28
‘TRF originator: SEVKEMAX
page 21 of 90
Report reference No: 208602900.51
IEC 60 947-2
Clause
Requirement - Test Result - Remark Verdict
7214
part 1
Limits of operation of shunt releases:
A shunt release for opening shall cause tripping
‘under all operating conditions of an equipment
|when the supply voltage of the shunt release
measured during the tripping operation remains
between 70% and 110% of the rated control supply
voltage and, ifa.c., at the rated frequency
NA
7215
part 1
Limits of operation of current operated relays and released
Limits of operation of current operated relays and
releases shall be stated in the relevant product
standard
NA
721.24
(Opening by over-current releases
a)
‘Opening under short-circuit conditions
‘The short-circuit release shall cause tripping of the | Compliance Pp
circuit-breaker with an accuracy of 20% of the
tripping current value of the current setting forall
values of the current setting of the short-circuit
current release
Where necessary for over-current co-ordination the
manufacturer shall provide information (usually
curves) showing
NA
= maximum cut-off (letthrough) peak current asa_ | Compliance Pp
function of prospective current (r.m.s. symmetrical)
~ Ftcharacteristics for circuit-breakers of utilization | Compliance P
category A and, if applicable, B for circuit-breakers
‘with instantaneous override (see not to 8.3.5)
b)
[Opening under overload conditions
1)
Instantaneous or definite time-delay operation
NA
The release shall cause tripping of the circut- | -
breaker with an accuracy of + 10% of the tripping
[current value of the current setting for all values of
[current setting of the overload release
NA
2)
Inverse timer-delay operation
[At the reference temperature and at 1,05 times the | Compliance P
current setting with the conventional non-tripping
current, the opening release being energized on all
poles, tripping shall not occur in less than the
‘conventional time from the cold state, ie. with the
Circuit-breaker at the reference temperature
‘Moreover, when at the end of the conventional time | Compliance Pp
the value of current is immediately raised to 1,30
times the current setting, ie. with the conventional
tripping current, tripping shall then occur in less
than the conventional time later
‘TRF No.: IEC 60947_28
‘TRF originator: SEVKEMAX
page 22 of 22
Report reference No: 208602900.51
IEC 60 947-2
Clause
Requirement — Test
Result - Remark
Verdict
Ifa release is declared by the manufacturer as
substantially independent of ambient temperature,
the current values of table 6 shall apply within the
{temperature band declared by the manufacturer,
within a tolerance of 0,394/K
|Compliance
P
[The width of the temperature band shall be at least
10 Kon either side of the reference temperature
Compliance
7.242
[Operational performance capability
7242
part 1
[The operational performance off-load for which the
{ests are made with the control circuits energized
and the main circuit not energized, in order to
[demonstrate that the equipment meets the
Joperating conditions specified atthe upper and
lower limits of supply voltage and/or pressure
specified for the control circuit during closing and
Jopening operations
Compliance
|The operational performance on-load during which
the equipment shall make and break the specified
[current corresponding, where relevant, to its
ttiization category for the number of operations.
stated in the relevant product standard
Compliance
TESTS
824
Mechanical properties of terminals
Mechanical strength of terminals
maximum cross-sectional area of conductor
(ram?) :
diameter of thread (mm)
8
{torque (Nm)
6
5 times on 2 separate clamping units _ Nm
66
Testing for damage to and accidental loosening of conductor (flexion test)
‘conductor of the smallest cross-sectional area
(mm?)
number of conductor of the smallest cross section
diameter of bushing hole (mm)
height between the equipment and the platen :
mass at the conductor(s) (kg)
1135 continuous revolutions: the conductor shall
neither slip out of the terminal nor break near the
[clamping unit
Pul-out test
force (N)
‘TRF No.: IEC 60947_2B
‘TRF originator: SEVKEMAX
page 23 of 90
Report reference No: 208602900.
51
IEC 60 947-2
[Clause
Requirement - Test
Result ~ Remark Verdict
4 min, the conductor shall neither slip out of the
terminal nor break near the clamping unit
- NA
Conductor of the largest cross-sectional area
(mm*)
umber of conductor of the largest cross section
diameter of bushing hole (mm)
height between the equipment and the platen
mass at the conductor(s) (kg)
135 continuous revolutions: the conductor shall
neither slip out ofthe terminal nor break near the
clamping unit
z
5
Pull-out test
force (N)
11min, the conductor shall neither slip out of the
terminal nor break near the clamping unit
<
5
[conductor of the largest and smallest cross-
sectional area (mm):
‘number of conductor of the smallest cross section,
number of conductor of the largest cross section
diameter of bushing hole (mm)
height between the equipment and the platen
mass at the conductor(s) (kg)
435 continuous revolutions: the conductor shall
neither slip out of the terminal nor break near the
[clamping unit
NA
Pull-out test
force (N)
1 min, the conductor shall neither slip out of the
terminal nor break near the clamping unit
5
333
TEST SEQUENCE |: GENERAL PERFORMANCE CHARACTERISTICS
33.3.1
Tripping limits and characteristic
8.3.3.1.2
(Opening under short-circuit conditions
[Manufacturer's name or trademark
Ls
‘Type designation or serial number
TS250L,
| Sample no:
si-1
Rated operational voltage: Ue (V)
/500V
‘TRF No.: IEC 60947_28
‘TRF originator: SEVay 4
setting current: (A)
page 24 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause _| Requirement - Test Result - Remark Verdict
Rated current: In (A) 250 A a
[Ambient temperature 10-40 °C. 24°C. Pp
Value ofthe tripping current dectared by the 1625 A (Im=5XIr) P
manufacturer for a single pole, at witch value they
shall operate. 3250 A (Im=10%Ir)
Range of adjustable setting current. (A) 1250 ~ 2500 A (Iim=5~10%Ir) P
Time delay stated by the manufacturer, in the case |- NIA
of definite time delay releases,
Test current: 80% of the rated, or minimum 1000 A (Im=5%Ir) P
adjustable setting current: (A)
(Operating time: >0,2s in case of instantaneous Pp
releases: L142: |L1412:>0,25
Li-L3: |L1-13:>028
L213: |L2-13:>0,28
Operating time: > twice time detay stated by the | NA
manufacturer, in the case of definite time delay
releases: Liz
Li
(243
Test current: 80% of the maximum adjustable [2000 A (Im=10xIr) Pp
setting current: (A)
Operating time: >0,2s in case of instantaneous Pp
releases: L142: |Lt-L2: 0.28
L113: |L1-13:>02s
L243: |L213:>02s
(Operating time: > twice time delay stated by the | NA
manufacture, in the case of definite time delay
releases: Liz:
bits:
3:
Test current: 120% of the rated, or minimum 1800 A (Im=5%Ir) Pp
adjustable setting current: (A)
[Opereting time: <0,2s in case of instantaneous Pp
releases: L112: |L1-L2: 0,0286 s .
LA-L3: |L4-13:0,0225 s
L213: |L2-3:0,0213 s
[Operating time: < twice time delay stated by the |- NA
manufacturer, in the case of definite time delay
releases: Liz
1-43:
Las:
Test current: 120% of the maximum adjustable Pp
‘TRF No: IEC 60947_28
‘TRF originator: SEVKEMAX
page 25 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause | Requirement - Test Result - Remark Verdict
Operating time: <0,2s in case of instantaneous. Pp
releases: LA-L2: |L1-12: 0,0228 s
L113: |L1-13:0,0310s
L213: |12-13: 0,0287 s
(Operating time: < twice time delay stated by the |- NA
manufacture, in the case of definite time delay
releases: Lia
L143:
L243:
Test current tripping current declared for single | 1625 A (Im=BXIr) P
le operation (A)
Pole operation (A) 3250 A (Im=10%Ir)
(Operating time: < 20 ms in case of instantaneous | Min / Max adjustable setting P
release: Li: |L1: 00191 s/0,0314s
L2: |L2: 0.0195 s/0,0211 s
L3: |L3:0,0190s/0,0219
(Operating time: < twice time delay stated by - NA
manufacturer in case of definite time delay
releases ut
2
B
8.3.3.1.3 _|Opening under overload conditions
a) Instantaneous or definite time-delay releases
Manufacturer's name or trademark -
Type designation or serial number - ee
[Sample no: -
Rated operational voltage: Ue (V) -
Rated current: In (A) .
|Ambient temperature 10-40 °C - NA
Value of the tripping current dectared by the - NA
manufacturer for a single pole, at witch value they
shall operate,
Range of adjustable setting current (A) - NA
Time delay stated by the manufacturer, inthe case |- NA
of definite time delay releases,
Test current: 90% of the rated, or minimum - NA
adjustable setting current: (A)
(Operating time: >0,2s in case of instantaneous —_|- NA
releases:
(Operating time: > twice time delay stated by the | NA
‘manufacturer, in the case of definite time delay
releases,
‘TRF No.: IEC 60947_2B TRF originator: SEVKEMAX
Reference temperature (°C)
Page 26 of 90 Report reference No: 208602900.51
EC 60 947-2
Clause | Requirement - Test Result ~ Remark Verdict
Test current: 90% of the maximum adjustable |- NA
setting current: (A)
Operating time: >0,2s in case of instantaneous |- NA
releases
(Operating time: > twice time delay stated by the |- NA
‘manufacturer, in the case of definite time delay
releases.
Test current: 110% of the rated, or minimum - NA
adjustable setting current: (A)
Circuit-breaker with neutral pole: 4,2x110% (A)
(Operating time: <0,2s in case of instantaneous |- NA
releases:
(Operating time: < twice time delay stated by the |- NA
‘manufacturer, in the case of definite time delay
releases.
Test current: 110% of the maximum adjustable |- NA
setting current: (A)
circuit-breaker with neutral pole: 4,2x110% (A)
(Operating time: <0,2s in case of instantaneous |- NA
releases
(Operating time: < twice time delay stated by the |- NA
manufacturer, in the case of definite time delay
releases.
b) Inverse time delay releases
Manufacturer's name or trademark ts
‘Type designation or serial number TS250L
[Sample no: st4 £
Rated operational voltage: Ue (V) 500 V
250A
For releases dependent of ambient air 40°C Pp
temperature: Reference temperature
Test ambient temperature (°C ) 25°C Pp
Iftest made at a difference ambient temperature: |See Remarks Pp
Aco. manufacturer's correction temperature/current
data
Range of adjustable setting current: (A) 0,8/ 0,9/ 1,0 xn Pp
For releases independent of ambient temperature: |- NIA
Test made at 30°C and/or at 20/40°C.
Test ambient air temperature: - NA
Releases, dependent of ambient air temperature: [40°C Pp
‘TRF No.: IEC 60947_28
‘TRF originator: SEVKEMAX
page 27 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause [Requirement — Test, Result ~ Remark Verdict
Releases, independent of ambient air temperature: |- NA
at 30°C
Test current: 105% of the rated, or minimum 225.8 P
adjustable setting current: (A)
Conventional non-tripping time: ‘2h P
‘th when In < 63A, 2h when In > 63 A
Test current: 130% ofthe rated, or minimum 279,58 P
adjustable setting current: (A)
Conventional tripping time: 40500 s P
63 A
Test current: 105% of the maximum adjustable |282,2 A Pp
setting current: (A)
Conventional non-tripping time: an Pp
‘hwhen In < 63A, 2h when In > 63 A.
Test current: 130% of the maximum adjustable |349,4.A Pp
setting current: (A)
Conventional tripping time: 1375 Pp
63 A
Releases, independent of ambient air temperature: at 20°C or 40°C. :
Test ambient air temperature: - NA
Test current: 105% of the rated, or minimum - NA
adjustable setting current: (A)
Conventional non-tripping time: - NA
‘1h when In < 63A, 2h when In > 63 A.
Test current: 130% of the rated, or minimum - NA
adjustable setting current: (A)
‘Conventional tripping time: - NA
-
63 A
Test current: 105% of the maximum adjustable |- NA
setting current: (A)
[Conventional non-tripping time: - NA
‘th when In < 63A, 2h when In > 63.A
Test current: 130% of the maximum adjustable |- NA
setting current: (A)
[Conventional tripping time: - NA
}<1h when In < 63A, <2h when In > 63.A
[An additional test, at a current specified by the manufacturer to verify the
{imefcurrent characteristic ofthe releases conform to the curves provided by the
manufacturer
Releases, dependent of ambient air temperature: |25 °C. Pp
Reference temperature (°C)
‘TRF No.: IEC 60947_28 ‘TRF originator: SEVa4
Page 28 of 90
Report reference No: 208602900.51
IEC 60 947-2
[Clause
Requirement - Test
Result - Remark
Verdict
Releases, independent of ambient air temperature:
[at 30°C.
NA
Test current
at current specified by the manufacturer to verity
the time/current characteristic of the releases
[conform to the curves provided by the
manufacturer.
4% at the rated, or minimum adjustable setting
current: (% or A)
1645,0 A (0,8 In)
806,3.A (1,0 In)
Tripping time ace. tme/current characteristic of the
releases conform to the curves provided by the
manufacturer. (within the stated tolorances)
107 s (0,8 In)
91.5 (1,0 In)
Releases, independent of ambient air temperature: at 20°C or 40°C
Test ambient air temperature:
Test current:
at current specified by the manufacturer to verify
the time/current characteristic ofthe releases
[conform to the curves provided by the
manufacturer.
5% at the rated, or minimum adjustable setting
current: (% or A)
Tripping time ace. time/current characteristic of the
releases conform to the curves provided by the
manufacturer, (Within the stated tolorances)
NA
3.3.3.1.4
Additional test for definite time-delay releases
|a)
Time delay
Test is made at a current equal to 1,5 times the current setting
[overload releases: (all phase poles loaded) - NA
short-circuit releases: - NA
wo poles in series carrying the test current, using
successively all possible combinations of poles
having a short-circuit release
Test current 1,5 tes of the rated, or minimum |- NA
adjustable setting current (A)
Operating time, overload releases: (S) : NA
Time-detay: between the limits stated by the : NA
manufacturer:
(Operating time, short-circuit releases: (s) L112: |- NA
U3
a
-Time-detay. between the limits stated by the - NA
manufacturer
FTest current 1,5 times of the maximum adjustable |- NA
setting current: (A)
‘TRF No.: IEC 60947_2B
‘TRF originator: SEVKEMAX
page 29 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause _|Requirement - Test Result ~ Remark Verdict
(Operating time, overioad releases: (5) - NA
Time-delay: between the limits stated by the - NA
manufacturer:
Operating time, short-circuitreleases: (s) L1-L2: |- NA
Ls:
Laas:
Time-delay: between the limits stated by the - NA
manufacturer:
by 'Non-tripping duration
Firstly, the test current equal to 1,5 times the current setting is maintained for a time =
interval equal to the non-tripping duration stated by the manufacturer.
overload releases: (all phase poles loaded) NA
short-circuit releases: - NA
two poles in series carrying the test current, using
successively all possible combinations of poles
having a short-circuit release,
Test current: 1,5 times of the rated, or minimum | NA
adjustable setting current: (A)
Time interval: non-tipping duration stated by the | NIA
manufacturer: (8)
[Operating time, overload releases: - NA
the circuit-breaker does not trip:
[Operating time, short-circuit releases: - NA
the circuit-breaker does not trip: Liz:
U3:
Las:
[Test current: 4,5 times of maximum adjustable |- NA
setting current: (A)
[Time interval: non-tripping duration stated by the |- NA
manufacturer: (8)
|Operating time, overioad releases: - NA
the circuit-breaker does not trip:
| Operating time, short-circuit releases: - NIA
the circut-breaker does not tip: Liz
U3:
3:
Then, the current is reduced to the rated current and maintained at this value for z
twice the time-delay stated by the manufacturer. The circuit-breaker shall not trip, be
Test current of the rated, or minimum adjustable |- NA
setting current: (A)
Time interval: twice the delay-time stated bythe | NA
manufacturer: (s)
‘TRF No.: IEC 60947_28 ‘TRF originator: SEVKEMAX
page 30 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause _|Requirement - Test Result - Remark Verdict
‘Operating time, overioad releases: a NIA
the circuit-breaker does not trip:
(Operating time, short-circuit releases - NA
the circuit-breaker does not trip: Lit:
L3:
L243
Test current: maximum adjustable setting - NA
current: (A)
Operating time, overload releases: - NA
the circuit-breaker does not trip:
Operating time, short-circuit releases: - NA
the circuit-breaker does not trip: La:
U3
1243;
83.32 __ | Test of dielectric properties, impulse withstand voltage (Uimp indicated):
83.3.4 |The 1,2/50us impulse voltage shall be applied five times for each polarity at intervals. E
partt of 4s minimum
rated impulse withstand voltage (KV) : 8kV
- sea level ofthe laboratory. [200 m
-test Uimp main circuits (KV) : 9,6 KV
- test Uimp auxiliary circuits (kV) - NA
-test Uimp control circuits (KV) : - NA
test Uimp on open main contacts (equipment [12,1 kV P
suitable for isolating) (KV)
a) [Application of test voltage
) Between all terminals of the main circuit Compliance P
[connected together (incl. control and auxiliary
circuits connected to the main circuit) and the
Jenclosure or mounting plate, with the contacts in all
normal positions of operation.
i) Between all terminals of the main circuit and the [compliance Pp
Jother poles connected together and to the
Jenciosure or mounting plate, with the contacts in all
normal positions of operation,
i) Between each control and auxiliary circuit not | Compliance P
normally connected to the main circuit and:
= the main circuit
other circuits - NA
~ exposed conductive parts : NA
- enclosure of mounting plate : NA
iv) equipment suitable for isolation Compliance P
equipment not suitable for isotation - NA
‘TRF No.: IEC 60947_28
TRF originator: SEVKEMAX
a
page 31 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause _[ Requirement - Test Result - Remark Verdict
no unintentional disruptive discharge during the | Compliance Pp
test's
Test of dielectric properties, dielectric withstand voltage (Uimp not indicated
= rated insulation voltage (V) - NA
- main circuits, test votage for + min (V) - NA
+ auxiliary circuits, test voltage for 1 min (V) - NIA
- control circuits, test voltage for 1 min (V) - NA
18.3.32.2 _ [Application of test voltage
1) with circuit-breaker in the closed position
= between allive parts of all poles connected ——|- NA
together and the frame of the crcul-breaker
between each pole and all the other poles
[connected to the frame of the circuit-breaker
NA
2) /with the circuit-breaker in the open position and,
additionally, in the tripped position, if any.
NA
- between all live parts of all poles connected - NA
{together and the frame of the circult-breaker.
|= between the terminals of one side connected | - NA
{together and the terminals of the other side
[connected together.
b) [Control and auxiliary circuits:
1» - between all the control and auxiliary circuits which
are not normally connected to the main circu,
[connected together, and the frame of the circuit-
breaker
NA
2) where appropriate, between each partofthe | NA
[control an auxiliary circuits which may be isolated
rom the other parts during normal operation and all
the other parts connected together.
No unintentional disruptive discharge during the
test's
NA
8332 |For circuit-breaker suitable for isolation, the - NA
leakage current shall be measured through each
pole with the contacts in the open position, at a test
voltage of 1,1 Ue, and shall not exceed 0,5mA.
83.33 __ [Mechanical operation and operational performance capability
83.3.3.2 _|Construction and mechanical operation a
a) (Construction
‘A withdrawable circuit-breaker shall be checked for
the requirements stated in 7.1.1
NA
‘TRF No.: IEC 60947_28 TRF originator: SEVKEMAX
page 32 of 90
Report reference No: 208602900.51
IEC 60 947-2
[Clause
Requirement - Test
Result - Remark Verdict
A circuit-breaker with stored energy operation shall
be checked for compliance with 7.2.1.1.5,
regarding the charge indicator and the direction of
Joperation of manual energy storing
NA
>)
Mechanical operation
A circuit-breaker with dependent power operation
shall comply with the requirements stated in
7.24.1.3
NIA
A circult-breaker with dependent power operation
shall operate with the operating mechanism
[charged to the minimum and maximum limits
stated by the manufacturer
NA
A circuit-breaker with stored energy operation shall
[comply with the requirements stated in 7.2.1.5 with
the auxiliary supply voltage at 85% and 110% of
the rated control supply voltage.
NA
It shall also be verified that the moving contacts
[cannot be moved from the open position when the
operating mechanism is charged to slightly below
the full charge as evidenced by the indicating
device
- NA
For a trip-free circult-breaker it shall not be possible
to maintain the contacts in the touching or closed
position when the tripping release isin the position
to trip the circuit-breaker
NA
If the closing and opening times of a circuit-breaker
are stated by the manufacturer, such times shall
comply with the stated values
NA
ic)
[Undervottage releases
[Undervottage releases shall comply with the
requirements of 7.2.1.3 of Part 1. For this purpose,
the release shall be fitted to a circuit-breaker
having the maximum current rating for which the
release is suitable
NA
Drop out voltage
It shall be verified that the release operates to open
the circuit-breaker between the voltage limits
specified
NA
The voltage shall be reduced from rated voltage at
a rate to reach 0 V in approximately 30 s
NA
The test forthe lower limit is made without current
in the main circuit and without previous heating of
the release coil
NA
In the case of a release with a range of rated
voltages, this test applies to the maximum voltage
of the range
NA
TRF No: IEC 60947_28
‘TRF originator: SEVKEMAX
page 33 of 90
Report reference No: 208602900.61
IEC 60 947-2
[Clause
Requirement - Test
Result - Remark
Verdict
The test for the upper limit is made starting from a
[constant temperature corresponding to the
application of rated control supply voltage to the
release and rated current in the main poles of the
circut-breaker
NA
This test may be combined with the temperature-
Tise test of 8.3.3.6
NA
In the case of a release with a range of rated
voltages, this testis made at both the minimum
[and maximum rated control supply voltages
NA
D
Test for limits of operation
Starting with the circuit-breaker open, at the
temperature of the test room, and withthe supply
voltage at 30% rated maximum control supply
voltage, it shall be verified that the circuit-breaker
[cannot be closed by the operation of the actuator
NA
When the supply voltage is raised to 85% of the
/minimurn control supply voltage, it shall be verified
that the circuit-breaker can be closed by the
operation of the actuator
NA
iy
Performance under overvottage conditions,
With the circuit-breaker closed and without current
in the main circuit, it shall be verified that the
‘undervoltage release will withstand the application
}of 110% rated control supply voltage for 4 h without
impairing its functions
NA
)
[Shunt releases
|Shunt releases shall comply with the requirements
of 7.2.1.4 of Part 1. For this purpose, the release
shall be fitted to a cirouit-breaker having the
maximum rated current for which the releas
suitable
NA
It shall be verified that the release will operate to
lopen the circuit-breaker at 70% rated control
supply voltage when tested at an ambient
temperature of + 55 °C +2 °C without current in the
main poles of the circuit-breaker
NA
In the case of a release having a range of rated
[control supply voltages, the test voltage shall be
'70% of the minimum rated control supply voltage
NA
8.3.3.3.3
[Operational performance capability without current.
Type designation or serial number
[Ts250L
Sample no:
St
Rated current In (A)
250A
Rated operational voltage: Ue (V)
500
‘TRF No.: IEC 60947_2B
‘TRF originator: SEVa4
page 34 of 90
Report reference No: 208602900.51
IEC 60 947-2
[Clause
Requirement - Test
Result ~ Remark Verdict
Rated control supply voltage of closing mechanism:
Uc (v)
Rated control supply voltage of shunt releases:
Uc (Vv)
Rated control supply voltage undervoltage
releases: Uc (V)
|Ambient temperature 10-40 °C.
125°C Pp
Number of operating cycles per hour
120 cycles per hour Pp
Number of cycles without current (total)
(Closing mechanism energized at the rated Uc)
- NA
Number of cyeles without current (without releases)
7000 cycles P
[Applied voltage: closing mechanism (V)
- NA
10% of total cycles for circuit-breaker with fitted
[shunt release:
(50% at the beginning- and 50% at the end of the
test)
Energized at the rated Uc
- NA
Applied voltage: shunt releases (V)
10% of total cycles for circuit-breaker with
Uundervottage releases:
(60% at the beginning- and 50% atthe end of the
Hest)
Energized at the minimum rated Uc
10 cycles without applied voltage at the
lundervottage releases.
(Shall not possible o close the circuit-breaker.)
- NA
[Applied voltage: undervottage releases (V)
- NA
Electrical components do not exceed the value
indicated in tab. 7.
‘Compliance Pp
83.3.3.4
[Operational performance capability with current.
Rated current: In (A)
250A
(Maximum rated operational voltage: Ue (V)
/500V
(Conductor cross-sectional area (mm)
10 mm* (8 AWG)
Number of operating cycles per hour
120 cycles per hour
Number of cycles with current (total)
(Closing mechanism energized at the rated Uc)
1000 cycles
Applied voltage: closing mechanism (V)
500 V Pp
For circuit-breaker fitted with adjustable releases,
{test shall be made with the overload setting at
[maximum and short-circuit setting at minimum.
NA
Conditions, makebreak operations:
‘TRF No.: IEC 60947_28
‘TRF originator: SEVay 4
age 35 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause _ [Requirement - Test Result - Remark Verdict
- test voltage U/Ue = 4,0 (V)... Li:|u1:5156V P
sowed 2:]L1: 5168 V
L3:]l2:5148Vv
- test current Ie = 1,0 (A) Ua:]L4:254,1A P
se L2:]L4 2533.4
L3:|L2: 251.84,
= power factoritime constant: 0,70 Pp
+ frequency: (Hz) [60 Hz Pp
~ on-time (ms): 1000 ms Pp
- offtime (5): 298 Pp
Electrical components do not exceed the value | Compliance Pp
indicated in tab. 7.
83.335 | Additional test of operational performance capability without current for
/withdrawable circuit-breaker. 2
Number of operations cycles : 100 - NA
After test, the isolating contacts, withdrawable | NA
mechanism and interlocks shall be suitable for
further service.
8.3.3.4 _ | Overload performance e
this test applies to circuit-breaker of rated current up to and including 630 A
‘Type designation or serial number
[Ts2s0L
‘Sample no:
sit
Rated current In (A)
[250A
Rated operational voltage: Ue (V)
500 V
Rated control supply voltage of closing mechanism:
ue (vy
Rated control supply voltage of shunt releases:
Uc (Vv)
Rated control supply voltage undervoltage
releases: Uc (V)
|Ambient temperature 10-40 °C.
[25°C
Number of operating cycles per hour
120 cycles per hour
|Maximum rated operational voltage: Ue (V)
500 V
Number of operating cycles per hour
NA
‘Number of cycles with current (total)
(Closing mechanism energized at the rated Uc)
NA
[Applied voltage: closing mechanism (V)
NAP.
‘TRF No.: IEC 60947_2B
‘TRF originator: SEVKEMAX
page 36 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause _ [Requirement - Test Result Remark Verdict
For circuit-breaker fitted with adjustable releases, |- NA
test shall be made with the overload/short-ircult
settings at maximum,
[Conditions, overload operations
- test voltage U/Ue = 1,05 (V) La: |L4 : 568,9V. Pp
12:|L4 :571,9V.
L3:|L2:568,.6V
test current AC/DC: Wle = 6,0/2.5 (A) U1: 1489. P
ss nn La:]L4 15144
12:|12:: 1820 A
13:
- power factoritime constant: 0.47
- Number of cycles manually opened: 9 12
- Number of cycles automatically opened by an |3 (at the lower voltage)
overtoad release: 3
~ frequency: (Hz) 60 Hz
~ on-time max 2s: 18
83.3.5 _| Verification of dielectric withstand =
~ equal to twice the rated operational voltage with |1000 V Pp
‘a minimum of 1000 V
= no breakdown or flashover No
- the leaking current for circuit-breaker suitable for | < 5uA/ 550 V
isolation: (<2mA/ 1.1 Ue)
83.3.6 __|Verification of temperature-rise
- the values of temperature-rise do not exceed the | See table P
those specified in tab. 7
Temperature rise of main circuit terminals < 80K [64,7 K P
«
[conductor cross-sectional area (mm?) 420 mm (250 Kemi) P
test current le (A) 250A
8.3.37 __ |Verification of overtoad releases
Test current: 1.45 times the value of their current. [393.3 A P
setting atthe reference temperature: (A)
‘Conventional tripping time: 2738 Pp
63 A
83.3.8 __ | Verification of undervoltage and shunt releases
Circuit-breaker fitted with undervoltage releases. NA
The release shall not operate at 70% of the
minimum control supply voltage -
‘TRF No.: IEC 60947_28 TRF originator: SEVKEMAX
page 37 of 90
Report reference No: 208602900.51
IEC 60 947-2
[Clause
Requirement - Test
Result ~ Remark
Verdict
and shall operate at 35% of the maximum control
supply voltage.
NA
Circuit-breaker fitted with shunt releases.
The release shall operate at 70% of the minimum,
rated control supply voltage. Test made at room
|temperature.
NA
83.3.9
Verification of the main contact position for circuit-breakers for isolation
‘actuating force for opening (N)
O1,1N
test force with blocked main contacts for 10 s (N)
273,4N
Dependent power operation
‘Supply votage of 110% of rated voltage (V)
NA
Three attempts of 5 s to operate the equipment at,
intervals of 5 min,
NA
Independent power operation
Three attempts to operate the equipment by the
stored energy.
NA
Lockabilty of driving mechanism in OFF-position at
test force and blocked main contacts
NA
Position indicator does not show OFF-position after
capture of test force at blocked main contacts
‘Compliance
83.4
TEST SEQUENCE Il (Ics):
83.4.1
Test of rated service short-circuit breaking capacity
Test sequence of operation: O-t-CO-t-CO
Type designation or serial number
‘Sample no:
Rated current: In (A)
Rated operational voltage: Ue (V)
Rated service short-circuit breaking capacity: (kA)
Rated control supply voltage of closing mechanism:
Uc(v)
Rated control supply voltage of shunt release:
Uc (v)
For circuit-breaker fitted with adjustable releases, |- NA
test shall be made with the current and time
settings at maximum.
[closing mechanism energized with 85% at the | - NA
rated Uc: (V)
The circuit-breaker is mounted complete on its own | NA
support or an equivalent support.
‘TRF No.: IEC 60947_28
TRF originator: SEVnea
page 38 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause | Requirement - Test Result — Remark Verdict
Test made in free air: : NA
Distances of the metalic screen's: (all sides) - NA
The characteristics of the metallic screen:
- woven wire mesh - NA
- perforated metal - NA
~ expanded metal - NA
= ratio hole areavtotal area: 0,45-0,65 - NA
= size of hole: <30mm* - NIA
= finish: bare or conductive plating - NA
Test made in specified individual enclosure: - NA
Details ofthese tests, including the dimensions of
the enclosure:
Fuse 'F: - NA
copper wire: diameter 0,8 mm, 50 mm long
Circuits earthed at: (load-star- or supply-star point) | - NA
(Conductor cross-sectional area (mn): - NA
If terminals unmarked: - NA
line connected at: (underside/upside)
‘Tightening torques: (Nm) - NA
Test sequence of operation: O-t-CO-t-CO
- test voltage U/Ue = 1,05 (V). ut] NA
-1.m.s. test current AC/DC: (A) = NA
*iiimmmammnm (2
Ls:
power factortime constant - NA
- Factor *n” - NIA
- peak test current (A) - NA
Test sequence “O" [-
~ max. letthrough current: (kApeak) ua] NA
- Joule integral Fat (A%s) ur] NA
a
Pause, t: (min) - NA
‘TRF No.: IEC 60947_2B TRF originator: SEVKEMAX
page 39 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause [Requirement Test Result ~ Remark Verdict
Test sequence “CO” =
max. letthrough current: (kApeak) ur] NA
- Joule integral Fdt (A?S) «nn nnnnsnnnnnnnek:]= NA
La:
<3:
Pause, t (min) -
Test sequence "CO"
- max. letthrough current: (kApeak) u:]- NA
= Joule integral Ft (A%S) «0. La:]- NA
: 3
Metting ofthe fusible element - NA
Holes in the PE-sheet for test sequence -
(Cracks observed -
8.3.42 _ | Operational performance capability with current.
Rated current: In (A)
‘Maximum rated operational voltage: Ue (V)
(Conductor cross-sectional area (mm)
Number of operating cycles per hour -
[Number (5% of the number given in columm 4, tab. |- NA
8) of cycles with current (total)
(Closing mechanism energized at the rated Uc)
‘Applied voltage: closing mechanism (V) - NA
For circuit-breaker fitted with adjustable releases, |- NA
test shall be made with the overload setting at
‘maximum and short-circuit setting at minimum.
(Conditions, makerbreak operations:
- test voltage U/Ue = 1,0 (V) nm onl >
2:
13:
- test current ie = 1,0 (A) ur] NA
“ La:
13:
- power factoritime constant: - NA
- frequency: (Hz) - NA
- on-time (ms) - NA
TRF No: IEC 60947_28
TRF originator: SEVKae
page 40 of 90
Report reference No: 208602900.51
IEC 60 947-2
Clause
Requirement - Test
Result - Remark
Verdict
- off-time (s):
NA.
Electrical components do not exceed the value
indicated in tab. 7.
NA
3.3.43
Verification of dielectric withstand
= equal to twice the rated operational voltage with
‘a minimum of 1000 V
NA
no breakdown or flashover
NA
- the leaking current for circuit-breaker suitable for
isolation: (<2mA / 1.1 Ue)
NA
83.4.4
Verification of temperature-rise
- the values of temperature-rise do not exceed the
those specified in tab. 7.
NA
Temperature rise of main circuit terminals.
80K (kK):
NA
‘conductor cross-sectional area (mm?)
NA
test current le (A)
NA
83.45
Verification of overload releases
Test current: 1.45 times the value of their current
setting at the reference temperature: (A)
NA
Conventional tripping time:
|<1h when In < 63A, <2h when In > 63 A
NA
83.4
TEST SEQUENCE Ihill(Ies=lcu):
83.44
Test of rated service short-circuit breaking capacity
‘Test sequence of operation: O-t-CO-t-CO.
Type designation or serial number
TS250L,
Sample no:
S24
Rated current: In (A)
250A
Rated operational voltage: Ue (V)
/240V
Rated service short-circuit breaking capacity: (kA)
200 kA
Rated control supply voltage of closing mechanism:
Uc (Vv)
Rated control supply voltage of shunt release:
Uc(V)
For circuit-breaker fitted with adjustable releases,
test shall be made with the current and time
settings at maximum.
‘Compliance
‘TRF No.: IEC 60947_2B
TRF originator: SEVKEMAX
page 41 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause [Requirement — Test Result - Remark Verdict
[closing mechanism energized with 85% atthe |- NA
rated Uc: (V)
‘The circuit-breaker is mounted complete on its own | Compliance P
support or an equivalent support.
Test made in free air Compliance
Distances of the metalic screen's: (all sides) 145(W) x 230(H) x 86(0)
The characteristics ofthe metallic screen: :
- woven wire mesh - NA
- perforated metal [Compliance P
- expanded metal - NA
ratio hole areattotal area: 0,45-0,65 0,85
- size of hole: <30mm? [28 mm?
finish: bare or conductive plating [Compliance
Test made in specified individual enclosure: - NA
Details of these tests, including the dimensions of
the enclosure:
Fuse "F’ [Compliance P
[copper wire: diameter 0,8 mm, 60 mm long
Circuits earthed at (load-star- or supply-star point | Load-star
Conductor cross-sectional area (mm?) 120 mm? (250 kemil)
If terminals unmarked: upside
line connected at: (underside/upside)
Tightening torques: (Nm) 6,0Nm P
83.5.1 | The operation of overload releases shall be verified at twice the value of their ;
current setting on each pole separately.
The operating time shall not exceed the max. value stated by the manufacturer for
twice the current setting at the reference temperature, on a pole singly.
Time specified by the manufacturer. 80~600 s
- Operation time: (5) L1:]L4 960s Pp
nnn L2:)L2: 293s
13:13: 234s
Test sequence of operation: O-t-CO-t-CO
- test voltage U/Ue = 1,05 (V) La: ]L4 2584 P
7 12:|L2 258.4
L3:|1L3 | 2584 V
-rm.s. test current AC/DC: (A) P
L1:]L1 : 205200 A
2:2 : 203800 A
“L3:|L3 : 207600 A
ower factoritime constant 018 Pp
‘TRF No.: IEC 60947_28
TRF originator: SEVnea 4
‘TRF No.: IEC 60947_28
page 42 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause | Requirement - Test Result — Remark Verdict
- Factor *n* 22 P
- peak test current (A) 457800 A P
Test sequence "0"
- max. let-through current: (KAPEAK) ..oneunobt:]L1: 2,9 kApeak P
2:]L2 : 25,2 kA peak
L3:|L3 : 16,3 kApeak
- Joule integral Fdt (A#s) se sovebds LA : 67,1 KA'S P
L2:|L2 : 328.4 kA’s.
L3:]L3: 1279 kA’s.
Pause, t: (min) [3 min P
Test sequence "CO" =
- max. let-through current: (kApeak) Ut:]L1: 18,1 kApeak P
sen so sone: |L2 : 24,7 KA peak
L3:|L3 | 24,7 kApeak
= Joule integral at (As) Lt: ]L1: 196,6 kA‘s. P
L2:|L2 : 338,7 kA’s.
L3;|L3 ; 838,7 kA’s:
Pause, t (min) 3min P
Test sequence "CO"
~ max. letthrough current: (kApeak) La:]L4:7,1 kApeak Pp
nnn 2: |L2 : 22,9 kA peak
L3:|L3 : 20,0 kApeak
= Joule integral Fat (AS) nonsunsnsnnnnnnnnkl: ]LA : 19,8 KAR P
L2:|L2: 310.0 ka’s
sol3: | LB | 206,3 kA’S
Melting of the fusible element No
Holes in the PE-sheet for test sequence No
Cracks observed No
83.42 ‘Operational performance capability with current. oes
Rated current: In (A) 250A
[Maximum rated operational voltage: Ue (V) 240V =e
|Conductor cross-sectional area (mm?) 120 mm? (250 kcmil)
Number of operating cycles per hour 120 cycles per hour
Number (5% of the number given in columm 4, tab. [50 cycles.
8) of cycles with current (total)
(Closing mechanism energized at the rated Uc)
[Applied voltage: closing mechanism (V) 240 V P
For circuit-breaker fitted with adjustable releases, |- NA
test shall be made with the overload setting at
maximum and short-circuit setting at minimum.
TRF originator: SEVKEMAX
a
page 43 of 90 Report reference No: 208602900.51
Clause [Requirement - Test Result - Remark Verdict
Conditions, make/break operations:
test voltage U/Ue = 1,0 (V) La: ]Lt :248,7 Pp
ssnnnininnnnninninnnninnnnnnnnnnnnnnee:|L2 : 245,4
L3:|L3 243.8 V
test current Ile = 1,0 (A) LA: 252.4) P
122251
L3:253.A
- power factortime constant: 0.73 Pp
- frequency: (Hz) [60 Hz Pp
- on-time (ms): 1000 ms P
- off-time (8): 298 Pp
Electrical components do not exceed the value |- NA
indicated in tab. 7.
8.3.43 __|Verification of dielectric withstand
- equal to twice the rated operational voltage with | 1000 Pp
ja minimum of 1000 V
= no breakdown or fashover No
- the leaking current for circuit-breaker suitable for |< 5 uA/264 V
isolation: (<2mA / 1,1 Ue)
83.44 __ |Verification of temperature-rise : a
- the values of temperature-rise do not exceed the |See Remarks. Pp
those specified in tab. 7
Temperature rise of main circuit terminals. 659K P
80K (K)
[conductor cross-sectional area (mm) 120 mm? (250 kemil)
test current le (A) 250A
83.45 | Verification of overioad releases
Test current: 4,45 times the value of their current ]392.A P
setting atthe reference temperature: (A)
Conventional tripping time: 300s Pp
63 A
8.3.5.4 | Verification of overload releases =
The operation of overload releases shall be verified at 2,5 times the value of their
current setting on each pole separately.
‘The operating time shall not exceed the max. value stated by the manufacturer for
twice the current setting at the reference temperature, on a pole singly.
Time specified by the manufacturer: '80~600 5 Pp
‘TRF No.: IEC 60947_2B ‘TRF originator: SEVKEMAX
page 44 of 90 Report reference No: 208602900.51
1EC 60 947-2
[clause [Requirement - Test Result - Remark Verdict
- Operation time: (s) La:|Lt= 1275 P
“ ss vn L:| 2 143s
13:13: 121s
834 TEST SEQUENCE IN (Ics=Icu)
83.41 _|Testof rated service short-circuit breaking capacity
‘Test sequence of operation: O-t-CO-t-CO.
Type designation or serial number TS250L
[Sample no: $2.2
Rated current: In (A) 404
Rated operational voltage: Us (V) 240
Rated service short-circuit breaking capacity: (KA) |200 kA
Rated control supply voltage of closing mechanism:
Uc(v)
Rated control supply voltage of shunt release: -
Uc(v)
For circuit-breaker fitted with adjustable releases, | Compliance Pp
test shall be made with the current and time
settings at maximum.
[closing mechanism energized with 85% atthe |- NIA
rated Uc: (V)
The circuit-breaker is mounted complete on its own | Compliance Pp
support or an equivalent support.
Test made in free ar: [Compliance
Distances of the metalic screen's: (all sides) 145(W) x 230(H) x 86(D)
‘The characteristics of the metalic screen:
= woven wire mesh : NA
- perforated metal Compliance P
- expanded metal : NA
ratio hole areatotal area: 0,45-0,65 056
~ size of hole: <30mm* 28 mm?
= finish: bare or conductive plating (Compliance
[Test made in specified individual enclosure: - NA
Details of these tests, including the dimensions of
the enclosure:
Fuse °F’ [Compliance P
copper wire: diameter 0,8 mm, 50 mm long
Circuit is earthed at: (load-star- or supply-star point) | Load-star
(Conductor cross-sectional area (mm*) 10 mm? (8 AWG) Pp
TRF No.: IEC 60947_2B
‘TRF originator: SEVKEMAX
page 45 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause | Requirement - Test Result - Remark Verdict
If terminals unmarked Upside Pp
line connected at: (underside/upside)
Tightening torques: (Nm) 6,0Nm P
8.3.5.1 | The operation of overload releases shall be verified at twice the value of their =
[current setting on each pole separately.
The operating time shall not exceed the max. value stated by the manufacturer for
twice the current setting at the reference temperature, on a pole singly.
Time specified by the manufacturer: [80~600 s
~ Operation time: (s) Li:]ut: 169s
12:12: 134s
L3:]13: 150s
Test sequence of operation: O- t- CO-t-CO
= test voltage UUe = 1,08 (V) on Li:]L1:258,4V P
L2:]12: 258.4
L3:|L3 : 258.4 V
~fm.s. test current AC/DC: (A) Pp
so . L:]L1 : 205200 A
wn L2:]L2 : 203800 A
L3:|L3 : 207600 A
power factortime constant 0,18
= Factor “n” 2.2
~ peak test current (A) 457800 A
Test sequence "0"
max. letthrough current: (kApeak) L1: 11,3 kApeak Pp
ssn 12: 27,0 kA peak
= 13 : 32,2 kApeak
= Joule integral Pat (A's) L:] 1: 37,7 kA’ P
1L2:]L2 : 493,2 kA’s
1L3: | L3 : 603,5 kA’s
Pause, t: (min) 3 P
Test sequence "CO" =
- max. letthrough current: (kApeak) 11: ]L4: 15,5 kApeak Pp
nnn srmensnnnnenneb: LB: 12,5 WA peak
L3:|L3 : 6.0 kApeak
- Joule integral Fat (A®S) .....csees L1:|L1 ; 185,6 kA’s P
L2: | L2 89,9 kA’s
L3:|L3 | 26,7 kA’S
Pause, t (min) 3min P
Test sequence "CO"
max. letthrough current: (kApeak) L1:]L1 : 9,3 kApeak Pp
an L2:|12: 17,1 KA peak
L3:|L3 : 8,6 kApeak
‘TRF No.: IEC 60947_28 TRF originator: SEVnae
page 46 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause _|Requirement - Test Result ~ Remark Verdict
- Joule integral Pat (A’s) La:[Lt : 76,2 ka’ Pp
semen : erm L2;]L2 : 206,8 kA’s
L3:|L3 : 39,2 ka’s
Melting ofthe fusible element No
Holes in the PE-sheet for test sequence "O" No
Cracks observed No
83.42 __ | Operational performance capability with current.
Rated current: In (A) ~
Maximum rated operational voltage: Ue (V) :
Conductor cross-sectional area (mm) - z
Number of operating cycles per hour : NA
Number (5% of the number given in columm 4, tab. |- NA
8) of cycles with current (total)
(Closing mechanism energized at the rated Uc)
Applied voltage: closing mechanism (V) : NA
For circuit-breaker fited with adjustable releases, |- NA
test shall be made with the overioad setting at
maximum and short-circuit setting at minimum.
(Conditions, make/break operations: ae
- test voltage U/Ue = 1,0 (V) cnet] NA
“12:
13:
test current He = 1,0 (A) nncnnnnnnnannkl:|= NA
on Le
“13:
- power factortime constant: 7 NA
- frequency: (Hz) = NA
- on-time (ms): - NA
- off-time (5): - NA
Electrical components do not exceed the value |- NA
indicated in tab. 7,
3.43 | Verification of dielectric withstand.
- equal to twice the rated operational voltage with [1000 V P
[a minimum of 1000 V
no breakdown or flashover No
- the leaking current for circuit-breaker suitable for | <5 uA/264 V
isolation: (<2mA / 1,1 Ue)
‘TRF No.: IEC 60947_28
‘TRF originator: SEVKEMAX
page 47 of 90
Report reference No: 208602900.51
IEC 60 947-2
Clause
Requirement ~ Test
Result - Remark
33.44
Verification of temperature-rise
- the values of temperature-rise do not exceed the
those specified in tab. 7.
Temperature rise of main circuit terminals,
<80K (K)
[conductor cross-sectional area (mm*)
test current le (A)
33.45
Verification of overioad releases
Test current: 4,45 times the value of their current
setting at the reference temperature: (A)
62a
Conventional tripping time:
63 A
6278
83.5.4
Verification of overload releases
‘The operation of overload releases shall be verified at 2,6 times the value of their
current setting on each pole separately.
‘The operating time shall not exceed the max. value stated by the manufacturer for
twice the current setting at the reference temperature, on a pole singly.
Time specified by the manufacturer:
80-600 s
~ Operation time: (s) Ly
L3:
Li:87s
12: 84s
L3:895
83.4
TEST SEQUENCE Will (Ics=lcu):
83.41
Test of rated service short-circuit breaking capacity
‘Test sequence of operation: O- t-CO-t-CO.
Type designation or serial number
TS250L,
[Sample no:
82-3
Rated current: In (A)
250A
Rated operational voltage: Ue (V)
415V
Rated service short-circuit breaking capacity: (kA)
150 kA
Rated control supply voltage of closing mechanism:
Uc(V)
Rated control supply voltage of shunt release:
Uc(V)
For circuit-breaker fitted with adjustable releases,
test shall be made with the current and time
settings at maximum.
Compliance
‘losing mechanism energized with 85% at the
rated Uc: (V)
NA
‘TRF No.: IEC 60947_28
‘TRF originator: SEVKEMAX
current setting on each pole separately
page 48 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause _|Requirement- Test Result ~ Remark Verdict
The circuit-breaker is mounted complete on its own | Compliance P
‘support or an equivalent support.
Test made in free ar: [Compliance
Distances ofthe metallic screen's: (all sides) 145(W) x 230(H) x 86(0)
The characteristics of the metallic screen:
= woven wire mesh - NA
perforated metal [Compliance P
~ expanded metal - NA
= ratio hole areavtotal area: 0,45-0,65 0,66
- size of hole: <30mm* }28 mm?
= finish: bare or conductive plating [Compliance
Test made in specified individual encosure: - NIA
Details ofthese tests, including the dimensions of
the enclosure:
Fuse "F” [Compliance P
Copper wire: diameter 0,8 mm, 50 mm long
Circuit is earthed at: (load-star- or supply-star point) |Load-star
‘Conductor cross-sectional area (mm?) 120 mm? (250 kemil)
If terminals unmarked: upside
line connected at: (underside/upside)
Tightening torques: (Nm) [6.0Nm P
8.3.5.1 | The operation of overload releases shall be verified at twice the value of their :
The operating time shall not exceed the max. value stated by the manufacturer for | _
twice the current setting at the reference temperature, on a pole singly. ee
Time specified by the manufacturer: 80~600 s Pp
- Operation time: (8) i Li:|L4 : 299s P
ssn 12:]L2: 290s
L3:]L3. 250s
Test sequence of operation: O-t-CO-t-CO
- test voltage U/Ue = 1,05 (V) .... L1:|L4 : not recorded Pp
snnnnnnn L2:|L2 : not recorded
L3:|L3 : not recorded
=1.m.s. test current AC/DC: (A) Pp
. La: ]L4 : 151800 A
12:12: 151800
Ls: 13 : 148400 A
ower factoriime constant 019
- Factor “a” 2,0
‘TRF No.: IEC 60947_28
‘TRF originator: SEVKEMAX
TRF No.: IEC 60947_28
page 49 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause _ [Requirement - Test Result ~ Remark Verdict
- peak test current (A) 333400 A P
[Test sequence ’O”
max. letthrough current: (KApEAK) .....euekt:[L1 14,5 kApeak P
L2:] 12 : 32,0 kA peak
L3:]L3 : 19,2 kApeak
- Joule integral Pat (A*s) L1:]L1:118,6 kA’s P
: 1L2:|L2 : 603,5 kAs
L3:|L3 : 20,5 ka’s
Pause, t: (min) 3 min P
Test sequence "CO" :
= max. letthrough current: (KAP@ak) .......ub4:|L1 : 27,7 KApeaK P
L2:] [2 : 27/5 kA peak
13:] 3 :0,2 kApeak
- Joule integral Pat (As) L1:]L4: 452,6 kA’s P
7 sovnitnnnneinennsenn L2:)L2: 471,3 kA’s.
L3:|L3 1,37 kA’,
Pause, t: (min) 3 min P
Test sequence "CO"
- max. letthrough current: (kApeak).. L1:]L1 : 30,9 kApeak P
L2:] 12: 19.9 kA peak
L3:|L3 : 12,9 kApeak
- Joule integral Fat (A’s) L1:]L1 :609,6 ka’s P
sone 1L2:|L2 : 238,7 kA’s
13:] 13 : 105,6 kas
Melting of the fusible element No
Holes in the PE-sheet for test sequence No
[Cracks observed No
8.3.42 __ | Operational performance capability with current
Rated current: In (A) 250A fe
Maximum rated operational voltage: Ue (V) 415V
‘Conductor cross-sectional area (mm?) 120 mm? (250 kcmil) Tee EB
Number of operating cycles per hour 120 cycles per hour
Number (5% of the number given in columm 4, tab. [50 cycles.
8) of cycles with current (total)
(Closing mechanism energized at the rated Uc)
Applied vottage: closing mechanism (V) 415V P
For circuit-breaker fitted with adjustable releases, |- NA
test shai! be made with the overload setting at
maximum and short-circuit setting at minimum,
‘TRF originator. SEVKEMAX
page 50 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause Requirement — Test Result — Remark Verdict
(Conditions, make/break operations: =
- test voltage U/Ue = 1,0 (V) ool: }L1 : 429,2 V P
L2:|L2: 428.2
ob: |L3: 429,4.V
test current ie = 1,0 (A) L.]L1: 252.8 Pp
bo svovenseneeel 2: | L2 2 251 A
13:]13: 251.8
| power factor/time constant: 0,74 P
= frequency: (Hz) 60 Hz P
|- on-time (ms): 1000 ms Pp
- off-ime (s): 298 P
Electrical components do not exceed the value - NA
indicated in tab. 7.
83.43 | Verification of dielectric withstand
- equal to twice the rated operational voltage with [1000 V P
{a minimum of 1000 V
= no breakdown or fashover No
|- the leaking current for circuit-breaker suitable for |200 uA / 457 V P
isolation: (<2mA / 1,1 Ue)
8.3.4.4 Verification of temperature-rise
~ the values of temperature-rise do not exceed the |See Remarks P
those specified in tab. 7.
| Temperature rise of main circuit terminals. 63,0 K P
|< 80 K (K)
‘conductor cross-sectional area (mm?) 120 mm? (250 kemil)
test current le (A) 250A
8.3.4.5, Verification of overload releases
‘Test current: 1,45 times the value of their current |390 A P
setting at the reference temperature: (A)
Conventional tripping time: 272s P
|<1h when In < 63A, <2h when In > 63 A
83.5.4 _ | Verification of overload releases
|The operation of overload releases shall be verified at 2,5 times the value of their
[current setting on each pole separately.
The operating time shall not exceed the max. value stated by the manufacturer for
twice the current setting at the reference temperature, on a pole singly.
Time specified by the manufacturer: '80~600 s P
TRF No.: IEC 60947_2B
‘TRF originator: SEVha 4
page 51 of 90
Report reference No: 208602900.51
IEC 60 947-2
Clause [Requirement — Test Result ~ Remark Verdict
= Operation time: (8) .. Li:|L4: 138s P
L2:|L2: 168s
onL3:]L3 123 8
834 TEST SEQUENCE Ill (Ics=Icu) =
8.3.4.1 __ |Test of rated service short-circuit breaking capacity
Test sequence of operation: O-t- CO-t-CO.
‘Type designation or serial number [rs250L
‘Sample no: S24
Rated current: In (A) 250A =
Rated operational voltage: Ue (V) 500 V
Rated service short-circuit breaking capacity: (kA) [85 kA fs
Rated control supply voltage of closing mechanism: | -
Uc (V)
Rated control supply voltage of shunt release: -
Uc (v) E
For circuit-breaker fitted with adjustable releases, [Compliance Pp
test shall be made with the current and time
settings at maximum,
closing mechanism energized with 85% atthe |- NA
rated Uc: (V)
The circuit-breaker is mounted complete on its own | Compliance Pp
support or an equivalent support.
Test made in free air: Compliance
Distances of the metallic screen's: (al sides)
145(W) x 230(H) x 86(D)
‘The characteristics of the metallic screen:
- NA
- woven wire mesh
- perforated metal ‘Compliance P
- expanded metal - NA
ratio hole areattotal area: 0,45-0,65 0,55
- size of hole: <30mm? 28 mm?
finish: bare or conductive plating [Compliance
Test made in specified individual enclosure: - NA
Details of these tests, including the dimensions of
the enclosure:
Fuse "F’ [Compliance P
[copper wire: diameter 0,8 mm, 50 mm long
Circuits earthed at: (load-star- or supply-star point | Load-star
Conductor cross-sectional area (mm*)
120 mm? (250 kemil)
‘TRF No.: IEC 60947_28
TRF originator: SEVRea
page 52 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause | Requirement - Test Result — Remark Verdict
If terminals unmarked: Underside Pp
line connected at: (underside/upside)
Tightening torques: (Nm) [6,0 Nm P
8.3.5.1 | The operation of overload releases shall be verified at twice the value of their
current setting on each pole separately.
The operating time shall not exceed the max. value stated by the manufacturer for E
twice the current setting at the reference temperature, on a pole singly.
Time specified by the manufacturer: 80-600 s
= Operation time: (8). seb: |L1 265 8
se L2:|L2:244 5
U3: |L3: 267s
Test sequence of operation: 0- t-CO-t-CO
test voltage U/Ue = 1,05 (V) soot: ]L4 : not recorded P
- 2:|12 not recorded
3: | L3 : not recorded
-r.m.s. test current AC/DC: (A) P
Li: ]L4 : 86400 A
L2:|L2: 85400 A
3: |L3: 86400 A
ower factorrime constant 0,18 P
- Factor *a" 22 P
peak test current (A) 189600 A P
Test sequence "0" F
- max. let-through current (kApeak) Li:]L4 = 16,0 kApeak P
“L2:|2:27,3 kA peak
L3:]L3 : 15/4 kApeak
- Joule integral Fdt (A?) ... sons LA 22,4 KARS Pp
L2:]L2 : 625.3 kA’s
sok] LB : 194,7 KA’S
Pause, t: (min) 3.min Pp
Test sequence "CO"
~max. let-through current: (kApeak) Lt: |L1 : 27,9 kApeak Pp
ene nnn L2:]L2 : 16,4 kA peak
1L3: | L3 : 13,6 kApeak
= Joule integral Fat (APS) ono somolel:] LA :701,9 kA’S P
- 12:|L2: 211.1 kA’s
L3:|L3 : 195\4 kA’s
Pause, t: (min) 3min P
Test sequence *CO”
- max, letthrough current: (kApeak) Lt: ]L4 : 24,1 kApeak P
- 12:|L2: 13,1 KA peak
L3:]13 25,7 kApeak
TRF No.: IEC 60947_2B TRF originator: SEVKEMAX
page §3 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause [Requirement - Test Result — Remark Verdict
- Joule integral Pat (A*s) L1:]L4 : 591,8 kA’s, P
esse sen L2;|L2 ; 307,7 kA?s
L3:]L3 : 70115 kA’s
Metting of the fusible element No
Holes in the PE-sheet for test sequence "O" No
[Cracks observed No
[8.3.42 | Operational performance capabilty with current.
Rated current: In (A) 250A
[Maximum rated operational voltage: Ue (V) [500 V
[Conductor cross-sectional area (mm?) 120 mm? (250 kemil)
Number of operating cycles per hour 120 oycles per hour
Number (5% of the number given in columm 4, tab. [50 cycles
8) of cycles with current (total)
(closing mechanism energized at the rated Uc)
[Applied voltage: closing mechanism (V) 500 V P
For circult-breaker fited with adjustable releases, |- NA
test shall be made withthe overload setting at
maximum and short-circuit setting at minimum.
[Conditions, make/break operations: 2
test voltage U/Ue = 1,0 (V) L:]L1:5153V P
sn eosin L2:|L2: 5213
L3:|L3 : 5208 V
= test current Mle = 1,0 (A) on. ui. [it 2518 P
ae L2:]L2: 252.4
13:13: 251A
- power factoritime constant 0,75 P
= frequency: (Hz) [60 Hz P
on-time (ms): 1000 ms P
-offtime (5): 298 P
Etectrical components do not exceed the value |- NA
indicated in tab. 7
83.43 __ | Verification of dielectric withstand =|
- equal to twice the rated operational voltage with ]1000 V Pp
[a minimum of 1000 V
-no breakdown or flashover No
=the leaking current for circuit-breaker suitable for |950 uA / 850 V
isolation: (<2mA / 1,1 Us)
‘TRF No.: IEC 60947_2B
‘TRF originator: SEVKEMAX
page 54 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause | Requirement — Test Result Remark Verdict
8.3.44 | Verification of temperature-rise
- the values of temperature-rise do not exceed the |See Remarks. Pp
those specified in tab. 7.
Temperature rise of main circuit terminals 724K Pp
<80K (K)
‘conductor cross-sectional area (mr*) 4120 mr? (250 kemil) P
test current le (A) 250 A Pp
83.4.5 _ | Verification of overload releases
‘Test current: 1,45 times the value of their current [390A Pp
setting at the reference temperature: (A)
[Conventional tripping time: 1708 P
/
63 A
8.3.5.4 __ | Verification of overload releases
The operation of overload releases shall be verified at 2,5 times the value of their
current setting on each pole separately
‘The operating ime shall not exceed the max. value stated by the manufacturer for =
twice the current setting at the reference temperature, on a pole singly. z
Time specified by the manufacturer: 80-600 s
- Operation time: (8) La:]U4: 125s
12 ]L2: 127s
L3:]L3: 1178
235 TEST SEQUENCE Il (Icu) :
Rated ultimate short-circuit breaking
Except where the combined test sequence applies, this test sequence applies to
circuit-breaker of utiization category A and to circuit-breaker of utiization B having a
rated ultimate short-circuit breaking capacity higher than the rated short-time
withstand current.
For circuit-breakers of utlization B having a rated short-time withstand current equal
to their rated ultimate short-circuit breaking capacity, this test sequence need not be
made, since, in this case, the ultimate short-circuit breaking capacity, is verified
when carrying out test sequence IV.
For integrally fused circuit-breakers, test sequence V applies in place or this
sequence.
‘Type designation or serial number -
‘Sample no: -
Rated current: In (A) -
Rated operational voltage: Ue (V) -
Rated ultimate short-circuit breaking capacity: (kA)
‘TRF No.: IEC 60947_28
TRF originator: SEVKEMAX
page 55 of 90,
Report reference No: 208602900.51
IEC 60 947-2
[Clause
Requirement — Test Result - Remark Verdict
Rated control supply voltage of closing mechanism:
Uc(v)
Rated control supply voltage of shunt release: -
Uc(v)
This test sequence need not be made when Icu = Ics
8.3.5.1
The operation of overload releases shall be verified at twice the value of their
[current setting on each pole separately.
The operating time shall not exceed the max. value stated by the manufacturer for | =
twice the current setting at the reference temperature, on a pole singly.
Time specified by the manufacturer: -
NA
- Operation time: (s) ur]
2
3.
NA
8352
Test of rated ultimate short-circuit breaking capacity
The test sequence of operations is O-t- CO
For circuit-breaker fitted with adjustable releases, |- NA
{test shall be made with the current and time
settings at maximum.
[closing mechanism energized with 85% at the |- NA
rated Uc: (V)
The circuit-breaker is mounted complete on its own | - NA
Support or an equivalent support.
Test made in free air - NA
Distances of the metallic screen’s: (al sides) - NA.
The characteristics of the metallic screen:
woven wire mesh -
= perforated metal -
- expanded metal -
ratio hole areartotal area: 0,46-0,65 - NA
~ size of hole: <30mm? - NA.
finish: bare or conductive plating - NA
“Test made in specified individual enclosure: - NA
Detaiis of these tests, including the dimensions of
the enclosure:
Fuse "F" - NA
copper wire: diameter 0,8 mm, 50 mm long
[Circuits earthed at (load-star-or supply-star point) |- NA
[Conductor cross-sectional area (mm) - NA
‘TRF No.: IEC 60947_28
‘TRF originator: SEVKEMAX
page 86 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause [Requirement Test Result - Remark Verdict
ifterminals unmarked > NA
line connected at: (underside/upside)
Tightening, torques: (Nm) - NA
Test sequence of operation: O-t-CO
test voltage U/Ue = 4,05 (V) La} NA
ms. test current AGIDG: (A) cnn > NA
i
power factortime constant - NA
= Factor “a - NA
= peak test current (Amax) - NA
Test sequence "O" a
= max. letthrough current (kApeak) Lt} NA
Joule integral Pat (A¥S) oo. Lf NA
i
Pause, t (min) - NA
Test sequence “CO”
max letthrough current (KApeak) Lr] NIA
= Joule integral Pat (A%S) conte NA
L3:
Melting ofthe fusible element - NA
Holes in the PE-sheet for test sequence “0 - NA
(Cracks observed a NA
8.3.5.3 [Verification of dielectric withstand
equal to twice the rated operational voltage with |-
ja minimum of 1000 V
=no breakdown or fashover - NA
the leaking current for circui-breaker suitable for |- NA
isolation: (<6mA /1,1 Ue)
TRF No.: IEC 60947_2B
TRF originator: SEVKEMAX
page 57 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause [Requirement - Test Result ~ Remark Verdict
83.54 | Verification of overload releases
The operation of overioad releases shall be verified at 2,5 times the value of their
current setting on each pole separately. =
The operating time shall not exceed the max. value stated by the manufacturer for a
twice the current setting atthe reference temperature, on a pole singly. E
[Time specified by the manufacturer - NA
= Operation time: (8) svn = NA
12
13:
836 TEST SEQUENCE IV
Rated short-time withstand current ei
Except where the combined test sequence applies, this test sequence applies to %
circuit-breakers of utilization category B and to those circuit-breaker of category A
[covered by note 3 of table 4, and comprises the following tests:
Where integrally fused circuit-breaker are of utilization category B, they shall meet
the requirements of this sequence.
Type designation or serial number =
Sample no: E
Rated current: In (A) -
Rated operational voltage: Ue (V) -
Rated short-time withstand current: (kAVs) -
Rated frequency. (Hz) -
[8.3.6.1 | Verification of overload releases
The operation of overtoad releases shall be verified at twice the value of their
[current setting on each pole separately.
The operating time shall not exceed the max. value stated by the manufacturer for
twice the current setting atthe reference temperature, on a pole singly.
Time specified by the manufacturer: - NA
= Operation time: (8) i - ua] NA
se 7 mes
Ls:
8362 __ | Testofrated short-time withstand current. eS
For this test, any over-current release, including the instantaneous override, fany, |
ikely to operate during the test, shall be rendered inoperative.
test frequency: (Hz) -
- duration ofthe test: (s) = NA
test frequency: (Hz) - NA
TRF No.: IEC 60947_2B
TRF originator: SEVKEMAX
page 58 of 90 Report reference No: 208602900.51
IEC 60 947-2
Clause | Requirement - Test Result - Remark Verdict
~ power factor / time constant (ms): - NA
factor *n” = NA
test voltage: (V) ut] NA
2:
13
=fm.s, test current: (KA) ut] NA
: sen oe 12:
1B
~ highest peak current: (kA) = NA
8363 _ | Verification of temperature-rise
- the values of temperature-rise do not exceed the |- NA
those specified in tab. 7.
‘Temperature rise of main circuit terminals. - NA
80K (K)
[conductor cross-sectional area (mn) - NA
test current le (A) - NA
836.4 _ | Test of short-circuit breaking capacity at the max. short-time withstand current.
Rated short-time withstand current: (kA/s)
Test sequence: O-t-CO
max. available time setting of the short-time delay |- NA
short-circuit release. (5)
- test frequency: (Hz) - NA
- power factor / time constant (ms): - NA
= factor *n* -
Test sequence "0"
test voltage: (V) nnn ron ur]
vn La:
Ls:
=F. test current: (kA) - NA
~ highest peak current: (kA) = NA
- the circuit-breaker shall remain closed for the |- NA
short-time corresponding to the max. available
time setting of the short-time delay short-circuit
release and -
- the instantaneous override, if any, shall not | NA
operate,
-pause: t(s) - NA
‘TRF No.: IEC 60947_2B
‘TRF originator: SEV